Sunteți pe pagina 1din 1

P&ID DEVELOPMENT GUIDELINES

P&ID CONTENT LIST AND CHECK LIST DETAILED DESIGN


For FEED final issue, items in YELLOW may not be required

Note: the details shown at each issue are subject to the standard HOLDS in force at that issue.

P&ID DETAIL First Issue Second issue AFD issue post-AFD AFC
IDC for HAZOP Final FEED issue
General
Legend Sheets: preliminary X X
approved X X
Drawing number, issue and rev number X X X X
Standard Holds List X X X X
Specific notes X X X X
IDC comments included X
Client comments included X
HAZOP actions included X X

Equipment
Equipment names and Nos. X X X X
Equipment data blocks: empty X
completed X X X
Equipment accessories and internals as data sheet X X X
Insulation and tracing X X X
Equipment trim numbers X X
Venting, draining, relief requirements X X X X
Positive isolation requirements: preliminary X X
to approved philosophy X X
Purging requirements X X X
Nozzles: Tag nos and locations X X X X
Manways X X X X
sizes X X X X
Elevation X X
Skirt details X
Pumps: autostart requirements shown X X X
warm-through requirements X X
minimum flow requirements X X X X
strainer type X X
Confirmed vendor data included X

Packages
Name and number of package X X X X
Names & nos. of equipment within package X
Tie-in points: preliminary X X X
as vendor requirements X
Vendor drg. References X

Piping & valves


Continuation flags X X X X
Line sizes: Major lines preliminary X
all lines confirmed X X X
Line numbers: X X X
piping spec X X X
insulation and tracing X X
spec breaks/line number changes X X X X
Piping SPs: identified unnumbered X X
numbers X X
Slopes and no-pocket requirements X X X X

Special layout requirements (min distances, straight


runs, symmetrical routing,pockets, falls, etc) X X X X
piping vents and drains X X X
Sectional and maintenance isolation X X X
Layout of headers and distribution systems: prelim X
confirmed X X
Underground system breaks and isolation joints X X X
Line List X X

Instrumentation
Instruments : without tag numbers X
tag numbers X X X
Main control loops X
All control loops X X X
Instrument package details ( eg metering units) X X
Standard valve hookup details on Legend Sheet X X
SCADA symbols X X X
ESD levels shown for inputs and outputs X X

Analytical
Sample points X X X X
Corrosion monitoring X X X
Auto analyser details X

Control valves
Location - unnumbered X
tag numbers X X X
Type - preliminary X X
Size - preliminary X X
vendor size confirmed X
blocks and bypasses: unsized X
size confirmed X X X
Failure mode X X X
Note if relief valve size is governed X X
Drain valves X X X

Relief valves & bursting discs


Location - unnumbered X
tag numbers X X X
Routing to which header: preliminary X
confirmed X X
Number and size of PSV and piping - preliminary X
vendor size confirmed X
set point X X X X
Sizing basis specified X X
isolation, interlocks, vents X X X X
Piping falls correctly shown X X
back pressure check against tailpipe routing X

ESD valves
Location - unnumbered X
tag numbers X X X
Hookup type confirmed X X
ESD input signals confirmed X X

Blowdown piping and valves


Location - unnumbered X
tag numbers X X X
Spec breaks shown as required X X X
Inlet and outlet sizes -preliminary X
confirmed X X
Special requirements (e.g. air reservoir, time delay) X X