Sunteți pe pagina 1din 3

TELECOM TOWER

COLOR CODING FOR HVAC PLANT ROOM


Date:
29/7/2011
ICI SHADE
S/No. SERVICE DESCRIPTION LEGEND COLOR
CODE NO.
1 CHILLED/ HOT WATER SUPPLY. CH/HWS LIGHT BLUE 4003

2 CHILLED/ HOT WATER RETURN. CH/HWR COMMET BLUE. 4008

3 BASE FOR CHILLED/ HOT WATER.   PALE CREAM 4004

4 CONDENSER WATER SUPPLY. CWS BUCKINGHAM GREEN 0202

5 CONDENSER WATER RETURN. CWR SEA GREEN 2229

6 CHILLER FLUE DUCT. FLUE GAS    

7 NATURAL GAS. NG YELLOW  


DARK ADMIRALITY
8 FUEL OIL SUPPLY FOS 0105
GRAY
DARK ADMIRALITY
9 FUEL OIL RETURN FOR 0105
GRAY
10 CITY WATER. CW BUCKINGHAM GREEN 0202

11 FIRE FIGHTING. FIRE SIGNAL RED. 0437

12 HOT WATER SUPPLY (Washrooms). HWS BROWN  

13 HOT WATER RETURN (Washrooms). HWR GOLDEN BROWN  


CHAMICAL FEED SYSTEM LINE
14 CFS BRILLIANT WHITE 0101
(NON ACID)
EQUIPMENT FOUNDATION
15   ORANGE  
CORNERS ANGLE.
ZEBRA (BLACK &
16 EQUIPMENT FOUNDATION SIDING YELLOW)
 
 
17 FOUNDATION TOP SMOKE GREY 0491
 
     
   

1. Color Numbers given are “Dulux Synthetic Enamel” paint from ICI PAINTS (PAK) LTD.
2. 3 Nos. Color coding Bands shall be provided on white color base at every 10Ft to 15Ft intervals of pipe length.
Size of Letters, Width of band & Space between bands will be according to table given below.
3. Reference: ASME A13.1 - 2007 Scheme for the Identification of Piping Systems and some colors are chosen /
defined by the owner (based on standard practice). This is intended to establish a common system to assist in
identification of hazardous materials conveyed in piping systems and their hazards when released in the
environment. Identification of contents of piping systems is recommended for the industrial power plants,
commercial & institutional installations and in buildings used for public assembly.

PTET Telecom Tower Project

PIPE MARKING SIZE CHART

PIPE DIA Minimum COLOR BAND WIDTH & Distance Between One
(With Insulation/ Height of SPACING Making to another
cladding) Letters "H"
Width "W" Space "S" Distance "D"
3/4" to 1-1/4" 1/2" 15 mm 7 mm
10 to 15 Ft as per site
1-1/2" - 2" 3/4" 20 mm 10 mm (at Band, Tee, wall
2-1/2" - 6" 1 -1/4" 30 mm 15 mm crossing etc this will
be as per below
8" - 10" 2 -1/2" 40 mm 20 mm
Drawing)
Over 10" 3 -1/2" 50 mm 25 mm
PIPE MARKER SIZE CHART
Minimum Length COLOR BAND
Outside Pipe Diameter Minimum Height
of Label Field WIDTH &
Including Covering of Letters
Color SPACING (mm)
Inch mm Inch (mm) Inch (mm) WIDTH SPACE
3/4" to 1-1/4" 19 - 32 mm 1/2" (13 mm) 8" (203 mm) 15 7
1-1/2" - 2" 38 - 51 mm 3/4" (19 mm) 8" (203 mm) 20 10
2-1/2" - 6" 64 - 152 mm 1-1/4" (32 mm) 12" (305 mm) 30 15
8" - 10" 203 - 254 mm 2-1/2" (64 mm) 24" (610 mm) 40 20
Over 10" Over 254 mm 3-1/2" (89 mm) 32" (813 mm) 50 25
           