Macros:
¾ LRAMPI: Linear RAMP, current
¾ LRAMPV: Linear RAMP, voltage
¾ LRAMPF: Liner RAMP, frequency
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
RELAY SETTING:
¾ Relay setting:
¾ I> = 0.2A
¾ t> = 45ms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Action Details:
¾ Offset current: 0.06A
¾ Offset duration: 10 cycles
¾ Delta current: 0.01A
¾ Delta Time: 10 cycles
¾ Current limit: 0.25A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Action:
0.25A
0.06A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
RAMP: GRAPH
E = 0.25A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Test:
Ampl: ACTION
Source: I1
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Macros:
¾ TIMEI: Time test, current
¾ TIMEV: Time test, voltage
¾ TIMEF: Time test, frequency
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Action Details:
¾ Offset current: 0.06A
¾ Offset duration: 10 cycles
¾ Test current: 1.02A
¾ Maximum on Time: 10 cycles
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Action:
0.2*5 = 1A
1.02A
0.06A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Action Graph:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Action Details:
Ampl: ACTION
Source: I1
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery