POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Sizing of Feeders: Vac1 = 0.866 x 1.9642 x 1.31


PP to A Vac1 = 2.2283 Volts
Power Plant to Reference Pole: Block 1
kVa total = 167 kVa

167 x 103
I total = = 24.203 A
6900
A to Ai
24 x 450 x 24.2029
CM = = 32074.129 CM Hospital
8.1496
kVa total = 225 kVa
From Table:
225 x 103
For Feeder 1: I total = = 18.8266 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 450 x 18.8266
CM = =¿24949.4CM
re-1/4
8.1496
D = 4.5’ D = 4.5’ From Table:
For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1

Xd = 0.2794log√3 4.52 x 9 d-1 = 0.005 x 92( 39 )= 0.365 in2


Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi


0.866 Xd = 0.2794log√3 4.52 x 9
AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e1 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 450 x 24.2029(0.895 cos 30+0.852 sin 30)
5280 Approximate Method:
e1 = 7.4327 Volts 3 dI (Racos Ø + Xtsin Ø )
e=
5280
AC Drop Method:
e2 =
24 dI
V dc actual = 3 x 450 x 18.8266 (0.895 cos 30+0.852 sin 30)
CM
5280
24 x 450 x 24.2029
V dc actual = = 1.9642 e2 = 5.7816 Volts
133076.55
Volts AC Drop Method:

1|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 450 x 18.8266
V dc actual = = 1.5279
133076.55
Volts
Vac2 = 0.866 x 1.5279 x 1.31
Vac2 = 1.7333 Volts

2|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Ai to Aii Vac3 = 0.5778 Volts


University
kVa total = 225 kVa

225 x 103
I total = = 18.8266 A
√ 3 x 6900 Aii to Aiii
24 x 150 x 18.8266
CM = =¿24949.7 CM Ice plant
2.7165
kVa total = 501 kVa
From Table:
501 x 103
For Feeder 1: I total = = 41.9206 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 150 x 41.9206
CM = =¿55554.6CM
re-1/4 2.7165

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e3 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:

e3 = 1.9272 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e4 =
24 dI
V dc actual = 3 x 150 x 41.9206 (0.895 cos 30+0.852 sin 30)
CM
5280
24 x 150 x 18.8266
V dc actual = = 0.5093 e4 = 4.2912 Volts
133076.55
Volts AC Drop Method:
Vac3 = 0.866 x 0.5093 x 1.31

3|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 150 x 41.9206
V dc actual = = 1.134 Volts
133076.55
Vac4 = 0.866 x 1.134 x 1.31
Vac4 = 1.2865 Volts

4|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Aiii to Bi Vac5 = 1.3481 Volts


Club
kVa total = 75 kVa

75 x 103
I total = = 6.2755 A
√ 3 x 6900 Bi to Bii
24 x 1050 x 6.2755
CM = =¿ 8316.42 CM University
19.0157
kVa total = 225 kVa
From Table:
225 x 103
For Feeder 1: I total = = 18.8266 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 150 x 18.8266
CM = =¿24949.7CM
re-1/4 2.7165

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e5 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 1050 x 6.2755(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:

e5 = 4.4968 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e6 =
24 dI
V dc actual = 3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 1050 x 6.2755
V dc actual = = 1.1884 e6 = 1.9272 Volts
133076.55
Volts AC Drop Method:
Vac5 = 0.866 x 1.1884 x 1.31

5|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 150 x 18.8266
V dc actual = = 0.5093
133076.55
Volts
Vac6 = 0.866 x 0.5093 x 1.31
Vac6 = 0.5778 Volts

6|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Bii to Biii Vac7 = 0.5778 Volts


Hospital
kVa total = 225 kVa

225 x 103
I total = = 18.8266 A
√ 3 x 6900 Biii to Biv
24 x 150 x 18.8266
CM = =¿24949.7CM Distillers
2.7165
kVa total = 501 kVa
From Table:
501 x 103
For Feeder 1: I total = = 41.9206 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 150 x 41.9206
CM = =¿55554.6CM
re-1/4 2.7165

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e7 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:

e7 = 1.9272 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e8 =
24 dI
V dc actual = 3 x 150 x 41.9206 (0.895 cos 30+0.852 sin 30)
CM
5280
24 x 150 x 18.8266
V dc actual = = 0.5093 e8 = 4.2912 Volts
133076.55
Volts AC Drop Method:
Vac7 = 0.866 x 0.5093 x 1.31

7|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 150 x 41.9206
V dc actual = = 1.134 Volts
133076.55
Vac8 = 0.866 x 1.134 x 1.31
Vac8 = 1.2865 Volts

8|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Biv to Bv Vac9 = 1.9259 Volts


Manufacturing Plant
kVa total = 750 kVa

750 x 103
I total = = 62.7555 A
√ 3 x 6900 Bv to Bvi
24 x 150 x 62.7555
CM = =¿83165.8CM Hospital
2.7165
kVa total = 225 kVa
From Table:
225 x 103
For Feeder 1: I total = = 18.8266 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 450 x 18.8266
CM = =¿24949.4CM
re-1/4 8.1496

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e9 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 62.7555(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:

e9 = 6.424 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e10 =
24 dI
V dc actual = 3 x 450 x 18.8266 (0.895 cos 30+0.852 sin 30)
CM
5280
24 x 150 x 62.7555
V dc actual = = 1.6977 e10 = 5.7816 Volts
133076.55
Volts AC Drop Method:
Vac9 = 0.866 x 1.6977 x 1.31

9|Page
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 450 x 18.8266
V dc actual = = 1.5279
133076.55
Volts
Vac10 = 0.866 x 1.5279 x 1.31
Vac10 = 1.7333 Volts

10 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Bvi to B Vac11 = 1.4811 Volts


Reference Pole: Block 3
kVa total = 333 kVa

333 x 103
I total = = 48.2609 A
6900
Bv to C
24 x 150 x 48.2609
CM = =¿63957CM Reference Pole: Block 5
2.7165
kVa total = 333 kVa
From Table:
333 x 103
For Feeder 1: I total = = 48.2609 A
6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 600 x 48.2609
CM = =¿63956.4CM
-1/4
re 10.8661

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e11 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 48.2609( 0.895 cos 30+0.852 sin30)
5280 Approximate Method:

e11 = 4.9403 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e12 =
24 dI
V dc actual = 3 x 600 x 48.2609 (0.895 cos 30+0.852 sin 30)
CM
5280
24 x 150 x 48.2609
V dc actual = = 1.3056 e12 = 19.7611 Volts
133076.55
Volts AC Drop Method:
Vac11 = 0.866 x 1.3056 x 1.31

11 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 600 x 48.2609
V dc actual = = 5.2222
133076.55
Volts
Vac12 = 0.866 x 5.2222 x 1.31
Vac12 = 5.9244 Volts

12 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

C to Ci Vac13 = 0.7704 Volts


Warehouse
kVa total = 300 kVa

300 x 103
I total = = 25.1022 A
√ 3 x 6900 C to Di
24 x 150 x 25.1022
CM = =¿ 33266.3CM Mall
2.7165
kVa total = 501 kVa
From Table:
501 x 103
For Feeder 1: I total = = 41.9206 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 450 x 41.9206
CM = =¿55554CM
re-1/4 8.1496

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e13 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 25.1022(0.895 cos 30+0.852 sin 30)
5280 Approximate Method:

e13 = 2.5696 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e14 =
24 dI
V dc actual = 3 x 450 x 41.9206(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 150 x 25.1022
V dc actual = = 0.6791 e14 = 12.8737 Volts
133076.55
Volts AC Drop Method:
Vac13 = 0.866 x 0.6791 x 1.31

13 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 450 x 41.9206
V dc actual = = 3.4021
133076.55
Volts
Vac14 = 0.866 x 3.4021 x 1.31
Vac14 = 3.8596 Volts

14 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Di to Dii Vac15 = 1.7333 Volts


Office Building
kVa total = 225 kVa

225 x 103
I total = = 18.8266 A
√ 3 x 6900 Dii to D
24 x 450 x 18.8266
CM = =¿24949.4CM Reference Pole: Block 7
8.1496
kVa total = 250 kVa
From Table:
250 x 103
For Feeder 1: I total = = 36.2319 A
6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 300 x 36.2319
CM = =¿ 48014.9CM
-1/4
re 5.4331

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e15 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 450 x 18.8266 (0.895 cos 30+0.852 sin 30)
5280 Approximate Method:

e15 = 5.7816 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e16 =
24 dI
V dc actual = 3 x 300 x 36.2319(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 150 x 25.1022
V dc actual = = 1.5279 e16 = 7.4178 Volts
133076.55
Volts AC Drop Method:
Vac15 = 0.866 x 1.5279 x 1.31

15 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 300 x 36.2319
V dc actual = = 1.9603
133076.55
Volts
Vac16 = 0.866 x 1.9603 x 1.31
Vac16 = 2.2239 Volts

16 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

D to Ei Vac17 = 1.7333 Volts


University
kVa total = 225 kVa

225 x 103
I total = = 18.8266 A
√ 3 x 6900 Ei to E
24 x 450 x 18.8266
CM = =¿24949.4 CM Reference Pole: Block 9
8.1496
kVa total = 333 kVa
From Table:
333 x 103
For Feeder 1: I total = = 48.2609 A
6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 450 x 48.2609
CM = =¿ 63956.2CM
-1/4
re 8.1496

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e17 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 450 x 18.8266 (0.895 cos 30+0.852 sin 30)
5280 Approximate Method:

e17 = 5.7816 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e18 =
24 dI
V dc actual = 3 x 450 x 48.2609(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 450 x 18.8266
V dc actual = = 1.5279 e18 = 14.8208 Volts
133076.55
Volts AC Drop Method:
Vac17 = 0.866 x 1.5279 x 1.31

17 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 450 x 48.2609
V dc actual = = 3.9167
133076.55
Volts
Vac18 = 0.866 x 3.9167 x 1.31
Vac18 = 4.4433 Volts

18 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

E to F Vac19 = 2.2239 Volts


Reference Pole: Block 21
kVa total = 500 kVa

500 x 103
I total = = 72.4638 A
6900
F to Fi
24 x 150 x 72.4638
CM = =¿ 96031.5 CM School
2.7165
kVa total = 150 kVa
From Table:
150 x 103
For Feeder 1: I total = = 12.5511 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 1350 x 12.5511
CM = =¿16632.9CM
re-1/4 24.4488
D = 4.5’ D = 4.5’ From Table:
For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1

Xd = 0.2794log√ 4.5 x 9 3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2


Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi


0.866 Xd = 0.2794log√3 4.52 x 9
AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e19 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 72.4638(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:
e19 = 7.4178 Volts 3 dI (Racos Ø + Xtsin Ø )
e=
5280
AC Drop Method:
e20 =
24 dI
V dc actual = 3 x 1350 x 12.5511(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 150 x 72.4638
V dc actual = = 1.9603 e20 = 11.5632 Volts
133076.55
Volts AC Drop Method:
Vac19 = 0.866 x 1.9603 x 1.31

19 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 1350 x 12.5511
V dc actual = = 3.0558
133076.55
Volts
Vac20 = 0.866 x 3.0558 x 1.31
Vac20 = 3.4667 Volts

20 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

F to G Vac21 = 1.4811 Volts


Reference Pole: Block 25
kVa total = 333 kVa

333 x 103
I total = = 48.2609 A
6900
G to Gi
24 x 150 x 48.2609
CM = =¿63957 CM University
2.7165
kVa total = 225 kVa
From Table:
225 x 103
For Feeder 1: I total = = 18.8266 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 300 x 18.8266
CM = =¿24949.2CM
re-1/4 5.4331
D = 4.5’ D = 4.5’ From Table:
For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1

Xd = 0.2794log√ 4.5 x 9 3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2


Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi


0.866 Xd = 0.2794log√3 4.52 x 9
AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e21 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 48.2609( 0.895 cos 30+0.852 sin30)
5280 Approximate Method:
e21 = 4.9403 Volts 3 dI (Racos Ø + Xtsin Ø )
e=
5280
AC Drop Method:
e22 =
24 dI
V dc actual = 3 x 300 x 18.8266(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 150 x 48.2609
V dc actual = = 1.3056 e22 = 3.8544 Volts
133076.55
Volts AC Drop Method:
Vac21 = 0.866 x 1.3056 x 1.31

21 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 300 x 18.8266
V dc actual = = 1.0186
133076.55
Volts
Vac22 = 0.866 x 1.0186 x 1.31
Vac22 = 1.1556 Volts

22 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Gi to Gii
Ice Plant
kVa total = 501 kVa

501 x 103 F to Hi
I total = = 41.9206 A
√ 3 x 6900 Club
24 x 150 x 41.9206
CM = =¿55554.6 CM kVa total = 75 kVa
2.7165
75 x 103
From Table: I total = = 6.2755 A
√ 3 x 6900
For Feeder 1:
24 x 1800 x 6.2755
o CM = =¿ 8316.41CM
Use: 3 – No. 2/0, ACSR 50 C,60 Hz 32.5984
re-1/4 From Table:

D = 4.5’ D = 4.5’ For Feeder 1:


Use: 3 – No. 2/0, ACSR 50oC,60 Hz
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 re-1/4

d-1 = (0.365 x 1000)2 = 133076.55 CM D = 4.5’ D = 4.5’

Ra = 0.895 Ω/cond/mi
36+1

Xa = 0.641 Ω/cond/mi d-1 = 0.005 x 92( 39 )= 0.365 in2


Xd = 0.2794log√3 4.52 x 9 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.211 + 0.641 Ra = 0.895 Ω/cond/mi

Xt = 0.852 Ω/cond/mi Xa = 0.641 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xd = 0.2794log√3 4.52 x 9


0.866 Xt = 0.211 + 0.641
AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.852 Ω/cond/mi
Approximate Method:
Ratio = Xt/Ra = 0.952 < 3.0
3 dI ( Racos Ø + Xtsin Ø )
e= 0.866
5280 AC Drop Factor = 1.29 x = 1.31
0.85
e23 =
Approximate Method:
3 x 150 x 41.9206 (0.895 cos 30+0.852 sin 30)
5280 3 dI (Racos Ø + Xtsin Ø )
e=
5280
e23 = 4.2912 Volts
e24 =
AC Drop Method:
3 x 1800 x 6.2755(0.895 cos 30+ 0.852sin 30)
24 dI 5280
V dc actual =
CM
e24 = 7.7088 Volts
24 x 150 x 41.9206
V dc actual = = 1.134 Volts AC Drop Method:
133076.55
24 dI
Vac23 = 0.866 x 1.134 x 1.31 V dc actual =
CM
Vac23 = 1.2865 Volts

23 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 x 1800 x 6.2755
V dc actual = = 2.0372
133076.55
Volts
Vac24 = 0.866 x 2.0372 x 1.31
Vac24 = 2.3111 Volts

24 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Hi to H Vac25 = 2.9622 Volts


Reference Pole: Block 23
kVa total = 333 kVa

333 x 103
I total = = 48.2609 A
6900
H to Hii
24 x 300 x 48.2609
CM = ¿63955.8 CM School
5.4331
kVa total = 150 kVa
From Table:
150 x 103
For Feeder 1: I total = = 12.5511 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 300 x 12.5511
CM = =¿16632.8CM
re-1/4 5.4331
D = 4.5’ D = 4.5’ From Table:
For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1

Xd = 0.2794log√ 4.5 x 9 3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2


Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi


0.866 Xd = 0.2794log√3 4.52 x 9
AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e25 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 300 x 48.2609(0.895 cos 30+0.852 sin 30)
5280 Approximate Method:
e25 = 9.8805 Volts 3 dI (Racos Ø + Xtsin Ø )
e=
5280
AC Drop Method:
e26 =
24 dI
V dc actual = 3 x 300 x 12.5511(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 300 x 48.2609
V dc actual = = 2.6111 e26 = 2.5696 Volts
133076.55
Volts AC Drop Method:
Vac25 = 0.866 x 2.6111 x 1.31

25 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 300 x 12.5511
V dc actual = = 0.6791
133076.55
Volts
Vac26 = 0.866 x 0.6791 x 1.31
Vac26 = 0.7704 Volts

26 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Hii to Hiii Vac27 = 0.7704 Volts


Warehouse
kVa total = 300 kVa

300 x 103
I total = = 25.1022 A
√ 3 x 6900 Hii to I
24 x 150 x 25.1022
CM = ¿33266.3 CM Reference Pole: Block 11
2.7165
kVa total = 500 kVa
From Table:
500 x 103
For Feeder 1: I total = = 12.5511 A
6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 150 x 72.4638
CM = =¿ 96031.5CM
-1/4
re 2.7165

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e27 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 25.1022(0.895 cos 30+0.852 sin 30)
5280 Approximate Method:

e27 = 2.5696 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e28 =
24 dI
V dc actual = 3 x 150 x 72.4638(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 150 x 25.1022
V dc actual = = 0.6791 e28 = 7.4178 Volts
133076.55
Volts AC Drop Method:
Vac27 = 0.866 x 0.6791 x 1.31

27 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI Ii to Iii
V dc actual =
CM
School
24 x 150 x 72.4638
V dc actual = = 1.9603 kVa total = 150 kVa
133076.55
Volts 150 x 103
I total = = 12.5511 A
Vac28 = 0.866 x 1.9603 x 1.31 √ 3 x 6900
Vac28 = 2.2239 Volts 24 x 1350 x 12.5511
CM = ¿16632.9 CM
24.4488
From Table:
For Feeder 1:
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4

D = 4.5’ D = 4.5’

36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi
Xa = 0.641 Ω/cond/mi

Xd = 0.2794log√3 4.52 x 9

Xt = 0.211 + 0.641
Xt = 0.852 Ω/cond/mi
Ratio = Xt/Ra = 0.952 < 3.0
0.866
AC Drop Factor = 1.29 x = 1.31
0.85
Approximate Method:
3 dI (Racos Ø + Xtsin Ø )
e=
5280
e29 =
3 x 1350 x 12.5511(0.895 cos 30+ 0.852sin 30)
5280
e29 = 11.5632 Volts
AC Drop Method:
24 dI
V dc actual =
CM
24 x 1350 x 12.5511
V dc actual = = 3.0558
133076.55
Volts
Vac29 = 0.866 x 3.0558 x 1.31

28 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Vac29 = 3.4667 Volts 24 dI


V dc actual =
CM
24 x 600 x 12.5511
V dc actual = = 1.3581
133076.55
Volts

Iii to Iiii Vac30 = 0.866 x 1.3581 x 1.31

School Vac30 = 1.5407 Volts

kVa total = 150 kVa

150 x 103
I total = = 12.5511 A
√ 3 x 6900
24 x 600 x 12.5511
CM = ¿16633CM
10.8661
From Table:
For Feeder 1:
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4

D = 4.5’ D = 4.5’

36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi
Xa = 0.641 Ω/cond/mi

Xd = 0.2794log√3 4.52 x 9

Xt = 0.211 + 0.641
Xt = 0.852 Ω/cond/mi
Ratio = Xt/Ra = 0.952 < 3.0
0.866
AC Drop Factor = 1.29 x = 1.31
0.85
Approximate Method:
3 dI ( Racos Ø + Xtsin Ø )
e=
5280
e30 =
3 x 600 x 12.5511( 0.895cos 30+ 0.852sin 30)
5280
e30 = 5.1392 Volts
AC Drop Method:

29 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Iiii to Iiv Vac31 = 1.5407 Volts


School
kVa total = 150 kVa

150 x 103
I total = = 12.5511 A
√ 3 x 6900 I to Ji
24 x 600 x 12.5511
CM = ¿16633CM Warehouse
10.8661
kVa total = 300 kVa
From Table:
300 x 103
For Feeder 1: I total = = 25.1022 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 150 x 25.1022
CM = =¿ 33266.3CM
re-1/4 2.7165

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e31 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 600 x 12.5511( 0.895cos 30+ 0.852sin 30)
5280 Approximate Method:

e31 = 5.1392 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e32 =
24 dI
V dc actual = 3 x 150 x 25.1022(0.895 cos 30+0.852 sin 30)
CM
5280
24 x 600 x 12.5511
V dc actual = = 1.3581 e32 = 2.5696 Volts
133076.55
Volts AC Drop Method:
Vac31 = 0.866 x 1.3581 x 1.31

30 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI Ji to Jii
V dc actual =
CM
Mall
24 x 150 x 25.1022
V dc actual = = 0.6791 kVa total = 501 kVa
133076.55
Volts 501 x 103
I total = = 41.9206 A
Vac32 = 0.866 x 0.6791 x 1.31 √ 3 x 6900
Vac32 = 0.7704 Volts 24 x 150 x 41.9206
CM = ¿55554.6CM
2.7165
From Table:
For Feeder 1:
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4

D = 4.5’ D = 4.5’

36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi
Xa = 0.641 Ω/cond/mi

Xd = 0.2794log√3 4.52 x 9

Xt = 0.211 + 0.641
Xt = 0.852 Ω/cond/mi
Ratio = Xt/Ra = 0.952 < 3.0
0.866
AC Drop Factor = 1.29 x = 1.31
0.85
Approximate Method:
3 dI (Racos Ø + Xtsin Ø )
e=
5280
e33 =
3 x 150 x 41.9206 (0.895 cos 30+0.852 sin 30)
5280
e33 = 4.2912 Volts
AC Drop Method:
24 dI
V dc actual =
CM
24 x 150 x 41.9206
V dc actual = = 1.134 Volts
133076.55
Vac33 = 0.866 x 1.134 x 1.31
Vac33 = 1.2865 Volts

31 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 x 150 x 18.8266
V dc actual = = 0.5093
133076.55
Volts
Vac34 = 0.866 x 0.5093 x 1.31
ii iii
J to J
Vac34 = 0.5778 Volts
Office Building
kVa total = 225 kVa

225 x 103
I total = = 18.8266 A
√ 3 x 6900
24 x 150 x 18.8266
CM = =¿24949.7CM
2.7165
From Table:
For Feeder 1:
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4

D = 4.5’ D = 4.5’

36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi
Xa = 0.641 Ω/cond/mi

Xd = 0.2794log√3 4.52 x 9

Xt = 0.211 + 0.641
Xt = 0.852 Ω/cond/mi
Ratio = Xt/Ra = 0.952 < 3.0
0.866
AC Drop Factor = 1.29 x = 1.31
0.85
Approximate Method:
3 dI ( Racos Ø + Xtsin Ø )
e=
5280
e34 =
3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
5280
e34 = 1.9272 Volts
AC Drop Method:
24 dI
V dc actual =
CM

32 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Jiii to J Vac35 = 6.6716 Volts


Reference Pole: Block 17
kVa total = 500 kVa

500 x 103
I total = = 72.4638 A
6900
J to Jiv
24 x 450 x 72.4638
CM = ¿96030.4CM Office Building
8.1496
kVa total = 225 kVa
From Table:
225 x 103
For Feeder 1: I total = = 18.8266 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 450 x 18.8266
CM = =¿24949.7CM
re-1/4 8.1496
D = 4.5’ D = 4.5’ From Table:
For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1

Xd = 0.2794log√ 4.5 x 9 3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2


Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi


0.866 Xd = 0.2794log√3 4.52 x 9
AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e35 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 450 x 72.4638(0.895 cos 30+0.852 sin 30)
5280 Approximate Method:
e35 = 22.2535 Volts 3 dI (Racos Ø + Xtsin Ø )
e=
5280
AC Drop Method:
e36 =
24 dI
V dc actual = 3 x 450 x 18.8266 (0.895 cos 30+0.852 sin 30)
CM
5280
24 x 450 x 72.4638
V dc actual = = 5.8809 e36 = 5.7816 Volts
133076.55
Volts AC Drop Method:
Vac36 = 0.866 x 5.8809 x 1.31

33 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 450 x 18.8266
V dc actual = = 1.5279
133076.55
Volts
Vac36 = 0.866 x 1.5279 x 1.31
Vac36 = 1.7333 Volts

34 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Jiii to Ki Vac37 = 1.9259 Volts


Manufacturing Plant
kVa total = 750 kVa

750 x 103
I total = = 62.756 A
√ 3 x 6900 Ki to K
24 x 150 x 62.7555
CM = ¿83165.8CM Reference Pole: Block 19
2.7165
kVa total = 500 kVa
From Table:
500 x 103
For Feeder 1: I total = = 72.4638 A
6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 300 x 72.4638
CM = =¿ 96029.8CM
-1/4
re 5.4331

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e37 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 62.7555(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:

e37 = 6.424 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e38 =
24 dI
V dc actual = 3 x 300 x 72.4638(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 150 x 62.7555
V dc actual = = 1.6977 e38 = 14.8356 Volts
133076.55
Volts AC Drop Method:
Vac37 = 0.866 x 1.6977 x 1.31

35 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 300 x 72.4638
V dc actual = = 3.9206
133076.55
Volts
Vac38 = 0.866 x 3.9206 x 1.31
Vac38 = 4.4478 Volts

36 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

K to Kii Vac39 = 0.7704 Volts


School
kVa total = 150 kVa

150 x 103
I total = = 12.551 A
√ 3 x 6900 Kii to Kiii
24 x 300 x 12.5511
CM = ¿16632.8CM Office Building
5.4331
kVa total = 225 kVa
From Table:
225 x 103
For Feeder 1: I total = = 18.827 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 150 x 18.8266
CM = =¿24949.7CM
re-1/4 2.7165

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e39 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 300 x 12.5511(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:

e39 = 2.5696 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e40 =
24 dI
V dc actual = 3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 300 x 12.5511
V dc actual = = 0.6791 e40 = 1.9272 Volts
133076.55
Volts AC Drop Method:
Vac39 = 0.866 x 0.6791 x 1.31

37 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI Iiii to Li
V dc actual =
CM
Office Building
24 x 150 x 18.8266
V dc actual = = 0.5093 kVa total = 225 kVa
133076.55
Volts 225 x 103
I total = = 18.827 A
Vac40 = 0.866 x 0.5093 x 1.31 √ 3 x 6900
Vac40 = 0.5778 Volts 24 x 150 x 18.8266
CM = =¿24949.7CM
2.7165
From Table:
For Feeder 1:
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4

D = 4.5’ D = 4.5’

36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi
Xa = 0.641 Ω/cond/mi

Xd = 0.2794log√3 4.52 x 9

Xt = 0.211 + 0.641
Xt = 0.852 Ω/cond/mi
Ratio = Xt/Ra = 0.952 < 3.0
0.866
AC Drop Factor = 1.29 x = 1.31
0.85
Approximate Method:
3 dI (Racos Ø + Xtsin Ø )
e=
5280
e41 =
3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
5280
e41 = 1.9272 Volts
AC Drop Method:
24 dI
V dc actual =
CM
24 x 150 x 18.8266
V dc actual = = 0.5093
133076.55
Volts
Vac41 = 0.866 x 0.5093 x 1.31

38 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Vac41 = 0.5778 Volts 24 dI


V dc actual =
CM
24 x 1050 x 12.5511
V dc actual = = 2.3767
133076.55
Volts

Li to Lii Vac42 = 0.866 x 2.3767 x 1.31

School Vac42 = 2.6963 Volts

kVa total = 150 kVa

150 x 103
I total = = 12.5511 A
√ 3 x 6900
24 x 1050 x 12.5511
CM = ¿16633 CM
19.0157
From Table:
For Feeder 1:
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
re-1/4

D = 4.5’ D = 4.5’

36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2
d-1 = (0.365 x 1000)2 = 133076.55 CM
Ra = 0.895 Ω/cond/mi
Xa = 0.641 Ω/cond/mi

Xd = 0.2794log√3 4.52 x 9

Xt = 0.211 + 0.641
Xt = 0.852 Ω/cond/mi
Ratio = Xt/Ra = 0.952 < 3.0
0.866
AC Drop Factor = 1.29 x = 1.31
0.85
Approximate Method:
3 dI ( Racos Ø + Xtsin Ø )
e=
5280
e42 =
3 x 1050 x 12.5511(0.895 cos 30+ 0.852sin 30)
5280
e42 = 8.9936 Volts
AC Drop Method:

39 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Lii to L Vac43 = 2.2239 Volts


Reference Pole: Block 13
kVa total = 250 kVa

250 x 103
I total = = 36.232 A
6900
L to M
24 x 300 x 36.2319
CM = =¿ 48014.9CM Reference Pole: Block 15
5.4331
kVa total = 333 kVa
From Table:
333 x 103
For Feeder 1: I total = = 48.261 A
6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 450 x 48.2609
CM = ¿63956.2 CM
-1/4
re 8.1496

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e43 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 300 x 36.2319(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:

e43 = 7.4178 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e44 =
24 dI
V dc actual = 3 x 450 x 48.2609(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 300 x 36.2319
V dc actual = = 1.9603 e44 = 14.8208 Volts
133076.55
Volts AC Drop Method:
Vac43 = 0.866 x 1.9603 x 1.31

40 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 450 x 48.2609
V dc actual = = 3.9167
133076.55
Volts
Vac44 = 0.866 x 3.9167 x 1.31
Vac44 = 4.4433 Volts

41 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

M to Mi Vac45 = 1.1556 Volts


School
kVa total = 150 kVa

150 x 103
I total = = 12.5511 A
√ 3 x 6900 Mi to Mii
24 x 450 x 12.5511
CM = =¿16632.9 CM Mall
8.1496
kVa total = 501 kVa
From Table:
501 x 103
For Feeder 1: I total = = 41.9206 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 150 x 41.9206
CM = ¿55554.6 CM
re-1/4 2.7165

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e45 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 450 x 12.5511 (0.895 cos 30+0.852 sin 30)
5280 Approximate Method:

e45 = 3.8544 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e46 =
24 dI
V dc actual = 3 x 150 x 41.9206 (0.895 cos 30+0.852 sin 30)
CM
5280
24 x 450 x 12.5511
V dc actual = = 1.0186 e46 = 4.2912 Volts
133076.55
Volts AC Drop Method:
Vac45 = 0.866 x 1.0186 x 1.31

42 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 150 x 41.9206
V dc actual = = 1.134 Volts
133076.55
Vac46 = 0.866 x 1.134 x 1.31
Vac46 = 1.2865 Volts

43 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Mii to Miii Vac47 = 0.5778 Volts


Hospital
kVa total = 225 kVa

225 x 103
I total = = 18.8266 A
√ 3 x 6900 Miii to Miv
24 x 150 x 18.8266
CM = =¿24949.7CM University
2.7165
kVa total = 225 kVa
From Table:
225 x 103
For Feeder 1: I total = = 18.8266 A
√ 3 x 6900
Use: 3 – No. 2/0, ACSR 50oC,60 Hz
24 x 150 x 18.8266
CM = =¿24949.7CM
re-1/4 2.7165

D = 4.5’ D = 4.5’ From Table:


For Feeder 1:
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 Use: 3 – No. 2/0, ACSR 50oC,60 Hz

d-1 = (0.365 x 1000)2 = 133076.55 CM re-1/4

Ra = 0.895 Ω/cond/mi D = 4.5’ D = 4.5’

Xa = 0.641 Ω/cond/mi
36+1
3 2 d-1 = 0.005 x 92( 39 )= 0.365 in2
Xd = 0.2794log√ 4.5 x 9

Xt = 0.211 + 0.641 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.852 Ω/cond/mi Ra = 0.895 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xa = 0.641 Ω/cond/mi

0.866 Xd = 0.2794log√3 4.52 x 9


AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.211 + 0.641
Approximate Method:
Xt = 0.852 Ω/cond/mi
3 dI ( Racos Ø + Xtsin Ø )
e= Ratio = Xt/Ra = 0.952 < 3.0
5280
0.866
e47 = AC Drop Factor = 1.29 x = 1.31
0.85
3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
5280 Approximate Method:

e47 = 1.9272 Volts 3 dI (Racos Ø + Xtsin Ø )


e=
5280
AC Drop Method:
e48 =
24 dI
V dc actual = 3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
CM
5280
24 x 150 x 18.8266
V dc actual = = 0.5093 e48 = 1.9272 Volts
133076.55
Volts AC Drop Method:
Vac47 = 0.866 x 0.5093 x 1.31

44 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 dI
V dc actual =
CM
24 x 150 x 18.8266
V dc actual = = 0.5093
133076.55
Volts
Vac48 = 0.866 x 0.5093 x 1.31
Vac48= 0.5778 Volts

45 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

Miv to Mv
Distiller
kVa total = 501 kVa

501 x 103 Mv to Mvi


I total = = 41.9206 A
√ 3 x 6900 Office Building
24 x 150 x 41.9206
CM = =¿55554.633CM kVa total = 225 kVa
2.7165
225 x 103
From Table: I total = = 18.8266 A
√ 3 x 6900
For Feeder 1:
24 x 150 x 18.8266
o CM = =¿24949.7CM
Use: 3 – No. 2/0, ACSR 50 C,60 Hz 2.7165
re-1/4 From Table:

D = 4.5’ D = 4.5’ For Feeder 1:


Use: 3 – No. 2/0, ACSR 50oC,60 Hz
36+1
d-1 = 0.005 x 92( 39 )= 0.365 in2 re-1/4

d-1 = (0.365 x 1000)2 = 133076.55 CM D = 4.5’ D = 4.5’

Ra = 0.895 Ω/cond/mi
36+1

Xa = 0.641 Ω/cond/mi d-1 = 0.005 x 92( 39 )= 0.365 in2


Xd = 0.2794log√3 4.52 x 9 d-1 = (0.365 x 1000)2 = 133076.55 CM

Xt = 0.211 + 0.641 Ra = 0.895 Ω/cond/mi

Xt = 0.852 Ω/cond/mi Xa = 0.641 Ω/cond/mi

Ratio = Xt/Ra = 0.952 < 3.0 Xd = 0.2794log√3 4.52 x 9


0.866 Xt = 0.211 + 0.641
AC Drop Factor = 1.29 x = 1.31
0.85
Xt = 0.852 Ω/cond/mi
Approximate Method:
Ratio = Xt/Ra = 0.952 < 3.0
3 dI ( Racos Ø + Xtsin Ø )
e= 0.866
5280 AC Drop Factor = 1.29 x = 1.31
0.85
e49 =
Approximate Method:
3 x 150 x 41.9206 (0.895 cos 30+0.852 sin 30)
5280 3 dI (Racos Ø + Xtsin Ø )
e=
5280
e49 = 4.2912 Volts
e50 =
AC Drop Method:
3 x 150 x 18.8266(0.895 cos 30+ 0.852sin 30)
24 dI 5280
V dc actual =
CM
e50 = 1.9272 Volts
24 x 150 x 41.9206
V dc actual = = 1.134 Volts AC Drop Method:
133076.55
24 dI
Vac49 = 0.866 x 1.134 x 1.31 V dc actual =
CM
Vac49 = 1.2865 Volts

46 | P a g e
POWER PLANT DESIGN UNIVERSITY OF THE EAST-MANILA

24 x 150 x 18.8266
V dc actual = = 0.5093
133076.55
Volts
Vac50 = 0.866 x 0.5093 x 1.31
Vac50= 0.5778 Volts

Voltage Regulation:

By Approximate Method:
By AC Drop Method:
e Total = e1 + e2 +e3 + … + e50
V ac total = Vac1 + Vac2 +Vac3 + … + Vac50
e Total = 7.4327 + 5.7816 + 1.9272 + 4.2912
+ 4.4968 + 1.9272 + 1.9272 + 4.2912 + V ac total = 2.2283 + 1.7333 + 0.5778 +
6.424 + 5.7816 + 4.9403 + 19.7611 + 1.2865 + 1.3481 + 0.5778 + 0.5778 +
2.5696 + 12.8737 + 5.7816 + 7.4178 + 1.2865 + 1.9259 + 1.7333 + 1.4811 +
5.7816 + 14.8208 + 7.4178 + 11.5632 + 5.9244 + 0.7704 + 3.8596 + 1.7333 +
4.9403 + 3.8544 + 4.2912 + 7.7088 + 2.2239 + 1.7333 + 4.4433 + 2.2239 +
9.8805 + 2.5696 + 2.5696 + 7.4178 + 3.4667 + 1.4811 + 1.1556 + 1.2865 +
11.5632 + 5.1392 + 5.1392 + 2.5696 + 2.3111 + 2.9622 + 0.7704 + 0.7704 +
4.2912 + 1.9272 + 22.2535 + 5.7816 + 2.2239 + 3.4667 + 1.5407 + 1.5407 +
6.424 + 14.8356 + 2.5696 + 1.9272 + 0.7704 + 1.2865 + 0.5778 + 6.6716 +
1.9272 + 8.9936 + 7.4178 + 14.8208 + 1.7333 + 1.9259 + 4.4478 + 0.7704 +
3.8544 + 4.2912 + 1.9272 + 1.9272 + 0.5778 + 0.5778 + 2.6963 + 2.2239 +
4.2912 + 1.9272 = 4.4433 + 1.1556 + 1.2865 + 0.5778 +
0.5778 + 1.2865 + 0.5778 =
316.239 Volts
94.8093 Volts
eTotal
% VR = x 100 %
V Primary V actotal
% VR = x 100 %
V Primary
316.239
% VR = x 100 %
6900 94.8093
% VR = x 100 %
6900
% VR = 4.583%
% VR = 1.374%