1.

CRP-01 (GIS Incomer-H02)

Description Sr No Interlock signal Remarks

Closing Circuit 1. GIS OG-1 OFF (TRAFO FDR)


2. GIS OG-2 OFF (OG TO 72.5 KV BKR)
3. 72.5 KV BKR OFF
4. CRP L/R SELECTOR SWITCH IN LOCAL FOR OPERATION THROUGH
TNC IN CRP
5. CRP L/R SELECTOR SWITCH IN REMOTE FOR OPERATION THROUGH SAS
6. 86/1 & 86/2 – HEALTHY
i. 87L(RED-615) NOT OPERATED
ii. 50 (REF 615) NOT OPERATED
iii. 51 (REF 615) NOT OPERATED
iv. 50N (REF 615) NOT OPERATED
v. 51N (REF 615) NOT OPERATED
vi. LBB NOT OPERATED
7. 95/1 & 95/2 - HEALTHY
8. GIS L/R SELECTOR SWITCH IN REMOTE WIRED IN GIS CLOSING CKT
9. SPRING CHARGED WIRED IN GIS CLOSING CKT
10. BUS E/W OFF WIRED IN GIS CLOSING CKT
11. DISCONNECTOR ON WIRED IN GIS CLOSING CKT
12. EARTH SWITCH OFF WIRED IN GIS CLOSING CKT
13. BUSBAR COMP GAS PRESSURE HEALTHY WIRED IN GIS CLOSING CKT
OFF CIRCUIT 1. TNC OFF OPERATED – TO REF-615 DIRECT SWITCHING OFF BY TNC
WILL TRIP CRP-04 (72.5 BKR) & HAS BEEN REMOVED.
THEN CRP-01 THOROUGH REF-615 (S01/S02)
TRIP CIRCUIT 1. REF-615 OPERATED
WILL TRIP CRP-04 (72.5 BKR) &
THEN CRP-01 THOROUGH REF-615
2.
3.
4.
2. CRP-02 (GIS OG1 TO TRAFO FDR-H01)

Description Sr No Interlock signal Remarks

Closing Circuit 1. GIS IC- ON (INCOMER FDR)


Closing Circuit 2. TRAFO ROOM DOOR-1 & 2 CLOSED
+ HV ROOM DOOR- 1 & 2 CLOSED
+ TRAFO ROOM LCP-1 /2 ESTOP OK
+ HV ROOM LCP-1 /2 ESTOP OK
Closing Circuit 3. HV ROOM ISOLATOR CLOSED + EARTH SW OFF
+ TRAFO ROOM ISOLATOR CLOSED + EARTH SW OFF
Closing Circuit 4. VI (JOSYLN) OFF
5. 72.5 KV BKR ON
6. CRP L/R/PLC SELECTOR SWITCH IN LOCAL FOR OPERATION THROUGH TNC IN CRP
7. CRP L/R/PLC SELECTOR SWITCH IN REMOTE FOR OPERATION THROUGH SAS
8. CRP L/R./ PLC SELECTOR SWITCH IN PLC FOR OPERATION THROUGH PLC
9. 86/1 & 86/2 – HEALTHY TRAFO FAULT COVERS
i. 50 (REF 615) NOT OPERATED i. OLTC OSR
ii. 51 (REF 615) NOT OPERATED ii. BUCHHOLZ TRIP
iii. 50N (REF 615) NOT OPERATED iii. WDG TEMP TRIP
iv. OIL TEMP TRIP
iv. 51N (REF 615) NOT OPERATED
v. PRV TRIP
v. LBB NOT OPERATED vi. WATER FLOW
vi. GAS PRESSURE LOW -IN TRIP ??? vii. OIL FLOW
vii. TRAFO NO FAULT viii.
viii. HV ROOM + TRAFO ROOM DOOR
LOCKED & ESTOP OK
10. 95/1 & 95/2 - HEALTHY
11. GIS L/R SELECTOR SWITCH IN REMOTE WIRED IN GIS CLOSING CKT
12. SPRING CHARGED WIRED IN GIS CLOSING CKT
13. DISCONNECTOR ON WIRED IN GIS CLOSING CKT
14. EARTH SWITCH OFF WIRED IN GIS CLOSING CKT
15. BUSBAR COMP GAS PRESSURE HEALTHY WIRED IN GIS CLOSING CKT
16.
OFF CIRCUIT 1. TNC OFF OPERATED
2. PLC OFF
3. SAS OFF
TRIP CIRCUIT 1. 86/1 OR 86/2 - OPERATED 86/1 , 86/2 – TRIP CONDITON SEE POINT
9.
2. GIS OG-2 OFF/TRIP ( OG TO 72.5KV BKR)
3. 72.5 KV BKR OFF/TRIP
4.
3. CRP-03 (GIS OG2 TO 72.5 KV BKR -H03)

Description Sr No Interlock signal Remarks

Closing Circuit 1. GIS IC- ON (INCOMER FDR)


2. 72.5 KV ROOM DOOR CLOSED
3. 72.5 KV BKR OFF
4. CRP L/R SELECTOR SWITCH IN LOCAL FOR OPERATION THROUGH TNC IN
CRP
5. CRP L/R SELECTOR SWITCH IN REMOTE FOR OPERATION THROUGH SAS
6. 86/1 & 86/2 – HEALTHY
i. 50 (REF 615) NOT OPERATED
ii. 51 (REF 615) NOT OPERATED
iii. 50N (REF 615) NOT OPERATED
iv. 51N (REF 615) NOT OPERATED
v. LBB NOT OPERATED
vi. GAS PRESSURE LOW -IN TRIP ???
vii. 72.5 KV DOOR CLOSED
7. 95/1 & 95/2 - HEALTHY
8. GIS L/R SELECTOR SWITCH IN REMOTE WIRED IN GIS CLOSING CKT
9. SPRING CHARGED WIRED IN GIS CLOSING CKT
10. BUS E/W OFF WIRED IN GIS CLOSING CKT
11. DISCONNECTOR ON WIRED IN GIS CLOSING CKT
12. EARYH SWITCH OFF WIRED IN GIS CLOSING CKT
13. BUSBAR COMP GAS PRESSURE HEALTHY WIRED IN GIS CLOSING CKT
14.
OFF CIRCUIT 4. TNC OFF OPERATED
5. PLC OFF
6. SAS OFF
TRIP CIRCUIT 5. 86/1 OR 86/2 - OPERATED 86/1 , 86/2 – TRIP CONDITON SEE
POINT 9.
6. GIS OG-2 OFF/TRIP ( OG TO 72.5KV BKR)
7. 72.5 KV BKR OFF/TRIP
8.
4. CRP-04 (72.5 KV BKR )

Description Sr No Interlock signal Remarks

Closing Circuit 1. GIS OG-2 ON (OG TO 72.5 KV BKR)


Closing Circuit 1. ISOLATOR 1 ON + E SW 1 -OFF + ISOLATOR 2 OFF + UNIT FOR PFC UNIT -1
1 DOOR CLOSED + TIMER 1 OK
Closing Circuit 2. ISOLATOR 2 ON + E SW 2 -OFF + ISOLATOR 1 OFF + UNIT FOR PFC UNIT -2
2 DOOR CLOSED + TIMER 2 OK
3. CRP L/R SELECTOR SWITCH IN LOCAL FOR OPERATION THROUGH
TNC IN CRP
4. CRP L/R SELECTOR SWITCH IN REMOTE FOR OPERATION THROUGH SAS
5. 86/1 & 86/2 – HEALTHY
i. 50 (REF615 -1 /2) NOT OPERATED
ii. 51 (REF615 -1 /2) NOT OPERATED
iii. 50N (REF615 -1 /2) NOT OPERATED
iv. 51N (REF615 -1 /2) NOT OPERATED
v. LBB NOT OPERATED
vi. REF-615/1 – UNIT1 DOOR CLOSED + ISO ON FOR UNIT -1 ONLY
vii. REV -1 NO TRIP FOR UNIT -1 ONLY
viii. REF-615/1 – UNIT1 DOOR CLOSED + ISO ON FOR UNIT -2 ONLY
ix. REV -2 NO TRIP FOR UNIT -2 ONLY
6. 95/1 & 95/2 - HEALTHY
7.
8.
9.
10.
11. 72.5KV L/R SELECTOR SWITCH IN REMOTE WIRED IN 72.5 KV BKR CLOSING
CKT
12. SPRING CHARGED WIRED IN 72.5 KV BKR CLOSING
CKT
13.
14.
OFF CIRCUIT 2. TNC OFF OPERATED – TO REF-615 DIRECT SWITCHING OFF BY TNC
WILL TRIP CRP-04 (72.5 BKR) & HAS BEEN REMOVED.
THEN CRP-01 THOROUGH REF-615 (S01/S02)
TRIP CIRCUIT 5. REF-615 OPERATED
WILL TRIP CRP-04 (72.5 BKR) &
THEN CRP-01 THOROUGH REF-615
6.
7.
8.