Sunteți pe pagina 1din 87

PROCON Pressure Control Trainer - Instruction Manual

38-714
PROCON
PRESSURE CONTROL TRAINER
INSTRUCTION MANUAL
38-714
1160–38714

Feedback
Feedback Instruments Ltd, Park Road, Crowborough, E. Sussex, TN6 2QR, UK.
Telephone: +44 (0) 1892 653322, Fax: +44 (0) 1892 663719.
email: feedback@fdbk.co.uk website: http://www.fbk.com
Manual: 38-Series Ed04 012003 Printed in England by Fl Ltd,Crowborough
Feedback Part No. 1160–38714
THE HEALTH AND SAFETY AT WORK ACT 1974

We are required under the Health and Safety at Work Act 1974, to make available to users of this equipment certain information
regarding its safe use.
The equipment, when used in normal or prescribed applications within the parameters set for its mechanical and electrical
performance, should not cause any danger or hazard to health or safety if normal engineering practices are observed and they are used
in accordance with the instructions supplied.
If, in specific cases, circumstances exist in which a potential hazard may be brought about by careless or improper use, these will be
pointed out and the necessary precautions emphasized.
While we provide the fullest possible user information relating to the proper use of this equipment, if there is any doubt whatsoever
about any aspect, the user should contact the Product Safety Officer at Feedback Instruments Limited, Crowborough.
This equipment should not be used by inexperienced users unless they are under supervision.
We are required by European Directives to indicate on our equipment panels certain areas and warnings that require attention by the
user. These have been indicated in the specified way by yellow labels with black printing, the meaning of any labels that may be fixed to
the instrument are shown below:

CAUTION - CAUTION - CAUTION -


RISK OF RISK OF ELECTROSTATIC
DANGER ELECTRIC SHOCK SENSITIVE DEVICE
Refer to accompanying documents

PRODUCT IMPROVEMENTS
We maintain a policy of continuous product improvement by incorporating the latest developments and components into our equipment,
even up to the time of dispatch.
All major changes are incorporated into up-dated editions of our manuals and this manual was believed to be correct at the time of
printing. However, some product changes which do not affect the instructional capability of the equipment, may not be included until it is
necessary to incorporate other significant changes.

COMPONENT REPLACEMENT
Where components are of a ‘Safety Critical’ nature, i.e. all components involved with the supply or carrying of voltages at supply
potential or higher, these must be replaced with components of equal international safety approval in order to maintain full equipment
safety.
In order to maintain compliance with international directives, all replacement components should be identical to those originally
supplied.
Any component may be ordered direct from Feedback or its agents by quoting the following information:

1. Equipment type 2. Component value


3. Component reference 4. Equipment serial number

Components can often be replaced by alternatives available locally, however we cannot therefore guarantee continued performance
either to published specification or compliance with international standards.

DECLARATION CONCERNING ELECTROMAGNETIC COMPATIBILITY


Should this equipment be used outside the classroom, laboratory study area or similar such place for which it is designed and sold then
Feedback Instruments Ltd hereby states that conformity with the protection requirements of the European Community Electromagnetic
Compatibility Directive (89/336/EEC) may be invalidated and could lead to prosecution.
This equipment, when operated in accordance with the supplied documentation, does not cause electromagnetic disturbance outside
its immediate electromagnetic environment.

COPYRIGHT NOTICE
© Feedback Instruments Limited
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any
means, electronic, mechanical, photocopying, recording or otherwise, without the prior permission of Feedback Instruments Limited.

ii 38 Series PROCON
38-714 Pressure Process Rig

Feedback Discovery Products CONTENTS

CHAPTER 1 INTRODUCTION

CHAPTER 2 DESCRIPTION

CHAPTER 3 INSTALLATION REQUIREMENTS

CHAPTER 4 COMMISSIONING

CHAPTER 5 EXPERIMENTAL INDEX

CHAPTER 6 EXPERIMENTS

38 Series Procon iii


38 Series
PROCON
EQUIPMENT LIST Feedback Discovery Products

NOTES

iv 38 Series PROCON
Chapter 1
38-714 Pressure Process Rig
Feedback Discovery Products INTRODUCTION

38-714 PRESSURE PROCESS RIG INTRODUCTION

The successful design and operation of industrial plant requires the optimum choices of
instrumentation and control equipment together with the ability to commission, monitor
and maintain such equipment. Technicians and engineers need to be trained in these
skills, particularly in view of the rapid advances in the use of electronics and
microcomputers in process control.

This range of specially designed equipment allows practical appreciation and


understanding of the whole spectrum of process control technology from the
characteristics of individual components to complex control loops operating on real
processes

This manual describes the 38-714 Pressure Process Rig, which is part of the PROCON
range of equipment designed to introduce and demonstrate the principles of process
measurement and control.

The system includes those pneumatic control components of interest to the process
industries. The design allows study of component operation and connection to electrical
control devices through the use of pressure/current transducers.

The unit consists of a pipeline on which are mounted a Pneumatic Control Valve, Orifice
Block, Flowmeter and pressure tappings. The flow discharges directly to atmosphere or
via an Air Receiver to vary the 'process lag'. The Pneumatic Control Valve is operated
from a Current/Pressure Converter, and sensors for direct and differential pressure
facilitate measurement of pressure and flow respectively. Both sensors are provided with
signal conditioning units.

The unit is designed to work with the 38-200 and 38-300 Process Interface and Controller,
to configure closed loop control circuits. A supply of compressed air is required for both
flow and control.

38 Series PROCON 1-1


Chapter 1
38-714 Pressure Process Rig
INTRODUCTION Feedback Discovery Products

NOTES

1-2 38 Series PROCON


Chapter 2
38-714 Pressure Process Rig
Feedback Discovery Products DESCRIPTION

38-714 PRESSURE PROCESS RIG DESCRIPTION

The front panel of the Pressure Control System incorporates a schematic diagram of the
equipment which identifies the major components and relevant connections in standard
pneumatic notation.

The unit consists of a pipeline on which are mounted a Pneumatic Control Valve, Orifice
Block and pressure tappings. The flow discharges directly to atmosphere or via an Air
Receiver to vary the 'process lag'. The valve is operated from a Current to Pressure
Converter, and sensors for direct and differential pressure facilitates measurement of
pressure and flow respectively.

The square root extraction facility of the 38-300 Process Controller is used with the latter
to provide a linear signal. Both sensors are provided with conditioners. The pipework and
fittings are mounted on a support frame which is designed to stand on a bench top. The
unit is designed to operate with the 38-200 and 38-300 Process Interface and Controller
to configure open or closed loop control circuits.

Compressed air for the pneumatic instrumentation and process is connected to a


common inlet. Air for the instrumentation is regulated by a Regulator (R1) and the
operating pressure in indicated on a Gauge (G1). Air for the process is regulated by a
Regulator (R2) and the operating pressure is indicated on Gauge (G3).

The pneumatic instrumentation comprises a I/P Converter and Pneumatic Control Valve.
The I/P Converter accepts a 4-2OmA control signal from the 38-200 Process Interface
and converts this to a 3-l5psi pneumatic signal which operates the control valve.

The control valve comprises a diaphragm actuator which positions the stem of a plug type
valve. An indicator on the valve stem shows the actual position of the valve. A Gauge
(G2) indicates the pneumatic signal applied to the control valve by the I/P Converter. The
4-2OmA input to the I/P Converter can be connected to the 38-200 Process Connections
or the Servo Valve connection.

The air flowing through the process pipe passes through the Pneumatic Control Valve and
an Orifice Block assembly before discharging to atmosphere via a Diffuser.

A set of Valves (V1, V2 and V3) allow a rear-mounted Air Receiver to be connected in
series or parallel with the process pipe to change the response of the system (to vary the
process lag). The Air Receiver incorporates a Pressure Relief Valve.

Step changes may be applied to the process by bleeding air through an additional
Diffuser by opening and closing the Valve (V4).

38 Series PROCON 2-1


Chapter 2
38-714 Pressure Process Rig
Feedback Discovery Products DESCRIPTION

This accessory incorporates pneumatic control components of great interest to the


process industries. The design allows study of component operation and connection of
control devices through the use of current to pressure converters.

Two pressure signal conditioning units are supplied with the 38-714 Pressure Process
Rig. The pressure conditioning module (38-461 Pressure Transmitter) is used in
conjunction with the Pressure Sensor for measurement of static pressure in the process
pipe. The Pressure Sensor is connected to the process pipe by a combination of rigid and
flexible tube which includes the Pressure Gauge (G5).

The differential pressure conditioning module (38-462 Differential Pressure Transmitter) is


used in conjunction with the Differential Pressure Sensor which measures the difference
in pressure across the Orifice Block (this is used for measurement of flow). The
Differential Pressure Sensor is housed in a box which incorporates the necessary
electrical connections on the front panel. The two ports on the sensor are connected to
the Orifice Block assembly by a combination of rigid and flexible tubes.

The Pressure and Differential Pressure Transmitters are designed for mounting on the
magnetic panel. They allow the sensor outputs to be connected to the four Process
Connections on the 38-200. Control and monitoring of the system is achieved in this way.
The Pressure Sensors are connected to the signal conditioners using the 5 pin DIN leads
which are supplied with the 38-714.

When despatched, the Pressure Transmitter is set up to give an operating range of


0-10psi. The Differential Pressure Transmitter is set up to suit the maximum flow rate
through the system of 24L/min. The 4-20mA output from the Transmitters must be
calibrated prior to them being used.

2-2 38 Series PROCON


Chapter 3
38-714 Pressure Process Rig
Feedback Discovery Products INSTALLATION REQUIREMENTS

INSTALLATION REQUIREMENTS

The Pressure Process Rig 38-714 must be operated in conjunction with the 38-200
Process Interface and 38-300 Process Controller which provide the necessary signal
conditioning and control circuits.

The Pressure Transmitter and Differential Pressure Transmitter are associated with the
Pressure Sensor and Differential Pressure Sensor. They are signal conditioning units
designed for connection to the 38-200 Process Interface.

The equipment is designed for bench mounting on a firm level surface and will require
permanent connection to a supply of clean compressed air capable of providing 4 cubic
metres per hour at a pressure of 40psi gauge.

Note: An air compressor can be noisy in operation. If using a portable compressor


(not supplied) to provide the air for the instruments and process line on the 38-
714, the compressor should be located as far from the equipment as possible
to reduce disturbances to the operator.

Overall dimensions are:

Height - 0.66m

Width - 0.90m

Depth - 0.40m

38 Series PROCON 3-1


Chapter 3
38-714 Pressure Process Rig
Feedback Discovery Products INSTALLATION REQUIREMENTS

Fig 1 - Current Source Connection Diagram

3-2 38 Series PROCON


Chapter 4
38-714 Pressure Process Rig
Feedback Discovery Products COMMISSIONING

COMMISSIONING

A 38-200 and 38-300 Process Interface and Controller will be required to commission the
38-714 Pressure Control System. A 38-490 Digital Display Module is used throughout this
commissioning chapter, although this is an optional extra. It is not essential to use a
38-490 with the Pressure Process Rig.

It should also be remembered that the most thorough commissioning can only take place
after full calibration of the instruments supplied as part of the package. It is suggested that
this chapter is carefully read before continuing. Particular attention is drawn to the
WARNING and CAUTION boxes.

The following instructions describe how to set-up the 38-714 Pressure Process Rig and its
associated components in order to check for correct and safe operation.

1. Connect a supply of clean compressed air to the inlet using a reinforced air hose.
The supply must be capable of providing the required volume of compressed air at
the operating pressure, otherwise flow and pressure in the system will be
inadequate for satisfactory demonstrations.

WARNING

The maximum supply pressure should not exceed 40psi. Supply pressure
should be adequately and reliably regulated prior to presentation to the
Pressure Process Rig.

2. From Figure 1 identify all the relevant gauges and valves. Open valve V1, V3 and
V4 adjacent to the air tank connection, close valves V2, V5 and V6.

3. Adjust instrumentation pressure regulator R1 to give 25psi at G1. Pull the collar
out to adjust the regulator. Turn the collar clockwise to increase the downstream
pressure and anticlockwise to reduce the pressure. Push the collar back into place
after adjustment.

4. Adjust process pressure regulator R2 to give 10psi at G3. Air will flow through the
system, pressurising the pipes and Air Receiver to 10 psi.

5. Calibrate the Process Interface 38-200 Current Source.

Connect the Current Source to the Digital Display Module 38-490 as shown in
Figure 1.

38 Series PROCON 4-1


Chapter 4
38-714 Pressure Process Rig
Feedback Discovery Products COMMISSIONING

Turn the Current Source control fully anticlockwise to reduce the output to the
minimum. The display should read 4mA or 0%. If it does not, adjust the zero
control using a small screwdriver or trim tool until the display shows 4mA or 0%.

Turn the Current Source control fully clockwise to increase the output to the
maximum. The display should read 20mA or 100%. If it does not, adjust the span
control.

The Current Source is now calibrated.

6. Check operation of I/P Converter and Pneumatic Control Valve.

Note

If you have the 37-820 compressor unit, then connect the male union from the
38-714 to the female union on the 38-820.

If you do not have the 38-820 compressor, then remove the male fitting from
the 38-714 and use your own fitting.

38 Series PROCON 4-2


Chapter 4
38-714 Pressure Process Rig
Feedback Discovery Products COMMISSIONING

Fig 2 - I/P Converter Connection Diagram

38 Series PROCON 4-3


Chapter 4
38-714 Pressure Process Rig
Feedback Discovery Products COMMISSIONING

CAUTION

The I/P Converter input pressure should not exceed 30psi. The instrument may be
permanently damaged if this pressure is exceeded.

Connect the I/P Converter to the 38-200 4-20mA supply by making the
connections shown in Figure 2.

Set the Current Source output to minimum (4mA) by turning the adjusting knob
fully anticlockwise. Gauge G2 should indicate 3 psi with control valve fully open.
The indicator on the valve stem should be in the raised position.

Set the current source output to maximum (20mA) by turning the adjusting knob
fully clockwise. Gauge G2 should indicate 15 psi with control valve fully closed.
The indicator on the valve stem should be in the lowered position.

Note that the indicator on the valve stem provides only an approximate indication
of valve position.

Note: If the pressures indicated on G2 differ from the values stated above it will be
necessary to recalibrate the I/P Converter. This procedure is detailed in
Experiment 2.

CAUTION

The Pressure Sensors are very delicate instruments. They may be damaged if
presented with differential pressures in excess of 30psi.

38 Series PROCON 4-4


Chapter 4
38-714 Pressure Process Rig
Feedback Discovery Products COMMISSIONING

Fig 3 - Pressure Sensor Connection Diagram

38 Series PROCON 4-5


Chapter 4
38-714 Pressure Process Rig
Feedback Discovery Products COMMISSIONING

7. Check operation of the Pressure Sensor and Transmitter.

Complete the connections shown in Figure 3.

Drain all pressure from the system by fully closing R2 and fully opening V2, V4
and V5. After a few moments the system will be at atmospheric pressure
throughout. The Digital Display Module should show 4mA or 0%. If it does not,
adjust the zero control until the desired reading is obtained.

Pressurise the Air Receiver by opening V1 and closing V2 then adjusting R2 to


produce a reading 0.7 bar of 10psi on G3. After a few moments the Air Receiver
pressure gauge will read 10psi.

The Digital Display Module should read 20mA or 100%. If it does not, adjust the
span control until the desired reading is obtained. Repeat the above process
checking readings of 0% at atmospheric pressure and 100% at 10psi.

38 Series PROCON 4-6


Chapter 4
38-714 Pressure Process Rig
Feedback Discovery Products COMMISSIONING

Fig 4 - Differential Pressure Sensor Connection Diagram

38 Series PROCON 4-7


Chapter 4
38-714 Pressure Process Rig
Feedback Discovery Products COMMISSIONING

8. Check operation of Differential Pressure Sensor and Transmitter.

Complete the connections shown in Figure 4.

Open valves V2, V4, V5 V6 and V7. Close valves V1 and V3 (ensure V7 is fully
open).

Drain all pressure from the system by fully closing R2 and fully opening V2. After a
few moments the system will be at atmospheric pressure throughout. The Digital
Display Module should show 4mA or 0% to indicate the zero flow condition. If it
does not, adjust the zero control until the desired reading is obtained.

Create a full flow condition by adjusting R2 until a 10psi difference is shown


between the reading on G4 and the reading on G5. This should easily be
achieved. The Digital Display Module should show 20mA or 100%. If it does not,
adjust the span control until the desired reading is obtained. When G4 indicates
10psi and G5 indicates zero the flow meter will show a flow of approx 24
litres/min.

38 Series PROCON 4-8


Chapter 5
38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTAL INDEX

EXPERIMENTAL INDEX

1 To Calibrate the Pressure Sensor and Transmitter and Investigate the Linearity and
Hysteresis of the Sensor/Transmitter.

2 To Calibrate the Current to Pressure Converter to Operate the Pneumatic Control


Valve and Investigate the Linearity and Hysteresis of the Converter.

3 To Demonstrate Manual Operation of the Pneumatic Control Valve and to


Determine its Characteristics (Pressure/Position).

4 To Determine the System Response With and Without the Air Receiver by Manually
Operating the Pneumatic Control Valve.

5 To Control Pressure in the Process Pipe using a Pressure Sensor and Three-Term
Controller with Proportional Output to an I/P Converter and Pneumatic Control
Valve.

Effect of Disturbances.

Changing the Set Point Remotely.

6 To Demonstrate the Characteristics of a (P) Proportional Only Process Controller


and the Response to a Change in Set Point or a Disturbance to the Process.

Effect of Disturbances.

Effect of Changing the Set Point.

Effect of Changing the Proportional Band.

7 To Demonstrate the Characteristics of a (P+I) Proportional+Integral Action Process


Controller and the Response to a Change in Set Point or a Disturbance to the
Process.

Effect of Disturbances.

Effect of Changing the Set Point.

Effect of Changing the Integral Action Time.

Effect of Changing the Proportional Band.

38 Series PROCON 5-1


Chapter 5
38-714 Pressure Process Rig
EXPERIMENTAL INDEX Feedback Discovery Products

8 Characteristics of a (P+D) Proportional + Derivative Action Process Controller and


the Response to a Change in Set Point or a Disturbance to the Process.

Effect of Disturbances.

Effect of Changing the Set Point.

Effect of Changing the Derivative Action time.

Effect of Changing the Proportional Band.

9 To Demonstrate Typical Procedures for Optimising the Settings of a Three-Term


Controller to Suit a Particular Process.

Ultimate Period Method (Ziegler Nichols).

Reaction Curve Method.

Auto-Tune.

Evaluation of the Controller Settings by Applying a Disturbance to the Process.

10 To Demonstrate the Effect of the Air Receiver on the Response of the Process
and to Determine the Optimum Settings for the Process Controller.

11 To Calibrate the Differential Pressure Sensor and Transmitter.

12 To Control Flow in the Process Pipe using a Differential Pressure Sensor/Orifice


Block with Square Root Extracting Three-Term Controller with Proportional Output
to an I/P Converter and Pneumatic Control Valve.

Effect of Disturbances.

Changing the Set Point Remotely.

Repeat of Pressure Control Experiments.

5-2 38 Series PROCON


Chapter 6
38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENTS

EXPERIMENT 1

Object of Experiment:

To calibrate the pressure sensor and pressure transmitter and to investigate the linearity
and hysteresis of the sensor/transmitter.

Equipment Required:

38-200 Process Interface

38-714 Pressure Process Rig

38-461 Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Optional Equipment:

0.5 Metre Mercury Manometer or Digital Pressure Sensor (not supplied).

38 Series PROCON 6-1-1


Chapter 6
38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 5 - Experiment 1 Connection Diagram

6-1-2 38 Series PROCON


Chapter 6
38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Initial Settings:

Complete the connections shown in Figure 5.

R1 & R2 Closed

V2 Open

(all other valves closed)

The Process Controller is not required for this experiment.

Experimental Details:

The aim of this experiment is to calibrate the Pressure Sensor and Transmitter to give the
following conditions.

Minimum pressure = 0 psi = 4mA output from the Pressure Transmitter

Maximum pressure = 10psi = 20mA output from the Pressure Transmitter

Note: The Pneumatic Control Valve is designed to open with lack of air. With R1
closed and the I/P Converter disconnected, the valve will remain open.

If an accurate Manometer or Digital Pressure Gauge is available this may be connected


underneath the Bourdon gauge (G5) to allow a more precise calibration to be performed.
(Note that the connection is a 1/4 inch push-fitting).

With R2 closed, the pressure in the system will be atmospheric (ie the minimum required,
0psi on gauge G5 or 0mm differential on the manometer). Use a small screwdriver or trim
tool to adjust the zero control on the Pressure Transmitter to give a reading of 4mA or 0%
on the Digital Display Module

Open valve V4. Set the pressure in the system to the maximum required (10.0psi on
gauge G5 or 414mm on the manometer) by adjusting valve R2. When the pressure is
steady, adjust the span control on the Pressure Transmitter to give a reading of 20mA or
100% on the Digital Display Module.

Repeat the minimum and maximum settings until no further adjustments of the zero and
span controls is required.

Linearity and hysteresis

Having calibrated the Pressure Sensor and Transmitter, it is interesting to determine the
linearity of the output over the operating range from minimum to maximum pressure.

Adjust the pressure in the system in steps of 2 psi from 0 psi to 10 psi indicated on gauge
G5.

38 Series PROCON 6-1-3


Chapter 6
38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Alternatively, if using a Mercury Manometer, adjust the pressure in steps of 50mm from
0mm to 515mm differential reading on the manometer

Note: 1mmHg = 0.01934 psi

Record the pressure and corresponding output from the Pressure Transmitter at each
step. Repeat for reducing pressure in the system to investigate the hysteresis in the
sensor. Plot the pressure versus the output voltage to determine the linearity and
hysteresis.

Typical Results:

Pressure (psi) Rising Percentage Falling Percentage

0 0 0.5

2 22 17

4 40 36

6 62 57

8 80 79

10 100 100

Note: The Bowden gauges fitted to the 38-714 are only 10% accurate therefore you
may get some variation from these results.

Further Experiments:

Repeat the procedures outlined above for different minimum and maximum pressures in
the system.

DO NOT EXCEED A READING OF 30PSI ON GAUGE G5 AS SENSOR DAMAGE


COULD OCCUR. PLEASE REFER TO ‘COMMISSIONING’.

Conclusions:

A Pressure Sensor may be used to give a remote reading of pressure in a system. This
feature will be used in later experiments to enable the level to be controlled automatically.

It is necessary to calibrate an electrical sensor (with its conditioning circuit) before use to
provide an output which is meaningful.

The Pressure Sensor may be calibrated to suit the operating range and datum required
for a particular application.

6-1-4 38 Series PROCON


Chapter 6
38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

The sensor supplied has an output which changes linearly with change in pressure, and
hysteresis is small. Note that this characteristic will not apply to all Pressure Sensors used
in process control.

Resolution of the Pressure Sensor is much finer than the Bourdon gauge which is
designed for indication of approximate pressure only.

For accuracy in operation, a Pressure Sensor should be calibrated using a manometer or


dead weight calibrator.

38 Series PROCON 6-1-5


Chapter 6
38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 6 - Experiment 2 Connection Diagram

6-1-6 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 2

Object of Experiment:

To calibrate the Current/Pressure (I/P) Converter to operate the Pneumatic Control Valve
and investigate the linearity and hysteresis of the converter.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Process Rig

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Optional Equipment:

None.

Initial Settings:

Complete the connections shown in Figure 6.

R2, V 1, V3, V5 & V6 Closed

R1, V2 & V4 Open

Adjust R1 to give a reading of 25 psi on gauge G1.

For this set of demonstrations the 38-300 Process Controller will be used in Manual
operation mode to operate the I/P Converter. Calibration of the controller is not required.

Switch-on the controller. The initial message ‘300 test’ will be seen. After a short time the
display then begins to show the set-point (SP) and process variable (PV) ready for normal
operation.

38 Series PROCON 6-2-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Experimental Details:

The aim of this experiment is to calibrate the I/P Converter to position the Pneumatic
Control Valve with the following characteristics:

4mA to converter = 3 psi from converter (on G2) = Pneumatic Control Valve open

20mA to converter = 15 psi from converter (on G2) = Pneumatic Control Valve closed

Note: The Pneumatic Control Valve is designed to open with lack of air.

Connect the I/P Converter to the output of the Process Controller as shown in the set-up
diagram.

Connect the compressed air supply to the inlet.

Ensure that gauge G1 reads 25psi. Adjust R1 if necessary.

Set the Process Controller to Manual operation by pressing the Auto/Manual button
until the LED marked ‘M’ lights.

Remove the plastic stoppers which seal the zero and span adjusting controls on the I/P
Converter. Note the span control on the I/P Converter is called 'Range'.

Press the Parameter Advance button once to display the control output in the lower
screen. The screen should show ‘op 0.0’ to show a zero output effort. If it does not,
press the Parameter Decrease button to reduce the value to zero.

Adjust the zero output on the I/P Converter to give a reading of 3 psi on gauge G2. The
Pneumatic Control Valve should be just on the point of starting to close. This could be
described as a ‘braced’ position.

Adjust the output from the Process Controller to 100% by pressing and holding the
Parameter Increase button. The Process Controller output is now 20mA.

Adjust the span (range) control on the I/P Converter to give a reading of 15 psi on gauge
G2. The Pneumatic Control Valve should be just fully closed.

Repeat the minimum and maximum settings until no further adjustments of the zero and
span controls is required.

Replace the plastic stoppers on the zero and span controls.

Check the operation of the Pneumatic Control Valve.

With the output from the controller set to 0%, adjust valve R2 until a reading of 10 psi is
indicated on gauge G5. Valve V2 should be open, all other valves should be closed.

6-2-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Adjust the output from the Process Controller to 100%.

Observe that the pressure in the system falls to zero with the valve closed.

Note: The Pneumatic Control Valve is not designed to isolate totally when in the
position. A small amount of air will leak past the valve seat and from the system.
An Isolation or Stop Valve is required to completely remove leakage. The small
amount of air bleeding through the valve causes the float in the flow meter to
attempt to lift very slightly and a clicking noise can be heard from the flow meter.

Adjust the output from the controller to intermediate settings (e.g. 40% and 60%) and
observe the change in valve position and the change in pressure on gauge G5.

Further Experiments:
To investigate the linearity and hysteresis of the I/P Converter
Close valve R2.
Adjust the controller output to 0% (4mA).
Confirm that the corresponding output from the I/P Converter is 3 psi on gauge G2.
Adjust the controller output from 0% to 100% in steps of 10% and record the
corresponding pressure from the I/P Converter on gauge G2. Repeat for reducing inputs
to the I/P Converter.
Plot the input versus the output for rising and falling inputs to determine the linearity and
hysteresis of the I/P Converter.
Note that the pressure gauge used to perform this experiment has a stated accuracy of
only ±3% of full scale.
Conclusions:
A Pneumatic Control Valve requires a current to pressure converter to change the
electrical signal from the control circuit to a corresponding pressure which can actuate the
valve.
It is necessary to calibrate a current to pressure converter before use to provide the
appropriate output to a Pneumatic Control Valve.
In this pneumatic control system, the equivalent of the 4 to 20mA electronic signal is 3 psi
to 15 psi.
The Pneumatic Control Valve should not be used in applications where total shut-off is
required. An additional Isolating or Stop valve should be used. Note that this
characteristic will apply to the majority of proportional control valves used in process
control.
The I/P Converter provides a largely linear conversion from current input to pneumatic
output. Hysteresis is small.

38 Series PROCON 6-2-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Control Valve Linearity

Typical Results:

Controller Output (%) Increasing G2 psi Decreasing G2 psi


0 3.0 3.0
10 3.5 4.0
20 5.0 5.0
30 6.0 6.5
40 7.3 7.8
50 8.5 9.0
60 10.0 10.0
70 11.0 11.5
80 12.5 13.0
90 13.7 14.0
100 15.0 15.0

6-2-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

NOTES

38 Series PROCON 6-2-5


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 7 - Experiment 3 Connection Diagram

6-2-6 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 3

Object of Experiment:

To demonstrate manual operation of the Pneumatic Control Valve and to determine its
characteristics (pressure/position).

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Process Rig

38-461 Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Optional Equipment:

None.

Initial Settings:

Complete the connections shown in Figure 7.

V1, V3 & V6 Closed

R1, R2, V2, V4 & V5 Open

Adjust R1 to give 25psi on gauge G1.

Adjust R2 to give 10 psi on gauge G5 with the Pneumatic Control Valve open.

For this set of demonstrations the controller will be used in Manual operation mode to
operate the I/P Converter.

Switch-on the controller. The initial message ‘300 test’ will be seen. After a short time the
display begins to show the set-point and process variable ready for normal operation.

38 Series PROCON 6-3-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

The Process Controller is factory calibrated in the following way:

Span 100% represents 20mA input or output

Zero 0% represents 4mA input or output

The Pressure Sensor and Transmitter are calibrated in the following way:

0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range

10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of range

Experimental Details:

The Pneumatic Control Valve comprises a plug type valve operated by a pneumatic
actuator which receives a 3 to 15 psi pneumatic signal from a Current to Pressure
Converter.

The most useful characteristic of the control valve is the relationship between current
input to the I/P Converter and pressure in the process pipe downstream of the valve.

The relationship between current input and corresponding process variable is relevant in
control applications.

The aim of this experiment is to demonstrate how the valve may be opened or closed to
any intermediate position using a 4-20mA current and to obtain the characteristics of
pressure versus position.

Connect the equipment as shown in the set-up diagram.

Set the Process Controller to Manual operation by pressing the Auto/Manual button
until the LED marked ‘M’ lights.

Fully open the Pneumatic Control Valve by manually changing the Process Controller
output in the following manner.

Press the Parameter Advance button once to display the control output in the lower
screen. The screen should show ‘op 0.0’ to show a zero output effort. If it does not,
press the Parameter Decrease button to reduce the value to zero.

The Pneumatic Control Valve should now be fully open as the control output is 0%.

Check that the maximum pressure is 100% on the process variable display of the
controller (10 psi on gauge G5). If not adjust R2.

Close the Pneumatic Control Valve by setting the controller output to 100% (20mA) by
pressing and holding the Parameter Increase button. Check that the process
variable falls to 0% (0 psi on gauge G5).

6-3-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Using the Parameter Increase and Decrease buttons, adjust the position of the
valve in steps of 10% from 0% to 100% by adjusting the controller output manually.

At each position of the valve record the corresponding pressure on the process variable
display.

Repeat the procedure for the valve opening in steps of 10% to determine any hysteresis.

Typical Results:

Controller Output (%) Process Variable (%)


0 100
10 98
20 95
30 89
40 81
50 71
60 57
70 37
80 21
90 7
100 0

Further Experiments:

To demonstrate the change in characteristic when operated over a different range


of pressures

The Pressure Sensor may be recalibrated to operate over a different range, e.g. 0 to 12
psi. However, for the purpose of demonstration, the pressures may be read directly on
gauge G5 to avoid the need for recalibration.

Adjust regulator R2 to give a reading of 12 psi on gauge G5 with the Pneumatic Control
Valve fully open.

Repeat the above procedure but read the corresponding pressures directly on gauge G5.

Observe the change in characteristic noting that the change from 10 psi to 12 psi
operating pressure is a relatively small change.

38 Series PROCON 6-3-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Conclusions:

The plug-type valve provides a fine adjustment of flow through the valve and is ideal for
the purpose of pressure control.

A 4-20mA control signal may be used to open or close a valve to any intermediate
position. This facility to operate a valve remotely allows a process to be controlled
automatically when the valve is connected to an appropriate sensor and controller.

Although the Pneumatic Control Valve supplied does not have a truly linear characteristic,
it is satisfactory for control purposes at the operating pressure suggested. As the pressure
is increased, the relationship becomes less linear.

The control valve must be carefully selected to give the correct characteristics over the
normal range of operation.

6-3-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

NOTES

38 Series PROCON 6-3-5


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 8 - Experiment 4 Connection Diagram

6-3-6 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 4

Object of Experiment:

To determine the system response with and without the Air Receiver by manually
operating the Pneumatic Control Valve.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Process Rig

38-461 Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Optional Equipment:

None.

Initial Settings:

Complete the connections shown in Figure 8.

V1, V3, V5 & V6 Closed

R1, R2, V2 & V4 Open

Adjust R1 to give 25psi on gauge G1.

Adjust R2 to give 10 psi on gauge G5 with Pneumatic Control Valve open.

Switch-on the controller. The initial message ‘300 test’ will be seen. After a short time the
display begins to show the set-point and process variable ready for normal operation.

The Process Controller is factory calibrated in the following way:

Span 100% represents 20mA input or output

Zero 0% represents 4mA input or output

38 Series PROCON 6-4-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

The Pressure Sensor and Transmitter are calibrated in the following way:

0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range.

10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of


range.

Experimental Details:

Connect the equipment as shown in the set-up diagram.

The current output from the Pressure Transmitter should be connected to the process
variable input of the Process Controller to indicate the pressure in the process pipe as
measured by the sensor. A chart recorder or the PROCON Discovery Software System
38-906 (if available) should be connected in the Pressure Transmitter output/Process
Controller input 4-20mA loop to give a clear indication of the responses. The changes
may best be observed by watching the pressure indicated on gauge G5 (the digital
changes on the process variable display may be too rapid to observe).

The object of the demonstration is to maintain the pressure of the air in the process pipe
at a preset value.

Operation without Air Receiver

Set the Process Controller to manual operation by pressing the Auto/Manual button.

Press the Parameter Advance button to show the controller output in the lower
display.

Using the button, adjust the output from the controller to 50% (the lower display will
show OP 50.0) and note the corresponding process variable (pressure in the process
pipe) when the system has settled.

Change the output from the controller to 60%. Observe the change in process variable.

Change the output from the controller to 50%. Note that the process variable returns to
the original value.

Adjust the position of the Pneumatic Control Valve to give a process variable reading of
50%. Note the output from the controller.

Open valve V5 to give additional outflow and observe the response of the process
variable.

Readjust the output from the controller to return the process variable to 50%.

Close valve V5 and observe the response of the process variable. Adjust the controller
output to its original value and observe that the process variable returns to 50%.

6-4-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Operation with Air Receiver

Fully open valve V1, open V3 and close valve V2 so that the air leaving the process pipe
travels through the Air Receiver before discharging.

Repeat the procedure outlined above and observe the slower changes in response with
the Air Receiver in series with the process pipe.

Conclusions:

Proportional adjustment of flow into the process pipe gives a steady pressure at the
required value provided the process characteristics remain constant, ie a change in
conditions in the system necessitates a corresponding change in valve position to
maintain the pressure.

The Pneumatic Control Valve provides proportional adjustment of flow into the process
pipe by remote operation using a 3-15 psi control signal.

Without the Air Receiver, disturbances cause the process variable to change very quickly.

With the Air Receiver in series, changes in process variable are much less fast.

The Air Receiver has the effect of changing the response of the process (time constant).

38 Series PROCON 6-4-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 9 - Experiment 5 Connection Diagram

6-4-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 5

Object of Experiment:

To control pressure in the process pipe using the Pressure Sensor and three-term
Process Controller with 4-20mA proportional output to an I/P Converter and Pneumatic
Control Valve.

Note: This experiment is intended to introduce and demonstrate the principle of using a
proportioning valve. Experiments 6 to 8 introduce the for setting up a Process
Controller.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Control Module

38-461 Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Initial Settings:

Complete the connections shown in Figure 5.

V2, V5 & V6 Closed

R1, R2, V1, V3 & V4 Open

Adjust R1 to give 25psi on gauge G1.

Adjust R2 to give 10 psi on gauge G5 with Pneumatic Control Valve open. The Air
Receiver pressure will begin to rise towards 10psi.

Switch-on the Process Controller. The initial message ‘300 test’ will be seen. After a
short time the display begins to show the set-point and process variable ready for normal
operation.

This experiment requires that the Process Controller be configured for three-term control.

38 Series PROCON 6-5-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

The following parameters should be set:

Controller Parameter Setting Units


Set Point 50 %
Proportional Band 300 %
Integral Time 5 Secs
Derivative Time OFF Secs
Span 100 % at 20mA input
Zero 0 % at 4mA input

The set-point can be assigned by pressing the Up or Down buttons until the
lower display shows ‘50.0’.

The proportional band is assigned by pressing the Page Advance button until the
‘Contrl page’ display is seen. Press the Parameter Advance button until the
proportional band page is reached; ‘prop’ is shown in the upper display. Change the
proportional band value to 300 by pressing the Up or Down buttons. Confirm
the change by pressing the Enter button.

The integral time is assigned by pressing the Parameter Advance button whilst in the
control page until ‘intgrl’ is shown in the upper display. Adjust the integral time using the
Up or Down buttons until ‘5’ is shown in the lower display. Confirm the change
by pressing the Enter button.

The derivative time is assigned by pressing the Parameter Advance button whilst in
the control page until ‘deriv’ is shown in the upper display. Adjust the derivative time
using the Up or Down buttons until ‘off’ is shown in the lower display. Confirm
the change by pressing the Enter button.

The span and zero parameters are preset and require no adjustment.

The Pressure Sensor and Transmitter are calibrated in the following way:

0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range

10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of range

Experimental Details:

To maintain a steady pressure in the process pipe, the Pneumatic Control Valve must be
opened to the appropriate position by the Process Controller and continually adjusted to
compensate for changes upstream or downstream in the system.

6-5-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

The Air Receiver has been included in the circuit to give a slow response to the process.
The object of the demonstration is to maintain the pressure at the set point (50% process
variable on the controller corresponds to 5psi on gauge G5).

As the Pneumatic Control Valve is open when 4mA is applied to the I/P converter and a
pressure below the set point requires the valve to be opened, the Process Controller is
configured for DIRECT action. The control action can be checked, and altered if
necessary, by pressing the Page Advance button until the display shows ‘setup
contrl’. Press the Parameter Advance button until the upper display shows ‘action’.
The lower display will toggle between ‘rev’ and ‘dir’ (the required setting) when pressing
the Up and Down buttons. Press the Enter button to confirm any change.

Connect the equipment as shown in the set-up diagram.

A recorder may be connected to the Pressure Transmitter output/controller input and


controller output/current to pressure converter input 4-20mA loops to provide a record of
the response.

If the set-up is correct, air should be delivered to the process pipe and discharge at the
outlet with the pressure remaining at 50% (process variable).

Observe that the pressure is controlled at the set point.

Effect of disturbances

Open valve V5 to give an additional outflow from the system.

Observe the response of the system. The Pneumatic Control Valve will open to give the
required additional flow of air to maintain the pressure in the process pipe at the set point.

Close valve V5. Observe the response as the Pneumatic Control Valve closes to maintain
the pressure.

Observe the changes in air flow on the flow meter.

Further Experiments:

Changing the set point remotely

In the basic set-up, the pressure was controlled about a mean value of 50% which
corresponds to 5 psi on gauge G5.

Adjust the set point to 70% on the Process Controller by pressing the Up button.

38 Series PROCON 6-5-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Observe how the pressure changes to the required setting and the position of the
Pneumatic Control Valve varies to suit the conditions.

Adjust the set point to 40% on the Process Controller, by pressing the Down button.

Once again, observe the changes in the level and the valve operation.

Conclusions:

Pressure in the process pipe can be controlled using a Pressure Sensor and Process
Controller configured for proportional output (4-20mA) to position a Pneumatic Control
Valve as required.

Proportional control of the Pneumatic Control Valve allows the pressure to be held at the
required set point despite changes in the upstream and downstream conditions.

The pressure in the system may be changed by setting an alternative set point on the
controller. No adjustment to the process or sensor is required provided the inlet and outlet
conditions are compatible with the new setting.

6-5-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

NOTES

38 Series PROCON 6-5-5


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 10 - Experiment 6 Connection Diagram

6-5-6 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 6

Object of Experiment:

To demonstrate the characteristics of a (P) Proportional only Process Controller and the
response to a change in set point or a disturbance in the process.

Note: It is assumed that the operator understands the meaning of Proportional Band.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Control Module

38-461 Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Optional Equipment:

None.

Initial Settings:

Complete the connections shown in Figure 10.

V1, V3, V5 & V6 Closed

R1, R2, V2 & V4 Open

Adjust R1 to give 25 psi on gauge G1.

Adjust R2 to give 10 psi on gauge G5 with Pneumatic Control Valve open.

38 Series PROCON 6-6-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

For this set of demonstrations the Process Controller should be configured for
proportional control with the following initial settings:

Controller Parameter Setting Units


Set Point 40 %
Proportional Band 300 % Check value
Integral Time OFF Secs
Reset 50 %
Derivative Time OFF Secs
Span 100 % at 20mA input
Zero 0 % at 4mA input

The set-point can be assigned by pressing the Up or Down buttons until the
lower display shows ‘50.0’.

The proportional band is assigned by pressing the Page Advance button until the
‘Contrl page’ display is seen. Press the Parameter Advance button until the
proportional band page is reached; ‘prop’ is shown in the upper display. Change the
proportional band value to 300 by pressing the Up or Down buttons. Confirm
the change by pressing the Enter button.

The integral time is assigned by pressing the Parameter Advance button whilst in the
control page until ‘intgrl’ is shown in the upper display. Adjust the integral time using the
Up or Down buttons until ‘off’ is shown in the lower display. Confirm the change
by pressing the Enter button.

The derivative time is assigned by pressing the Parameter Advance button whilst in
the control page until ‘deriv’ is shown in the upper display. Adjust the derivative time
using the Up or Down buttons until ‘off’ is shown in the lower display. Confirm
the change by pressing the Enter button.

The span and zero parameters are preset and require no adjustment.

The Pressure Sensor and Transmitter are calibrated in the following way:

0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range

10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of range

6-6-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Experimental Details:

The object of the demonstration is to control the pressure in the process pipe using a P'
only controller to operate the Pneumatic Control Valve.

As the Pneumatic Control Valve is open when 4mA is applied to the I/P Converter and a
pressure below set point requires the valve to be opened, the controller must be
configured for DIRECT action. The control action can be checked, and altered if
necessary, by pressing the Page Advance button until the display shows ‘setup
contrl’. Press the Parameter Advance button until the upper display shows ‘action’.
The lower display will toggle between ‘rev’ and ‘dir’ (the required setting) when pressing
the Up and Down buttons. Press the Enter button to confirm any change.

Connect the equipment as shown in the set-up diagram.

A recorder may be connected to the Pressure Transmitter output/Controller input and


Controller output/Current to Pressure Converter input 4-20mA loops to provide a record of
the response.

Removing offsets

The controller fitted in the 38-300 has an option for the removal of offsets in proportional
only systems. This option is known as manual reset and allows the operator to reduce the
offsets to zero by offsetting the proportional band between 0 and 100% in 0.1%
increments.

The Manual reset option will only function when no integral action has been selected.

We need to consider how the manual reset function operates.

Ensure the Integeral and Derivative options are turned off.

Set the Proportional Band to 300% and set the setpoint to 50%.

On the process rig set valves V1, V3 and V6 to closed and valves V2, V4 and V5 to open.

From the operating panel of the controller select the manual reset option by pressing the
Paramater Advance twice. The lower display shows the character r followed by the
current value of manual reset. The top display shows the measured value of the process
variable, in this case the pressure at gauge G5.

Adjust the manual reset option until the measured value is 50%, hence there is no offset.
This should be till about 38% of normal reset.

38 Series PROCON 6-6-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Change the set point to 40% and observe the effect on offset. Notice the offset has
returned. Hence we have shown the manual reset option only reduces the offset for a
given setpoint. Moving the setpoint requires the operator to make an adjustment to the
amount of normal reset.

Return the setpoint to 50% and observe the offset is removed using the proceedure
previouly outlined.

Close valve V4 and observe the effect on the offset. Adjust the manual reset until the
offset is reduced to zero. This should be around 21%. Hence we have shown that when
there is a change in demand in the process the controller requires manual adjustment to
reduce the offset in a Proportional only system.

Reduce the Proportional Band to 200% and observe the effect on the offset. Notice the
offset is unaffected by the changed PB.

Reduce the PB to 100% and open valve V4 to introduce a step response on the system.
Observe the oscillating response from the process. It takes around 20 seconds to settle.
Increase the PB to 400% and close valve V4. Once the system has settled, open valve
V4. Notice how less oscillatory the process is.

Effect of disturbances

Open valve V3 a little more to give a disturbance to the process.

Observe the response of the system. The Pneumatic Control Valve will open to give
additional inflow to maintain the pressure at the set point.

Observe the offset from the set point.

Return valve V4 to its original position. Observe the response as the Pneumatic Control
Valve closes to maintain the pressure. Observe that the pressure returns to the set point.

Effect of changing the set point

Adjust the set point to 70% on the Process Controller.

The Pneumatic Control Valve will open to increase the flow into the process pipe to
compensate for the increased pressure requirement. Observe that the pressure does not
achieve the revised set point.

Adjust the set point to 30% on the Process Controller. Once again, observe the changes
in the pressure and the valve operation.

Adjust the set point to 50% on the Process Controller.

Observe that the pressure returns to the set point.

Adjust the set point to 70% on the Process Controller.

6-6-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Manually adjust output from the controller to maintain the process variable at 70%.
Return the controller to Automatic operation and observe that offset from the set point is
removed.
Adjust the set point to 50% on the Process Controller.
Observe that the process variable is offset from the set point.
Further Experiments:
Effect of changing the Proportional Band:
Set the Proportional Band to 20% on the controller. Repeat the above experiment and
observe the reduction in offsets.
Set the Proportional Band to 5% on the controller. Repeat the above experiment and
observe the dramatic reduction in offsets.
Set the Proportional Band to 1% on the controller. Observe that the process has become
unstable, ie the Proportional Band setting is too small.
Conclusions:
As the process variable deviates from the set point, the output from the controller will
change in an attempt to restore the process variable to the set point.
A small setting of Proportional Band means a large change in controller output (large
movement of the valve) for a small deviation from the set point.
If the setting of the Proportional Band is too small, the control loop will be unstable and
continuous large scale oscillation of the control valve will occur.
If the setting of the Proportional Band is too large, the process variable will be offset from
the set point by a large amount.
The controller centralises the Proportional Band about the set point. If a new set point is
instructed by the operator, the controller will produce an output of 50% (12mA) when the
process variable matches the new set point.
The operator can offset the output to give accurate control of the process by setting the
system up manually before transferring to Automatic control. Any changes in the process
(e.g. change in outflow from the process tank) will result in an offset from the set point.
Any offset applied to the controller output will be transferred if a new set point is
instructed, ie the output will be centralised about the new set point but offset by the
amount of offset at the previous set point.
The optimum setting of Proportional Band is the smallest setting which will allow the
process to operate with minimum offset while not allowing the system to become unstable.
The process should be operated manually to achieve the required operating conditions
then transferred to Automatic operation to minimise offsets from the set point.

38 Series PROCON 6-6-5


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 11 - Experiment 7 Connection Diagram

6-6-6 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 7

Object of Experiment:

To demonstrate the characteristics of a (P + I) Proportional + Integral Action Process


Controller and the response to a change in set point or a disturbance to the process.

Note: It is assumed that the operator understands the meaning of Proportional Band

and Integral Action.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Control Module

38-461 Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Initial Settings:

Complete the connections shown in Figure 11.

V1, V3 & V6 Closed

R1, R2, V2, V4 & V5 Open

Adjust R1 to give 25psi on G1.

Adjust R2 to give 10psi on G5 with the Pneumatic Control Valve open.

38 Series PROCON 6-7-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

For this set of demonstrations the Process Controller should be configured for three-term
control with the following initial settings:

Controller Parameter Setting Units

Set Point 50 %

Proportional Band 300 %

Integral Time 5 Secs

Derivative Time OFF Secs

Span 100 % at 20mA input

Zero 0 % at 4mA input

Follow the instructions given in earlier experiments regarding operation of the Process
Controller. Further information can be found in the Process Controller user manual.

The Pressure Sensor and Transmitter are calibrated in the following way:

0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range

10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of range

Experimental Details:

The object of the demonstration is to control the pressure in the process pipe using a 'P+I'
controller to operate the Pneumatic Control Valve.

As the Pneumatic Control Valve is open when 4mA is applied to the current/pressure
converter and a pressure below the set point requires the valve to be opened, the
Process Controller is configured for DIRECT action. See the instructions given in earlier
experiments regarding setting the controller for direct or reverse action.

Connect the equipment as shown in the set-up diagram.

A recorder or the 38-906 Software running on a suitable computer may be connected to


the Pressure Transmitter output/controller input and controller output/current to pressure
converter input 4-20mA loops to provide a record of the response.

Note: The controller is set for 300% Proportional Band and 5 secs Integral Action Time.

6-7-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Effect of disturbances

Allow the system to settle with no deviation.

Close valve V4 further to give a disturbance to the process.

Observe the response of the system. The Pneumatic Control Valve will close to reduce
the pressure at the set point. Observe that the initial offset from the set point is gradually
removed as the Integral Action moves to the required position. Now open V4 and observe
the system responding by increasing the air flow until the pressure is returned to the
setpoint.

Effect of changing the set point

Adjust the set point to 70% on the Process Controller.

Observe the initial response due to Proportional Action followed by the gradual correction
due to Integral Action.

Adjust the set point to 30% on the Process Controller. Once again, observe the changes
in the pressure and the valve operation.

Adjust the set point to 50% on the Process Controller and allow the process to settle at
the set point.

Further Experiments:

Effect of changing the Integral Action Time

Set the Integral Action Time to 1 second on the controller.

Repeat the above experiment and observe the reduced effect of the Integral Action (the
effect is the same but the time taken to reduce the offset is decreased).

Effect of changing the Proportional Band

Set the Proportional Band to 200% and the Integral Action to 5 seconds on the controller.

Apply a disturbance to the process or change the set point as described above and
observe the response of the process.

Besides the reduced offset due to Proportional Action observe that the amount of
correction applied by Integral Action is increased.

Open valves V1 & V3 and close V2 to connect the air receiver. Observe the effect of this
while repeating the above.

38 Series PROCON 6-7-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Conclusions:

Integral Action will remove offsets from the set point which occur with Proportional control.

Correction is applied to the output from the controller while any deviation from the set
point exists.

A short setting of Integral Action Time means greater Integral Action effect on the output
from the controller. (The output is corrected more frequently).

The amount of correction applied to the output by the Integral Action is related to the
Proportional Band setting. (A large Proportional Band means a smaller correction due to
the Integral Action).

Increasing the time constant of the system makes the process more oscillatory and
increases the setting time.

Note: Short settings of the Integral Action Time can be used in the pressure control
demonstration to give fast correction of large offsets because the system
responds quickly to changes. In a process where disturbances take a long time to
affect the process variable, the amount of Integral Action must be limited (ie use
longer Integral Action Time) to avoid problems of saturation. If the IAT setting is
too small, extreme actuation of the control valve will occur before the process has
responded to initial valve adjustments. 38-100 and 38-600 involve processes with
longer response times and may be used to demonstrate this feature.

6-7-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

NOTES

38 Series PROCON 6-7-5


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 12 - Experiment 8 Connection Diagram

6-7-6 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 8

Object of Experiment:

To demonstrate the characteristics of a (P + D) Proportional + Derivative Action Process


Controller and the response to a change in set point or a disturbance to the process.

Note: It is assumed that the operator understands the meaning of Proportional Band
and Derivative Action.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Control Module

38-461 Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Initial Settings:

Complete the connections shown in Figure 12.

V1, V3 & V6 Closed

R1, R2, V2, V4 & V5 Open

Adjust R1 to give 25psi on G1.

Adjust R2 to give 10psi on G5 with the Pneumatic Control Valve open.

38 Series PROCON 6-8-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

For this set of demonstrations the Process Controller should be configured for three-term
control with the following initial settings:

Controller Parameter Setting Units

Set Point 50 %

Proportional Band 300 %

Integral Time OFF Secs

Derivative Time 2 Secs

Span 100 % at 20mA input

Zero 0 % at 4mA input

Follow the instructions given in earlier experiments regarding operation of the Process
Controller. Further information can be found in the Process Controller user manual.

The Pressure Sensor and Transmitter are calibrated in the following way:

0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range

10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of range

Experimental Details:

The object of the demonstration is to control the pressure in the process pipe using a
'P+D' controller to operate the Pneumatic Control Valve.

As the Pneumatic Control Valve is open when 4mA is applied to the current/pressure
converter and a pressure below the set point requires the valve to be opened, the
Process Controller is configured for DIRECT action. See the instructions given in earlier
experiments regarding setting the controller for direct or reverse action.

Connect the equipment as shown in the set-up diagram.

A recorder may be connected to the Pressure Transmitter output/controller input and


controller output/current to pressure converter input 4-20mA loops to provide a record of
the response.

Note: The controller is set for a 50% Proportional Band and a Derivative Action Time of
6 seconds.

6-8-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Manual operation to remove initial offsets

Carry out the procedure for removal of offsets detailed on page 6-6-3.

Effect of disturbances

Close valve V4 further to give a disturbance to the process. Observe the response of the
system as the Pneumatic Control Valve closes to reduce the pressure at the set point.
Observe the large initial closing of the control valve occurs as the process variable moves
away from the set point followed by an opening of the valve as the process variable
approaches the set point. Note that the offset from the set point is not removed by the
Derivative Action.

Return valve V4 to its initial position. Observe the response as the Pneumatic Control
Valve opens to maintain the pressure. Observe that the large movements of the control
valve as the process variable moves away from and towards the set point.

Effect of changing the set point

Adjust the set point to 70% on the Process Controller.

Observe the initial response due to Derivative Action followed by the conventional
response due to the Proportional action. Note once again that the deviation from the set
point is not corrected.

Adjust the set point to 30% on the Process Controller. Once again, observe the changes
in the pressure and the valve operation.

Further Experiments:

Effect of changing the Derivative Time:

Adjust the Derivative Action Time in steps of 1 until the process becomes unstable. This
will happen at a setting of 8 or 9.

Repeat the above experiment at each step and observe the increased effect of the
Derivative Action (the effect is the same but the time taken for the valve to return to the
position dictated by the Proportional setting is increased).

Effect of changing the Proportional Band

Set the Proportional Band to 20% on the controller. Set the Derivative Action Time to 6
seconds.

38 Series PROCON 6-8-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Apply a disturbance to the process by opening valves V6 and V7 or change the set point.

Besides the reduced offset due to Proportional Action observe that the amount of
correction applied by Derivative Action is increased.

Conclusions:

Derivative Action cannot reduce offsets from the set point which result with Proportional
control.

Correction is applied to the output from the controller whenever the process variable is
changing. (The faster the process variable changes, the larger the amount of correction
due to Derivative Action).

A short setting of Derivative Action Time means less Derivative Action effect on the output
of the controller. (Any correction applied to the output lasts for a shorter period of time).

The amount of correction applied to the controller output by the Derivative Action is
related to the proportional Band setting. (A large Proportional Band means a smaller
correction due to the Derivative Action).

Note: Short settings of the Derivative Time may be applied to this pressure process for
the purpose of demonstration provided the setting of the Proportional Band is not
too small. If the Derivative Time setting is too long, the corrections to the control
valve will be excessive and the process will be unstable. Derivative Action is
usually applied to processes which have a slow reaction rate, moderate lags and
small changes in load to the process. The large initial correction to the control
valve allows the process to stabilise more quickly. The 38-100 Basic Process Rig
and 38-600 Temperature Process Rig involve processes with longer response
times and may be used to demonstrate this feature.

6-8-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

NOTES

38 Series PROCON 6-8-5


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 13 - Experiment 9 Connection Diagram

6-8-6 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 9

Object of Experiment:

To demonstrate typical procedures for optimising the settings of a three-term controller to


suit a particular process.

When selecting the settings for a three-term controller, consideration must be given to
those characteristics of the process which affect its controllability. These are load
changes (how large and how fast), process lags (capacity lags and resistance lags),
process reaction lags, response lags of sensors etc. and dead time.

The object of this experiment is to use one of the widely used field methods for optimising
the P, I and D settings on the controller to suit the characteristics of the process. In this
instance the Ultimate Period/Ziegler-Nichols (closed loop) and Reaction Curve (open
loop) methods will be used.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Control Module

38-461 Pressure Transmitter

38-490 Digital Display Module

Chart Recorder (not supplied)

Note: The equipment requires a supply of clean compressed air.

Initial Settings:

Complete the connections shown in Figure 13.

V1, V3 & V6 Closed

R1, R2, V2, V4 & V5 Open

Adjust R1 to give 25 psi on G1.

Adjust R2 to give 10 psi on G5 with V2 open and V4 closed.

38 Series PROCON 6-9-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

For this set of demonstrations the Process Controller should be configured for
Proportional control with the following initial settings:

Controller Parameter Setting Units

Set Point 50 %

Proportional Band 300 %

Integral Time OFF Secs

Derivative Time OFF Secs

Span 100 % at 20mA input

Zero 0 % at 4mA input

Follow the instructions given in earlier experiments regarding operation of the Process
Controller. Further information can be found in the Process Controller user manual.

The Pressure Sensor and Transmitter are calibrated in the following way:

0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range

10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of range

Experimental Details:

Connect the equipment as shown in the set-up diagram. A recorder must be connected to
the Pressure Transmitter output/controller input and controller output/current to pressure
converter input 4-20mA loops to provide a record of the process response.

ULTIMATE PERIOD METHOD (Ziegler-Nichols)

Data for the analysis is obtained using the controller configured for Proportional control
only.

Ensure that the Integral and Derivative settings on the controller are turned off.

Allow the process variable to settle then apply a step change to the process by closing
valve V4.

As the process variable remains steady, decrease the Proportional Band and re-apply a
step change (by closing V4).

Continue adjusting the Proportional Band and applying a step change until the process
variable continually oscillates. Note the setting of the Proportional Band at which continual
cycling occurs. From the trace obtained on the recorder measure the Period of the
oscillation Pc in minutes.

6-9-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Fig 9.1
Typical response obtained using 38-200 and 38-300 Process Interface and Controller.
The optimum settings for the controller may be calculated as follows:
P only PB = 2 PBc
P+I PB = 2.2 PBc IAT = 0.83 Pc
P + I + D PB = 1.7 PBc IAT = 0.50 Pc DAT = 0.13 Pc
REACTION CURVE METHOD
Set the controller for Manual operation.
Adjust the output from the controller to give a steady pressure in the system with the
process variable display showing 50%.
Leave the controller in Manual operation and apply a step disturbance to the process by
changing the position of the Pneumatic Control Valve slightly. Note the step change
applied (M%).
The step change will result in a new pressure in the system. The open loop response may
be analysed from the trace on the recorder to determine the optimum settings for P, I & D.
A typical response curve is shown below.

Fig 9.2

38 Series PROCON 6-9-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Draw a straight line through the point of maximum slope so that the line intersects the
time axis.

Measure the dead time L in minutes. (Time at which step change is applied to time where
straight line intersects time axis).

Calculate the maximum slope R.

R
Determine R1 using the equation R1 =
∆M

The optimum settings for the controller may be calculated as follows:

P only PB = R1 x L
PI PB = 1.1 (R1 x L) IAT= 3.0 L
PID PB = 0.5 (R1 x L) to 0.8 (R1 x L) IAT= 2.0 L to2.5 L DAT=0.3 L to0.5 L

Compare the values obtained with those obtained using the Zieglar-Nichols method.

Further Experiments:

Evaluation of the controller settings by applying a disturbance to the process

Enter the settings of P, I and D to be evaluated on the Process Controller. Set the set
point to 50%.

Set the controller to Manual operation and adjust the valve position to maintain the
required set point (50% process variable, 4 psi on G5). Set the controller to Automatic
operation then apply a disturbance by opening valve V4. Observe the behaviour of the
process.

Repeat the procedure for the settings of the controller suggested by the other technique.

Conclusions:

Techniques exist which allow the settings of a three-term controller to be determined to


suit a particular process.

The settings predicted by these techniques will differ and should be treated as a starting
condition for the setting up of the controller. Satisfactory control may be obtained from
these settings but the commissioning engineer may need to make fine adjustments to
obtain the required operating characteristics.

6-9-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

NOTES

38 Series PROCON 6-9-5


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 14 - Experiment 10 Connection Diagram

6-9-6 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 10

Object of Experiment:

To demonstrate the effect of the Air Receiver on the response of the process and to
determine the optimum settings for the Process Controller.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Control Module

38-461 Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Initial Settings:

Complete the connections shown in Figure 14.

V2 & V6 Closed

R1, R2, V1, V2, V4 & V5 Open

Adjust R1 to give 25 psi on G1.

Adjust R2 to give 10 psi on G5 with the Pneumatic Control Valve open.

38 Series PROCON 6-10-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

For this set of demonstrations the Process Controller should be configured for three-term
control with the following initial settings:

Controller Parameter Setting Units

Set Point 50 %

Proportional Band 50 %

Integral Time 12 Secs

Derivative Time OFF Secs

Span 100 % at 20mA input

Zero 0 % at 4mA input

Follow the instructions given in earlier experiments regarding operation of the Process
Controller. Further information can be found in the Process Controller user manual.

The Pressure Sensor and Transmitter are calibrated in the following way:

0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range

10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of range

Experimental Details:

Connect the equipment as shown in the set-up diagram with the Air Receiver in series
with the process pipe.

A recorder may be connected to the Pressure Transmitter output/controller input and


controller output/current to pressure converter input 4-20mA loops to provide a record of
the response.

As the Pneumatic Control Valve is open when 4mA is applied to the I/P Converter and a
pressure below set point requires the valve to be opened, the Process Controller is
configured for DIRECT action.

Observe the response of the system when valve V4 is opened and closed to give a
disturbance.

Isolate the Air Receiver from the process pipe by opening V2 and closing V1 and V3.

Apply a disturbance to the new configuration and observe the change in response.

6-10-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Further Experiments:

Determining optimum settings for the Process Controller

Using the techniques described in Experiment 9, determine the optimum settings for the
three-term controller to suit the two systems. Apply the optimum settings for each system
and evaluate the response of both systems using valve V4 to apply a step change to the
outflow from the system. Observe that the process becomes unstable if the settings
relating to the Air Receiver in series are applied to the process without the Air Receiver.

Conclusions:

The addition of the Air Receiver makes the response of the system correspondingly
slower. (Pressure cannot change as quickly in the process pipe when a disturbance
occurs or a new set point is instructed).

Any change in the response of a process will necessitate a change in the settings of the
three terms on the controller to achieve optimum control.

Where the response of a process will change in operation, the controller must be
configured to give stable control under all operating conditions. This may necessitate a
reduction in performance at some conditions.

38 Series PROCON 6-10-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 15 - Experiment 11 Connection Diagram

6-10-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 11

Object of Experiment:

To calibrate the Differential Pressure Sensor and Differential Pressure Transmitter.

Equipment Required:

38-200 Process Interface

38-300 Process Controller

38-714 Pressure Process Rig

38-472 Differential Pressure Transmitter

38-490 Digital Display Module

Note: The equipment requires a supply of clean compressed air.

Initial Settings:

Complete the connections shown in Figure 15.

V1, V3, V4 & V5 Closed

R1, R2, V2, V6 Open and V7 fully open

Adjust R1 to give 25 psi on G1.

Adjust R2 to give 15 psi on G4 with the Pneumatic Control Valve open. Adjust V4 to give
5 psi on G5. Re-adjust R2 and V4 until G4 reads 15 psi and G5 reads 5.

For this set of demonstrations the controller will be used manually to operate the control
valve via the I/P Converter and to monitor the differential pressure in the process pipe.

Once there is a pressure difference of 10 psi between G4 and G5, reduce the pressure
with R2 until G4 reads 10 psi. G5 will now be reading zero.

Controller Calibration:

Span 100% at 20mA input

Zero 0% at 4mA input

38 Series PROCON 6-11-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Experimental Details:

The aim of this experiment is to calibrate the Differential Pressure Sensor/Transmitter to


suit the process.

The Differential Pressure Sensor is connected to the tappings upstream and downstream
of an Orifice Block located in the process pipe. Pressure drop across the Orifice Block is
related to the flow of air in the pipe (pressure drop is proportional to the square of the
flow). The aperture in the Orifice Block is 1.5mm in diameter.

The flowmeter installed on the 38-714 allows the relationship between the actual flow rate
and the output from the sensor to be considered. The sensor and transmitter can be
calibrated to the minimum and maximum conditions of flow through the pipe so as to be of
use in control applications (the corresponding real values of the flow being known from
the flowmeter reading).

Minimum flow produces 4mA output from the transmitter.

Maximum flow produces 20mA output from the transmitter.

All connections are shown in the equipment set-up diagram.

Connect the compressed air supply to the inlet.

Note: The Pneumatic Control Valve is designed to open with lack of air. With 4mA input
to the I/P Converter, the valve will remain open.

Set the controller to Manual operation and open the control valve by setting output to 0%.

With the Pneumatic Control Valve open adjust R2 to give a flow rate of 25 L/min, adjust
the span on the differential pressure transducer to give 100% reading on the controller.

Increase the controller output to close the control valve until the flow is zero, gauge G5
will read 0 psi. Use the trim tool supplied with 38-300 to adjust the zero control on the
Differential Pressure conditioning module to give a reading of 4.0mA on the Digital
Display Module.

Set the flow in the system to the maximum required by opening the Pneumatic Control
Valve (pressure process variable should return to 100%). When the flow is steady, adjust
the span control on the Differential Pressure conditioning module to give a reading of
20.0mA on the Digital Display Module.

Repeat the minimum and maximum settings until no further adjustments of the zero and
span controls is required.

The Differential Pressure Sensor/Transmitter has now been calibrated to give readings
from 4-20mA (0-100% if used with the Process Controller) corresponding to the range of
flow rates available in the process pipe.

6-11-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

Conclusions:

A Differential Pressure Sensor may be used to give a remote reading of the differential
pressure in a system. (This feature will be used in later experiments to enable the flow to
be controlled automatically).

It is necessary to calibrate an electrical sensor before use to provide an output which is


meaningful.

The Differential Pressure Sensor may be calibrated to suit the operating range and datum
required for a particular application. The readings obtained can be related to actual flow
rates from the flowmeter.

38 Series PROCON 6-11-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Fig 16 - Experiment 12 Connection Diagram

6-11-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

EXPERIMENT 12

Object of Experiment:

To control flow in the process pipe using a Differential Pressure Sensor/Orifice Block with
square root extractor and three-term Process Controller with a 4-20mA proportional
output to an I/P Converter and Pneumatic Control Valve.

Equipment Required:

38-200 Process Interface


38-300 Process Controller
38-714 Pressure Process Rig
38-462 Differential Pressure Transmitter
38-490 Digital Display Module
Note: The equipment requires a supply of clean compressed air.
Initial Settings:

Complete the connections shown in Figure 16.


V1, V3, V4, &V5 Closed
V2, V6 & V7 (fully open) R1 & R2 Open
Adjust R1 to give 25 psi on G1.
Adjust R2 to give 25 L/min on the flow meter with the Pneumatic Control Valve open.
For this set of demonstrations the Process Controller should be configured for three-term
control with the following initial settings:
Controller Parameter Setting Units

Set Point 50 %
Proportional Band 300 %
Integral Time 5 Secs
Derivative Time OFF Secs
Span 100 % at 20mA input
Zero 0 % at 4mA input

38 Series PROCON 6-12-1


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Follow the instructions given in earlier experiments regarding operation of the Process
Controller. Further information can be found in the Process Controller user manual.
The Pressure Sensor and Transmitter are calibrated in the following way:
0 psi at G5 produces 4mA from Pressure Transmitter, representing 0% of range
10 psi at G5 produces 20mA from Pressure Transmitter, representing 100% of range
The Process Controller must also be configured to extract the square root from the
process variable. This will produce a controller input which is linear to flow.

From the normal process variable/set-point display press the Page Advance button
until the Setup Process display is seen. ‘Setup PrCESS’ will be displayed. Press the
Parameter Advance button until ‘lntypi’ is shown in the upper display. This indicates
the Lineariser Type page. Press the Up or Down buttons until ‘SQ.rt’ is shown
in the lower display. Press the Enter button to confirm the selection.

The input range must now be specified. Press the Parameter Advance button once
to show the Input Range Full Scale page (r-hi-i in upper display). A full scale of 20.0mA is
required, so the lower display must be set to 200 by use of the Up or Down
buttons. The decimal point is added by pressing the Parameter Advance button
once to the Decimal Point page (dec-pt in upper display). Move the decimal point to the
correct position by use of the Up or Down buttons. Press the Enter button
to confirm the change.

Press the Parameter Advance button once to show the Input Range Zero page
(r-lo-i in upper display). Set this to 4.0 by use of the Up or Down buttons. Press
the Enter button to confirm the change.

Return to the Operating Page by pressing the Page Advance button followed by the
Enter button.
Experimental Details:

The object of the demonstration is to maintain the flow at mid range in the process pipe
(50% set point) by adjusting the opening of the Pneumatic Control Valve to allow the
required amount of air to flow through the pipe.
As the Pneumatic Control Valve is open when 4mA is applied to the I/P Converter and a
low flow (below set point) requires the valve to be opened, the Process Controller is
configured for DIRECT action.
Connect the equipment as shown in the set-up diagram.

6-12-2 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

A recorder may be connected to the sensor output/controller input and controller


output/current to pressure converter input 4-20mA loops to provide a record of the
response.
If the set-up is correct, air should discharge from the main orifice. The flow should remain
at 50% (process variable).
Observe that the flow is controlled at the set point.
Operation of Square Root Extractor
Connect the equipment as shown in fig 16.
To demonstrate the effect of the square root extractor, the output from the differential
pressure transmitter will be plotted against flow with the square root option set on the
process controller.
Open valves V2, V4, V5, V6 & V7 (fully open)
Close valves V1 & V3.
With the control valve fully open adjust the flow rate to 24 L/min. This should give a
pressure drop of about 10 psi across the orifice plate (G4 – G5 = 10 psi).
Set the span on the differential pressure transmitter to 100%.
Reduce the flow to zero and set the zero on the differential pressure transmitter to 0%.
With the controller in manual mode set the o/p to 0%. Increase the output in steps of 10%
up to 100%. Record the process variable display on the controller and the actual flow rate
on the flow meter.
Controller O/P Flow L/min Process variable %
0 24.0 100
10 23.0 98.4
20 22.0 95.6
30 21.0 91.7
40 19.5 85.2
50 17.0 77.0
60 14.5 64.0
70 11.0 49.2
80 7.5 34.0
90 3.0 16.1
100 0 0

38 Series PROCON 6-12-3


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

Repeat the reading with the square root extraction option turned off. Plot the two sets of
data flow against process variable.

Controller O/P Flow L/min Process variable %


0 24.0 100
10 23.0 92.4
20 22.0 86.0
30 21.0 78.2
40 19.5 68.0
50 17.0 54.0
60 14.5 38.0
70 11.0 21.9
80 7.5 9.2
90 3.0 1.7
100 0 0

Flow Control

The object of the demonstration is to maintain the flow at the mid point in the process pipe
at a set point of 50% by controlling the opening of the pneumatic control valve.

Further Experiments:

Changing the set point remotely

In the basic set-up the flow was controlled about a mean value of 50%.

Adjust the set point to 60% on the Process Controller. Observe how the flow changes to
the required setting and the position of the Pneumatic Control Valve varies to suit the
conditions.

Adjust the set point to 40% on the Process Controller. Once again, observe the changes
in the flow and the valve operation.

Repeat of pressure control experiments

If required, the flow process may be studied in detail by following the procedures detailed
in Experiments 6 to 9 for pressure control. Optimum controller settings and effects of the
Air Receiver may be investigated.

Conclusions:

Flow in the process pipe can be measured using a Differential Pressure Sensor
connected to an Orifice Block.

6-12-4 38 Series PROCON


38-714 Pressure Process Rig
Feedback Discovery Products EXPERIMENTS

As the pressure drop across the Orifice Block changes with the square of the velocity, the
output from the Differential Pressure Sensor is highly non-linear. The output from the
Transmitter can be linearised using a square root extractor to provide a signal which is
proportional to flow.

Flow in the process pipe can be controlled using a flow sensor/conditioner and Process
Controller configured for proportional output (4-20mA) and square-root extraction to an I/P
Converter to position a Pneumatic Control Valve as required at the inlet to the pipe.

Proportional control of the pneumatic control valve allows the flow to be held at the set
point without the undue oscillations which are inherent in an on/off control system.

The flow in the pipe may be changed by setting an alternative set point on the controller.
No adjustment to the process or sensor is required provided the inlet and outlet conditions
are compatible with the new setting.

38 Series PROCON 6-12-5


38-714 Pressure Process Rig
EXPERIMENTS Feedback Discovery Products

NOTES

6-12-6 38 Series PROCON

S-ar putea să vă placă și