Documente Academic
Documente Profesional
Documente Cultură
DOCUMENT DETAILS:
Revision No REV 01
AC HT CABLE SCHEDULE
AC
Cable
Cable Total cable Full Load AC Resistance Reactance Total AC
Rating Power Factor Size Total No. Total Cable Rated Cable Voltage drop % Voltage Power Loss
Sr No. Source Destination Length length with 5% Currrent of cable at 90 ° of cable at Resistance %Power Loss
(kW) ( Cos Ф) sin Ф selected( of runs length (Mtr) Volatge(Volts) Derate (V) drop (W)
(Mtr) extra (Mtr) (Amps) C (ohm/km) 50 Hz ( Ohm)
Sq mm )
(mho/km)
1 ICR 01 IDT ICOG ( ICR 01 ) 7500 1 0 300 25 1 25 26.25 33000 131.2 0.13 0.111 0.960 0.003 0.74 0.002% 174.87 0.002%
2 ICR 02 IDT HT PANEL ( ICR 02 ) 7500 1 0 300 25 1 25 26.25 33000 131.2 0.13 0.111 0.960 0.003 0.74 0.002% 174.87 0.002%
3 ICOG ( ICR 01 ) HT PANEL ( ICR 02 ) 7500 1 0 300 250 1 250 262.5 33000 131.2 0.13 0.111 0.960 0.034 7.39 0.022% 1748.67 0.023%
4 HT PANEL ( ICR 02 ) Metering Yard 15000 1 0 300 290 1 290 304.5 33000 262.4 0.13 0.111 0.960 0.039 17.14 0.052% 8113.81 0.054%
Note : Lenghts Given in schedule are indicative only. Actual Cable length shall be as per site conditions.