Thar Energy Limited

1 x 330MW Coal Fired Power Plant

O&M HPSL – Hub Power Services Ltd.

Document OPERATING MANUAL


TITLE POST MAINTENANCE CHECKS OF FOAM SYSTEM FOR HSD STORAGE TANKS

Document
Number
---UNCONTROLLED---
HPSL/TEL/O/OM/SG.N.---

WHEN PRINTED
PREPARED CHECKED APPROVED
REV. DATE MODIFICATIONS
BY BY BY

ALL RIGHT PERTAINING TO THE REPRODUCTION, TRANSFORMATION AND USE OF THIS DOCUMENT. IN ANY
FORM OR MANNER REMAIN THE EXCLUSIVE PROPERTY OF HPSL

1. REFERENCES
POST MAINTENANCE CHECKS OF FOAM SYSTEM FOR HSD STORAGE TANKS
HPSL/TEL/O/OM/SG.N.---

Drawing No: FA07892C-S12-05

2. SCOPE
The scope of this document is to take up the fuel unloading tanks CO2 system in service after
major maintenance works, in order to avoid any potential obstruction in the system while
heading towards operation.

ADDITIONAL
STEP ACTIONS REMARKS
INFORMATION

Post Maintenance Checks of Foam System For HSD Storage Tanks


1. Check Foam Filling system is normal
2. Close Foam Storage Tank Drain Valve 10XXXAA--
Check Foam Storage Tank Safety valve 10XXXAA—is
3.
intact
Check Foam Storage Tank level indicator 10XXXCL— is
4.
intact and open its root isolation valve
Close Foam pumps common suction line drain valve
5.
10XXXAA—
Open Foam pumps common suction line isolation valve
6.
10XXXAA—
Open Foam pumps common recirculation valve
7.
instrument air supply isolation valve 10XXXAA—
Open Foam pumps common recirculation valve
8.
10XXXAA—
Open Foam pumps common recirculation valve inlet
9.
isolation valve 10XXXAA—
Open Foam pumps common recirculation valve outlet
10.
isolation valve 10XXXAA—
Close Foam pumps common recirculation valve bypass
11.
valve 10XXXAA—
Close Foam pumps common recirculation line drain
12.
valve 10XXXAA—
Open Foam pumps common recirculation line isolation
13.
valve 10XXXAA—
Check Foam Pump-A coupling guard is intact & motor
14.
grounding wire is connected
15. Open Foam Pump A suction valve 10XXXAA—
Check Foam Pump A lubrication oil level is normal & Oil level is more than
16.
also check the oil colour 50 %
17. Check Foam Pump A electrical supply is available From electrical Board #
Check Foam Pump-A coupling guard is intact & motor
18.
grounding wire is connected
19. Open Foam Pump B suction valve 10XXXAA—

1
POST MAINTENANCE CHECKS OF FOAM SYSTEM FOR HSD STORAGE TANKS
HPSL/TEL/O/OM/SG.N.---

Check Foam Pump B lubrication oil level normal & also Oil level is more than
20.
check the oil colour 50 %

21. Check Foam Pump B electrical supply is available From electrical Board #

Close Foam Pumps common discharge line isolation


22.
valve 10XXXAA—
Close Buried Water Fire Pipe main isolation valve
23.
10XXXAA—
Close Buried Water Fire Pipe isolation valve to line #1
24.
10XXXAA—
Close Buried Water Fire Pipe main isolation valve to
25.
line#2 10XXXAA—
Close Foam Line mixer inlet isolation valve to foam line
26.
10XXXAA—
Open Foam Line mixer outlet isolation valve to foam
27.
line 10XXXAA—
28. Close Foam Line drain valve 10XXXAA—
Close Foam Line isolation valve to fuel forwarding
29.
pumps 10XXXAA—
Close Foam Line isolation valve to fuel forwarding
30.
pump house 10XXXAA—
31. Close Foam Line isolation valve to XXXXXX 10XXXAA—
Open Foam Line #1 to Fuel Storage Tanks isolation
32.
valve 10XXXAA—
Open Foam Line #2 to Fuel Storage Tanks isolation
33.
valve 10XXXAA—

AUTHORIZED BY:
NAME & SIGN DATE

PERFORMED BY:
NAME & SIGN DATE

COMPLETED BY:
NAME & SIGN DATE