Documente Academic
Documente Profesional
Documente Cultură
“RELAY PROTECTION”
ADVISER:
Ali Basrah Pulungan ST., MT.
ARRANGED BY :
1.Fadel Rahman (180630)
2.Dina Salsa Fauzia (18063002)
3.Dioan Perdana Adfry (180630)
4. Najmu Nura Rizqa (18063041)
Author
PREFACE..........................................................................................
CHAPTER I INTRODUCTION
A.Background...........................................................................
B. Formulation of The Problem.................................................
C. Writing Purpose....................................................................
CHAPTER II DISCUSSION
A.System configurations...........................................................
1. Faults.................................................................................
2. Unearthed systems............................................................
3. Impedance earthed systems................................................
4. Solidly earthed systems.....................................................
5. Network arrangements......................................................
B. Power system protection principle........................................
1. Discrimination by time....................................................
2. Discrimination by current magnitude..............................
3. Discrimination by time and fault direction......................
4. Unit protection.................................................................
5. Signalling channel assistance...........................................
C. Current relays........................................................................
1. Inverse definite minimum time lag (IDMTL) relays.......
2. Alternative characteristic curves......................................
3. Plotting relay curves on log/log graph paper...................
4. Current relay application examples.................................
D. Differential protection schemes...........................................
1. Biased differential protection...........................................
2. High impedance protection..............................................
3. Transformer protection application examples.................
4. Pilot wire unit protection.................................................
5. Busbar protection.............................................................
INTRODUCTION
A. BACKGROUND
Switchgear, cables, transformers, overhead lines and other electrical equip-ment
require protection devices in order to safeguard them during fault condi-tions. In
addition, the rapid clearance of faults prevents touch and step potentialson equipment
from reaching levels which could endanger life. The function ofprotection is not to
prevent the fault itself but to take immediate action uponfault recognition. Protection
devices detect, locate and initiate the removal ofthe faulted equipment from the power
network in the minimum desirable time.It is necessary for all protection relays, except
those directly associated with the fault clearance, to remain inoperative during transient
phenomena whichmay arise during faults, switching surges or other disturbances to the
network.Protection schemes are designed on the basis of:
•safety,
•reliability,
•selectivity.
The requirements for CTs and VTs associated with relay protection are describedin
Chapter 5 and fuse and MCB protection devices in Chapter 11. Standard ref-erence texts
are provided in the references section at the end of this chapter. Theyvery adequately
cover protection theory and particular relays UK[1],US[2] and general[3] practice. Graphical
symbols for switchgear, control gear and protectivedevices are given in IEC 60617-7.
This chapter therefore concentrates on theprincipal relay protection schemes and typical
applications with practical calcu-lation and computer assisted examples.While the
earliest relays were electromechanical in construction, technolog-ical developments led
to the introduction of solid state or static relays usingdiscrete devices such as transistors,
resistors, capacitors, etc. Advent of micro-processors led to the development of
microprocessor-based relays and this culminated with today’s state of the art system of
numerical relaying where themeasurement principles themselves changed from analogue
to numerical. Otherrecent advances are discussed in the following sections.
B. FORMULATION OF THE PROBLEM
1. Describe all about Relay Protection
2. What is System Configurations, Current Relays
3. What is Power system protection principle, Differential protection
schemes
C. WRITING PURPOSE
1. Students can find out what is relay protection
2. Student can knows System configurations , Power system protection
principle, Current relays, and Differential protection schemes
CHAPTER II
DISCUSSION
A. SYSTEM CONFIGURATION
1. Faults
All power system components are liable to faults involving anomalous
current flow and insulation breakdown between conductors or between
conductors and earth. The insulation material may vary from air, in the case
of a transmission line, to oil, SF6 or a vacuum, in the case of switchgear. The
transmission and distribution engineer is concerned with symmetrical faults
involving all three phases with or without earth, and asymmetrical faults
involving phase-to- phase and one or two phase-to-earth faults. In addition,
interturn winding faults also occur in transformers and electrical machines.
Chapter 1 describes computer assisted methods of deriving fault levels in
power system networks and Chapter 26 describes the basic fundamentals
involved.
2. Unearthed systems
Such arrangements are only found in small isolated networks. At first
sight the earth fault current would seem to be negligible with this
connection. In practice, for all but the smallest networks the capacitive
current becomes sig- nificant and dangerous transient overvoltages can
occur due to low power fac- tor arcing faults to earth. Unearthed systems
therefore require high insulation levels and are limited to low voltage
distribution where insulation costs are less significant. The main application
is for very critical systems where con- tinuity of supply is of paramount
importance; two separate faults are required before an outage occurs and the
first earth fault simply causes alarms which enables damage to be located
and repaired before the critical supply is lost.
3. Impedance earthed system
In this configuration a resistance or reactance is placed between the
trans- former neutral and earth. The earth fault current may be limited by the
sizing of the impedance. This has the advantage of limiting:
possible damage to equipment from the fault current;
interference to control and communication circuits from the resulting
induced currents.
4. Solidly earthed system
Solidly earthed systems have the transformer neutral connected directly
to earth. This has the advantage that it limits the likely overvoltages during
fault conditions and is applied by most electricity supply companies for
rated volt- ages above 145 kV. The voltage-to-earth levels on the unfaulted
phases should not exceed 80% of the normal system phase voltage with the
solidly earthed arrangement. The system is then known as ‘effectively’
earthed and is consid- ered to be satisfied for ratios of X0 /X1 3 and R0 /X1 1
throughout the sys- tem under all conditions. In practice, these ratios will
vary according to the network switching conditions and connected
generation. The disadvantage is that the earth fault current can exceed the
three phase fault current depending upon the ratio of zero-to-positive
sequence impedance (see Fig. 10.1). Substation equipment must be rated
accordingly. Sufficient current to operate the protec- tion relay equipment is,
however, not normally a problem. In addition, it should be noted that a high
earth fault current will lead to high touch and step poten- tials during the
fault conditions. This must be limited to safe levels by adequate substation
earthing. Further, control and communication circuits must be pro- tected
against induced currents and possible interference resulting from the earth
fault.
5. Network arrangements
a) Radial
A simple radial feeder is shown in Fig. 10.2. The fault level is highest
closest to the source and limited by the impedances from source to fault
location. Clearance of a fault near the source will result in loss of supply to
downstream loads. Protection selectivity must be such that a fault on busbar
A must be isolated by only tripping the circuit breaker X via relay R1 and
maintaining supply to load busbar B.
c) Basic schemes
The fundamental difference between biased differential protection and
pilotwire differential protection is that relays are required at each end of the
pilotwire scheme. Only one relay is required for the biased differential
schemesdescribed in Section 10.5.1.
The long distances involved between the two ends of a feeder cable or
anoverhead line circuit necessitates the use of a relay at each end of the
protec-tion zone. The relays control the associated circuit breakers and
minimize the effects of pilot cable characteristics on relay performance. In
addition, a sin-gle relay scheme is not used because the CTs would
have to be impossiblylarge in order to avoid saturation on through fault
current when used in con-junction with a pilot cable burden of
approximately 1000 ohms. The relays arearranged to operate
simultaneously with intertripping to provide very rapidfault clearance
irrespective of whether the fault is fed from one or both endsof the protected
zone.
5. Busbar protection
a) Frame leakage detection
This is the cheapest form of busbar protection for use with indoor metal-
clad ormetal-enclosed switchgear installations. Since the probability of a
busbar faulton such modern equipment is very small, busbar protection on
such equipmentis only considered for the most important installations.
The switchboard islightly insulated from earth (above, say, 10 ohms) and
currents in a single con-nection to earth measured via a CT and frame
leakage relay. This arrangementrequires care to ensure all main and
multicore cable glands are insulated andthat bus sections are not
shorted by bolted connections through the concretefloor rebar or
switchgear steel floor fixing channel arrangements (Fig. 10.18a).
b) Bus zone
A comparison is made between the currents entering and leaving the busbar
orbusbar zone. CTs are therefore required on all circuits and the CT
locations arearranged to maximize the required zone of protection coverage
as shown in Fig.10.18b. Conventionally, main and check high impedance
relays are used in con-junction with these CTs to measure the sum of all the
currents. Very fast operat-ing times (40 msec) are feasible with such
schemes. An example of the practicalapplication of traditional busbar
protection principles is given in Section 10.9.The check feature makes
tripping dependent upon two completely separatemeasurements of fault
current using separate CTs and different routing for CT wiring to the
protection relays. In a double busbar arrangement a separateprotective relay
is applied to each bus section (zones 1 and 2) and an overallcheck system
arranged to cover all sections of both main and reserve busbars.
In current practice, schemes based on multiple operating principles
andsometimes based on a distributed concept, are applied for EHV
substations.These schemes are typically low impedance types and
handle differing CTratios, a high amount of CT saturation, diverse issues
such as evolving faultsand CT remanance. Continuous self-supervision and
the ability to detect abnor-malities on CT’s, CT wiring and the auxiliary
contacts used to provide a busimage make the scheme complete and highly
reliable, thus obviating needs fora separate set of check zone CT’s and
relays.
c) CT selection
In order to ensure stability under load, switching transient and external
faultconditions the CTs must be all carefully matched up to the
maximum faultlevel with the same ratio and characteristics. As explained in
Section 10.5.2 itis the voltage required to operate the relay rather than its
current setting whichdetermines the stability level of the scheme. The CT
‘knee point’ voltage mustbe kept as high as possible and at least three times
the relay voltage setting.The testing of busbar protection schemes will
therefore necessitate particularcare over CT polarities, correct operation of
busbar selector auxiliary contactsand primary operating current at the
selected relay settings.
An interruption in CT wiring will cause an unbalance and anomalous bus-
bar protection operation. Wiring supervision is therefore a feature of
mostschemes in order to raise an alarm with typical settings of unbalance at
10%of minimum circuit rating.See also Section 10.10 regarding optical
communication links.
CHAPTER III
CLOSING
A. CONCLUSION
Switchgear, cables, transformers, overhead lines and other electrical
equip-ment require protection devices in order to safeguard them during
fault conditions. In addition, the rapid clearance of faults prevents touch and
step potentialson equipment from reaching levels which could endanger life.
The function ofprotection is not to prevent the fault itself but to take
immediate action uponfault recognition. Protection devices detect, locate
and initiate the removal ofthe faulted equipment from the power network in
the minimum desirable time.It is necessary for all protection relays, except
those directly associated with the fault clearance, to remain inoperative
during transient phenomena whichmay arise during faults, switching surges
or other disturbances to the network.
Relay protection schemes and typical applications with practical calcu-
lation and computer assisted examples.While the earliest relays were
electromechanical in construction, technolog-ical developments led to the
introduction of solid state or static relays usingdiscrete devices such as
transistors, resistors, capacitors, etc. Advent of micro-processors led to the
development of microprocessor-based relays and this culminated with
today’s state of the art system of numerical relaying where themeasurement
principles themselves changed from analogue to numerical. Otherrecent
advances are discussed in the following sections.