Submittal Transmittal, Consultant

(D) Grouped by Each Number

Due Date:

Boeing 4-20 VPAL - VPAL Construction Project # 4212054-007 Skanska USA Building Inc.
Tel: Fax:

Date: 2/21/2014 Reference Number: 0086

Transmitted To: Dave Ginestra Transmitted By: Chris Heinle


Dutton Electric Company Inc. Skanska USA Building Inc.
12407 Mukilteo Speedway Suite A170 221 Yale Ave. N., Suite 400
Lynnwood, WA 98087-1518 Seattle, WA 98109
Tel: (425) 347-7600 Tel: 206-726-8000
Fax: (425) 355-1610 Fax: 206-328-9235

Submittal Package No Description Due Date


0053 - 283100 - 0 Electrical - Fire Alarm
Transmitted For Delivered Via Tracking Number
Construction Email

Items Qty Spec SectionSub Section Description Type ID Notes

0001 1 283100 1.5.B Fire Alarm and Detection - PDS


Product Data
0002 1 283100 1.5.D Fire Alarm and Detection - Shop SD
Drawings

Cc: Company Name Contact Name Copies Notes

Remarks

Signature Signed Date


Submittal Transmittal, Consultant
(D) Grouped by Each Number

Due Date: 2/21/2014

Boeing 4-20 VPAL - VPAL Construction Project # 4212054-007 Skanska USA Building Inc.
Tel: Fax:

Date: 2/7/2014 Reference Number: 0079

Transmitted To: Gene Coltran Transmitted By: Chris Heinle


The Boeing Company Skanska USA Building Inc.
PO BOX 3707 221 Yale Ave. N., Suite 400
MC 92-58 Seattle, WA 98109
SEATTLE, WA 98124-2207 Tel: 206-726-8000
Fax: 206-328-9235

Submittal Package No Description Due Date


0053 - 283100 - 0 Electrical - Fire Alarm 2/21/2014
Transmitted For Delivered Via Tracking Number
Approval Email

Items Qty Spec SectionSub Section Description Type ID Notes

0001 1 283100 1.5.B Fire Alarm and Detection - PDS Reviewed As Noted
Product Data
0002 1 283100 1.5.D Fire Alarm and Detection - Shop SD
Drawings

Cc: Company Name Contact Name Copies Notes

Remarks

This submittal has been reviewed by the REVIEWED X REVIEWED AS NOTED No exception taken
Electrical Engineer of Record and marked REJECTED REVISE/RESUBMIT Rejected
'No Exceptions Taken'.
Comments made on shop drawings or submittals Make corrections noted
This submittal has been reviewed by the
during this review do not relieve contractor from
compliance with requirements of drawings and See Attached Letter
Architect of Record and marked specifications. This review is only a check for
general conformance with design concept of Revise & Resubmit
'Reviewed Corrections Noted'. Reference project and general compliance with information Check is only for general conformance with the
comments on sheet FA-00. given within the contract documents. This review design concept of the project and general
does not constitute approval or acceptance of
compliance with the information given in the contract
deviations from contract documents. Any
This submittal review has concurrence deviations must be requested in writing in documents. Any action shown is subject to the
accordance with the contract documents. The requirements of the plans and specifications.
from Boeing Engineering, Dave contractor is responsible for confirming and Contractor is responsible for; dimensions which shall
Honarkhah, George Wagersky, 2/18/2014 correlating quantities and dimensions; selecting be confirmed and correlated at the job site;
fabrication processes and the techniques of
and Boeing Fire Protection Engineering, construction; coordinating work with all other
fabrication processes and techniques of
Robert Eaker, 2/20/2014 trades; and performing work in a safe and construction; coordination of his work with that of all
satisfactory manner. other trades and the satisfactory performance of his
work.
COFFMAN ENGINEERS
John N. Barton Date; 2/18/2014
THE MILLER|HULL PARTNERSHIP, LLP 02/13/2014
Date ___________ R. Ramos
By _______________

Signature Signed Date


Fire Alarm Submittal For:

BOEING 04-20 V-PAL


Logan Ave.,
Renton, WA 98055

System Type: Siemens XLS


Siemens Project #: 44OP-142436

Siemens Industry, Inc.


Building Technologies FIS Division
22010 SE 51st Street
Issaquah, WA 98029
Ph (425) 507-4300
Fax (425) 507-4350
Submittal Index

BOEING 04-20
V-PAL
Fire Alarm System
Siemens Job Number: 44OP-142436

November 15, 2013

Qty Cat# Manuf. Model Description

1 6300 SIEMENS XLS Intelligent Fire Alarm Control Panel


1 6326 SIEMENS SSD-C-REM REMOTE LCD DISPLAY W CONTROL
1 6327 SIEMENS CAB-2 & CAB-BATT XLS CABINET & BATTERY BOX ENCLOSURE
1 6103 SIEMENS HFP-11 FIREPRINT DETECTOR
21 6304 SIEMENS HTRI-D DUAL INPUT MONITOR MODULE
1 6304 SIEMENS HTRI-S SINGLE INPUT MONITOR MODULE
9 6304 SIEMENS HTRI-R SINGLE INPUT W/RELAY MODULE
1 6306 SIEMENS HMS-D MANUAL STATION -DUAL ACTION
1 6185 SIEMENS AD2-P AD2-P DUCT HOUSING FOR USE WITH HFP-11 SMOKE DETECTOR
1 6307 SIEMENS RL-HC DUCT DETECTOR REMOTE LAMP

1 of 1
s Data Sheet
Fire Safety & Security Products

FireFinder® XLS
Advanced Fire Alarm Control Panel
ARCHITECT AND ENGINEER SPECIFICATIONS
 Standard / 2500-point-capacity
 User help screens
addressable fire-alarm control  Multiple command stations
panel (FACP)  Menu-driven operator commands
 Ability to network with other  5000-event, history-logging capability
FireFinder XLS systems with on-line and off-line reports
 Powerful, easy-to-use programming  Multiple levels of password protection
capabilities
 Automatic environmental compensation
 Fully field programmable, via for smoke detectors
Windows® laptop PC
 Alarm verification
 6", backlit LCD display  by device or zone
 User-friendly system interface  Pre-alarm operation
 Touch screen for maintenance  Logic-controlled output functions
operations and function keys
 Time-based-controlled output functions
 Global annunciation and control
capability  Holiday schedule

 Multi-language display  City tie / leased line


 Universal AC power input:  200 notification-appliance-circuits
120VAC – 240VAC @ 50 / 60Hz (NACs) capacity
 12 amps of system power  Modular assembly  Up to 3.0 amps (24VDC) per NAC
(expandable to 48 amps)
 Supervised remote printer  Built-in strobe synchronization protocol
 Numerous Relays: Alarm, Trouble,
 32-character custom messages  Supports pre-action, deluge and agent
Programmable, etc. releasing
  Thermal strip printer
SureWireTM addressable-loop technology  Voice evacuation system (optional)
  Security-device monitoring
Polarity-insensitive detection circuits
 ( UL 1076 Listed)  NEC 760 power-limited circuits
(patented)  ( UL 864 Compliant)
  Sprinkler Supervision
Useful diagnostic LEDs on all cards  Intelligent interface to building / process
 Supports FirePrintTM application-specific  Degrade-mode operation management systems
detection  Coded outputs  Operates as interactive peer with other
 Intelligent / analog detection circuits:  NCCG Graphics support XLS or XLSV units in a XNET network
‘Class A’ or ‘Class B’  UUKL Listed for smoke control  Distributed processing
 Supports single-person ‘ Walk Test ‘  UL 864 9th Edition Listed & ULC Listed;  Detector Sensitivity Readout / Printout
 Seismic certified FM, CSFM & NYC Fire Dept. Approved  per NFPA 72

System Overview
FireFinder XLS is a microprocessor-based, advanced Underwriter's Laboratories of Canada also lists this FACP for
life-safety system that has a 6" display and large, fire applications under ULC-S527. FireFinder XLS is Factory
lighted buttons; making it a highly intuitive fire-alarm Mutual Approved; as well as CSFM and NYC Fire Department
user interface. Through the use of the unique Approved for use in those specific locales. In addition to the
multiprocessor ‘Network’ design – along with the ability standard fire applications, FireFinder XLS is UL Listed
to utilize analog and conventional detection devices – under the category UUKL for smoke control. FireFinder XLS
FireFinder XLS exemplifies a flexible and highly can be used as a listed Fireman's Smoke Control Station in
configurable life-safety system. high-rise office buildings, malls and other large structures.
FireFinder XLS is ideally suited for commercial, FireFinder XLS is UL Listed and FM Approved for
institutional and industrial fire detection and SinorixTM clean-agent systems and pre-action or deluge
notification applications. This FACP complies with the sprinkler systems, which include foam or water
requirements of NFPA Standard 72, and is listed by applications. FireFinder XLS operates on the releasing
Underwriters Laboratories under their UL 864 standard. requirements specified in NFPA 13 and 2001.

FireFinder® XLS Overview 6300


s Industry, Inc.
Building Technologies Division
System Overview ─ (continued)
The FireFinder XLS system has been seismic qualified Model PMI contains the site-specific program configuration
in accordance with: created in the Zeus system software-programming tool.
 International Building Code, 2006 Edition The controller in Model PMI provides all system logic and
 California Building Code, 2007 Edition supervision. Model PMI contains a large, 6" (1/4 VGA)
 ASCE Standard 7, 2005 Edition monochrome LCD display, touch screen and LEDs for
 OSHPD CAN 2-1708A.5, Rev. 3 displaying system status. A sound is made when there is
 ICC-ES AC 156, Effective 1/1/2007 any unacknowledged event from Model PMI. The display
FireFinder XLS is also OSHPD preapproved under: is surrounded by keys that are used to control the
OSP-0057-10. displayed information and to navigate through these
screens. Keys are also provided to obtain and enter "Help"
FireFinder XLS Components into the menu features of Model PMI.
A basic FireFinder XLS FACP consists of the following The FireFinder XLS system is controlled and operated
sub-assemblies: Person Machine Interface (Model PMI); from Model PMI. The intuitive Person Machine Interface
Power Supply (Model PSC-12); Device Loop Card (Model uses large, lighted buttons to prompt users as to the next
DLC); Zone Indicating Card (Model ZIC-4A); Card cage correct system operation that is available (Acknowledge,
(Model CC-5); Inner Door Blank Single Plate (Model ID-SP); Silence, Unsilence, Audible or Reset).
CAB-1, CAB-2 or CAB-3 enclosures.
Optional modules that can be installed with this FACP
include: Card Cage (Model CC-2); Network Interface Card
(Model NIC-C); Zone Indicating Card 8 circuits (Models
ZIC-8B / ZIC-2C); Control Relay Card (Model CRC-6);
Output Control Module (Model OCM-16); Switch
Control Module (Model SCM-8); LED Control Module
(Model LCM-8); Fan Control Module (Model FCM-6);
Supervised Input Module (Model SIM-16); Power Supply DLC Device Loop Card
Extender (Model PSX-12); Remote Network Interface
(Model RNI); Remote Printer Module (Model RPM); DLC Device Loop Card
System Status Display (Model SSD); Multi-Point Digital The Device Loop Card (Model DLC) is the interface for
Alarm Communicator (Model MDACT); Two-Module connection with FireFinder XLS detectors and initiating
Remote Enclosure (Model REMBOX2); Four-Module devices ─ including manual stations, control and input
Remote Enclosure (Model REMBOX4). devices. Model DLC plugs into one (1) slot of the CC-2 or CC-
The XLS FACP is compatible with a full line of intelligent 5 card cage. Programming Model DLC is accomplished
initiating devices, highlighted by the FirePrint application- using the FireFinder XLS Zeus system software-
specified detectors: Models HFP-11 and HFPT-11. XLS is also programming tool.
compatible with the NCC series of graphics command Moreover, Model DLC takes one (1) address on the
centers. network, and communicates with two (2) device
circuits for a total of 252 detectors and devices. Model
DLC has 12 LEDs for diagnostic purposes, and provides
ground-fault detection and zone-isolation circuitry.

PM I Person Machine I nterface

PMI Person Machine Interface


The Person Machine Interface (Model PMI) is the core of the ZIC-4A Zone I ndicating Card
FireFinder XLS system. Model PMI serves as both
operator interface and central microprocessor for the ZIC-4A Zone Indicating Card
FireFinder XLS system. From Model PMI, the end user The Zone Indicating Card (Model ZIC-4A) provides four (4)
can acknowledge events, control the system- fully supervised, programmable output circuits for use
notification appliance circuits and reset the system. on each FireFinder XLS. Model ZIC-4A supplies four (4)
Detailed information about the nature and location of the ‘Class B’ (Style Y) or ‘Class A’ (Style Z) type output circuits,
events can also be displayed. power limited to 3.0 amps maximum per circuit.

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)
Each circuit can be independently programmed for use When Model NIC-C is used for XNET communications,
with listed audible or visual notification appliances; listed Model NIC-C provides communication between systems.
emergency audio speakers; municipal tie boxes; leased The maximum of XNET Model NIC-C cards on a single
lines, or as releasing circuits. Model ZIC-4A plugs into one system (single node) is one (1), for a total of 64 XNET
(1) slot in the Model CC-5 or Model CC-2 card cage, and has Model NIC-C cards on a peer-to-peer networked system.
on-board LEDs for system status and troubleshooting. Model NIC-C has diagnostic LEDs that indicate: Card Fail,
Indication of power, communication, internal operation, CAN Fail, HNET Fail, XNET Fail, Ground Fault, Loop ‘A’ Fail and
and ground-fault conditions are provided, as well as Loop ‘B’ Fail. Model NIC-C Card also has LEDs to indicate
indication of circuit activation or Trouble conditions. Power, Style and Active Networks.

ZIC-8B / ZIC-2C  Zone Indicating Cards


HL I M  Line Isolator Module
ZIC-8B / ZIC-2C
The Zone Indicating Card (Model ZIC-8B) provides eight (8) HLIM Line Isolator Module
fully supervised, programmable output circuits for use on The loop-isolator module (Model HLIM) provides short-
FireFinder XLS. Model ZIC-8B supplies eight (8) ‘Class B’ circuit protection on FireFinder XLS intelligent device
(Style Y) type output circuits, power limited to 2.0 amps circuits (see: Model DLC). When Model HLIM detects a
maximum per circuit. Each circuit can be independently short circuit, Model HLIM is able to isolate the affected
programmed for use with listed audible or visual segment of the circuit – allowing the remaining devices
notification appliances, or listed emergency audio to continue operation. Model HLIM is self-restoring –
speakers. Model ZIC-8B plugs into one (1) slot in the automatically reconnecting to circuit segment when the
Model CC-5 or Model CC-2 card cage, and has on-board fault is removed. Model HLIM can be wired in either a
LEDs for system status and troubleshooting. Style 4 or Style 6 configuration.
Model ZIC-2C mounts directly on Model ZIC-8B, and Model HLIM does not occupy a device address on the Model
allows each of the Model ZIC-8B output circuits to be used DLC circuit, and does not require programming. Up to 15
for two-channel voice applications. Indication of power, Model HLIM modules may be installed on each Model
communication, internal operation, and ground-fault DLC loop.
conditions are provided, as well as indication of circuit
activation or Trouble conditions.

HCP  Control Point Module

HCP Control Point Module


NIC-C  Network Interface Card
Model HCP provides an intelligent control point for the
NIC-C Network Interface Card FireFinder XLS. Model HCP can be programmed as an
The Network Interface Card (Model NIC-C) provides HNET or independent, remotely located telephone zone, speaker
XNET network communications between enclosures. In zone or notification appliance circuit. Model HCP is
addition to the HNET or XNET communication, Model NIC-C designed to be used with the Siemens – Fire Safety
provides CAN network communication within an enclosure Alarm Signaling Devices product line.
or external to the enclosure. HNET or XNET communication Model HCP communicates through the Model DLC
can be wired Style 4 or Style 7, but the CAN network can analog loop, and can be wired either ‘Class A’ (Style Z)
be wired Style 4 only. or ‘Class B’ (Style Y). The 24 VDC power input comes
When used for HNET communications, Model NIC-C from either the control panel or from any UL Listed
provides communication between enclosures on a single power-limited, auxiliary-power supply.
system.

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)

CC-2 Card Cage-2 Slots CC-5 Card Cage-5 Slots


CRC-6  Controllable Relay Card

CRC-6 Controllable Relay Card CC-5 / CC-2 Card Cages


The Controllable Relay Card (Model CRC-6) is used with The Models CC-5 / CC-2 card cages provide the physical
the FireFinder XLS FACP. Model CRC-6 is designed to mounting location and all wiring connection points for all
provide auxiliary control of building functions, such as: fire-and-voice system options cards for the FireFinder XLS
door-holder release, elevator capture, smoke control, lock system. Model CC-5 has five (5) slots, while Model CC-2
release, etc. Model CRC-6 plugs into one (1) slot in the has two (2) slots.
Model CC-5 or Model CC-2 card cage. Model CRC-6 All cards plugged into the CC-5 / CC-2 card cage
provides six (6), fully programmable relays. Each relay communicate with other FireFinder XLS modules via a
contains one (1) set of SPDT contacts rated at 4 Amps 30 common data bus. Connectors are provided on the left and
VDC / 120VAC resistive and 3.5 amps 120VAC inductive (0.6 right side of the CC-5 to connect a 60-pin cable for
P.F.) communications with the FireFinder XLS operator interface,
power supplies and amplifiers modules.
Field wiring to devices and circuits terminates on the
Models CC-5 / CC-2 card cages. All cards designed for use
with the Models CC-5 / CC-2 route their field wiring
terminations to the ‘top’ of the Model CC-5 / CC-2 card
cages. These connections are all power limited. Internal
wiring connections distribute 24VDC to cards or high-level
SI M-16  Supervised Input Module audio signals (depending on application used) connect to
the ‘bottom’ of the Model CC-5 / CC-2 card cages. These
SIM-16 Supervised Input Module connections are all non-power limited.
The Supervised input Module (Model SIM-16) is a
All wiring connections to the Model CC-5 / CC-2 card cages
remotely located, general-purpose input module. Model
are to removable terminal blocks. Terminal blocks are rated
SIM-16 provides 16 input circuits for remote system
for use with wire sized 12 American Wire Gauge (AWG) to
monitoring. Each input can be individually programmed
24AWG. Each connector is numbered to make wiring
as supervised (dry-contact only) or unsupervised (general-
terminations to the correct position on the terminal block
purpose input.) Model SIM-16 has two (2) ‘Form C’ relays.
simple in order to reduce potential wiring errors.
The relays and inputs are programmed using the Zeus
system software-programming tool.

SCM-8  Switch Control Module


SCM-8 Switch Control Module
CDC-4 Conventional Detector Card The Switch Control Module (Model SCM-8) is a FireFinder
CDC-4 Conventional Detector Card XLS-option module that provides manual control to the
The Conventional Detector Card (Model CDC-4) is used Emergency Voice Evacuation System (EVAC) or manual
fire-system control. Each Model SCM-8 module provides
to monitor Siemens Fire Safety conventional detectors
on the FireFinder XLS system. Model CDC-4 can be eight (8) momentary push-button switches and 16
light-emitting diodes (LEDs) to indicate their status.
used in applications where conventional detectors are
more suited than addressable detectors, such as Each switch is assigned two (2) LEDs, as well as a label
hallways or large meeting rooms. Also, Model CDC-4 to indicate the switch's programmed usage. The label
can be used to upgrade Siemens conventional fire-alarm slides behind a clear protective membrane. One of the
panels to the FireFinder XLS system without requiring LEDs assigned to each switch is a dual-colored LED,
detector replacement. which is used to indicate what type of signal is active.

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d) PSC-12 Power Supply Charger Module
Each Model SCM-8 switch is fully programmable, and may The Power Supply Charger Module (Model PSC-12) is a
be used to control speaker circuits and a wide range of high-current power supply that provides the FireFinder
general-system functions such as: All Call, All Evac, XLS primary-regulated 24VDC power to operate. Model
Warden's Page, Speaker, etc. Any number of circuits may PSC-12 is rated at 12Amps (Alarm) / 5Amps (Standby), and
be grouped and controlled by a single switch. Switch has a built-in battery charger, capable of charging up to 100
usages and zone groupings are assigned using the Zeus AH batteries. Model PSC-12 is an addressable-intelligent,
system software-programming software. Model SCM-8 microprocessor-controlled module that communicates its
modules are mounted on a hinged panel, as a part of the status to the system-operator interface (PMI). Model PMI is
FireFinder XLS Command Console enclosure. able to query the status of the power supply to obtain
information regarding system-charging current, terminal-
loading information, ground-fault conditions and more.

LCM-8  LED Control Module


LCM-8 LED Control Module
The LED Control Module (Model LCM-8) is a FireFinder
XLS-option module that provides LED annunciation for
FireFinder XLS system activity. Each Model LCM-8
contains eight (8) groups of two (2) LEDs – each of which PTB  Power Termination Board
can be assigned to desired outputs using the Zeus
PTB Power Termination Board
system software-programming tool.
Model PSC-12 comes packaged with a module called the
Eight (8) LEDs are dual-color capable (Red or Green / Power Termination Board (Model PTB). Model PTB is
flashing or steady). The remaining LEDs are Amber required for operation with Model PSC-12. Model PTB filters
flashing or steady. A space is provided for labeling of LED the power from the incoming AC mains, and distributes
functions. The label slides behind a clear, protective it to the Model PSC-12 power supply and the optional Model
membrane. Model LCM-8 dimensions are identical to Model PSX-12 power-supply extender.
SCM-8, and Model LCM-8 is mounted on the same hinged
Model PTB has an optional connector that can be used during
panel, as a part of the FireFinder XLS Command Console
system installation, commissioning and service to provide
enclosure.
the technician with a place to plug in their laptop PC, if
required. Model AC-ADPT is an optional accessory cable
that allows connection on one side to Model PTB, via a
keyed connector and on the other end directly into to the
laptop's transformer.
Most laptop-computer external power transformers have
removable AC power cords, which can be replaced by the
FCM-6  Fan, Motor, Dampers Control Module
optional Model AC-ADPT to temporarily provide an AC
FCM-6 Fan, Motor, Dampers Control Module power source for laptop-PC usage during system
The Fan, Motor, Dampers Control Module (Model FCM-6) is a installation, service and maintenance calls when needed.
FireFinder XLS command-console option module that
provides manual control of building HVAC system fans,
motors, and dampers. Each Model FCM-6 module provides
six (6) sets of three (3) push-button switches for manual-
system control. Each switch has three (3), associated
LEDs to indicate Fan / Damper / Motor status: OFF (Red LED),
ON (Green LED), TROUBLE (Yellow LED).

PSX-12  Power Supply Extender

PSX-12 Power Supply Extender


The Power Supply Extender (Model PSX-12) is a high-current,
auxiliary power supply that expands the main Model PSC-12
power supply and battery charger of the FireFinder XLS
system with an additional 24VDC power. Model PSX-12
PSC-12  Power Supply Charger Module is rated at 12 Amps.

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)
Models SSD-C and SSD-C-INT have an integral keyswitch
that enables these control buttons to operate.
Model SSD-C-REM is located within a locked cabinet.
Hence, no additional keyswitch is required for enabling
RN I  Remote Network Interface the control buttons.
RNI Remote Network Interface
The Remote Network Interface (Model RNI) provides a
connection point for use with equipment mounted in a
remote-lobby enclosure on the FireFinder XLS FACP. Model
RNI is used to provide additional input, output and control
features to the system remotely, via the main FACP. These
additional features may include control switches and
indicators: (Models SCM-8, LCM-8 and FCM-6), remote-
emergency paging microphones or telephones: (Models
LVM, FMT), or controls used in graphic annunciators (Models CAB1  Single Row Enclosure
SIM16, OCM-16) or system-status display with the ability to
acknowledge alarms, silence audibles and reset the CAB1 Single Row Enclosure
system (Model SSD-C-REM). Model RNI allows Model Model CAB 1, the smallest of the FireFinder XLS
PMI to be mounted in the Model REMBOX2 or Model enclosures, can house a single Model CAB-MP cabinet
REMBOX4 remote lobby enclosure. mounting plate for mounting card cages, power supplies
and bulk amplifiers. Model CAB1 also has four (4)
mounting slots on the inner door for mounting Model PMI
and Model ID-MP switch module brackets.
Model CAB1 comes complete with a black back box; black
inner and outer doors; a single lock and key set on the outer
door; a single, installed cabinet mounting plate (Model
RPM  Remote Printer Module
CAB-MP), and a single, installed outer door lens plate
(Model OD-LP). A red version (Model CAB1-R) is also
RPM Remote Printer Module available – approximate size: 27" (68.6cm.) high, 26"
The Remote Printer Module (Model RPM) provides a means (66cm.) wide, and 8" (20.3cm.) deep.
of connecting the FireFinder XLS system to a printer, such
as Model PAL-1, for creating a hard copy of system status and
configuration reports. Simultaneously, Model RPM
provides an output port that can be configured to
communicate with external systems.

MDACT  Multi-Point Digital Alarm


Communicator Transmitter

MDACT - Multi-Point Digital Alarm Communicator


Transmitter
System-Status Display
The Multi-Point Digital Alarm Communicator Transmitter
SSD-Series System-Status Display (Model MDACT) is used in FireFinder XLS systems where
The System Status Display (SSD-series model displays) is a point identification of Alarm, Supervisory, Security and
remote LED / LCD display that shows the local status of a Trouble events is required at Central or Remote Receiving
FireFinder XLS system. An LED illuminates when Alarm, Stations. An intelligent RS−485 communications protocol
Supervisory, Trouble, and Security events occur on the transmits all system information to Model MDACT.
system. A (4) four-line liquid-crystal display (LCD) will The installer selects the specific event or groups of
give details of the event in alphanumeric form. events that are set to transmit from Model MDACT over
The display can be toggled to display additional events. phone lines to listed receiving station equipment. In
Optional remote system control capabilities are available. turn, Model MDACT can transmit point information, via
Models SSD-C, SSD-C-INT, and Model SSD-C-REM have three the Ademco Contact ID and the SIA protocol. A Mounting
(3) additional control buttons to acknowledge events, Plate (Model MOM2-XMP), MOM-2 card cage, and an XMI
silence audible circuits, and reset the system. Interface Card are required for installation.

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)
The outer door can be configured to open from either
side. Model CAB3 consists of the Model CAB3-BB back box,
the Model CAB3-BD black inner and outer door package,
and one (1) Model OD-LP lens plate. The outer door has
two (2) locks and key sets installed. A red version (Model
CAB3R) is also available. Approximate size is 63"
TSP-40A  Thermal Strip Printer (160cm.) high, 26" (66.4cm.) wide, and 8" (20.3cm.)
deep.
TSP-40A Thermal Strip Printer
The Thermal Strip Printer (Model TSP-40A) is designed for Enclosure Trim Kits
use with the FireFinder XLS system. Model TSP-40A acts Trim kits are available for all system enclosures for semi-
as an event-logging device, providing a permanent history flush mounting applications. Model CAB1-TK (for black
report of all system activity. Model TSP-40A mounts in enclosures) and the Model CAB1R-TK (for red enclosures)
the FireFinder XLS Model CAB 1, Model CAB2 or Model fit inside the Models CAB1 and CAB1-R enclosures.
CAB3 enclosure, and its printout is visible through a Similarly, Models CAB2-TK and CAB-2R-TK fit inside the
window in the locked-door enclosure. Printouts are Model CAB-2 enclosure, while Models CAB3-TK and CAB3R-
automatically spooled onto a take-up reel for tidy, uniformed TK fit the Model CAB-3 enclosure.
records storage. Remote Transponders
The FireFinder XLS system can use remote transponders
for mounting additional modules such as amplifiers
without requiring Model PMI or any control switches.
Special doors are available for systems using Model CAB-2
or Model CAB-3 remote transponders. These doors (Models
CAB2-XBD and CAB3-XBD) omit the unused inner door, and
come complete with ventilation louvers built into the door.
Model CAB2-XBD fits into Model CAB2-BB, and Model
CAB2  Two-Row Enclosure CAB3-XBD fits into Model CAB3-BB. Model CAB2-XBD and
CAB2 Two-Row Enclosure CAB3-XBD are supplied in black. Red versions (Models
The Two-Row Enclosure (Model CAB2) is the mid-sized CAB2-XRD and CAB3-XRD) are also available. Complete box
FireFinder XLS enclosure capable of housing up to two and door kits are available, Models CAB2-X and CAB3-X.
(2) Model CAB-MP cabinet mounting plates. The inner
door has two (2) rows of four (4) mounting slots. The
outer door has space for mounting two (2) outer door
plates (Models OD-LP, OD-BP or OD-GP). The outer door
can be configured to open from either side. Model CAB2
consists of the Model CAB2-BB back box, the Model CAB2-
BD black inner and outer door package, and one (1) Model CAB-MP  Cabinet Mounting Plate
OD-LP lens plate. The outer door has a single lock and key
set installed. A red version (Model CAB2R) is also available. CAB-MP Cabinet Mounting Plate
Approximate size is 45” (114.3cm.) high, 26” (66cm.) The Model CAB-MP cabinet mounting plate provides
wide, and 8” (20.3cm.) deep. mounting for a single row of modules in a FireFinder XLS
cabinet. Four (4) module spaces are available on Model
CAB-MP, which is used to mount the Model CC-5 card
cage; the Model CC-2 card cage; the Model PSC-12 power
supply; the Model PSX-12 power-supply extender, and the
Model ZAM-80 / 180-zone amplifiers.

CAB3  Three-Row Enclosure


CAB3 Three-Row Enclosure
Model CAB3, the single largest FireFinder XLS enclosure
available, can house a maximum three (3) Model CAB-
MP cabinet mounting plates in the enclosure, and three
ID-MP  I nner Door Mounting Plate
(3) rows of inner-door mounting slots.

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)
ID-MP Inner Door Mounting Plate
The inner door mounting plate (Model ID-MP) is
mounted on the inner door of any given model CAB
enclosure. Model ID-MP plates are used to mount
switch-control modules (Model SCM-8); LED control
modules (Model LCM-8), or fan-control modules (Model
FCM-6). OD-LP  Outer Door Lens Plate
Four (4) mounting plates are included in each Model ID- OD-LP Outer Door Lens Plate
MP. Each mounting plate has four (4) spaces for control The Outer Door Lens Plate (Model OD-LP) is a clear plastic
modules, and can hold either four (4) Model SCM-8 lens plate mounted on the outer door of a system cabinet.
modules (one [1] control module space for each Model OD-LP is used to allow operators to see the system
module); four (4) LCM-8 (one [1]control module space interface and controls mounted on the inner door, but
for each module), or two (2) Model FCM-6 modules (two restricts access to unauthorized users. Moreover, the plate
[2] module spaces for each module). covers an entire row on the outer door. A single lens plate
Combinations are also allowed. Blank spaces in Model ID- is included with each Model OD-LP.
MP can be covered using the blank-control-module
plate (Model BCM). Up to four (4) Model ID-MP
modules can be mounted in a single row on the inner
door.

OD-BP  Outer Door Blank Plate


OD-BP Outer Door Blank Plate
The Outer Door Blank Plate (Model OD-BP) is used to
cover an entire row on the outer door of a system
cabinet. Model OD-BP is used when there is no Model
PMI or control modules mounted on the adjacent row of
the inner door. One (1) blank plate is included in each
ID-SP  I nner Door Blank Single Plate
Model OD-BP.
ID-SP Inner Door, Blank Single Plate
The inner door, blank single plate (Model ID-SP) is used to
cover any single-module blank spaces on the inner door
not used to mount Model PMI or Model ID-MP. Up to
four (4) Model ID-SP modules can be mounted in a
single row on the inner door. Two (2) blank plates are
OD-GP  Outer Door Grill Plate
included in each Model ID-SP.
OD-GP Outer Door Grill Plate
ID-FP Inner Door Full-Blank Plate The Outer Door Grill Plate (Model OD-GP) also covers an
Model ID-FP is a blank plate that covers the full opening entire row on the outer door of a system cabinet, but has
of the row on an inner door, and is used for applications four (4) rows of ventilation louvers on it. Model OD-GP is
requiring full, dead-front protection. A single, full blank mounted in front of system bulk amplifiers, card
plate is included in Model ID-FP. amplifiers, or other modules that generate heat. Using
Model OD-GP will permit airflow across these modules to
aid in heat dissipation. One (1) grill plate is included
with each Model OG-GP.
Remote System Enclosures
Models REMBOX2 and REMBOX4 are FireFinder XLS
system enclosures that are used for remotely mounting
BCM  Blank Control Module Plate inner-door modules, such as: Model PMI; switch modules
BCM Blank Control-Module Plate (Model SCM series); Live Voice Modules (Model LVM), and
Firefighters’ Master Telephone (Model FMT) modules.
Model BCM plates can be mounted on a single ID-MP.
Four (4) blank module plates are included in each Models REMBOX2 and REMBOX4 are thinner than regular
Model BCM. Model CAB-series of enclosures – just 5" (12.7cm.) deep
overall, and are perfect for mounting in limited-space areas
(e.g. – office-complex lobbies or behind a receptionist's
desk).

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)
No card cages, power supplies or bulk amplifiers can be A bracket known as Model REMBOX4-MP can be used
mounted in a given Model REMBOX-series enclosure to mount up to eight (8) output control modules (Model
due to their smaller depth. However, Model PMI and OCM-16) or supervised input modules (SIM-16). The
some modules (e.g. – the remote network interface REMBOX4-MP must be purchased separately.
module [Model RNI]; the output control module [Model Approximate size of the REMBOX4 is 24" (61cm.)
OCM-16], and the supervised input module [Model SIM- wide, 18-1/2" (47cm.) high and 5" (12.7cm.) deep.
16]) can be mounted in a given Model REMBOX-series
enclosure.
Due to the depth of Models LVM and FMT, no Model
OCM-16 or Model SIM-16 modules can be used
simultaneously with Model LVM or Model FMT. Model
REMBOX2 and Model REMBOX4 are designed for flush
mounting with no trim kit required. Both enclosures also
come with a clear lens plate on the cover. NRC  Network Ring Card
NRC Network Ring Card
Model NRC provides XNET, peer-to-peer communication
between FireFinder XLS systems. One (1) Model NRC is
required for each XLS FACP, in order to allow FireFinder XLS
nodes to be wired in a ‘Class A’, [Style 7] ring topology.

REMBOX2  Two-Module Remote Enclosures


REMBOX2 Two Module Remote Enclosures
REMBOX2 has two (2) inner-door module spaces, and can
hold a single Model PMI, up to two (2) switch module
brackets and one (1) Model LVM. Combinations are also
allowed. NCC-G  Network Color Graphics
REMBOX2 can also mount a single RNI remote network NCC-G - Network Color Graphics
interface on a bracket included in the backbox. A bracket
Model NCC-G is a PC-based, color-graphics command
called the REMBOX2-MP can be used to mount up to four center designed for use with the XNET network, and
OCM-16 output control modules or SIM-16 supervised provides full control and annunciation for a XNET network
input modules. Model REMBOX2-MP must be purchased for a maximum 63 XLS, MXL-IQ or MXL systems. Model
separately. Approximate size of Model REMBOX2 is NCC-G is used to monitor and control Alarm, Trouble,
14-1/2" (36.8cm.) wide, 18-1/2" (47cm.) high Security, Supervisory and all system events from an
and 5" (12.7cm.) deep. individual (of many) XLS FACPs.
Model NCC-G maintains a widespread history log of all
system events, as well as extensive report-generation
capabilities. User programmable function buttons allow
site specific control functions. Multiple NCC-Gs may be
connected to XNET network. Each NCC-G ordered
separately.

REMBOX4  Four-Module Remote Enclosures

REMBOX4 Four-Module Remote Enclosures


Model REMBOX4 has space for mounting four (4) inner-
door modules. Any combination of Model PMI (two-
module spaces); switch module brackets; Model LVM,
or Model FMT (one-module space each) can be used.
Unused module spaces can be covered with Model ID-SP
blank plates. The REMBOX4 can also mount a single
remote network interface (Model RNI) on a bracket MLC  MXL Line Card [for FireFinder XLS]
included in the backbox.

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)
MLC - MXL Line Card [for FireFinder XLS]
The MXL Line Card (Model MLC) is an optional card for
the FireFinder XLS panel that supplies two (2)
intelligent analog circuits, utilizing the Model ‘ I ‘ series;
Model ‘ ID ‘ series; Model ‘ IL ‘ series or Model ‘ FP ‘ series-
type intelligent devices. Model MLC occupies two (2)
addresses on the HNET network, and devices connected
to the Model MLC circuits are dynamically supervised by XLS-MLE6-ADPT Enclosure Adapter
FireFinder XLS through the use of a unique
XLS-MLE6/R-ADPT − XLS MLE-6/R Enclosure Adapter
communications protocol.
Model XLS-MLE6-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in older-
generation MXL Model MLE-6 large black enclosures.
Model XLS-MLE6R-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in older-
generation MXL MLE-6R large red enclosures.

XLS-MSE2-ADPT Enclosure Adapter

XLS-MSE2/R-ADPT − XLS MSE-2/R Enclosure Adapter


Model XLS-MSE2-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that
XLS-MSE3-ADPT Enclosure Adapters
allows FireFinder XLS cards to be mounted in older-
generation MXL Model MSE-2 small black enclosures. XLS-MSE3/R-ADPT − XLS MSE-3L/R or MSE-3M/R
Model XLS-MSE2R-ADPT, which must be used in Enclosure Adapters
conjunction with Model CAB-MP, is an adapter that Model XLS-MSE3-ADPT is an adapter that allows
allows FireFinder XLS cards to be mounted in older- FireFinder XLS cards to be mounted in older-
generation MXL Model MSE-2R small red enclosures. generation MXL-IQ Model MSE-3L or Model MSE-3M
black enclosure.
Model XLS-MSE3R-ADPT is an adapter that allows
FireFinder XLS cards to be mounted in older-
generation MXL-IQ Model MSE-3LR or Model MSE-3MR
red enclosure.

XLS-MME3-ADPT Enclosure Adapters

XLS-MME3/R-ADPT − XLS MME-3/R or MBR-2


Enclosure Adapters
XLS-RCC1-ADPT Enclosure Adapter
Model XLS-MME3-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that XLS-RCC-1-ADPT − XLS RCC-1 Enclosure Adapter
allows FireFinder XLS cards to be mounted in older- Model XLS-RCC1-ADPT is an adapter that allows the
generation MXL Model MME-3 or Model MBR-2 FireFinder XLS Model SSD/-C series remote annunciator
medium black enclosures. to be mounted in older-generation Model RCC-1 surface-
Model XLS-MME3R-ADPT, which must be used in mount enclosure.
conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in older-
generation MXL Model MME-3R medium red
enclosures.

XLS-RCC13F-ADPT Enclosure Adapters

s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)
XLS-RCC13F/R-ADPT − XLS RCC-1F/R or RCC-3F/R
Enclosure Adapters
Model XLS-RCC13F-ADPT is an adapter that allows the
FireFinder XLS Model SSD/-C series remote annunciator
to be mounted in older-generation Model RCC-1F or C900V2 Dialer-Capture Ethernet Module
Model RCC-3F black, flush-mount enclosure.
C900V2 − Dialer-Capture Ethernet Module
Model XLS-RCC13FR-ADPT is an adapter that allows the
The Dialer-Capture Ethernet Module (Model C900V2) links
Model SSD/-C series to be mounted in older-generation
the data output of Model MDACT from the FireFinder
RCC-1FR and RCC-3FR, red flush-mount enclosure.
XLS FACP to an Ethernet connection ─ on a local-area
network (LAN) or wide-area network (WAN) ─ for
communication to a central station over the Internet.
Model C900V2 also allows Model MDACT to be
optionally linked to the public switched telephone
network (PSTN) for communication to a central station
VPM  VESDA Interface Equipment over telephone lines.

VESDA-HLI-KIT  VESDA High-Level Interface Kit IIC  I nterface I solation Card

IIC − Interface Isolation Card


The Interface Isolation Card (Model IIC) is designed to
isolate network signals when used with a Model NCC
ring configuration, via Model NRC. Model IIC executes
the aforementioned isolation by removing the backplane
network signals from each Model CC-2 card cage. Model
IIC also provides one (1) end of CAN termination on
VPM-MP  VESDA Mounting Plate each side of Model CC-2.
VPM, VESDA-HLI-KIT and VMP-MP −
VESDA Interface Equipment
The Very Early Smoke Detection Aspiration (VESDA)
Peripheral Module (Model VPM) and the VESDA High-
Level Interface Kit (Model VESDAHLI-KIT) are optional
FireFinder XLS modules that work in conjunction to PM I -2 Person Machine I nterface 2
provide bi-directional communication between the PMI-2  Person Machine Interface 2
FireFinder XLS FACP and multiple VESDA detection
The Person Machine Interface 2 (Model PMI-2) is the
networks for the following types of VESDA detectors:
primary user interface for the FireFinder FACP. Model PMI-
 LaserCOMPACT
2 serves as both operator interface and central
 LaserFOCUS
microprocessor for each XLS system.
 LaserPLUS
 LaserSCANNER From each Model PMI-2, the end-user can Acknowledge
events; control the system notification appliance circuits
Model VPM allows each FireFinder XLS FACP to
(NACs), and reset the system. Detailed information about
annunciate ‘Alert,’ ‘Action,’ ‘Fire 1,’ and ‘Fire 2’ levels,
the nature and location of the events can also be displayed.
as well as provide ‘faults’ from any zone on a
connected VESDA network.
Temperature and Humidity Range
The VPM Mounting plate (Model VPM-MP) allows
mounting one (1) Model VPM and two (2) of Model FireFinder XLS components are UL 864 9th Edition
VESDAHLI-KIT inside a standard FireFinder XLS Model Listed for indoor dry locations within a temperature
CAB1, Model CAB2 or Model CAB3 enclosure. Model range of 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C) and
VPM-MP utilizes two (2) module spaces on a single a relative-humidity range of 93+/-2% at a temperature
row of each enclosure. of 90+/-3°F (32+/-2°C).

s Industry, Inc.
Building Technologies Division
Details for Ordering ─ (continued) Details for Ordering ─ (continued)
Model Part Model Part
Description Description
Number Number Number Number
── 599-050092 PMI and GPMI MXL module card cage
MOM-2 500-892766
AC-ADPT 500-633992 Technician laptop power connector [one (1) full slot]
Blank control module plate, NIC-C 500-033240 Network interface card
BCM 500-033320
[four (4) per package] NRC 500-050337 Network ring card
C900V2 S54430-C13-A2 Dialer-Capture Ethernet Module OD-BP 500-633017 Outer door blank plate
CAB-1 500-633007 Complete single-row cabinet, black OD-BP-R 500-634919 Outer door blank plate, red
CAB-1R 500-633728 Complete single-row cabinet, red OD-GP-R 500-634920 Outer door grill plate, red
CAB1-TK 500-633013 Single-row trim-kit cabinet, black OD-GP 500-633018 Outer door grill plate
CAB1R-TK 500-633729 Single-row trim-kit cabinet, red OD-LP 500-633016 Outer door lens plate
CAB2-BB 500-633009 (2) Two-row back box, black PAL-1 500-692407 UL Listed parallel printer
CAB2-RB 500-634941 (2) Two-row back box, red PMI 500-033070 Person Machine Interface
CAB2-BD 500-633008 (2) Two-row inner & outer door set, black PMI-2 S54430-C1-A1 Person Machine Interface 2
CAB2-RD 500-633755 (2) Two-row inner & outer door set, red Person machine interface
PMI-INT 500-034160
CAB2-TK 500-633014 (2) Two-row trim-kit cabinet, black [with multi-lingual overlays]
CAB2R-TK 500-633753 (2) Two-row trim-kit cabinet, red Power supply with battery charger
PSC-12 500-033340
CAB2-XBD 599-633768 CAB2 transponder door [12A @ 24VDC]
Complete CAB2 w/ transponder door Power supply extender
CAB2-X 599-034252 PSX-12 500-034120
[12A @ 24VDC]
[no inner door]
PTB 500-033390 Power termination board
Medium-enclosure transponder door, red
CAB2-XRD 500-633792 REMBOX2 500-633772 (2) Two-module remote lobby enclosure, black
[mounts to CAB2-RB]
CAB3-BB 500-633011 (3) Three-row back box, black REMBOX2R 500-650612 (2) Two-module remote
CAB3-RB 500-634942 (3) Three-row back box, red lobby enclosure, red
Mounting plate for Models
CAB3-BD 500-633010 (3) Three-row inner & outer door set, black REMBOX2-MP 500-634211
OCM-16 / SIM-16 in Model REMBOX2
CAB3-RD 500-633757 (3) Three-row inner & outer door set, red
REMBOX4 500-633914 (4) Four-module remote lobby enclosure, black
CAB3-TK 500-633015 (3) Three-row trim-kit cabinet, black
Mounting plate for Models OCM-16 /
CAB3R-TK 500-633754 (3) Three-row trim-kit cabinet, red REMBOX4-MP 500-634212
SIM-16 in Model REMBOX4
CAB3-XBD 599-633769 CAB3 transponder door
REMBOX4R 500-650613 (4) Four-module remote lobby enclosure, red
Complete CAB3 w/ transponder door
CAB3-X 599-034253 RNI 500-033420 Remote network interface module
[no inner door]
RPM 500-033270 Remote printer module
Large-enclosure transponder door, red
CAB3-XRD 500-633793 SCM-8 500-033040 Switch module, eight (8) switches
[mounts to CAB3-RB]
SIM-16 500-034060 Supervised input module
CAB-MP 500-633012 Back box module mounting plate
SSD 500-034740 System-status display
CAN Cable
3 ft. (91.4 cm.) Length required for:
SSD-C 500-648733 System-status display with control
CCL 599-634214 SCM / LCM / FCM modules from Models SSD-INT 500-034740 System-status display with
CC-5 / CC-2 Inner Doors and from Row-to-Row on multi-lingual overlays
Model CAB-series Inner Doors
SSD-C-INT 500-034750 System-status display with control
CC-2 500-633440 Two (2) slot card cage and multi-lingual overlays
CC-5 500-633037 Five (5) slot card cage SSD-C-REM 500-634773 System-status display with control for
CDC-4 500-034200 Conventional detector card remote lobby enclosure
CRC-4 500-033250 Controllable relay card TSP-40A 500-634933 Thermal-strip printer
CSB 500-033130 CAN Sounder Board TSP-XB 500-849949 Brackets for thermal-strip printer
DCT-P 500-699291 MDACT programmer TSP-XC 500-849950 Cables for thermal-strip printer
DLC 500-033090 Device loop card VPM S54430-F93-A2 VESDA Peripheral Module

FCM-6 500-033140
Fan-control-module switches VPM-MP S54430-F95-A2 Mounting Plate for VESDA
{ON, OFF, AUTO} Peripheral Module
Software-upgrade kit for PMI VESDA-HLI-KIT S54430-F99-A2 VESDA High-Level Interface Kit
GPMI-UK 500-650066
{to allow global functionality} XLS-MLE6-ADPT S54430-C9-A1 MLE-6 enclosure adapter for XLS, black
HCP 500-034860 Intelligent control point XLS-MLE6R-ADPT S54430-C9-A2 MLE-6R enclosure adapter for XLS, red
HLIM 500-033170 Line-isolator module MME-3 and MBR-2 enclosure adapters for
XLS-MME3-ADPT S54430-C8-A1
ID-FP 500-633029 (4) Four module inner-door blank plate FireFinder XLS, black
Inner-door enclosure mounting plate, XLS-MME3R-ADPT S54430-C8-A2 MME-3R enclosure adapter for XLS, red
ID-MP 500-633027
[four (4) per package] XLS-MSE2-ADPT S54430-C7-A1 MSE-2 enclosure adapter for XLS, black
Single-module inner-door enclosure XLS-MSE2R-ADPT S54430-C7-A2 MSE-2R enclosure adapter for XLS, red
ID-SP 500-633028
mounting plate, [two (2) per package] MXL-IQ MSE-3L and MSE-3M enclosure adapters
XLS-MSE3-ADPT S54430-C14-A1
IIC 500- 850328 Interface Isolation card for XLS, black
LED Annunciator Module XLS-MSE3R-ADPT S54430-C14-A2 MXL-IQ MSE-3LR & MSE-3MR enclosure
LCM-8 500-033100 adapters for XLS, red
[eight (8) LED sets]
XLS-RCC1-ADPT S54430-Z14-A1 RCC-1enclosure adapter for XLS-SSD, black
MDACT 500-699254 Multi-point digital-alarm XLS-RCC13F-ADPT S54430-Z13-A1 RCC-1F & RCC-3F enclosure adapters, black
communication transmitter
XLS-RCC13FR-ADPT S54430-Z13-A2 RCC-1FR & RCC-3FR enclosure adapters, red
MXL addressable-device line card
MLC S54431-B4-A1
[used for FireFinder XLS] ZIC-2C 500-648671 (2) Two-channel adapter card,
via (Model ZIC-8B)
Mounting plate for Model MOM-2
MOM2-XMP 500-634822 ZIC-4A 500-033050 (4) Four-circuit zone indicating card
[used for FireFinder XLS]
ZIC-8B 500-648670 (8) Eight-circuit zone indicating card

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
June 2013
Building Technologies Division Tel: (973) 593-2600 (SII-FS) L6T 5E4 / Canada Supersedes sheet dated 9/12
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (Rev. 9)
URL: www.usa.Siemens.com/Fire FAX: (905) 799-9858
s Catalog Sheet 
Fire Safety & Security Products 

FireFinder XLS
System-Status Display Series
Models SSD, SSD-C and SSD-C-REM

• 4 x 40” backlit LCD screen


• Event and audible status LEDs
• Scroll buttons to view additional events
• Local sounder
• Supports Style 4 or Style 7 wiring
• Built-in transient protection
• Mounts in its own enclosure or REMBOX
• Optional local-system control
• Downloadable firmware
• UL 864 9th Edition Listed and ULC Listed;
FM, CSFM & NYMEA Approved

Product Overview
The System-Status Display (SSD Series) is a remote LED / The LCD display on the SSD Series display has four (4)
LCD display that shows the local status of a FireFinder rows – 40 characters for each row. When the FireFinder
XLS system. A LED will illuminate when Alarm, XLS system is in its normal supervisory state with no
Supervisory, Trouble and Security events occur on events present, the display will annunciate the system
the system. A four-line LCD will give details of the ID information, the date and the time of day.
event in alphanumeric form. The display can be When an event occurs on the system, the LCD display
toggled to display additional events. Optional will show the event type and address, the time of the
remote-system control capabilities are available. event, the custom message for that address, the usage
of the device, and whether the event is acknowledged
Specifications or not. Additionally, the display will show the total
The SSD Series display has separate LEDs for Alarm, number of all types of events present on the system.
Supervisory, Trouble and Security events on the The display has a backlight feature that operates upon
FireFinder XLS system. Each LED will flash when receiving any event information or when any operator
unacknowledged events of that type are present on the buttons are pressed.
system. The LED will change to steady, upon A local sounder is included with the SSD Series display
acknowledgment of the event. Also, there are two (2) that operates when any events are displayed on the
LEDs that indicate the state of audible circuits on the system. The sounder can be optionally disabled
system: one (1) LED to indicate that the circuits are through software programming. Pressing any
active and one (1) LED to indicate the circuits have operator buttons will silence the local sounder
been silenced. when an event is present.

FireFinder XLS 6326


s Industry, Inc.
Building Technologies Division
Specifications – (continued) Details for Ordering
The SSD Series display has two (2) display-control buttons
Model Part
that are used to display the next or the previous event Description
Number Number
information in the sequence, and a local sounder silence
button. Programming for the SSD Series display is done SSD 500-034170 System-Status Display
with the Zeus programming tool.
SSD-C 500-648733 System-Status Display [with control]
Models SSD-C and Model SSD-C-REM have three (3)
System-Status Display [with control for
additional control buttons for acknowledging events, SSD-C-REM 500-634773
remote-lobby enclosure]
silencing audible circuits, and resetting the system.
Model SSD-C has an integral key switch that enables these REMBOX2 500-633772 Small Remote-Lobby Enclosure
control buttons to operate. Model SSD-C-REM is located
REMBOX4 500-633914 Large Remote-Lobby Enclosure
within a locked cabinet, so no additional key switch is
required for enabling the control buttons. BCM 500-033320 Blank Control Module Plate
The SSD Series display is remotely connected to the
H-Net communication bus from any Model NIC-C interface in a
FireFinder XLS system enclosure using Class B, Style 4 or
Class A, Style 7 wiring. 24VDC is required to run the SSD
Electrical Ratings
Series display, and can be provided from a Model PSC-12
Power Supply or PSX-12 Power Supply Extender in the
FireFinder XLS system enclosure. Power from other
UL Listed 24VDC power sources is also acceptable.
The SSD Series display has screw terminals capable of Notes:   An auxiliary‐regulated, power‐limited power supply may be used 
supporting 12 to 22-gage wires. The H-Net to provide power to Model SSD. The power supply must be  UL Listed for 
communication from the FireFinder XLS system can be Fire‐Protection Signaling Application.  Be sure to also include Model SSD‐C 
terminated on the SSD Series display, or may pass  
in the battery calculations.

through for communication with other modules.


Diagnostic LEDs on the SSD Series display indicate
power and communication status.
Models SSD and SSD-C can be mounted in a (2) two-gang
electrical box or a (4) four-inch square electrical box. No
flush-trim kit is required. The unit is approximately Notes: An auxiliary‐regulated, power‐limited power supply may be used to 
10-1/2“(26.7cm.) wide, 6-1/8” (15.2cm.) high, and provide power to Model SSD. The power supply must be  UL Listed for Fire‐
Protection Signaling Application.
1-1/2” (3.8cm.) deep.
The Model SSD-C-REM is mounted in a Model
REMBOX2 or Model REMBOX4 Remote Lobby Enclosure, or
any CAB enclosure inner door. Model SSD-C-REM requires
two (2) module spaces in the remote lobby enclosure,
and its bracket supports the mounting of four (4) inner
door modules (such as Model SCM-8 or Model LCM-8 Notes: An auxiliary‐regulated, power‐limited power supply may be used 
modules) below the display. The inner door module spaces to provide power to Model SSD‐C‐REM. The power supply must be  UL / 
are arranged in two (2) rows of (2) two-module spaces. ULC approved for Fire Protection Signaling Application.  Be sure to also 
include Model SSD‐C‐REM in the battery calculations.
Products are UL 864 9th Edition listed for indoor dry
locations within a temperature range of 120+/-3°F
(49+/-2°C) to 32+/-3°F (0+/-2°C) and at a relative
humidity of 93+/-2% at a temperature of 90+/-3°F
(32+/-2°C).

Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
August 2010
Building Technologies Division Tel: (973) 593-2600 (SII) L6T 5E4 / Canada
Supersedes sheet dated 5/10
FAX: (908) 547-6877 Printed in U.S.A.  Tel: (905) 799-9937 (Rev. 3)
URL: www.SBT.Siemens.com/FIS   FAX: (905) 799-9858
s Data Sheet 
Fire Safety & Security Products 

FireFinderTM XLS
Fire Alarm Enclosures & Equipment
Models: CAB1, CAB-BATT, CAB-BATT-R, CAB2-BB, CAB2-BD, CAB3-BB, CAB3-BD, CAB-MP,
ID-MP, ID-SP, ID-FP, BCM, OD-LP, OD-BP, OD-GP, REMBOX2, REMBOX4, XLS-MLE6-ADPT,
XLS-MME3-ADPT, XLS-MSE2-ADPT, XLS-MSE3-ADPT and XLS-RCC13F-ADPT

ARCHITECT AND ENGINEER SPECIFICATIONS

• One (1), two (2), and (3) three-row enclosures


for the FireFinder XLS system
• Blank plates for inner and outer doors
• Lens and grill plates for outer door
• UL 864 9th Edition Listed and ULC Listed;
FM, CSFM & NYMEA Approved

CAB1 CAB2 CAB3

Product Overview Enclosures, Doors & Plates


The FireFinder XLS fire alarm enclosures (Models CAB1 − Single-Row Enclosure
CAB1, CAB2, and CAB3) and their accessories Model CAB1, the smallest of the FireFinder XLS
provide a complete set of hardware for mounting enclosures, can house a single Model CAB-MP
all FireFinder XLS main system and remote cabinet mounting plate for mounting card cages,
transponder cards and modules. power supplies and bulk amplifiers. Model CAB1
The hardware allows the FireFinder XLS system to also has four (4) mounting slots on the inner door for
be configured for a wide variety of applications, mounting a Model PMI interface and Model ID-MP
and allows for future system upgrades. Included in switch module brackets.
the enclosure series are backbox and door sets, Model CAB1 comes complete with a black back box,
removable mounting plates and clear lenses, with black inner and outer doors, a single lock and
louvered ventilation grill plates, and blank plates for key set on the outer door, and a single OD-LP outer
use with the enclosure doors. door lens plate (installed). A red version (Model
All enclosures come with ground straps for the inner CAB1-R) is also available. Approximate size is 27"
and outer doors, shield termination lugs, (68.6cm.) high, 26" (66cm.) wide, and 8" (20.3cm.)
grounding lugs, and tie wrap lances for securing deep.
wire. All enclosures can also mount system backup
batteries up to 31AH in capacity.

FireFinderTM XLS Enclosures 6327


s Industry, Inc.
Building Technologies Division
Enclosures, Doors & Plates ─ (cont.’d)
Enclosure Trim Kits
Trim kits are available for all system enclosures for
semi-flush mounting applications. Model CAB1-TK
(for black enclosures) and Model CAB1R-TK (for red
enclosures) fit Models CAB1 and CAB1-R enclosures.
Similarly, Models CAB2-TK and CAB2R-TK fit the Model
CAB2 enclosure, and Models CAB3-TK and CAB3R-
TK fit the Model CAB-3 enclosure.
CAB1 Enclosure
Door Remote Transponders
CAB2 − Two-Row Enclosure
The FireFinder XLS system can use remote transpon-
Model CAB2 is the mid-sized FireFinder XLS enclosure
ders for mounting additional modules such as
capable of housing a maximum two (2) Model CAB-MP
amplifiers without requiring a Model PMI or any
cabinet mounting plates. The inner door has two (2)
rows of four (4) mounting slots. The outer door has control switches. Special doors are available for
space for mounting two (2) outer door plates (Models OD- systems using Model CAB2 or Model CAB3 remote
LP, OD-BP or OD-GP). The outer door can be configured transponders. These doors, Models CAB2-XBD and
to open from either side. Model CAB2 consists of the CAB3-XBD, omit the unused inner door and come
Model CAB2-BB back box; the Model CAB2-BD black inner complete with ventilation louvers built into the
and outer door package, and one (1) Model OD-LP lens door. Model CAB2-XBD fits on Model CAB2-BB, and
plate. The outer door has a single lock and key set Model CAB3-XBD fits on Model CAB3-BB. The
installed. Red doors are available in Model CAB2-RD. transponder doors are supplied in black.
Additional door mounting plates must be ordered Complete box and door kits are available as Models
separately. Approximate size is 45" (114.3cm.) high, 26" CAB2-X and CAB3-X.
(66cm.) wide, and 8" (20.3cm.) deep.

CAB2 Enclosure

CAB3 − Three-Row Enclosure CAB2-XBD Door CAB3-XBD Door

Model CAB3, the largest single FireFinder XLS enclosure OD-GP − Outer-Door Grill Plate
available, can house a maximum three (3) Model CAB-MP Model OD-GP also covers an entire row on the outer
cabinet mounting plates in the enclosure, and three door of a system cabinet, but has four rows of ventilation
(3) rows of inner door mounting slots. The outer door louvers on it. Model OD-GP is mounted
can be configured to open from either side. Model in front of system bulk amplifiers, card amplifiers,
CAB3 consists of the Model CAB3-BB back box; the Model or other modules that generate heat. Using Model
CAB3-BD black inner and outer door package, and one (1) OD-GP will permit airflow across these modules to aid
Model OD-LP lens plate. The outer door has two (2) locks in heat dissipation. A single grill plate is included with
and key sets installed. Red doors are available via each Model OG-GP.
Model CAB3-RD.
Additional door mounting plates must be ordered
separately. Approximate size is 63" (160cm.) high, 26"
(66cm.) wide, and 8" (20.3cm.) deep.

OD-GP
Remote System Enclosures
Models REMBOX2 and REMBOX4 are FireFinder XLS
system enclosures that are used for remotely
mounting inner-door modules, such as the Model PMI
interface, switch modules, Model LVM live-voice
CAB3 Enclosure modules, and Model FMT Firefighters’ Master
Telephone modules.
s Industry, Inc.
Building Technologies Division
Enclosures, Doors & Plates ─ (cont.’d)
REMBOX4 are FireFinder XLS system are thinner than
the regular CAB enclosures (just 5" deep overall), and are
perfect for mounting in places where space is limited
(such as lobbies or behind a receptionist’s desk).
Due to their smaller depth, no card cages, power supplies
or bulk amplifiers can be mounted in a REMBOX. However,
modules such as the Remote Network Interface Module REMBOX4 REMBOX4
(with doors closed) (with doors open)
(Model RNI); the Output-Control Module (Model OCM-16)
Note: A red, (4) four-module remote lobby enclosure
and the Supervised Input Module (Model SIM-16) can be (Model REMBOX4R) is also available.
mounted in a REMBOX. Due to the depth of the live-voice
module and the firefighters’ master telephone, no Model CAB-MP − Cabinet Mounting Plate
OCM-16 or Model SIM-16 modules can be used The cabinet mounting plate (Model CAB-MP) provides
simultaneously with Model LVM or Model FMT. mounting for a single row of modules in a FireFinder
Both Models REMBOX2 and REMBOX4 are designed for XLS cabinet. Four (4)-module spaces are available on
flush mounting with no trim kit required. Both enclosures Model CAB-MP. Model CAB-MP is used to mount the Model
also come with a clear lens plate on the cover. CC-5 card cage, the Model CC-2 card cage, the Model
PSC-12 power supply, the Model PSX-12 power supply
REMBOX2 − Two-Module Remote Enclosure extender, and the Model ZAM-80 / 180 zone amplifiers.
Model REMBOX2 has two (2) inner door module spaces,
and can hold a single Model PMI, up to two (2)
switch module brackets, one (1) Model LVM live voice
module. Combinations are also allowed. Model
REMBOX2 can also mount a single Model RNI on a
bracket included in the backbox. A bracket (Model
REMBOX2-MP) can be used to mount up to four (4) Model
OCM-16s or Model SIM-16 enclosures. Model REMBOX2-
CAB-MP
MP must be purchased separately. Approximate size of
Model REMBOX2 is 14-1/2" (36.8cm.) wide, 18-1/2" ID-MP − Inner Door Mounting Plate
(47cm.) high and 5" (12.7cm.) deep. The inner door mounting plate (Model ID-MP) is mounted
on the inner door of a CAB enclosure. Model ID-MP plates
are used to mount Model SCM-8 switch control modules;
Model LCM-8 LED control modules, or with Model FCM-6.
Four (4) mounting plates are included in each Model ID-
MP. Each mounting plate has four (4) spaces for control
modules, and can hold either four (4) Model SCM-8
modules {one [1] control module space each}; four (4)
Model LCM-8 modules {one [1] control module space
REMBOX2 REMBOX2 each}; or two (2) Model FCM-6 modules {two [2] module
(with doors closed) (with doors open)
spaces each}.
Note: A red, (2) two-module remote lobby enclosure
(Model REMBOX2R) is also available. Combinations are also allowed. Blank spaces in Model
ID-MP can be covered using the Model BCM blank
REMBOX4 − Four-Module Remote Enclosures
control module plate. A maximum four (4) Model
Model REMBOX4 has space for mounting four (4) inner door ID-MP plates can be mounted in a single row on the
modules. Any combination of Model PMI (two-module inner door.
spaces), switch module brackets, Model LVM or Model
FMT (one-module space each) can be used. Unused
module spaces can be covered with Model ID-SP blank
plates.
Model REMBOX4 can also mount to a single Model RNI
on a bracket included in the backbox. A bracket known
as Model REMBOX4-MP can be used to mount a
maximum eight (8) Model OCM-16s or Model SIM-16s.
Model REMBOX4-MP must be purchased separately.
Approximate size of Model REMBOX4 is 24" (61cm.)
wide, 18-1/2" (47cm.) high and 5" (12.7cm.) deep. ID-MP

s Industry, Inc.
Building Technologies Division
Enclosures, Doors & Plates ─ (cont.’d) XLS-MSE2/R-ADPT − XLS MSE-2/R Enclosure Adapter
ID-SP − Inner-Door Single Blank Plate Model XLS-MSE2-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that
Model ID-SP is used to cover any single module blank
allows FireFinder XLS cards to be mounted in older-
spaces on the inner door not used to mount the Model
generation MXL Model MSE-2 small black enclosures.
PMI or a Model ID-MP. Up to four (4) Model ID-SP plates
can be mounted in a single row on the inner door. Two (2) Model XLS-MSE2R-ADPT, which must be used in
blank plates are included in each Model ID-SP. conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in older-
generation MXL Model MSE-2R small red enclosures.

ID-SP

ID-FP − Inner-Door Full Blank Plate


Model ID-FP, which is a blank plate that covers the full XLS-MSE2-ADPT
opening of the row on an inner door, is used for
XLS-MME3/R-ADPT − XLS MME-3/R or MBR-2
applications requiring full dead-front protection. Enclosure Adapters
A single full blank plate is included with Model ID-FP.
Model XLS-MME3-ADPT, which must be used in
BCM − Blank Control Module plate conjunction with Model CAB-MP, is an adapter that
Model BCM is used on Model ID-MP to cover any blank allows FireFinder XLS cards to be mounted in older-
areas where control modules are not used. A maximum generation MXL Model MME-3 or Model MBR-2
four (4) Model BCM plates can be mounted on a single medium black enclosures.
Model ID-MP. Four (4), blank-module plates are included Model XLS-MME3R-ADPT, which must be used in
in each Model BCM. conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in older-
generation MXL Model MME-3R medium red
enclosures.

BCM

OD-LP − Outer Door Lens Plate


Model OD-LP is a clear plastic lens plate mounted on
the outer door of a system cabinet. Model OD-LP is
used to allow operators to see the system interface and XLS-MME3-ADPT
controls mounted on the inner door, but restricts access XLS-MLE6/R-ADPT − XLS MLE-6/R Enclosure Adapter
to unauthorized users. Model OD-LP covers an entire Model XLS-MLE6-ADPT, which must be used in
row on the outer door. A single lens plate is included conjunction with Model CAB-MP, is an adapter that
with each Model OD-LP. allows FireFinder XLS cards to be mounted in older-
OD-BP − Outer-Door Blank Plate generation MXL Model MLE-6 large black enclosures.
Model OD-BP is used to cover an entire row on the Model XLS-MLE6R-ADPT, which must be used in
outer door of a system cabinet. Model OD-BP is used conjunction with Model CAB-MP, is an adapter that
when there is no Model PMI or control modules mounted allows FireFinder XLS cards to be mounted in older-
on the adjacent row of the inner door. A single blank generation MXL MLE-6R large red enclosures.
plate is included in each Model OD-BP.

OD-BP XLS-MLE6-ADPT
s Industry, Inc.
Building Technologies Division
Enclosures, Doors & Plates ─ (cont.’d) Details for Ordering
XLS-MSE3/R-ADPT − XLS MSE-3L/R or MSE-3M/R Model Part
Enclosure Adapters
Number Number Description
Model XLS-MSE3-ADPT is an adapter that allows
FireFinder XLS cards to be mounted in the older BCM 500-033320 Blank control module plate,
four [4] per package
generation MXL-IQ Model MSE-3L or Model MSE-3M CAB-1 500-633007 Complete single-row cabinet, black
black enclosure. CAB-1R 500-633728 Complete single-row cabinet, red
CAB1-TK 500-633013 Single-row trim-kit cabinet, black
Model XLS-MSE3R-ADPT is an adapter that allows
CAB1R-TK 500-633729 Single-row trim-kit cabinet, red
FireFinder XLS cards to be mounted in the older CAB2-BB 500-633009 (2) Two-row back box, black
generation MXL-IQ Model MSE-3LR or Model MSE-3MR CAB2-RB 500-634941 (2) Two-row back box, red
red enclosure. CAB2-BD 500-633008 (2) Two-row inner & outer door set, black
CAB2-RD 500-633755 (2) Two-row inner & outer door set, red
CAB2-TK 500-633014 (2) Two-row trim-kit cabinet, black
CAB2R-TK 500-633753 (2) Two-row trim-kit cabinet, red
CAB2-XBD 599-633768 CAB2 transponder door
Complete CAB2 w/ transponder door
CAB2-X 599-034252
[no inner door]
CAB3-BB 500-633011 (3) Three-row back box, black
XLS-MSE3-ADPT CAB3-RB 500-634942 (3) Three-row back box, red
CAB3-BD 500-633010 (3) Three-row inner & outer door set, black
XLS-RCC-1-ADPT − XLS RCC-1 Enclosure Adapter CAB3-RD 500-633757 (3) Three-row inner & outer door set, red
Model XLS-RCC1-ADPT is an adapter that allows the CAB3-TK 500-633015 (3) Three-row trim-kit cabinet, black
FireFinder XLS Model SSD/-C series remote annunciator CAB3R-TK 500-633754 (3) Three-row trim-kit cabinet, red
to be mounted in the older generation Model RCC-1 CAB3-XBD 599-633769 CAB3 transponder door
surface-mount enclosure. Complete CAB3 w/ transponder door
CAB3-X 599-034253
[no inner door]
Field-mounted enclosure for 100AH
CAB-BATT 500-633917
batteries, black
Field-mounted enclosure for 100AH
CAB-BATT-R 500-634925
batteries, red
CAB-MP 500-633012 Back box module mounting plate
ID-FP 500-633029 (4) Four module inner-door blank plate
Inner-door enclosure mounting plate,
XLS-RCC1-ADPT ID-MP 500-633027
four [4] per package
XLS-RCC13F/R-ADPT − XLS RCC-1F/R or RCC-3F/R Single-module inner-door enclosure
ID-SP 500-633028
mounting plate [two (2) per package]
Enclosure Adapters
OD-BP 500-633017 Outer door blank plate
Model XLS-RCC13F-ADPT is an adapter that allows the OD-BP-R 500-634919 Outer door blank plate, red
FireFinder XLS Model SSD/-C series remote annunciator OD-GP 500-633018 Outer door grill plate
to be mounted in the older generation Model RCC-1F or OD-GP-R 500-634920 Outer door grill plate, red
Model RCC-3F black, flush-mount enclosure. OD-LP 500-633016 Outer door lens plate
REMBOX2 500-633772 (2) Two-module remote lobby enclosure, black
Model XLS-RCC13FR-ADPT is an adapter that allows the REMBOX2R 500-650612 (2) Two-module remote lobby enclosure, red
Model SSD/-C series to be mounted in the older REMBOX2-MP 500-634211
Mounting plate for Models OCM-16 /
generation RCC-1FR red and RCC-3FR red flush-mount SIM-16 in Model REMBOX2
REMBOX4 500-633914 (4) Four-module remote lobby enclosure, black
enclosure.
REMBOX4R 500-650613 (4) Four-module remote lobby enclosure, red
Mounting plate for Models OCM-16 /
REMBOX4-MP 500-634212
SIM-16 in Model REMBOX4
XLS-MLE6-ADPT S54430-C9-A1 MLE-6 enclosure adapter for XLS, black
XLS-MLE6R-ADPT S54430-C9-A2 MLE-6R enclosure adapter for XLS, red
MME-3 and MBR-2 enclosure adapters
XLS-MME3-ADPT S54430-C8-A1
for FireFinder XLS, black
XLS-MME3R-ADPT S54430-C8-A2 MME-3R enclosure adapter for XLS, red
XLS-RCC13F-ADPT XLS-MSE2-ADPT S54430-C7-A1 MSE-2 enclosure adapter for XLS, black
XLS-MSE2R-ADPT S54430-C7-A2 MSE-2R enclosure adapter for XLS, red

Temperature and Humidity Range XLS-MSE3-ADPT S54430-C14-A1


MXL-IQ MSE-3L and MSE-3M enclosure
adapters for XLS, black
Products are UL 864 9th Edition listed for indoor / dry MXL-IQ MSE-3LR & MSE-3MR enclosure
XLS-MSE3R-ADPT S54430-C14-A2
locations within a temperature range of 120+/-3°F adapters for XLS, red
(49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity XLS-RCC1-ADPT S54430-Z14-A1 RCC-1 enclosure adapter, black
of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C). XLS-RCC13F-ADPT S54430-Z13-A1 RCC-1F & RCC-3F enclosure adapters, black
XLS-RCC13FR-ADPT S54430-Z13-A2 RCC-1FR & RCC-3FR enclosure adapters, red

s Industry, Inc.
Building Technologies Division
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
October 2011
Building Technologies Division Tel: (973) 593-2600 (SII‐FS)  L6T 5E4 / Canada Supersedes sheet dated 8/11
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (Rev. 7)
URL: www.SBT.Siemens.com/FIS   FAX: (905) 799-9858
s Data Sheet
Fire Safety & Security Products

Intelligent Detection Devices


Intelligent Thermal Detector
[For use with FireFinder® XLS and FS-250 Panels]
Model HFP-11
ARCHITECT AND ENGINEER SPECIFICATIONS
 Most sophisticated ‘detector intelligence’ available
 FirePrint™ technology to differentiate between deceptive phenomena and an actual fire
 Easily programmed to match specific hazard profiles from the fire alarm control panel (FACP)
 Supports software-based automatic environmental compensation
 System logic activation based on any of three (3) inputs
from the detector (smoke, heat or neural network)
 Remote sensitivity-measurement capability
 Pre-alarm reporting based on fire-profile selection
 Polarity insensitive utilizing SureWireTM technology
 Multi-color detector status light-emitting diode (LED)
 Compatible with Model DPU (device programmer / tester unit)
 Field-cleanable chamber with replaceable chamber parts available
 Multi-criteria fire detection for the price of a photoelectric detector
 Optional fully programmable relay base, audible base and duct housing
 Detectors are self-testing:
 complete diagnostics every four seconds  UL and ULC Listed;
 Two-wire operation FM, CSFM & NYC Fire Department Approved
Product Overview
Model HFP-11 utilizes advanced detection technology Model HFP-11 is Underwriters’ Laboratory and
that allows each detector to distinguish non- Underwriters’ Laboratory of Canada listed.
threatening deceptive phenomena ─ such as cigarette
smoke, from actual fire hazards, while optimizing Specifications
detection for the area it is intended to detect. Model Model HFP-11 is a plug-in, two-wire and multi-sensor detector
HFP-11 uses state-of-the-art microprocessor circuitry (with both photoelectric and thermal inputs) that is compatible
with error check, detector self-diagnostics and with FireFinder XLS and FS-250 series of FACPs.
supervision programs. Each detector consists of a dust-resistant, field-cleanable and
Model HFP-11 is compatible with the Siemens ─ Fire photoelectric chamber; a solid state, non-mechanical thermal
Safety field device program / test unit (Model DPU), sensor, and microprocessor-based electronics with a low-profile
which is a compact, portable, menu-driven accessory plastic housing. Model HFP-11 utilizes state-of-the-art ASIC
for electronically programming and testing detectors, circuitry and surface-mount technology for maximum reliability.
easily and reliably. Every Model HFP-11 fire detector is shipped with a protective dust
Model DPU eliminates the need for cumbersome, cover. Model HFP-11 utilizes an infrared light emitting diode
unreliable mechanical programming methods ─ such (IRLED), and light-sensing photodiode. Under normal conditions,
as dials or switches, and reduces installation and light transmitted by the LED is directed away from the
service costs by electronically programming and testing photodiode and scattered through the smoke chamber in a
the detector prior to installation. Model HFP-11 is controlled pattern.
compatible with FS-250 and Fire Finder XLS FACPs.

Addressable FirePrintTM Detector 6301


s Industry, Inc.
Building Technologies Division
Specifications ─ (continued)
The smoke chamber is designed to manage light The FirePrint technology was developed over years of research
dissipation and extraneous reflections from dust particles and reviewing the results of over 20 years of fire test data in one
or other non-smoke, airborne contaminants in such a way of the world’s most advanced fire-research centers.
as to maintain stable, consistent detector operation. The results of this research are the mathematical models that
When smoke enters the detector chamber, light emitted form the algorithms used in FirePrint. No other fire detector has
from the IRLED is scattered by the smoke particles, and is this level of intelligence or this amount of research and
received by the photodiode. development supporting its design. The microprocessor’s
Model HFP-11 also utilizes a modern, accurate and software can identify and disregard false input caused by radio
shock-resistant thermistor to sense temperature frequency (RFI) and electromagnetic (EMI) interference, while
changes. The ‘on-board’ FirePrintTM technology allows validating all Trouble conditions before annunciating or
the detector to first gather smoke and thermal data, and reporting to the FACP.
then analyze this information in the detector’s ‘neural
network.’ By comparing data received with the common Model HFP-11
characteristics of fires or fire fingerprints, Model HFP-11 The Model HFP-11 detector’s microprocessor uses an essential
can compare these ‘fire prints’ to those of deceptive electronically erasable programmable read-only memory
phenomena that cause other detectors to false alarm. (EEPROM) to store the detector’s address and other critical
operating parameters, including the assigned program values for
FirePrint Alarm and Trouble thresholds.
The advanced FirePrint technology allows Model HFP-11
Communication within the detector, as well as between Model
to accurately determine a true fire hazard from
HFP-11 and the control panel, or with Model DPU (field device
unthreatening, deceptive phenomena. Further, the
programmer / test unit), are supervised and safe-guarded against
advanced FirePrint technology will not require a need to
disruption by reliable, microprocessor-based error checking
use alarm-delaying verification and confirmation
routines.
techniques, which can increase the probability of losses
due to fire. Model HFP-11 provides the highest level of Additionally, the micro-processor supervises all EEPROM memory
detector intelligence available today with a detector / locations, and provides a high degree of EEPROM-failure fault
control panel link that allows the user to program the tolerance. Model HFP-11 determines its operating status to be
detector for the specific hazard profile, using a simple Normal in Alarm or in Trouble modes, depending on the
software menu selection. difference between the alarm threshold values stored in the
Model HFP-11’s FirePrint application monitors input detector’s memory and the detector’s latest analog measurement.
from both the photo chamber and the thermal sensor, The detector then communicates changes in its status to the
evaluating this information with sophisticated control panel. In addition, the FireFinder XLS control panel will
mathematical formulas or algorithms, comparing this sample the value of the analog signal for Model HFP-11 over a
input to characteristics of both threatening fires and period of time, in order to determine if those values indicate
deceptive phenomena that would mislead any ordinary excessive buildup in the photo chamber. If such is the case, the
detector. FireFinder XLS control panel will indicate the particular detector
Detectors are optimized by selecting one (1) of the requires maintenance.
following 11 applications: Model HFP-11 is listed as a self-testing device. The visible light
• Office / Retail emitting diode (LED) for Model HFP-11 flashes green every four
• Lobby (4) seconds to indicate it is communicating with the control
• Computer room panel, as well as to indicate it has passed its internal self-test.
• Dormitory Should the detector sense a fault or failure within its systems, the
• Healthcare LED will flash amber, and the detector will transmit that
• Parking garage data to the control panel.
• Utility / Transformer room A quick visual inspection is enough to indicate the condition of
• Hostile environment the detector at any time. If more detailed information is required,
• Precious storage a printed report can be provided from the FireFinder XLS FACP,
• Air Duct indicating the status and settings assigned to each individual
• Warehouse / Light Manufacturing detector. When Model HFP-11 moves to the Alarm mode, it will
The control panel programs Model HFP-11 detector for flash red, and will continue flashing until the system is reset at
the protected area without hassle and without confirmation the FACP. Simultaneously, any user-defined, system-alarm
delays. Once optimized for the hazards in the protected functions programmed into the system are activated.
area, Model HFP-11 provides the best detection. Should
the operator or installer forget to program the detector,
Model HFP-11 will revert to a default setting, allowing
operation as an office-environment detector.

s Industry, Inc.
Building Technologies Division
Specifications ─ (continued) Application Data
Detector sensitivity, calibration and identification are Installation of the Model HFP-11 series of fire detectors
dynamically supervised at the respective FACP. requires a two-wire circuit. In many retrofit cases, existing
Detector sensitivity and pre-alarm levels are a wiring may be used. ’T-tapping’ is permitted only for Style
function of the application chosen at the control 4 (Class B) wiring. Model HFP-11 is polarity insensitive,
panel, and are controlled by the panel. If an which can greatly reduce installation and debugging time.
alternate, non-FirePrint mode is selected, then the Model HFP-11 fire detectors can be applied within the
sensitivity can be changed from the control panel. maximum 30 foot center spacing (900 sq. ft. areas,) as
All Model HFP-11 detectors use a surface mounting referenced in NFPA 72. This application guideline is based
base, Model DB-11, which mounts on a 4-inch on ideal conditions, specifically, smooth ceiling surfaces,
octagonal, square or single gang electrical box. The minimal air movement, and no physical obstructions
base utilizes screw-clamp contacts for electrical between potential fire sources and the actual detector.
connections and self-wiping contacts for increased Do not mount detectors in close proximity to ventilation
reliability. Model DB-11 can be used with the optional or heating and air conditioning outlets. Exposed joints or
Model LK-11 detector locking kit, which contains 50 beamed ceilings may also affect safe spacing limitations
detector locks and an installation tool to prevent for detectors.
unauthorized removal of the detector head. Model Should questions arise regarding detector placement,
DB-11 has integral decorative plugs to cover the outer observe NFPA 72 guidelines. Good fire-protection system
mounting screw holes. engineering and common sense dictate how and when fire
Model HFP-11 may be installed on the same initiating detectors are installed and used. Contact your local
circuit with Model HMS-series manual stations; Model Siemens ─ Fire Safety distributor or sales office whenever
HTRI-series interfaces; Model HCP output-control you need assistance applying FirePrint in unusual
devices, or Model HZM series of addressable, applications. Be sure to follow NFPA guidelines and UL
conventional zone modules. All Model HFP-11 Listed / ULC Listed installation instructions ─ included with
detectors can be cleaned in the field  when required every Siemens − Fire Safety detector ─ and local codes as
 via easily removing the detector cover and for all fire protection equipment.
unsnapping the photo chamber. There is also the
option of cleaning the interior of the detector with a
clean, soft cloth or brush  or by replacing the
labyrinth and bug screen included in the detector
Technical Data
maintenance kit, Model DMK-11. Operating Temperatures: +32°F (0°C) to
All Model HFP-11 detectors are approved for operation 100°F (38°C),
within the UL-specified temperature range per UL 268 / 268A
of 32 to 100°F (0 to 38°C).
Model DPU Relative Humidity: 0-93%
The Device Program / Test Unit accessory is used to
program and verify the address of the detector. The
technician selects the accessory’s program mode, and
enters the desired address. Model DPU automatically Non-condensing
sets and verifies the address and tests the detector. Maximum Spacing: 30-foot Centers
Model DPU operates on AC power or rechargeable (900 Square Feet),
batteries, providing flexibility and convenience in per NFPA 72 Chapter 5
programming and testing equipment from practically and ULC-S524
any location.
When in ‘test’ mode, Model DPU will perform a series
of diagnostic tests without altering the address or
Current Draw: 1mA in Alarm or
other stored data, allowing technicians to determine
Supervisory mode
if the detector is operating properly.

s Industry, Inc.
Building Technologies Division
Mounting Diagram Details for Ordering
Model Part
Number Number Description
HFP-11 500-033290 Addressable FirePrintTM Fire Detector
DB-11 500-094151 Detector Mounting Base for Series 11
DB-11E 500-094151E Detector Base {small}
AD2-P 500-649706 Air-Duct Housing
AD2-XHR 500-649708 Air-Duct Housing {with relay}
DB-HR 500-033220 Relay Base for
H-Series Intelligent Detectors
ADBH-11 500-033210 Audible Base
RL-HC 500-033230 Remote Alarm Indicator:
4” octagon-box mount, red
RL-HW 500-033310 Remote Alarm Indicator:
Single-gang box mount, red
LK-11 500-695350 Base Locking Kit for Series 11
Detectors
Series 11 Maintenance Kit
DMK-11 500-695338 {replacement labyrinth and
bug screen}

In Canada, order
Model Part
Number Number Description

DB-11C 500-095687 Detector Mounting Base


for Series 11 Detectors ( ULC)

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Tel: (973) 593-2600 L6T 5E4 / Canada September 2013
Building Technologies Division [SII-FS]
Supersedes sheet dated 10/10
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (Rev. 4)
URL: www.usa.Siemens.com/Fire FAX: (905) 799-9858
s Data Sheet 
Fire Safety & Security Products 

HTRI-Series Interface Modules


Models HTRI-D, HTRI-R and HTRI-S
ARCHITECT AND ENGINEER SPECIFICATIONS
• Interfacing and supervising normally open (N.O) or normally
closed (N.C) contacts
• Integral single-pole, double-throw (SPDT) relay on Model HTRI-R
(up to 4 amps)
• Dual input on Model HTRI-D, using a single address
• Polarity insensitive with SureWireTM technology
• Multi-color light-emitting diode (LED) indicates system status:
ƒ green / amber / red
• Easy front access to programming port and wiring terminals
• Mounts in a 4-inch square, 2-¼”-deep box (or double-gang box)
• Dynamic supervision
• Comes with 5-x-5” faceplate
• Two-wire operation
• Device Programmer / Tester programs and verifies address of the
device and tests for proper functionality
• Electronic address programming is easy and dependable
• UL Listed & ULC Listed;
FM, CSFM and NYC Fire Department Approved

Product Overview
The Siemens ─ Fire Safety HTRI-series Intelligent The interface module reports the status of the (N.O)
interface modules are designed to provide the means or (N.C) contact to the control panel. Model HTRI-S
of interfacing direct shorting devices to the fire-alarm can only monitor and report the status of the contact,
control panel (FACP) loop circuit. while Model HTRI-R incorporates an addressable
The HTRI-series modules provide the most advanced ‘Form C’ relay.
method of address programming and supervision on The Model HTRI-R relay and contact device input are
the market ─ combined with sophisticated control controlled at the same address. For the FACP, the
panel communication. Each HTRI-series interface relay and input contact can be controlled as a
module incorporates a microcomputer chip, and each separate function. The relay is typically used where
interface module achieves the state of an ‘intelligent control or shunting of external equipment is
device’ through its microcomputer chip technology, required.
combined with its sophisticated, bi-directional The Model HTRI-D is a dual-input module that is
communication capabilities with the FACP. designed to supervise and monitor two (2) sets of dry
contacts. Model HTRI-D only requires one (1)
Specifications address, but responds independently to each input.
The HTRI-series intelligent interface modules are Model HTRI-D is ideal for monitoring a water-flow
available in three (3) models. Models HTRI-S and switch and its respective valve tamper switch.
HTRI-R are designed to monitor a (N.O) or (N.C) dry
Model HTRI has a multi-color LED that flashes green
contact.
when operating in Normal; ‘amber’ if unit is in Trouble
condition, and ‘red’ to indicate a change of state.

HTRI Series Interface Modules 6304


s Industry, Inc.
Building Technologies Division
Specifications (continued) Mounting Diagram
Model HTRI-D flashes twice ─ once for each Models HTRI-S, HTRI-D and HTRI-R mount directly into
address, and Model HTRI-R LED indicates a change a 4-inch square, 2 ¼-deep box or to a user-supplied
of state in the relay. The device’s microcomputer double-gang box. A 5-inch square, off-white
chip has the capacity of storing, in memory, faceplate is included with each HTRI-series module.
identification information; as well as important
operating-status information.
Siemens ─ Fire Safety innovative technology
allows all HTRI-series intelligent interface modules
to be programmed via the Device Programming /
Test Unit: a compact, portable and menu-driven
accessory that makes programming and testing
an interface device faster, easier and more
dependable than previous methods.
The programmer / tester eliminates the need for
mechanical addressing mechanisms, such as:
program jumpers, DIP switches or rotary dials,
since Model DPU electronically sets the HTRI-
series interface address into the non-volatile
memory of the interface microcomputer-chip.
Vibration, corrosion and other conditions that
deteriorate mechanical addressing mechanisms
are no longer a cause for concern.
The HTRI-series is fitted with screw terminals for
connection to an addressable circuit, and is fully
compatible on the same Siemens FACPs with all
intelligent ‘H’-series detectors, ‘HMS’-series
addressable manual stations, or any other
addressable intelligent modules, such as Model Details for Ordering
HZM or Model HCP.
All HTRI-series intelligent interface modules are
UL Listed. Environmental operating conditions
for all HTRI-series modules are 32ºF (ºC) to 120ºF
(49ºC) with a relative humidity of no greater than
93%, non-condensing.

Electrical Ratings
Current Draw
(Active or Standby) 1mA

Model HTRI-R Relay Ratings


Resistive: 4 Amps, 125 VAC
4 Amps, 30 VDC
Inductive: 3.5A, 120 VAC (0.6P.F.)
3.0A, 30 VDC (0.6P.F.)
2.0A, 120 VAC (0.4P.F.)
2.0A, 120 VAC (0.35P.F.)
2.0A, 30 VDC (0.35P.F.)

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
December 2011
Building Technologies Division Tel: (973) 593-2600 (SII) L6T 5E4 / Canada
Supersedes sheet dated 6/10
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (Rev. 2)
URL: www.SBT.Siemens.com/FIS   FAX: (905) 799-9858
s Data Sheet
Fire Safety & Security Products

Intelligent Initiating Devices


HMS-Series
Models HMS-D, HMS-S
ARCHITECT AND ENGINEER SPECIFICATIONS
 Durable design
 Shock-and-vibration resistant
 Pull-down lever is down, until manually reset
 Reset with Allen Key
 No break rods necessary
 Custom microcomputer-chip technology
 Dynamic supervision to the fire-alarm control
panel (FACP)
 Polarity insensitive via SureWireTM technology
 Two-wire operation
 Surface or semi-flush installation
 Model DPU programs and verifies address
and tests functionality of each device
 Electronic-address programming is easier, more
efficient and more dependable
 Comes in single-action (Model HMS-S) and
double-action (Model HMS-D) stations Model HMS-D Model HMS-S
 UL Listed; Dual-Action Station Single-Action Station
FM, CSFM & NYC Fire Dept. Approved
Product Overview
The Siemens intelligent manual fire-alarm boxes Models HMS-S and HMS-D operate with Siemens ─
(Models HMS-S and HMS-D) provide the most Fire Safety FACPs. The microcomputer chip to the
advanced method of address programming and manual fire-alarm box has the capacity of storing ─ in
supervision. Each Model HMS-series manual box memory ─ identification information as well as
achieves the state of an ‘intelligent-initiating device’ important operating-status data.
by incorporating custom microcomputer-chip Innovative technology from Siemens ─ Fire Safety
technology with sophisticated, bi-directional also allows all Model HMS-series intelligent manual
communication capabilities with the FACP. fire-alarm boxes to be programmed via the Device
Specifications Programmer / Test Unit (Model DPU). Model DPU is a
compact, portable and menu-driven accessory that
Models HMS-S and HMS-D are constructed of
makes programming and testing of a manual fire-
durable, molded polycarbonate material that is matte
alarm box device faster, easier and more dependable
finished in red with raised white lettering. The
than previous methods.
housing accommodates a ‘pull-down’ lever, which ─
when operated ─ locks into position; indicating the The programmer / tester eliminates the need for
manual fire-alarm box has been activated. mechanical-addressing mechanisms of a device
because Model DPU electronically sets the address of
The pull down lever remains down / in the ‘locked’
the manual fire-alarm box into its microcomputer
position, until the fire-alarm box is manually reset.
chip, non-volatile memory. Hence, vibration,
The manual fire alarm box can only be reset by
corrosion and other conditions that can compromise
opening the hinged housing cover with an Allen key;
or even deteriorate mechanical-addressing
followed by closing and locking the cover.
mechanisms are no longer a cause for concern.

HMS Series Intelligent Initiating Devices 6306


s Industry, Inc.
Building Technologies Division
Specifications ─ (continued) Electrical Ratings
Models HMS-S and HMS-D are fitted with screw Current Draw (Active or Standby) ─ 1.5mA
terminals for connection to an addressable circuit,
and can be either surface or semi-flush mounted.
Details for Ordering
The Model HMS-series manual fire-alarm boxes
Model Part Shipping
derive their power, communicate information and Description
Number Number Weight
receive commands over a single pair of wires.
Addressable Manual Fire
HMS-D 500-033400 2.5 Lbs. 1.13 Oz.
The Model HMS-series is compatible on the same Alarm Box, Dual Action
circuit with all Model ‘H’-series detectors, interfaces HMS-S 500-033200
Addressable Manual Fire
2.0 Lbs. 0.9 Oz.
or addressable, conventional zone modules. Alarm Box, Single Action
Reset Tool Package
LTP 500-620490 0.5 Lb. 0.23 Oz.
[contains two (2) tools]
SB-5R 310-019860 Surface-Mounting Box 1.5 Lbs. 0.7 Oz.

Mounting Diagram

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
September 2013
Building Technologies Division Tel: (973) 593-2600 (SII) L6T 5E4 / Canada
Supersedes sheet dated 2/13
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (Rev. 4)
URL: www.usa.Siemens.com/Fire FAX: (905) 799-9858
s Catalog Sheet 
Fire Safety & Security Products 

Air-Duct Housings and Detectors


Air-Duct Housings ─ AD2 Series
Models AD2-P, AD2-PR, AD2-XHR, AD2-4W, ST(s): 10, 25, 50 and 100
ARCHITECT AND ENGINEER SPECIFICATIONS

• For use with Series 11 detectors


• Relay models available
• Design for air-velocity range of 100 to 4,000 fpm
• Alarm LED visible from front
• Self-contained model available with
‘on-board’ power supply
• Clear housing cover for quick
identification of detector type;
removable with only four (4) captive screws
• UL and ULC Listed;
FM, CSFM & NYMEA Approved
Product Overview
The Siemens Industry, Inc. ─ Fire Safety Air-Duct Notes - (cont.’d): With the MXL series of control panels, up to 60
Detector Housings are designed to be used with the detectors (per circuit) having relays may be used. The connection of
a remote lamp or a remote relay is allowed for each detector, but not
Series 11 detectors. Designed for installation simultaneously.
directly to heating, ventilating and air-conditioning
With the FireFinder XLS series of control panels, up to 252
duct systems, they comply with National Fire detectors (per circuit) having relays may be used. The connection of an
Protection Association Standard No. 90A. When intelligent remote lamp (ILED) and a remote Relay is allowed for each
equipped, the air-duct detector housing will signal the detector simultaneously.
presence of smoke being carried through the duct Air-duct housings (see: Details for Ordering) are Underwriters’
system. Air-duct detectors are not intended to be Laboratories, Inc. listed.
substituted for open-area detection.
Specifications
Air-duct housings can be equipped with optional relays,
The air-duct housings are uniquely designed to use
which are utilized to operate any supplementary
with the photoelectric detector. Sensitivity of PE-11
equipment when smoke is detected.
detectors can be checked by viewing the LED or a
Notes: Most conventional time-control equipment guarantee RSAW- 11 or RSAC-11 multicolor remote lamp. A green
only one (1) detector per zone when the detector operated flash indicates the detector has passed its self test.
relay function is critical. The connection of a remote
lamp and a remote relay per detector is allowed with Amber indicates a ‘Trouble’ condition, and red indicates
PXL or System 3 TM only; other conventional systems may an ‘Alarm’ state. HFP-11, HFPO-11 and FP-11 sensitivity
use either a remote lamp or a relay. may be viewed from the multi-color LED on the detector
or, preferably, may be printed by command on an
optional printer from the MXL control panel.

Air-Duct Housings and Detectors 6185


s Industry, Inc.
Building Technologies Division
Specifications ─ (continued)
The detector unit employs a cross-sectional sampling All that is necessary for installation of the air-duct
principle of operation. Inlet sampling tubes are detector is the cutting of three (3) small holes for the
available in four (4) lengths (see: Sampling Tube Sampling Tube installation (template included),
Selection Table ). Outlet sampling tubes are one (1) and the drilling of two (2) holes for mounting the
common length and draw. A continuous, cross-sectional air-duct housing. The unit is then easily mounted in
sample of air moves through the duct. Stratification or place, and connection made to the existing wires
skin affect phenomenon that occurs in the duct can or terminals ─ if optional accessories are
prevent smoke (especially in large ducts) from reaching utilized.
a spot-type detector. (For full details, refer to installation instructions part number
315-049708-4.)
In addition, the unique design of the sampling chamber
insures uniform sensitivity in air velocities, ranging ST-50 and ST-100 require support. ST-100 is shipped in
from a low of 10- feet-per-minute to as high as 4,000- two (2) 5-ft. (152 cm.) pieces with a coupling for field
feet-per-minute. Each housing comes with three (3) assembly.
wiring entry ports:
ƒ Two (2) 3/4” conduit knockouts
Technical Data
ƒ One (1) 1/2” conduit opening Temperature Range: 32°F (0°C) -100°F (38°C)
The inlet sampling tube length is determined by the Altitude Range: No Altitude Limitations
width of the air duct being protected. The inlet tube ─ 10 - 85%
Relative Humidity:
greater than and nearest to the duct width ─ should be (non-condensing / non-freezing)
used (see: Sampling Tube Selection Table). The inlet Air-Duct Velocity Range: 100 - 4,000 Ft. /Min.
tube can then be trimmed at the job site to the exact Sampling Tube Pressure Greater than 0.01 inches; less
width of the duct. The outlet sampling tube for all ducts Range of Differences: than 1.2 inches of water column
─ irrespective of width ─ has a fixed length of Note to Architect: When building codes regulate the location of
approximately 5.5 inches (14cm.), and is supplied with detectors within ventilating systems, make sure the number and
the air-duct housing. locations of detectors is in accordance with the code regulations.
Note: When the use of a remote relay is required, order model
AD2-PR for conventional systems; AD2-XHR for addressable Details for Ordering
systems. When required the WP-2000 weatherproof enclosure
for duct housing is available. Model Part
Description
(For full details, refer to installation instructions part number
Number Number
315-049708.) Air-Duct Housing for use with FP-11,
AD2-P 500-649706
HFP-11, HFPO-11 and PE-11
Note: When a self-contained duct detector with power
supply is required, order model AD2-4W. Air-Duct Housing for use
AD2-PR 500-649707
with PE-11 relay
(For full details, refer to installation instructions part number
315-049708.) Air-Duct Housing for use with FP-11,
AD2-XHR 500-649708 HFP-11 and HFPO-11, with relay
Sampling Tube Selection Table Self-contained Air-Duct Housing with
AD2-4W 500-649709 ‘on board’ power supply and relay
Sampling Tube
Duct Width
(Model No.) ST-10 500-649710 Sampling tube for Ducts 6” to 1’
For duct widths 6” to 1’ ST-10 ST-25 500-649711 Sampling tube for Ducts over 1’ to 3’
For duct widths 1’ to 3’ ST-25 ST-50 500-649712 Sampling tube for Ducts 3” to 5’
For duct widths 3’ to 5’ ST-100 500-649713 Sampling tube for Ducts 5’ to 10’
ST-50
(requires support)
For duct widths 5’ to 10’ Product Includes:
ST-100
(requires support)
- (1) short-return (outlet) tube
Maintenance of the detector is easily accomplished - (1) stopper
by the removal of the Series 11 duct-housing - (2) #12 + 3/4” sheet-metal screws
sampling chamber cover. The detector, which plugs - (1) mounting template
into the housing, is easily removed for cleaning by Note: Detector and sampling tube to be purchased separately.
a trained technician. Minimum hardware required is: one (1) air-duct housing
assembly; one (1) sampling tube and one (1) detector.

Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Tel: (973) 593-2600 L6T 5E4 / Canada December 2009
Building Technologies Division SFS
Supersedes sheet dated 9/09
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (Rev. 2)
URL: www.SBT.Siemens.com/FIS   FAX: (905) 799-9858
s Catalog Sheet 
Fire Safety & Security Products 

FireFinder XLS and FS-250 Detectors


Remote Alarm Lamps
Models RL-HC and RL-HW

• Multi-color LED (green, amber, red)


mimics detector
• Becomes second accessory
(used with relay or audible base)
• Canbe addressed and
independently controlled by
panel logic
• Can be installed anywhere on the
‘H’-series device circuit
Model RL-HW • UL Listed and ULC Listed; Model RL-HC
[Wall] FM, CSFM & NYMEA Approved [Ceiling]

Product Overview Specifications


The Remote Alarm Lamps (Models RL-HW and RL-HC) The Remote Alarm Lamps can be mounted
are designed for use with initiating devices that are anywhere on the ‘H’-series device loop, and are
concealed or otherwise not exposed to view (e.g. ─ addressed with the Device Program / Tester Unit
in false ceilings, under sub-floors, in unexposed (Model DPU).
ventilating ducts, normally locked vaults, within
computer consoles, etc.) Even though the device Models RL-HW and RL-HC have screw-type
initiating the alarm is out of sight, these remote terminals for ease of installation. The mounting
alarm-lamp assemblies will readily identify the plates for both units are comprised of an off-
aforementioned non-concealed initiating devices. white plastic, presenting an attractive
Model RL-HC is designed for mounting to a 4” appearance that will blend with any decor.
octagon outlet box, and Model RL-HW is designed
for mounting on a standard single-gang switch box. Details for Ordering
Although there is no mounting limitation, Model
Model Part
RL-HC is normally ceiling mounted, while Model RL- Number Number Description
HW is normally mounted to a wall. The remote
RL-HC 500-033230 Remote Lamp, Ceiling
lamps may be placed up to 25 feet from the detector RL-HW 500-033310 Remote Lamp, Wall
and use 14-to-18 gauge, 3-conductor wire.
The light-emitting diode (LED) can be controlled by
panel logic ─ even on different device loops, or on
another panel in the network configuration, since
Model RL-HC or Model RL-HW is given its own
unique address.

FireFinder XLS 6307


s Industry, Inc.
Building Technologies Division
Mounting Diagram

Model RL-HC Model RL-HW


[Ceiling] [Wall]

Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
July 2010
Building Technologies Division Tel: (973) 593-2600 (SII) L6T 5E4 / Canada
Supersedes sheet dated 12/04
FAX: (908) 547-6877 Printed in U.S.A.  Tel: (905) 799-9937 (Rev.1)
URL: www.SBT.Siemens.com/FIS   FAX: (905) 799-9858
Operations Matrix shall include Waterflow, Tamper, or Other Sprinkler Valve
Events.

In the event of a Waterflow, a general evacuation notification (horns & strobes)


and a "Northeast Waterflow AFA" signal should be sent to the Monitoring
System.
In the event of a tamper or other sprinkler valve event (air hi/lo for example), a
"Supervisory" signal should be sent to the Monitoring system.

Boeing Comment, George Wangersky, 2/18/2014

Design is acceptable pending final field review and testing and the following
comment:

The Duct Detectors should be monitored as a "Supervisory Trouble Alarm".

Boeing Comment, Robert Eaker, 2/20/2014

Siemens Industry, Inc.


SIEMENS
**

**

SIEMENS

Siemens Industry, Inc.


120 VAC RELAY
120 VAC DOOR HOLDER
POWER POWER

Siemens Industry, Inc.


A D G J M P S

11

BUILDING 04-020 KEY PLAN


SCALE: N.T.S.

Siemens Industry, Inc.


A D G J M P S

11

BUILDING 04-020 KEY PLAN


SCALE: N.T.S.

Siemens Industry, Inc.


A D G J M P S

11

BUILDING 04-020 KEY PLAN


SCALE: N.T.S.

Siemens Industry, Inc.


A D G J M P S

11

BUILDING 04-020 KEY PLAN


SCALE: N.T.S.

Siemens Industry, Inc.


A D G J M P S

11

BUILDING 04-020 KEY PLAN


SCALE: N.T.S.

Siemens Industry, Inc.