1. CONTAINS OF DELIVERY 2.3 WARNINGS, REGULAR 3.

INTRODUCTION
INFORMATION AND REMARKS 3.3 LAYOUT AND MODE OF
REFERRING TO CE-MARKING OPERATION
The delivery contains: 3.1 FEATURES
• Measuring transducer MI454 Resistance on the input terminals is measured
• User’s manual In this manual installations and working
instructions for the measuring transducer MI454 • Measuring of resistance on potentiometers with U-I method. Enforced current causes a
and tap position voltage drop (A - Picture 1) on the measured
is to be found. Installation as well as use of the
2. SAFETY measuring transducer will involve working with • Programmable input and output resistor which is supplied to the programmable
dangerous currents and voltages. Professionals • Low power consumption amplifier B. After A/D conversion the signal is
This Safety Section should be read before must handle these areas. ISKRA MIS d.d. does • Universal AC/DC or AC Auxiliary power computed in microprocessor C. The measured
commencing any work on the equipment supply value determined by the microprocessor is
not take on responsibility for the use and
installation. If any doubt comes up concerning • Accuracy class: 0.5 assigned to the programmable analogue output
• Serial communication RS232 or RS485 E. Communication D enables programming of
• Protection: Protection class II the installation or use of the system, on which
very high speed data rate: up to 115,200 the measuring transducer and monitoring of the
300 V rms, installation category III the measuring transducer is to be used for
bit/s, MODBUS protocol (optional) measuring resistance on the input terminal.
500 V rms, installation category II measurement, the person responsible for the
power installation should be contacted. • Housing for DIN rail mounting Communication, analogue output and auxiliary
Pollution degree 2
• Correspond to EN 60770-1:1999 power supply are electrically insulated from
• Test voltage: 3.7 kV rms other system by means of separation
according to EN 61010-1: 1990 Measuring transducer MI454 is CE-marked
transformer.
according to the LV-directive and EMC- 3.2 APPLICATION
directive for housing and light industry, which
2.1 HEALTH AND SAFETY normally covers the most common use of the
measuring transducer. Measuring transducer MI454 is designed to
convert the wiper position of potentiometer or
The information in the Safety Section of the Before energising the equipment, the slide wire into an accurate proportional DC
product documentation is intended to ensure that following should be checked: current or DC voltage signal. Typically these
products are properly installed and handled in • Protective fuse rating (the recommended kinds of transducers are used for measuring of
order to maintain them in a safe condition. It is maximum rating of the external protective resistance on TAP position changers, used on
assumed that everyone who will be associated fuse for this equipment is 6A - Red Spot high voltage transformers or to measure variable
with the equipment will be familiar with the resistance on 3 wire system. The analogue Picture 1: Block diagram
type or equivalent);
contents of the Safety Section. • Integrity of earth connection (where output signal is proportional to the measured
applicable) value and it is appropriate for regulation of
3.4 PROGRAMMING
analogue and digital devices.
2.2 EXPLANATION OF SYMBOLS Waste disposal site
AND LABELS Input and output values are programmed1) by
Waste electrical and electronic equipment shall
setting software MiQen via RS232 or RS485
not be handed over to a local waste disposal
communication. Before setting the transducer,
The meaning of symbols and labels which may company or be disposed of as unsorted
output value must be selected by the jumpers on
be used on the equipment or in the product municipal waste. The electrical and electronic
the output module2). It is possible to chose
documentation is given below. equipment producer or purchaser shall at the end
between three ranges 0…±10 V, 0…±5 mA and
A Caution: refer to product user's request collect waste electrical and
0…±20 mA. Within this three ranges it is
electronic equipment free of charge provided the
documentation electrical and electronic was put on the market possible to set any linear output characteristic.
1) – Programming is not possible in versions without communication
by it. Waste electrical and electronic equipment
. Caution: risk of electric shock does not fall within the scope of old waste
2) – Qualified person only

 Functional earth terminal electrical and electronic equipment load. The


treatment after the expired life shall comply with
Note: this symbol may also be used for a provisions of the Directive 2002/96/EC, or
protective/safety earth terminal if that terminal Regulations on Management Treatment of
is part of a terminal block or sub-assembly eg. Waste Electrical and Electronic Equipment
power supply. (Official Journal of the Republic of Slovenia
No. 118/04).

User's manual MI454 Page 1 User's manual MI454 Page 2


3.5 VERSIONS 4.4 POWER SUPPLY: MI454
9 pin D connector 25 pin D connector (PC)
(PC)

The following transducer versions are available (Table 1). Auxiliary AC/DC voltage (universal): Rx (21) Tx (3) Tx (2)

Number of steps Measuring • Rated voltage (Ur): 24…300 V DC  (22) GND (5) GND (7)
Input [Ω] Output Supply Communication
voltage 40…276 V AC
Universal or • Frequency range: 40…70 Hz Tx (23) Rx (2) Rx (3)
Programmable

Adjustable:
57 V • Power consumption: < 3 VA Table 3: RS232 connections
0 – linear 5 mA AC:
100 to 500 k (potenciometer) < 2,2 V 20 mA 100 V RS232 or RS485
from 1 to 100 steps 10 V 230 V Auxiliary AC voltage:
(TAP position) 400 V
500 V Rated voltage (Ur) Rated operating range RS485
100, 1 k, 2 k, 5 k, 57.74 V • Connection type: Multi-drop
10 k, 20 k, 50 k, 100 V (32 connections per link)
Fixed configuration

0 - linear 230 V 80…120 % Ur


100 k, 200 k, 5 mA
400 V 5) • Signal levels: RS485
500 k3) 10 mA RS232, RS485
20 mA
Universal or
or
500 V 5) • Cable type: Screened twisted pair
300, 1 k, 2 k, 5 k,
< 2,2 V
4...20 mA AC: 57 V
without 5) – to 300 V installation category III, from 300 to 500 V installation • Maximum cable length: 1000 m
100 V
10 k, 20 k, 50 k, 10 V
230 V
communication category II – see chapter Regulations. • Connector: Screw terminals
10 steps other on request
100 k, 200 k, 400 V • Isolation: 3.7 kV rms for 1 minute
Table 2: Rated AC voltage for Auxiliary power
500 k3) 500 V between all terminals and all other circuits,
supply
except between communication terminals
Table 1: Versions of MI454 • Frequency range: 45…65 Hz and output terminals, 2 kV rms for 1 minute
3) – Other versions on request, measuring current compliance with range • Power consumption: < 3 VA • Transmission mode: Asynchronous
Transducers are mounted on standard rail 35 x 15 mm (according to SIST EN 60715). • Message format: MODBUS RTU
4.5 ACCURACY: • Data rate (very high speed):
4. TECHNICAL DATA 1,200 to 115,200 bits/s
• Burden voltage: 15 V • RS485 connections
• External resistance: • Reference value: Input range end value MI454 RS485
• Accuracy class:
4.1 GENERAL: RBmax.[kΩ]= 15V
Analogue output: Resistance 0.5 A (21) DATA +
IOutN [mA] Communication: Resistance 0.5
C (22) NC 6)
• Measured quantity: resistance ratio Reference conditions:
• Measured principle: 4) - Depends of set jumpers on output module
• Ambient temperature: 15…30 °C B (23) DATA -
microprocessor sampling Programmable DC voltage output: • Input: 0...100 % RN
• Output UOutN (output range end value): Table 4: RS485 connections
6) – NC – do not connect
• Output range values 0…1 V to 0…10 V
4.2 INPUT: 4.6 COMMUNICATION (OPTIONAL):
• Burden current: 20 mA
• External resistance:
• Input range limit values: 4.7 HOUSING:
RBmin.[kΩ]=
UOutN [V] RS232
Measuring voltage:
0...100 Ω to 0...500 kΩ < 2,2 V 20 mA • Connection type: Point to point • Material of housing: PC/ABS
• Number of steps: 0 – linear (potenciometer) General: • Signal levels: RS232 uninflammable, according to UL 94 V-0
from 1 to 100 steps (TAP position) • Response time: • Maximum cable length: 15 m • Mounting: For rail mounting, 35 x 15 mm
• Minimal step: 30 Ω programmable from 0.5 s to 60 s • Connector: Screw terminals according to SIST EN 60715
• Lead resistance < 50 Ω per lead • Residual ripple: < 1 % p.p. • Isolation: 3.7 kV rms for 1 minute • Enclosure protection: IP 50
• Consumption: < 0.5 VA • Maximum output value: between all terminals and all other circuits, (IP 20 for connection terminals)
limited at 125 % analogue output signal except between communication terminals according to SIST EN 60529: 1997
The output may be either short or open-circuited and output terminals, 2 kV rms for 1 minute • Weight including packing: 0,282 kg
4.3 ANALOGUE OUTPUT: and it is electrically insulated from all other • Transmission mode: Asynchronous
circuits (floating). • Message format: MODBUS RTU
All the output range end values can be reduced • Data rate (very high speed): 4.8 CONECTION TERMINALS:
Programmable DC current output:
• Output IOutN (output range end value): subsequently using the programming software, 1,200 to 115,200 bits/s
• Output range values 4): but a supplementary error results. • RS232 connections • Permissible cross section of the connection
0…1 mA to 0…5 mA or, leads:
0... 5 mA to 0... 20 mA ≤ 4.0 mm2 single wire
2 x 2.5 mm2 fine wire
• Small cross-section cables shall be equipped
with cable conduit (bushing?). The
minimum conduit diametre required
amounts ot 0.14 mm2.
User's manual MI454 Page 3 User's manual MI454 Page 4
4.9 ENVIRONMENTAL 6. CONNECTION 6.2 DIMENSIONAL DRAWING
CONDITIONS: 6.3 MARKING
The connection terminals marking can be found
on the front plate. For measuring of resistance One label at the front of housing (Picture 5):
• Climatic rating: Climate class 2
acc. to EN 60688: 1992 lower than 200 Ω, it is recommended to connect
• Operating temperature -10 to +55 °C contact 3 as shown below, to reduce influence of
• Storage temperature -40 to +70 °C connection wires.
• Annual mean relative humidity: ≤ 75% r.h.

4.10 EU DIRECTIVES
CORRESPONDING FOR CE Picture 4: Dimensional drawing (all dimensions
MARKING are in mm)

Low voltage directive 73/23/EEC: EN 61010-1: Picture 3: Connection diagram


1993 and EN 61010-A3: 1995 Safety Picture 5: Example of label for MI454
requirements for electrical equipment for transducer
measurement, control, and laboratory use, Part 6.1 CONNECTION TABLE
1: General requirements
EMC directive 89/336/EEC: EN 61326-1: 1997 Function Connection 6.4 STEP DEFENITION
Electrical equipment for measurement, control, Ri 1
and laboratory use EMC requirements, Part 1: Measuring
Resistance Ru 2
General requirements. input:
Ri 4

5. MOUNTING Outputs: Output 1


+ 15
- 16
MI454 is appropriate for rail mounting + / AC 13
according to SIST EN 60715 Auxiliary power supply:
- / AC 14
On picture below you can see rail mounting
Rx / A 21/21 Picture 6: Example of n step TAB use
RS232 or GND /
Communication: 22/22
RS485 NC 7)
Tx / B 23/23

Table 5: Connections
7) – NC – do not connect