PART 1 GENERAL
1.1 SUMMARY
A. Section includes pipe, pipe fittings, connections and equipment for storm water
piping systems. This Section also includes roof and floor-drains, cleanouts,
interceptors, catch basins and sump pumps.
B. Related Sections:
1. Building Services Piping: (Optional short phrase).
2. Concrete Forms and Accessories: Execution requirements for placement
of inserts and sleeves specified by this section.
3. Cast-in-Place Concrete: Execution requirements for placement of concrete
specified by this section.
4. Paints and Coatings: Execution requirements for painting material
specified by this section.
5. Mechanical Identification: Product requirements for pipe identification for
placement by this section.
6. Wiring Devices: Execution requirements for electric connections to
equipment specified by this section.
7. Motors: Product requirements for motors for placement by this section.
1.2 REFERENCES
G. ASTM C14 - Concrete Sewer, Storm Drain, and Culvert Pipe (ASTM C14M -
Concrete Sewer, Storm Drain, and Culvert Pipe).
H. ASTM C425 - Compression Joints for Vitrified Clay Pipe and Fittings.
J. ASTM C564 - Rubber Gaskets for Cast Iron Soil Pipe and Fittings.
K. ASTM C700 - Vitrified Clay Pipe, Extra Strength, Standard Strength, and
Perforated.
M. ASTM D2665 - Poly (Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe
and Fittings
P. ASTM D3034 - Type PSM Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings.
R. CISPI 301 - (Cast Iron Soil Pipe Institute) Cast Iron Soil Pipe and Fittings for
Hub less Cast Iron Sanitary Systems.
1.3 SUBMITTALS
C. Product Data: Submit data on pipe materials, fittings, and accessories. Submit
manufacturers catalog information. Submit component sizes, rough-in
requirements, service sizes, and finishes. Submit pump type, capacity, and
certified pump curves showing pump performance characteristics with pump and
C. Operation and Maintenance Data: Submit spare parts lists, exploded assembly
views for pumps and equipment.
1.5 QUALIFICATIONS
A. Product Requirements.
PART 2 PRODUCTS
A. Drain, Waste, and Vent: Conform to ASME B31.9, ASTM F708, MSS SP58,
MSS SP69 and MSS SP89.
C. Hangers for Pipe Sizes 2 inches and Over: Carbon steel, adjustable, clevis.
D. Multiple or Trapeze Hangers: Steel channels with welded spacers and hanger
rods.
F. Wall Support for Pipe Sizes over 3 inches welded steel bracket and wrought steel
clamp.
H. Floor Support: Cast iron adjustable pipe saddle, lock nut, nipple, floor flange, and
concrete pier or steel support.
B. General Purpose Vibration Resistant Fire Stopping Sealant: Silicone based, non-
slumping, premixed sealant with in tumescent properties, vibration and moisture
resistant, rated for 3 hours in accordance with ASTM E814 and UL 1479.
C. DWV Plastic Pipe Systems Fire Stopping Sealant: Silicone based, premixed
sealant with in tumescent properties, vibration and moisture resistant, and rated
for 3 hours in accordance with ASTM E814 and UL 1479 with metal collars.
A. Manufacturers:
1. Jason
2. Terain
Or approved equal
B. Floor Drain (FD-1): ANSI A112.21.1; galvanized cast iron two piece body with
double drainage flange, weep holes, reversible clamping collar, and round,
adjustable nickel-bronze strainer.
C. Floor Drain (FD-6): Lacquered or Galvanized cast iron two piece body with
drainage flange, heavy duty grate 6 inches wide, 12 inches long, dome strainer,
end plates with gaskets.
B. Strainer: Removable [polyethylene ,cast metal ,cast aluminum ,cast bronze ,cast
iron dome with stainless steel or bronze screen.
C. Accessories: Membrane flange and membrane clamp with integral gravel stops.
2.8 CLEANOUTS
A. Exterior Surfaced Areas (CO-1): Round or Square cast nickel bronze access
frame and non-skid cover.
B. Exterior Unsurfaced Areas (CO-2): Line type with lacquered cast iron body and
round epoxy coated cover with gasket.
C. Interior Finished Floor Areas (CO-3): Galvanized cast iron body with anchor
flange, [reversible clamping collar, threaded top assembly, and round scored
cover with gasket in service areas and round or square depressed cover with
gasket to accept floor finish in finished floor areas.
D. Interior Finished Wall Areas (CO-4): Line type with lacquered cast iron body and
round epoxy coated cover with gasket, and round stainless steel access cover
secured with machine screw.
2.9 SUMPS
A. Manufacturers:
1. Terain
2. Jason
Or approved equal
B. Sump: Precast concrete specified in Section 03400 Precast concrete Epoxy coated
fabricated steel, Glass fiber reinforced encased with 8 inches concrete with
required openings and drainage fittings.
A. Manufacturers:
1. Terain
2. Jason
Approved or equal
B. Sediment Interceptor: Epoxy coated cast iron ,Stainless steel ,Precast concrete
body and secured cover with removable stainless steel sediment bucket.
A. Manufacturers:
1. Jason
2. Terain
Approved or equal
2.12 MANHOLES
A. Manufacturers:
1. Jason
2. Flycot
Approved or equal
C. Casing: Cast iron volute with radial clearance around impeller, inlet strainer, slide
away couplings.
D. Impeller: Cast iron; bronze; open non-clog, closed, keyed to corrosion resistant
alloy steel, stainless steel shaft.
E. Support: Cast iron pedestal motor support on steel floor plate with gas tight
gaskets.
G. Drive: Flexible coupling to vertical, solid shaft ball bearing electric motor.
H. Sump: Steel cover plate [with steel curb frame for grouting into concrete sump
on steel sump basin with inspection opening and cover, and alarm fittings.
J. Controls (Duplex): Float operated mechanical alternator with float rod, stops, and
corrosion resistant float to alternate operation of pumps. Cut-in second pump on
rising level or lead pump failure. Furnish separate pressure switch high level
alarm with transformer, alarm bell, and stand pipe ,and extra set of wired
terminals for remote alarm circuit] [and emergency float switch with float rod,
stops, and corrosion resistant float to operate both pumps on failure of alternator.
A. Manufacturers:
1. Flycot
2. Jason
Approved or equal
C. Casing: Cast iron , Bronze pump body and oil filled motor chamber.
D. Impeller: Cast iron ,Bronze; closed, stainless steel or corrosion resistant alloy
steel shaft.
G. Accessories: Oil resistant cord and plug with three-prong connector for
connection to electric wiring system including grounding connector.
I. Controls: Integral diaphragm, mercury switch type level controls with separate,
liquid-level, and control high level alarm.
3.1 EXAMINATION
3.2 PREPARATION
A. Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe.
3.3 INSTALLATION
E. Route piping in orderly manner and maintain gradient. Route parallel and
perpendicular to walls.
H. Install piping to allow for expansion and contraction without stressing pipe,
joints, or connected equipment.
I. Provide clearance in hangers and from structure and other equipment for
installation of insulation and access to valves and fittings.
J. Provide access where valves and fittings are not exposed. Coordinate size and
location of access doors with Section 08310.
K. Establish elevations of buried piping outside building to provide not less than ft
of cover.
N. Prepare exposed, unfinished pipe, fittings, supports, and accessories ready for
finish painting. Refer to Section 09910.
R. Inserts:
1. Provide inserts for placement in concrete forms.
2. Provide inserts for suspending hangers from reinforced concrete slabs and
sides of reinforced concrete beams.
3. Provide hooked rod to concrete reinforcement section for inserts carrying
pipe over 4 inches
4. Where concrete slabs form finished ceiling, locate inserts flush with slab
surface.
5. Where inserts are omitted, drill through concrete slab from below and
provide through-bolt with recessed square steel plate and nut above flush
with top of slab.
9. Prime coat exposed steel hangers and supports. Hangers and supports
located in crawl spaces, pipe shafts, and suspended ceiling spaces are not
considered exposed.
10. Provide hangers adjacent to motor driven equipment with vibration
isolation; refer to Section
11. Support cast iron drainage piping at every joint.
T. Pumps:
4. Decrease from line size with long radius reducing elbows or reducers.
Support piping adjacent to pump independently of pump casings. Install
supports under elbows on pump suction and discharge line sizes 4 inches
and over.
5. Provide pumps operating at specified system fluid temperatures without
vapor binding and cavitations, non-overloading, in parallel or individual
operation, and operating within 25 percent of midpoint of published
maximum efficiency curve.
6. Align and verify alignment of base mounted pumps prior to start-up.
B. Establish invert elevations, slopes for drainage to ¼ inch per foot minimum.
Maintain gradients.
3.5 SCHEDULES
All Sizes:
1. Maximum hanger spacing: 6 ft
2. Hanger rod diameter: 38/inch