Apparatus Maintenance and Power Management


for Energy Delivery

F6150
Power System Simulator
Basic information
Kamin Dave
Application Engineer (Protective Relaying)
DOBLE ENGINEERING COMPANY
F6-SERIES INTRODUCTION

¾ Hardware
¾ Software
¾ World wide Applications Engineers for
Application support

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6-SERIES INTRODUCTION
¾ High & Constant power output at all ranges
¾ All Power outputs are independent control of
magnitude, Phase Angle & Frequency
¾ All specifications are for worst case operating
condition
¾ Sources have AC/DC outputs

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6000: Single Box Solution
INBUILD F6910+F6810 OPTION

Single Ph. Electro Mech

Dir. Solid State

Three ph. Numerical

Impedance V, I and F Protection


Differential

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6000: Single Box Solution
INBUILD F6800-OPTION

Disc type Energy meter testing Static/digital Energy meter testing


Transducer testing
Cl. Accuracy = 0.02%

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6000: Single Box Solution
INBUILD F6820-OPTION

Analogue Input Measurement

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6000: Family of Power System Simulators

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150/F6150A Front Panel
Left Bank Right Bank
On/Enabled AC, DC
Source Signal Sources Synch Port
Voltages, Low Range Currents High Range Currents

Battery Ethernet
Simulator Com. Port

Low Level
Sources

Communication
RS232 Port

GPS Antenna
Receiver Port

Logic Contact, Logic-1 Contact, DC Meters Aux Logic-2 Outputs ##1 - 8,


Power Supply
Potential Inputs Outputs (Galvanic Isolated) Inputs
##1 - 8 ##1 - 8
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: Power System Simulator
¾ Total Number of Sources = 12
¾ Left Bank Sources = 6Nos.
¾ Right Bank Sources = 6Nos.
¾ Left Bank 6Nos. Of Sources are Convertible Sources.
¾ Convertible Sources means use as a Voltage/low range High Power
Current Sources.
¾ Right Bank Sources are high range Current Sources.
¾ Maximum Source configurations are 6-Voltage & 6-Current Sources
or 12-Current Sources.
¾ Advantage of 6-Voltage & 6-Current Sources are capable to do a
Testing of End-to-End Scheme testing with Backup Protection using
one PC.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: Power System Simulators Features

¾ Convertible Sources as a Voltage sources.


ƒ 3*150VA & 6*75VA CONST. POWER
ƒ 1*300V (L-N), 6*150V (L-N) insteps of 0.01V
ƒ 1*600V (L-L) & 3*520V (L-L) advantage is capable to do a Testing of
fixed 380V U/V relay type “VAG-11”.
ƒ Accuracy = 0.03% at 30 degree & 0.3% at 50 degree
¾ Convertible Sources as a Low range Current Sources with High Power
Output:
ƒ Use as a Convertible to current sources for High Burden
Electromechanical Earth fault relays like CDG-11(E/F), CAG-14,
RADHD, ICM-21, TJM-12.
ƒ 1*450VA, 3*150VA & 6*75VA CONST. POWER
ƒ 1*675VA, 3*225VA FOR 1.5s
ƒ 1*6A, 3*2A & 6*0.5A CONTINUOUS
ƒ Accuracy = 0.03% at 30 degree & 0.3% at 50 degree
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: Power Convertible Voltage Source
ƒ 3*150 VA continuous
ƒ 3*225 VA for 1.5 seconds
Source Mode Range Comment
Voltage 50/60 Hz 75, 150, 300 Volts Continuous
Voltage DC 106, 212, 424 Volts Continuous
Current DC 1.41, 0.707, 0.354 A Continuous
Range Compliance
Current 50/60 Hz 0.5 A 300 Volts Continuous
1.0 A 150 Volts
2.0 A 75 Volts
Current 50/60 Hz 0.75 A 260 Volts 1.5 Seconds
1.5 A 130 Volts
3A 65 Volts
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: Power System Simulator
¾ High Range Current sources with High Power Output.
ƒ 1*450VA, 3*150VA & 6*75VA CONST. POWER
ƒ 1*675VA, 3*225VA FOR 1.5s
ƒ 1*90A, 3*30A & 6*7.5A CONTINUOUS insteps of 0.001A.
ƒ 1*180A, & 3*60A for 1.5s
ƒ 1*90A Output is capable to do a Testing of 5A relays up to 10-15
times (Highset)
ƒ 6 - 75 VA current sources or 6 - 75 VA voltage sources for
differential Protection Test.
ƒ All Sources are independently controlled with its own Frequencies
& Phase angles.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: Current Source Power
ƒ 3*150 VA continuous
ƒ 3*225 VA for 1.5 seconds
Source Range Com pliance Comment
voltage
Current 7.5 A 20 V Continuous
50/60 Hz 15 A 10 V
30 A 5V
Current 15 A 15 V 1.5 Seconds
50/60 Hz 30 A 7.5 V
60 A 3.75 V
Current DC 5A 30 V Continuous
10 A 15 V
20 A 7.5 V

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: Power System Simulator
¾ Frequency Output.
ƒ RANGE:
ƒ 0.1Hz – 2kHz & DC insteps of 0.001Hz
ƒ DC – 3.1kHz TRANSIENT
¾ Phase Angle Output:
ƒ RANGE:
ƒ 0 – 359.9 degree (Lag/Lead) insteps of 0.1degree

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: Power System Simulators
Features: Inputs/Outputs

¾ 8 isolated digital inputs (galvanic)


ƒ Voltage (Voltage Input=0-250Vac/dc) or Contact
sense
¾ 8 isolated digital outputs (galvanic)
ƒ Field Programmable to NO or NC
ƒ Software controllable for power system event
simulation

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: Power System Simulators
Features

¾ Battery simulator for powering static or digital relays


ƒ 48, 125 and 250 Volts DC, 60 W or 6 to 300Vdc insteps of 0.1V
resolution.
¾ PC communication via RS-232 Serial or Ethernet port (RJ-485)
¾ GPS (Global Positioning System) satellite synchronization for End-to-
End testing

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150: SOURCE CONFIGURATION

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Test Sources Configurations
VA VB VC I1 I2 I3

Convertible Sources Current Sources


75VA 75VA 75VA 75VA 75VA 75VA
(Voltages or Low Currents)

75VA 75VA 75VA Left Bank (L) 75VA 75VA 75VA Right Bank (R)

VR VS VT IR IS IT

1. User Defined

L R L R
2. 3 x V + 3 x I (all 150 VA) 8. 4 x V + 4 x T (150 & 75 VA) x 1.5

3. 3 x V + 3 x T (all 150 VA) x 1.5 9. 6 x V (75 VA)

4. 4 x V + 4 x I (all 150 & 75 VA) 10. 6 x I (75 VA) x 1.5

5. 6 x I (R) (75 VA) 11. 6 x T (75 VA) x 1.5

6. 1 x V + 2 x I (L) (150 VA) 12. 6 x T (R) (75 VA) x 1.5

7. 1 x V + 1 x I (150 & 450 VA) 13. 1 x V + 2 x T (150 VA) x 1.5


NOTES: 1.) For I & V Sources the power is for continuous injection.
2.) For Transient (T) Current Sources the limited 1.5 sec. power is multiple x 1.5 of continuous.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Current Sources Configurations (Right Bank)

I1
150 VA (30/60 A) I1
I2 450 VA (90/180 A)
150 VA I1
I3 150 VA I1

I1 I1
150 VA (30/60 A)
I2 I2
150 VA (30/60 A)
I3 I3
IN 75 VA (15/30 A)
75 VA (15/30 A)
IR 75 VA
IS 15/30 A
IT
I1
300 VA (60/120 A)
I1
I2
150 VA (30/60 A)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Convertible Sources Configurations (Left Bank)

Low Currents
Voltage Configuration
High Compliance Voltage 75-300V
For High Impedance Relays
VA
I1 150 VA (0.5-2) A
150 VA (0.5-2) A VB
I2 150 VA
150 VA (0.5-2) A
I3 3V VC 150 VA
3I 150 VA (0.5-2) A

I1 VA
150 VA (0.5-2) A 150 VA (0.5-2) A
I2 VB
150 VA (0.5-2) A
I3 150 VA
4I 75 VA (0.25-1) A VC
IN 4V 75 VA (0.25-1) A
75 VA (0.25-1) A VN
75 VA
I1
450 VA (1.5-6) A VA
I1
1I
I1 6V VB
VC

I1 VR
6I I2 VS (0.25-1) A
I3
VT

IR 75 VA
IS 0.25-1 A
IT
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
EXAMPLE: 3-VOLTAGE & 1-CURRENT SOURCES CONFIGURATION OF F6150 for CDG or
CDD Relay Testing

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
EXAMPLE: 3-VOLTAGE & 1-CURRENT (TRANSIENT) SOURCES CONFIGURATION OF
F6150

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Modular Technology

EASY FOR TROUBLE SHOOTING

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Modular Technology
Just “REMOVE/INSERT” CARD from SLOT

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
DOBLE ENGINEERING PVT. LTD
305-SAKAR, OLD PADRA ROAD,
VADODARA.
PH: (+91)(265) 555 77 15 & Fax: (+91)(265) 235 62 85
Cell: (+91) 94267 47545
E-MAIL: kdave@doble.com
infokamindave@yahoo.com
Website: www.doble.com