Documente Academic
Documente Profesional
Documente Cultură
HERMETIC SCROLL
INSTALLATION, OPERATION, MAINTENANCE Replaces 201.26-NM1 (1207) Form 201.26-NM1 (308)
035-21965-101
YCWL0056 -0156
WATER-COOLED LIQUID CHILLERS
STYLE A (60 Hz)
50 - 150 TONS
175kW THROUGH 530kW
Form 201.26-NM1 (308)
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation, maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
oils, materials under pressure, rotating components, operating/service personnel. It is expected that this
and both high and low voltage. Each of these items individual possesses independent training that will
has the potential, if misused or handled improperly, to enable them to perform their assigned tasks properly
cause bodily injury or death. It is the obligation and and safely. It is essential that, prior to performing any
responsibility of operating/service personnel to identify task on this equipment, this individual shall have read
and recognize these inherent hazards, protect themselves, and understood this document and any referenced
and proceed safely in completing their tasks. Failure to materials. This individual shall also be familiar with and
comply with any of these requirements could result in comply with all applicable governmental standards and
serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
2 JOHNSON CONTROLS
Form 201.26-NM1 (308)
It is the responsibility of operating/service personnel to verify the applicability of these documents to the equipment in
question. If there is any question in the mind of operating/service personnel as to the applicability of these documents,
then prior to working on the equipment, they should verify with the owner whether the equipment has been modified
and if current literature is available.
JOHNSON CONTROLS 3
Form 201.26-NM1 (308)
TABLE OF CONTENTS
SECTION 1 – GENERAL CHILLER INFORMATION & SAFETY........................................ 13
INTRODUCTION .........................................................................................................................................13
WARRANTY ................................................................................................................................................13
SAFETY .......................................................................................................................................................13
Standards for Safety ...........................................................................................................................13
Responsibility for Safety ....................................................................................................................14
MISUSE OF EQUIPMENT ...........................................................................................................................14
Suitability for Application ...................................................................................................................14
Structural Support ...............................................................................................................................14
Mechanical Strength ..........................................................................................................................14
General Access ....................................................................................................................................14
Pressure Systems ...............................................................................................................................14
Electrical...............................................................................................................................................14
Rotating Parts ......................................................................................................................................14
Sharp Edges.........................................................................................................................................14
Refrigerants and Oils ..........................................................................................................................14
High Temperature and Pressure Cleaning ........................................................................................15
Emergency Shutdown .........................................................................................................................15
4 JOHNSON CONTROLS
Form 201.26-NM1 (308)
TABLE OF CONTENTS (CONT’D)
SECTION 4 – INSTALLATION ............................................................................................. 35
INSTALLATION CHECKLIST......................................................................................................................35
LOCATION REQUIREMENTS ....................................................................................................................35
UNIT ISOLATION (NOISE SENSITIVE LOCATION) ..................................................................................35
FOUNDATION .............................................................................................................................................35
INSTALLATION OF VIBRATION ISOLATORS ..........................................................................................36
PIPEWORK CONNECTION ........................................................................................................................36
General Requirements ........................................................................................................................36
WATER TREATMENT .................................................................................................................................38
Glycol Solutions ..................................................................................................................................38
OPTION FLANGES .....................................................................................................................................38
REFRIGERANT RELIEF VALVE PIPING....................................................................................................38
CONDENSER COOLING LIQUID SYSTEMS .............................................................................................38
Direct Pressure Control (by others)...................................................................................................39
Inlet Temperature Control (by others) ...............................................................................................39
PIPEWORK ARRANGEMENT ....................................................................................................................40
CONNECTION TYPES & SIZES .................................................................................................................40
Cooler Connections ............................................................................................................................40
ELECTRICAL CONNECTION .....................................................................................................................41
Remote Emergency Stop Device (QRRSB) .......................................................................................41
COMMON INPUT SECTION WIRING .........................................................................................................41
Chilled Liquid Pump (CLP) (Evaporator Pump Start Contacts) ......................................................41
Common Run Signal (CRS) (System run Contacts) .........................................................................41
FIELD WIRING ............................................................................................................................................41
CONTROL PANEL WIRING ........................................................................................................................42
Flow Switch (SF) ..................................................................................................................................42
POWER WIRING .........................................................................................................................................42
Units with Single-Point Power Supply Wiring ..................................................................................43
Units with Multi Point Power Supply Wiring .....................................................................................43
Control Transformer Primary Voltage Tappings ...............................................................................43
COMPRESSOR HEATERS .........................................................................................................................43
RELIEF VALVES .........................................................................................................................................43
HIGH PRESSURE CUTOUT .......................................................................................................................43
CONTROL WIRING .....................................................................................................................................44
JOHNSON CONTROLS 5
Form 201.26-NM1 (308)
SECTION 6 – COMMISSIONING......................................................................................... 91
COMMISSIONING .......................................................................................................................................91
PREPARATION – POWER OFF..................................................................................................................91
Inspection ............................................................................................................................................91
Refrigerant Charge ..............................................................................................................................91
Service and Oil Line Valves ................................................................................................................91
Compressor Oil....................................................................................................................................91
Fans .....................................................................................................................................................91
Isolation / Protection ...........................................................................................................................91
Control Panel .......................................................................................................................................91
Power Connections .............................................................................................................................91
Grounding ............................................................................................................................................91
Supply Voltage .....................................................................................................................................92
PREPARATION – POWER ON ...................................................................................................................92
Switch Settings ....................................................................................................................................92
Compressor Heaters ...........................................................................................................................92
Water System .......................................................................................................................................92
Flow Switch ..........................................................................................................................................92
Temperature Sensor(s) .......................................................................................................................92
6 JOHNSON CONTROLS
Form 201.26-NM1 (308)
JOHNSON CONTROLS 7
Form 201.26-NM1 (308)
8 JOHNSON CONTROLS
Form 201.26-NM1 (308)
TABLE OF CONTENTS
OPTIONAL PRINTER INSTALLATION .....................................................................................................143
Parts....................................................................................................................................................143
Assembly and Wiring ........................................................................................................................143
Obtaining a Printout ..........................................................................................................................143
TROUBLESHOOTING ..............................................................................................................................144
JOHNSON CONTROLS 9
Form 201.26-NM1 (308)
LIST OF TABLES
TABLE 1 – CONDENSER / COOLER CONNECTIONS .............................................................................41
TABLE 2 – TEMPERATURES AND FLOWS ..............................................................................................45
TABLE 3 – VOLTAGE LIMITATIONS ..........................................................................................................45
TABLE 4 – TEMPERATURES AND FLOWS ..............................................................................................46
TABLE 5 – VOLTAGE LIMITATIONS ..........................................................................................................46
TABLE 6 – ETHYLENE & PROPOLYNE GLYCOL CORRECTION FACTORS .........................................49
TABLE 7 - RECOMMENDED GLYCOL SOLUTION STRENGTHS ............................................................49
TABLE 8 – MICRO PANEL POWER SUPPLY ............................................................................................63
TABLE 9 – VOLTAGE RANGE (LIMITATIONS)..........................................................................................63
TABLE 10 – SETPOINTS ENTRY LIST ......................................................................................................94
TABLE 11 – STATUS KEY MESSAGES QUICK REFERENCE LIST ......................................................104
TABLE 12 – OPERATION DATA ...............................................................................................................108
TABLE 13 – COOLING SETPOINTS, PROGRAMMABLE LIMITS AND DEFAULTS ............................. 116
TABLE 14 – PROGRAM KEY LIMITS AND DEFAULT ............................................................................ 119
TABLE 15 – SETPOINTS QUICK REFERENCE LIST .............................................................................120
TABLE 16 – SAMPLE COMPRESSOR STAGING FOR RETURN WATER CONTROL ..........................129
TABLE 17 – RETURN CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)....................130
TABLE 18 – RETURN CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)....................130
TABLE 19 – COMPRESSOR OPERATION – LOAD LIMITING ...............................................................132
TABLE 20 – I/O DIGITAL INPUTS ............................................................................................................137
TABLE 21 – I/O DIGITAL OUTPUTS ........................................................................................................137
TABLE 22 – I/O ANALOG INPUTS ...........................................................................................................137
TABLE 23 – I/O ANALOG OUTPUTS .......................................................................................................137
TABLE 24 – ENTERING/LEAVING CHILLED LIQUID TEMP. SENSOR,
TEMPERATURE/VOLTAGE CORRELATION .......................................................................140
TABLE 25 – PRESSURE TRANSDUCERS ..............................................................................................141
TABLE 26 – TROUBLESHOOTING ..........................................................................................................144
TABLE 27 – ISN RECEIVED DATA...........................................................................................................148
TABLE 28 – ISN TRANSMITTED DATA ...................................................................................................148
TABLE 29 – ISN OPERATIONAL AND FAULT CODES ...........................................................................150
TABLE 30 – MINIMUM, MAXIMUM AND DEFAULT VALUES .................................................................152
TABLE 31 – REAL TIME ERROR NUMBERS ..........................................................................................153
10 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LIST OF FIGURES
FIG. 1 - YCWL WATER COOLED LIQUID CHILLER .................................................................................17
FIG. 2 - CONTROL/PANEL COMPONENTS ..............................................................................................22
FIG. 3 - CONTROL POWER PANEL COMPONENTS ................................................................................23
FIG. 4 - UNIT COMPONENTS .....................................................................................................................24
FIG. 5 - CONTROL / POWER PANEL COMPONENTS DUAL SYSTEM UNITS .......................................25
FIG. 6 - REFRIGERANT FLOW DIAGRAM ................................................................................................31
FIG. 7 - REFRIGERANT FLOW DIAGRAM (CONT.) ..................................................................................32
FIG. 8 - CHILLER RIGGING & LIFTING WEIGHTS ...................................................................................34
FIG. 9 - VICTAULIC - ADAPTER FLANGES ..............................................................................................38
FIG. 10 - DIRECT PRESSURE CONTROL DIAGRAM ...............................................................................39
FIG. 10A - INLET TEMPERATURE CONTROL DIAGRAM ........................................................................39
FIG. 11 - CHILLED LIQUID SYSTEM .........................................................................................................40
FIG. 12 - CONDENSER COOLING LIQUID SYSTEM ................................................................................40
FIG. 13 - PIPEWORK ARRANGEMENTS LEGEND...................................................................................40
FIG. 14 - COOLER CONNECTIONS ...........................................................................................................40
FIG. 15 - CONTROL WIRING ......................................................................................................................44
FIG. 16 - EVAPORATOR WATER PRESSURE DROP CURVES (ENGLISH) ............................................47
FIG. 17 - CONDENSER WATER PRESSURE DROP CURVES (SI) ..........................................................48
FIG. 18 - GLYCOL SOLUTION STRENGTHS ............................................................................................49
FIG. 19 - SINGLE POINT POWER SUPPLY CONNECTION – STANDARD UNIT ....................................62
FIG. 20 - CONTROL CIRCUIT, 4 COMPRESSOR UNIT ............................................................................66
FIG. 21 - CONTROL CIRCUIT, 6 COMPRESSOR UNIT ............................................................................68
FIG. 22 - POWER CIRCUIT, 4 COMPRESSOR UNIT .................................................................................70
FIG. 23 - POWER CIRCUIT, 6 COMPRESSOR UNIT .................................................................................71
FIG. 24 - CONNECTION WIRING DIAGRAM, 4 COMPRESSOR UNIT .....................................................72
FIG. 25 - CONNECTION WIRING DIAGRAM, 6 COMPRESSOR UNIT .....................................................74
FIG. 26 - ELEMENTARY WIRING DIAGRAM DETAILS, 4 COMPRESSOR ..............................................76
FIG. 27 - ELEMENTARY WIRING DIAGRAM DETAILS, 6 COMPRESSOR ..............................................78
FIG. 28 - UNIT KEYS OPTIONS PROGRAMMING QUICK REFERENCE LIST ......................................126
FIG. 29 - LEAVING WATER TEMPERATURE CONTROL EXAMPLE .....................................................128
FIG. 30 - SETPOINT ADJUST...................................................................................................................128
FIG. 31 - MICROBOARD LAYOUT ...........................................................................................................138
FIG. 32 - I/O BOARD RELAY CONTACT ARCHITECTURE ...................................................................142
FIG. 33 - PRINTER TO MICROBOARD ELECTRICAL CONNECTIONS.................................................143
JOHNSON CONTROLS 11
Form 201.26-NM1 (308)
12 JOHNSON CONTROLS
Form 201.26-NM1 (308)
This manual contains all the information required for • All the scheduled maintenance operations detailed
correct installation and commissioning of the unit, in this manual must be performed at the specified
together with operating and maintenance instructions. times by suitably trained and qualified personnel.
This manual should be read thoroughly before attempting See Maintenance Section, page 143.
to operate or service the unit.
• Failure to satisfy any of these conditions will
All procedures detailed in the manuals, including automatically void the warranty.
installation, commissioning and maintenance tasks must
only be performed by suitably trained and qualified SAFETY
personnel.
Standards for Safety
The manufacturer will not be liable for any injury or YCWL chillers are designed and built within an ISO
damage caused by incorrect installation, commissioning, 9002 accredited design and manufacturing organization.
operation or maintenance resulting from a failure to Products shall be designed, tested, rated and certified
follow the procedures and instructions detailed in the in accordance with, and installed in compliance with
manuals. applicable sections of the following Standards and
Codes:
WARRANTY 1. ANSI/ASHRAE Standard 15 – Safety Code for
Johnson Controls warrants all equipment and materials Mechanical Refrigeration.
against defects in workmanship and materials for 2. ASHRAE 90.1 – Energy Efficiency Compliance.
a period of eighteen months from shipment unless 3. ANSI/NFPA – Standard 70 – National Electrical
extended warranty has been purchased as part of the Code (N.E.C.)
contract.
4. ASME Boiler & Pressure Vessel Code, Section
The warranty is limited to parts only replacement and VIII, Division 1.
shipping of any faulty part, or sub-assembly which has 5. ASHRAE 34 – Number Designation and Safety
failed due to poor quality or manufacturing errors. All Classification of Refrigerants.
claims must be supported by evidence that the failure 6. ARI Standard 550/590 – Positive Displacement
has occurred within the warranty period, and that the Compressors and Water Cooled Rotary Screw
unit has been operated within the designed parameters Water-Chilling Packages.
specified. Labor warranty may be purchased as part 7. Conform to UL code 1995 for construction of chill-
of the contract. Labor warranty must be performed by ers and provide ETL/cETL listing label.
JOHNSON technicians.
8. Manufactured in facility registered to ISO 9001.
All warranty claims must specify the unit model, serial 9. OSHA – Occupied Safety and Health Act.
number, order number and run hours/starts. These details
are printed on the unit identification plate.
JOHNSON CONTROLS 13
General Chiller Introduction & Safety
Form 201.26-NM1 (308)
Electrical
• Correct utilization of the machinery in accordance
with the procedures detailed in the manuals. The unit must be grounded. No installation or
maintenance work should be attempted on the electrical
MISUSE OF EQUIPMENT equipment without first switching power OFF, isolating
and locking-off the power supply. Servicing and
Suitability for Application
maintenance on live equipment must only be performed
The unit is intended for cooling water or glycol solutions by suitably trained and qualified personnel. No attempt
and is not suitable for purposes other than those specified should be made to gain access to the control panel or
in these instructions. Any use of the equipment other electrical enclosures during normal operation of the
than its intended use, or operation of the equipment unit.
contrary to the relevant procedures may result in injury
to the operator, or damage to the equipment. Rotating Parts
Fan guards must be fitted at all times and not removed
The unit must not be operated outside the design
unless the power supply has been isolated. If ductwork is
parameters specified in this manual.
to be fitted, requiring the wire fan guards to be removed,
alternative safety measures must be taken to protect
Structural Support
against the risk of injury from rotating fans.
Structural support of the unit must be provided as
indicated in these instructions. Failure to provide proper Sharp Edges
support may result in injury to the operator, or damage
The fins on the air-cooled condenser coils have sharp
to the equipment and/or building.
metal edges. Reasonable care should be taken when
working in contact with the coils to avoid the risk of
Mechanical Strength
minor abrasions and lacerations. The use of gloves is
The unit is not designed to withstand loads or stresses recommended.
from adjacent equipment, pipework or structures.
Additional components must not be mounted on the unit. Frame rails, brakes, and other components may also have
Any such extraneous loads may cause structural failure sharp edges. Reasonable care should be taken when
and may result in injury to the operator, or damage to working in contact with any components to avoid risk
the equipment. of minor abrasions and lacerations.
14 JOHNSON CONTROLS
Form 201.26-NM1 (308)
Emergency Shutdown
In case of emergency, the control panel is fitted
with a Unit Switch to stop the unit in an emergency.
When operated, it removes the low voltage 120
VAC electrical supply from the inverter system, thus
shutting down the unit.
JOHNSON CONTROLS 15
Form 201.26-NM1 (308)
16 JOHNSON CONTROLS
Form 201.26-NM1 (308)
3
LD12931
4 5
FIG. 1 - YCWL WATER COOLED LIQUID CHILLER
INTRODUCTION
YORK YCWL chillers are designed for water or water- dynamically balanced. A large internal volume and oil
glycol cooling. reservoir provides greater liquid tolerance. Compressor
crankcase heaters are also included for extra protection
All models are designed for indoor installation. The against liquid migration. All compressors are mounted
units are completely assembled with all interconnecting on isolator pads to reduce transmission of vibration to
refrigerant piping and internal wiring, ready for field the rest of the unit.
installation.
REFRIGERANT CIRCUITS
The unit consists of up to 6 scroll compressors in a Two independent refrigerant circuits are provided on
corresponding number of separate refrigerant circuits, a each unit, Each circuit uses copper refrigerant pipe
shell and tube DX evaporator, a water cooled condenser formed on computer controlled bending machines to
and oil separators for each circuit. reduce the number of brazed joints resulting in a pliable
and leak resistant system.
Before delivery, the unit is pressure tested, evacuated,
and fully charged with environmentally friendly Liquid line components include: a service valve with
refrigerant (R410A) and YORK “V” oil (POE synthetic) charging port, a high absorption removable core filter-
oil in each of the independent refrigerant circuits. After drier, a solenoid valve, a sight glass with moisture
assembly, an operational test is performed with water indicator and a thermal expansion valve. Liquid lines
flowing through the cooler to ensure that each refrigerant between the expansion valve and the cooler are covered
circuit operates correctly. with flexible, closed-cell insulation.
The unit framework is fabricated using heavy-gauge Suction line components include: a pressure relief valve,
galvanized steel which is zinc phosphate pre-treated and a pressure transducer and a service valve. Optional
powder coated to minimize corrosion. isolation ball valves are available. Suction lines are
covered with flexible, closed-cell insulation.
COMPRESSORS
The chiller utilizes suction-gas cooled. hermetic, scroll Discharge lines include service and isolation (ball)
compressors. The YCWL compressors incorporate valves, two high-pressure cutout switches, a pressure
a compliant scroll design in both the axial and transducer and a pressure relief valve.
radial direction. All rotating parts are statically and
JOHNSON CONTROLS 17
Product Description
Form 201.26-NM1 (308)
18 JOHNSON CONTROLS
Form 201.26-NM1 (308)
• Remote water temperature reset via a pulse width • Load & unload timer status
modulated (PWM) input signal or up to two steps • Water pump status
of demand (load) limiting.
• Software stored in non-volatile memory System Safeties
(EPROM), with programmed setpoints retained Cause individual compressors to perform auto shut down
in a lithium battery backed Real Time Clock and require manual reset in the event of three trips in a 2
(RTC) memory for a minimum of five years. 90-minute time period:
• High discharge pressure
• Forty character liquid crystal display, with de- • Low suction pressure
scription available in five languages (English,
French, German, Spanish or Italian) • High pressure switches
• Motor protector
Programmable setpoints:
• Chilled liquid temperature setpoint and range Unit Safeties
Are automatic reset and cause all compressors to shut
• Remote reset temperature range down:
• Set daily schedule/holiday for start/stop • Low leaving chilled liquid temperature
• Manual override for servicing • Under voltage
• LOW liquid temperature cutout • Loss of liquid flow (through flow switch)
• LOW suction pressure cutout • Low battery
• High discharge pressure cutout
• Anti-recycle timer (compressor start cycle Power and Control Panels
time) All power and controls are contained in an IP32 cabinet
• Anti-coincident timer (delay compressor starts) with hinged, latched and gasket sealed outer doors.
JOHNSON CONTROLS 19
Product Description
Form 201.26-NM1 (308)
20 JOHNSON CONTROLS
Form 201.26-NM1 (308)
JOHNSON CONTROLS 21
Product Description
Form 201.26-NM1 (308)
DISPLAY
UNIT
SWITCH
22 JOHNSON CONTROLS
Form 201.26-NM1 (308)
OPTIONAL
CIRCUIT CR2
BREAKER
CR1 2T
COMPRESSOR
OVERLOAD
CTB2
(Evap Pump, Alarm &
Chiller Run)
FTB
COMPRESSOR COMPRESSOR
COMPRESSOR
CONTACTOR CONTACTOR
OVERLOAD LD12921
JOHNSON CONTROLS 23
Product Description
Form 201.26-NM1 (308)
UNIT COMPONENTS
COMPRESSORS
POWER PANEL
MICRO PANEL
LD12919
CONDENSER EVAPORATOR
24 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LIQUID LINE
EVAPORATOR
SOLENOID VALVE
WATER OUTLET
LD12920
EVAPORATOR / INLET
WATER
JOHNSON CONTROLS 25
Product Description
Form 201.26-NM1 (308)
26 JOHNSON CONTROLS
Form 201.26-NM1 (308)
CONTROL TRANSFORMER
TRANS X NO OPTION
(PIN 18)
F CONTROL TRANSFORMER (FIELD)
T CONTROL TRANSFORMER (FACTORY)
Q SPECIAL QUOTE
POWER FACTOR
PFC X NO OPTION
CAPACITOR (PIN 19)
C POWER FACTOR CAPACITOR
Q SPECIAL QUOTE
PIN20 PIN 20 X NO OPTION
Q SPECIAL QUOTE
BAS BAS INTERFACE (PIN 21) X BAS/EMS TEMP RESET/OFFSET (STANDARD)
Q SPECIAL QUOTE
LCD LANGUAGE (PIN 22) X STANDARD (ENGLISH) LANGUAGE KIT
F FRENCH LCD & KEYPAD
G GERMAN LCD & KEYPAD
H HUNGARIAN LCD & KEYPAD
I ITALIAN LCD & KEYPAD
N DUTCH LCD & KEYPAD
L POLISH LCD & KEYPAD
P PORTUGUESE LCD & KEYPAD
R RUSSIAN LCD & KEYPAD
S SPANISH LCD & KEYPAD
Q SPECIAL QUOTE
JOHNSON CONTROLS 27
Product Description
Form 201.26-NM1 (308)
28 JOHNSON CONTROLS
Form 201.26-NM1 (308)
JOHNSON CONTROLS 29
Product Description
Form 201.26-NM1 (308)
30 JOHNSON CONTROLS
Form 201.26-NM1 (308)
REFRIGERANT FLOW
Low-pressure liquid refrigerant enters the evaporator tubes and is evaporated and superheated by the heat energy
absorbed from the chilled liquid passing through the evaporator shell. Low-pressure vapor enters the compressor where
pressure and superheat are increased. High-pressure vapor is passed through the condenser where heat is rejected
to the condenser water passing through the tubes. The fully condensed and subcooled liquid leaves the condenser
and enters the expansion valve, where pressure reduction and further cooling take place. The low pressure liquid
refrigerant then returns to the evaporator.
JOHNSON CONTROLS 31
Product Description
Form 201.26-NM1 (308)
38.6 bar
Control Functions: Components:
Refer to
DV - Display Value Options
CHT - Chilled Liquid Temperature Pressure Relief Valve
HPC - High Pressure Cutout
LPC - Low Pressure Cutout Service (Ball) Valve
HPL - High Pressure Load Limiting Condenser
Expansion Valve
S
Solenoid Valve
Sight Glass
Sensor Pressure
or Temperature
36.3 bar 34.7 bar 38.6 bar
Service (Stop) Access Valve
Refer to
Options PS Pressure Switch
Filter Drier
(Removable Core)
27.6 bar
Refer to
Option Options
Compressors
Evaporator
-YLLSV
LD12938
32 JOHNSON CONTROLS
Form 201.26-NM1 (308)
INSPECTION
Immediately upon receiving the unit, it should be
inspected for possible damage which may have
occurred during transit. If damage is evident, it should
be noted in the carrier’s freight bill. A written request
for inspection by the carrier’s agent should be made at
once. See “Instruction Manual”, Form 50.15-NM for
more information and details.
JOHNSON CONTROLS 33
Handling and Storage
Form 201.26-NM1 (308)
LIFTING WEIGHTS
For details of weights and weight distribution see Fig.
8.
34 JOHNSON CONTROLS
Form 201.26-NM1 (308)
SECTION 4 – INSTALLATION
To ensure warranty coverage, this The clearances recommended are
equipment must be commissioned nominal for the safe operation and
and serviced by an authorized YORK maintenance of the unit and power and
service mechanic or a qualified service control panels. Local health and safety
person experienced in chiller installa- regulations, or practical considerations
tion. Installation must comply with all for service replacement of large com-
applicable codes, particularly in regard ponents, may require larger clearances
to electrical wiring and other safety ele- than those given in Section 5.
ments such as relief valves, HP cutout
settings, design working pressures, and Units should be installed indoors where they are not
ventilation requirements consistent exposed to rain or water splash. Chillers should be
with the amount and type of refriger- located near a drain. The use of chillers in corrosive,
dusty or explosive atmospheres should be avoided unless 4
ant charge.
the unit is properly protected. A unit in a clean room
will run best, require least maintenance, and last longest.
Lethal voltages exist within the control
Heat or ventilation may be required to maintain the
panels. Before servicing, open and tag ambient between 40°F and 115°F (4 4°C and 46.1°C).
all disconnect switches.
Units are designed for indoor installation and not
INSTALLATION CHECKLIST intended for wet, corrosive or explosive atmospheres.
The following items, 1 through 5, must be checked Installation should allow for water drain, ventilation
before placing the units in operation. and sufficient clearance for service, including tube
cleaning.
1. Inspect the unit for shipping damage.
2. Rig unit using spreader bars. UNIT ISOLATION (Noise Sensitive Location)
3. Open the unit only to install water piping system. For installation in equipment rooms near noise-critical
Do not remove protective covers from water con- areas, common walls should be of adequate sound
nections until piping is ready for attachment. Check attenuating construction, all doors should be tightly
water piping to ensure cleanliness. gasketed, and the unit should have vibration isolators
fitted.
4. Pipe unit using good piping practice (see ASHRAE
handbook Section 215 and 195).
FOUNDATION
5. Check to see that the unit is installed and operated
The unit must be installed on a suitable flat and level
within limitations (refer to LIMITATIONS).
concrete base that extends to fully support the unit base
frame. The chiller foundation must be rigid to reduce
The following pages outline detailed procedures to be vibration transmission to a minimum. All upper story
followed to install and start-up the chiller. installations should use vibration isolators under the unit
base. To maintain isolator efficiency, no mechanical ties
LOCATION REQUIREMENTS should be made to the building. Properly selected flexible
connectors and piping isolators are recommended. All
To achieve optimum performance and trouble-free the above recommendations will help to reduce vibration
service, it is essential that the proposed installation transmission and ‘result in a quieter operation.
site meets with the location and space requirements for
the model being installed. For dimensions, weight and On basement foundations remove a portion of the
space requirements, including service access details, basement floor so that a concrete base can be poured
refer to Section 5. resting on the ground, with a corkboard installed on both
sides, and a waterproof sealing compound.
JOHNSON CONTROLS 35
Installation
Form 201.26-NM1 (308)
The concrete base must capable o f supporting 150% • The liquid pump(s) installed in the pipework
of the operating weight. In case of upper floors, the unit system(s) should discharged directly into the
and piping should be isolated from walls and ceiling. unit heat exchanger section of the system. The
The unit may be bolted to the foundation using 1/2” pump(s) require an auto-starter (by others) to be
(13 mm) dia. holes in the base of the framework. When wired to the control panel. For details refer to
lower transmitted vibration levels are required optional “Electrical Connection”.
anti-vibration isolators can be supplied loose for site
installation. • All chilled liquid piping should he thoroughly
flushed to free it from foreign material before
INSTALLATION OF VIBRATION ISOLATORS the system is placed into operation. Use care not
An optional set of vibration isolators can he supplied to flush any foreign material into or through the
loose with each unit (refer to Section 5 for details). cooler.
The maximum flow rate and pressure • Pipework and fittings immediately next to the heat
drop for the cooler and condenser must exchangers should he readily de-mountable to en-
not be exceeded at any time. Refer to able cleaning prior to operation, and to facilitate
Section 5 for details. visual inspection of the exchanger nozzles.
36 JOHNSON CONTROLS
Form 201.26-NM1 (308)
• Liquid systems at risk of freezing, due to low Any debris left in the water pipework
ambient temperatures, should he protected using between the strainer and heat exchang-
insulation and heater tape and/or a suitable glycol er could cause serious damage to the
solution. The liquid pump(s) must also he used tubes in the heat exchanger and must
to ensure liquid is circulated when the ambient be avoided. The installer/user must
temperature approaches freezing point. Insulation
also ensure that the quality of the wa-
should also he installed around the heat exchanger
nozzles. ter in circulation is adequate, without
any dissolved gasses which can cause
• A small valve or valves should be installed at the oxidation of steel parts within the heat
highest point or points in the chilled water piping exchanger(s).
to allow any trapped air to be purged. Vent and
drain connections should be extended beyond the The flow switch MUST NOT be used to
insulation to make them accessible. start and stop the chiller (i.e. starting
and stopping the chilled water pump).
• Piping must comply in all respects with applicable It is intended only as a safety switch.
4
local plumbing codes and ordinances. In no case It is recommended to interlock the
should the unit support the weight of connecting
auxiliary contacts of the pump contac-
piping. Since elbows, tees, and valves increase
pressure drop, all piping should be kept as simple tor in series with the flow switch. The
as possible. Hand stop valves should be installed coil of the pump contactor must have
where required to facilitate servicing. Piping to a voltage suppressor installed across
the inlet and outlet connections of the evaporator the terminals.
and condenser may include high-pressure rubber
hose or piping loops to ensure against water pump The heat exchangers must not be ex-
transmission of vibration. posed to flushing velocities or debris
released during flushing. It is recom-
• Facilities should be provided for measuring mended that a suitably sized by-pass
temperature and pressure in the evaporator and and valve arrangement be installed
condenser field water piping. Drain connections
to allow flushing of the pipework
should be provided at all low points to permit com-
plete drainage of the evaporator(s), condenser(s),
system. The by-pass can be used dur-
and system piping. This is especially important ing maintenance to isolate the heat
if the unit is located in an unheated room where exchanger without disrupting flow to
freezing could prevail. Water lines subjected to other units.
ambient temperatures below freezing may require
heater cables or antifreeze (by others). Liquid systems at risk of freezing, due
to low ambient temperatures, should be
protected using insulation and heater
tape and/or a suitable glycol solution.
The liquid pumps must also be used
to ensure liquid is circulated when
the ambient temperature approaches
freezing point. Insulation should also
be installed around the heat exchanger
nozzles.
JOHNSON CONTROLS 37
Installation
Form 201.26-NM1 (308)
Aerated, brackish or salt water is not recommended for The size of any pipework attached to a relief valve must
use in the water system(s). YORK recommends that be of sufficient diameter so as not to cause resistance to
a water treatment specialist is consulted to determine the operation of the valve. For piping size requirements
that the proposed water composition will not affect the and specifications, refer to ASHRE-15 (latest edition).
evaporator materials of carbon steel and copper. The pH
value of the water flowing through the heat exchangers If relief pipework is common to more than one valve its
must be kept between 7 and 8.5. cross sectional area must be at least the total required
by each valve. Valve types should not be mixed on a
Glycol Solutions common pipe. Precautions should be taken to ensure
that the exit of relief valves/vent pipe remain clear of
For unit operation with chilled liquid temperatures
obstructions at all times.
leaving the cooler at below 40°F (4.4°C), glycol
solutions should be used to help prevent freezing. Section
Unless otherwise specified by local regulations, the
9, gives recommended solution strength with water, as
internal diameter depends on the length of pipe required
a percentage by weight, for the most common types of
and is given by the following formula:
glycol. It is important to check glycol concentration
regularly to ensure adequate concentration and avoid
possible freeze-up in the cooler. D5 = 1.447 x L
LD06602
Direct Pressure Control (by others) Inlet Temperature Control (by others)
With liquid cooled units it is necessary to control For a cooling tower/dry cooler system, the simplest
coolant flow and/or temperature into the condenser to forms of control are to use fan cycling, fan speed control,
maintain refrigerant pressure as constant as possible to or air damper control, with the tower having a thermostat
ensure satisfactory operation of the expansion valves. in its sump. This will ensure stable condenser cooling
The refrigerant pressure can either be used to control liquid temperature sensing at design conditions and
cooling tower/dry cooler effectiveness by controlling should be adjusted to ensure a condenser cooling liquid
fans or dampers on the tower, or to control condenser entering temperature of not lower than 65°F (18°C).
flow using a three way bypass valve.
If these methods are not available, or a cooling tower
The aim is to maintain a stable discharge pressure as low is not the source of cooling water, then a three way
as possible, but at least 100 PSI above suction pressure. valve recirculation system can be used with control
This can be done at a fixed value above the highest based on condenser inlet liquid temperature. In this
expected suction pressure, or by also measuring suction case the objective is to maintain the inlet cooling liquid
pressure and using differential control. In either case temperature as low as possible, although still observing 4
condenser cooling liquid flow and temperature limits the minimum limit of 65°F (18°C).
must also be observed.
LD12941
JOHNSON CONTROLS 39
Installation
Form 201.26-NM1 (308)
PIPEWORK ARRANGEMENT
ISOLATING VALVE - NORMALLY OPEN
The following are suggested pipework arrangements for
single unit installations, for multiple unit installations, ISOLATING VALVE - NORMALLY CLOSED
each unit should be piped as shown in Fig’s 11 & 12.
STRAINER
PRESSURE TAPPING
Cooler Connections
Standard chilled and condenser cooling liquid connections
are of the Victaulic groove type.
LD06598
LD06601
40 JOHNSON CONTROLS
Form 201.26-NM1 (308)
ELECTRICAL CONNECTION The volt-free contacts are rated at 125VA. All inductive
The following connection recommendations are devices (relays) switched by the volt-free contacts
intended to ensure safe and satisfactory operation of must have their coil suppressed using standard R/C
the unit. Failure to follow these recommendations could suppressors.
cause harm to persons, or damage to the unit, and may 4
Chilled Liquid Pump (CLP) (Evaporator Pump Start
invalidate the warranty.
Contacts)
No additional controls (relays, etc.) Terminals 5 and 6 (XVFT) close to start the chilled liquid
should be mounted in the control pump. These terminals can be used as a master start/stop
panel. Power and control wiring not for the pump in conjunction with the daily start/stop
schedule. If no schedule is set, and the customer has
connected to the control panel should
master control of the pump, the terminals must be used
not be run through the control panel.
to override the customer master start/stop so that the
If these precautions are not followed it unit can start the pump in the event of a low liquid
could lead to a risk of electrocution. In temperature condition.
addition, electrical noise could cause
malfunctions or damage the unit and Common Run Signal (CRS) (System run Contacts)
its controls. Terminals 3 and 4 close to indicate that a system is
running. These terminals may be used to start the cooling
Remote Emergency Stop Device (QRRSB)
liquid pump(s) for the condenser.
A remote emergency stop device may be wired into
the unit. This device should be rated at 8 amps, 230V, System Alarm (SA) (System Alarm Contacts)
AC-15 and is protected by a maximum fuse size of 8
amps class gG. Terminals 29 and 30 (system 1) and 31 and 32 (system 2)
close to indicate an alarm condition whenever a system
The emergency stop device should be wired into locks out, or there is a power failure.
terminals 3 and 4 of the door interlocked emergency
stop device located in the common input section after FIELD WIRING
removing the link. All field wiring must comply with the National Electric
Code and all applicable local codes. YORK liquid chiller
COMMON INPUT SECTION WIRING units are factory wired for optimum reliability. Therefore
All wiring to the customer relay board (ACRB) volt the unit controls must not be modified without expressed
free contacts (XVFT) require a supply, maximum 254V, written consent by YORK. The use of a simple switch
provided by the customer. The customer must take or timer from a remote point is permitted; but it must be
particular care deriving the supplies for the volt free connected to the YORK unit panel at points expressly
terminals with regard to a common point of isolation. indicated for that purpose.
These circuits when used must be fed via the common
point of isolation so that the voltage is removed when
the common point of isolation to the unit is opened.
JOHNSON CONTROLS 41
Installation
Form 201.26-NM1 (308)
Copper power wiring only should be used for supplying Flow Switch (SF)
power to the chiller. This is recommended to avoid safety A chilled liquid flow switch of suitable type must be
and reliability issues resulting from connection failure at connected to terminals 13 and 14 to provide adequate
the power connections to the chiller. Aluminum wiring is protection against loss of liquid flow.
not recommended due to thermal characteristics that may
cause loose terminations resulting from the contraction
After connection, do not switch on
and expansion of the wiring. Aluminum oxide may
also build up at the termination causing hot spots and
mains power to the unit until it has
eventual failure. If aluminum wiring is used to supply been commissioned by YORK Au-
power to the chiller, AL-CU compression fittings should thorized personnel. Some internal
be used to transition from aluminum to copper. This components are live when mains is
transition should be done in an external box separate switched on.
to the power panel. Copper conductors can then be run
from the box to the chiller. The unit ON/OFF rocker switch on the front of the
control panel has been set in the “OFF” position at the
A 120-1-60, 15 amp source must be supplied for the factory.
control panel through a fused disconnect when a control
panel transformer (optional) is not provided (refer to This switch MUST remain in the “OFF” position
Fig. 15). until the unit is commissioned by YORK Authorized
personnel. If the switch is set to the “ON”position before
See unit wiring diagrams for field and power wiring commissioning then it must be reported to YORK,
connections, chilled water pump starter contacts, otherwise the warranty may be invalidated.
alarm contacts, compressor run status contacts, PWM
input, and load limit input. Refer to section on UNIT POWER WIRING
OPERATION for a detailed description of operation All electrical wiring should be carried out in accordance
concerning aforementioned contacts and inputs. with local regulations. Route properly sized cables to
cable entries on the bottom of the control panel. For
CONTROL PANEL WIRING wiring specifications, refer to Section 5.
All wiring to the control panel terminal block (XTBI)
(nominal 30VDC) must be run in screened cable, with In accordance with National Electric Code (N.E.C.) it
the screen earthed at the panel end only. Run screened is the responsibility of the user to install overcurrent
cable separately from mains cable to avoid electrical protection devices between the supply conductors and
noise pick-up. the power supply terminals on the unit.
The voltage free contacts connected to XTB1 must be To ensure that no eddy currents are set up in the metal
suitable for 30VDC (gold contacts recommended). If the gland plate the cables forming each 3-phase power
voltage free contacts form part of a relay or contactor, the supply must enter via the same hole in the gland plate.
coil of the device must be suppressed using a standard If separate entries for each cable forming the 3-phase
R/C suppressor. The above precautions must be taken to supplies are used, the metal gland plate must be replaced
avoid electrical noise which could cause a malfunction by a non-metallic gland plate, with due regard given to
or damage to the unit and its controls. sealing the panel to NEMA 1.
The length of cable to these terminals All sources o f supply to the unit must
must not exceed 24 ft. (7.5 m). be taken via a common point of isola-
tion (not supplied by YORK).
42 JOHNSON CONTROLS
Form 201.26-NM1 (308)
JOHNSON CONTROLS 43
Installation
Form 201.26-NM1 (308)
CONTROL WIRING
CTB1 LD07725A
CTB2 LD07730
It is possible that multiple sources of power can be supplying the unit power panel. To prevent
serious injury or death, the technician should verify that NO LETHAL VOLTAGES are
present inside the panel AFTER disconnecting power, PRIOR to working on equipment.
The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at
or below freezing temperatures, can result in damage to the evaporator and unit as a result
of the chilled liquid freezing.
44 JOHNSON CONTROLS
Form 201.26-NM1 (308)
46 JOHNSON CONTROLS
Form 201.26-NM1 (308)
TECHNICAL DATA
PRESSURE DROP CHARTS
100.0
B D F
Pressure Drop (ft H2O)
10.0
A
E
C
1.0
10 100 1000
Water Flow Rate (GPM)
5
YCWL Model Number Evap
0056SE, 0064SE, 0074SE, 0084SE A
0064HE, 0094SE B
0104SE, 0118SE C
0074HE, 0084HE, 0094HE, 0118HE, 0132SE D
0096HE, 0156SE E
0126HE, 0156HE F
1000.0
D
B
100.0
Pressure Drop (kPa)
10.0 A E
C
1.0
1.0 10.0 100.0
Water Flow Rate (l/s)
JOHNSON CONTROLS 47
Technical Data
Form 201.26-NM1 (308)
48 JOHNSON CONTROLS
Form 201.26-NM1 (308)
ETHYLENE & PROPOLYNE GLYCOL CORRECTION Pressure drop across the evaporator should only be used
FACTORS as a guide for setting up flow. When very accurate flows
Evaporator Pressure Drop need to be measured, use a flowmeter. When gauges are
used to measure pressure drop and calculate flow, always
When using evaporator pressure drop to determine
use a single gauge to measure the pressure drop at both
flow, error may result due to actual pressure drops
inlet and outlet of the evaporator to avoid introducing
that are below the published data. In all cases, the
more error into the measurement resulting from the use
published values are worst case values. Errors of 10-
of two gauges.
25% below published values are not uncommon due to
manufacturing differences. When attempting to operate
The cooler and condenser design al-
with flow near the high end of the pressure drop curve,
always use a flowmeter to avoid excessive flow through lows for an increase in pressure drop
the evaporator, which will cause damage and premature of up to 15% above the design value
failure. given. Debris in the water may also
cause additional pressure drop.
Table 6 lists glycol correction factors that should be used
in conjunction with pressure drops. Pressure drop will When using glycol solutions, pressure
increase at a given flow rate as the glycol concentration drops are higher than with water. Spe-
is increased. cial care must be taken not to exceed
the maximum allowed.
TABLE 6 – ETHYLENE & PROPOLYNE GLYCOL
CORRECTION FACTORS
5
ETHYLENE GLYCOL
ETHYLENE GLYCOL
% COMPR GPM PRESS FREEZE
TONS
WEIGHT KW F/TON DROP PT
10.0 1.0 1.0 24.3 1.0 26.2
20.0 1.0 1.0 25.1 1.1 17.9
30.0 1.0 1.0 25.9 1.2 6.7 A
40.0 1.0 1.0 26.9 1.4 -8.1
C
50.0 1.0 1.0 28.0 1.6 -28.9
PROPYLENE GLYCOL
% COMPR GPM PRESS FREEZE B
TONS
WEIGHT KW F/TON DROP PT
PROPYLENE GLYCOL
10.0 1.0 1.0 24.0 1.0 26.0
20.0 1.0 1.0 24.3 1.1 19.0
30.0 1.0 1.0 24.9 1.3 9.0
40.0 1.0 1.0 25.6 1.4 -6.0
A
50.0 0.9 1.0 26.6 1.7 -28.0
C
JOHNSON CONTROLS 49
Technical Data
Form 201.26-NM1 (308)
Nominal Unit Capacity (Tons) 52.4 59.9 67.8 76.6 85.8 92.7 108.4 129.6 140.5
Number of Independent Refriger- 2 2 2 2 2 2 2 2 2
ant Circuits
Refrigerant Charge, R-410A, Ckt 60/60 60/60 60/60 70/70 65/65 80/80 80/80 130/130 170/170
1/Ckt. 2 (lbs.)
Oil Charge, Ckt. 1/Ckt. 2, (gal.) 1.7/1.7 2.2/2.2 2.5/2.2 2.5/2.5 3.1/2.5 3.1/3.1 3.3/3.1 3.3/3.3 4.7/4.7
Shipping Weight (lbs.) 3154 3522 3700 4107 4446 4679 4625 4860 6526
Operating Weight (lbs.) 3455 3823 4001 4470 4878 5132 5078 5440 7316
Compressors, Scroll
Water Volume (gal.) 19.4 19.4 19.4 26.9 26.9 26.9 26.9 35.2 52.4
Maximum Water Side Pressure 150 150 150 150 150 150 150 150 150
(PSIG)
Maximum Refrigerant Side Pres- 560 560 560 560 560 560 560 560 560
sure (PSIG)
Dia. X Length (inches X feet) 13” X 8’ 13” X 8’ 13” X 8’ 14” X 8’ 14” X 8’ 14” X 8’ 14” X 8’ 16” X 8’ 18” X 10’
Water Nozzle Connection Size, 4 4 4 4 4 4 4 5 5
(inches)
Evaporator
Water Volume (gals.) 22.4 22.4 22.4 22.4 37.3 37.3 37.3 59.8 57.6
Maximum Water Side Pressure 150 150 150 150 150 150 150 150 150
(PSIG)
Maximum Refrigerant Side Pres- 450 450 450 450 450 450 450 450 450
sure (PSIG)
Dia. X Length (inches X feet) 11” X 8’ 11” X 8’ 11” X 8’ 11” X 8’ 13” X 8’ 14” X 8’ 14” X 8’ 16” X 8’ 15” X 10’
Water Nozzle Connection Size, 6 6 6 6 6 6 6 8 8
(inches)
50 JOHNSON CONTROLS
Form 201.26-NM1 (308)
Nominal Unit Capacity (Tons) 62.4 72.7 82.6 89.4 94.6 114.9 123.7 144.9
Number of Independent Refriger- 2 2 2 2 2 2 2 2
ant Circuits
Refrigerant Charge, R-410A, Ckt 65/65 90/90 90/90 155/155 170/170 155/155 180/180 195/195
1/Ckt. 2 (lbs.)
Oil Charge, Ckt. 1/Ckt. 2, (gal.) 2.2/2.2 2.5/2.2 2.5/2.5 3.1/2.5 3.3/3.3 3.3/3.1 3.7/3.7 4.7/4.7
Shipping Weight (lbs.) 3904 4294 4472 5019 5434 5151 6115 6760
Operating Weight (lbs.) 4336 4805 4983 5674 6224 5806 6996 7697
Compressors, Scroll
Water Volume (gal.) 26.9 26.9 26.9 44.1 52.4 44.1 52.4 59.1
Maximum Water Side Pressure 150 150 150 150 150 150 150 150
5
(PSIG)
Maximum Refrigerant Side Pres- 560 560 560 560 560 560 560 560
sure (PSIG)
Dia. X Length (inches X feet) 14” X 8’ 14” X 8’ 14” X 8’ 18” X 8’ 18” X 10’ 18” X 8’ 18” X 10’ 18” X 10’
Water Nozzle Connection Size, 4 4 4 5 5 5 5 5
(inches)
Evaporator
JOHNSON CONTROLS 51
Technical Data
Form 201.26-NM1 (308)
Shipping Weight (kg) 1431 1598 1678 1863 2017 2122 2098 2204 2960
Operating Weight (kg) 1567 1734 1815 2028 2213 2328 2303 2468 3318
Compressors, Scroll
Water Volume (liters) 73.4 73.4 73.4 101.8 101.8 101.8 101.8 133.2 198.4
Maximum Water Side Pressure 1 1 1 1 1 1 1 1 1
(MPa)
Maximum Refrigerant Side Pres- 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
sure (MPa)
Dia. X Length (mm x m) 330 x 2.4 330 x 2.4 330 x 2.4 356 x 2.4 356 x 2.4 356 x 2.4 356 x 2.4 406 x 2.4 457 x 3.0
Water Nozzle Connection Size, 101.6 101.6 101.6 101.6 101.6 101.6 101.6 127 127
(mm)
Evaporator
Water Volume (liters) 84.8 84.8 84.8 84.8 141.2 141.2 141.2 226.4 218
Maximum Water Side Pressure 1 1 1 1 1 1 1 1 1
(MPa)
Maximum Refrigerant Side Pres- 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
sure (MPa)
Dia. X Length (mm x m) 279 x 2.4 279 x 2.4 279 x 2.4 279 x 2.4 330 x 2.4 356 x 2.4 356 x 2.4 406 x 2.4 381 x 3.0
Water Nozzle Connection Size, 152.4 152.4 152.4 152.4 152.4 152.4 152.4 203.2 203.2
(mm)
52 JOHNSON CONTROLS
Form 201.26-NM1 (308)
Shipping Weight (kg) 1771 1948 2028 2277 2465 2336 2774 3066
Operating Weight (kg) 1967 2180 2260 2574 2823 2634 3173 3491
Compressors, Scroll
Water Volume (liters) 101.8 101.8 101.8 166.9 198.4 166.9 198.4 223.7
Maximum Water Side Pressure
5
1 1 1 1 1 1 1 1
(MPa)
Maximum Refrigerant Side Pres- 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
sure (MPa)
Dia. X Length (mm x m) 356 x 2.4 356 x 2.4 356 x 2.4 457 x 2.4 457 x 3.0 457 x 2.4 457 x 3.0 457 x 3.0
Water Nozzle Connection Size, 101.6 101.6 101.6 127 127 127 127 127
(mm)
Evaporator
Water Volume (liters) 141.2 226.4 226.4 226.4 218 226.4 291.5 291.5
Maximum Water Side Pressure 1 1 1 1 1 1 1 1
(MPa)
Maximum Refrigerant Side Pres- 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
sure (MPa)
Dia. X Length (mm x m) 330 x 2.4 406 x 2.4 406 x 2.4 406 x 2.4 381 x 3.0 406 x 2.4 432 x 3.0 432 x 3.0
Water Nozzle Connection Size, 152.4 203.2 203.2 203.2 203.2 203.2 203.2 203.2
(mm)
JOHNSON CONTROLS 53
Technical Data
Form 201.26-NM1 (308)
ELECTRICAL DATA
STANDARD EFFICIENCY - W/O EXTERNAL COMPRESSOR OVERLOADS
54 JOHNSON CONTROLS
Form 201.26-NM1 (308)
ELECTRICAL DATA (CONT)
SYSTEM # 1 SYSTEM # 2
RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA
51.3 300 51.3 300 51.3 300 51.3 300
51.3 300 51.3 300 51.3 300 51.3 300
26.9 139 26.9 139 26.9 139 26.9 139
23.1 150 23.1 150 23.1 150 23.1 150
19.9 109 19.9 109 19.9 109 19.9 109
55.8 425 55.8 425 55.8 425 55.8 425
55.8 425 55.8 425 55.8 425 55.8 425
36.0 239 36.0 239 36.0 239 36.0 239
26.9 187 26.9 187 26.9 187 26.9 187
23.7 148 23.7 148 23.7 148 23.7 148
73.9 505 73.9 505 55.8 425 55.8 425
73.9 505 73.9 505 55.8 425 55.8 425
38.2 290 38.2 290 36.0 239 36.0 239
30.4 225 30.4 225 26.9 187 26.9 187
24.6 180 24.6 180 23.7 148 23.7 148
73.9
73.9
505
505
73.9
73.9
505
505
73.9
73.9
505
505
73.9
73.9
505
505
5
38.2 290 38.2 290 38.2 290 38.2 290
30.4 225 30.4 225 30.4 225 30.4 225
24.6 180 24.6 180 24.6 180 24.6 180
89.1 500 89.1 500 73.9 505 73.9 505
89.1 500 89.1 500 73.9 505 73.9 505
54.5 305 54.5 305 38.2 290 38.2 290
42.9 250 42.9 250 30.4 225 30.4 225
32.1 198 32.1 198 24.6 180 24.6 180
89.1 500 89.1 500 89.1 500 89.1 500
89.1 500 89.1 500 89.1 500 89.1 500
54.5 305 54.5 305 54.5 305 54.5 305
42.9 250 42.9 250 42.9 250 42.9 250
32.1 198 32.1 198 32.1 198 32.1 198
109.6 599 109.6 599 89.1 500 89.1 500
109.6 599 109.6 599 89.1 500 89.1 500
69.2 358 69.2 358 54.5 305 54.5 305
54.5 310 54.5 310 42.9 250 42.9 250
49.4 239 49.4 239 32.1 198 32.1 198
109.6 599 109.6 599 109.6 599 109.6 599
109.6 599 109.6 599 109.6 599 109.6 599
69.2 358 69.2 358 69.2 358 69.2 358
54.5 310 54.5 310 54.5 310 54.5 310
49.4 239 49.4 239 49.4 239 49.4 239
89.1 500 89.1 500 89.1 500 89.1 500 89.1 500 89.1 500
89.1 500 89.1 500 89.1 500 89.1 500 89.1 500 89.1 500
54.5 305 54.5 305 54.5 305 54.5 305 54.5 305 54.5 305
42.9 250 42.9 250 42.9 250 42.9 250 42.9 250 42.9 250
32.1 198 32.1 198 32.1 198 32.1 198 32.1 198 32.1 198
JOHNSON CONTROLS 55
Technical Data
Form 201.26-NM1 (308)
56 JOHNSON CONTROLS
Form 201.26-NM1 (308)
SYSTEM # 1 SYSTEM # 2
RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA
55.8 425 55.8 425 55.8 425 55.8 425
55.8 425 55.8 425 55.8 425 55.8 425
36.0 239 36.0 239 36.0 239 36.0 239
26.9 187 26.9 187 26.9 187 26.9 187
23.7 148 23.7 148 23.7 148 23.7 148
73.9 505 73.9 505 55.8 425 55.8 425
73.9 505 73.9 505 55.8 425 55.8 425
38.2 290 38.2 290 36.0 239 36.0 239
30.4 225 30.4 225 26.9 187 26.9 187
24.6 180 24.6 180 23.7 148 23.7 148
73.9 505 73.9 505 73.9 505 73.9 505
73.9 505 73.9 505 73.9 505 73.9 505
38.2 290 38.2 290 38.2 290 38.2 290
30.4 225 30.4 225 30.4 225 30.4 225
24.6 180 24.6 180 24.6 180 24.6 180
89.1 500 89.1 500 73.9 505 73.9 505 5
89.1 500 89.1 500 73.9 505 73.9 505
54.5 305 54.5 305 38.2 290 38.2 290
42.9 250 42.9 250 30.4 225 30.4 225
32.1 198 32.1 198 24.6 180 24.6 180
55.8 425 55.8 425 55.8 425 55.8 425 55.8 425 55.8 425
55.8 425 55.8 425 55.8 425 55.8 425 55.8 425 55.8 425
36.0 239 36.0 239 36.0 239 36.0 239 36.0 239 36.0 239
26.9 187 26.9 187 26.9 187 26.9 187 26.9 187 26.9 187
23.7 148 23.7 148 23.7 148 23.7 148 23.7 148 23.7 148
109.6 599 109.6 599 89.1 500 89.1 500
109.6 599 109.6 599 89.1 500 89.1 500
69.2 358 69.2 358 54.5 305 54.5 305
54.5 310 54.5 310 42.9 250 42.9 250
49.4 239 49.4 239 32.1 198 32.1 198
73.9 505 73.9 505 73.9 505 73.9 505 73.9 505 73.9 505
73.9 505 73.9 505 73.9 505 73.9 505 73.9 505 73.9 505
38.2 290 38.2 290 38.2 290 38.2 290 38.2 290 38.2 290
30.4 225 30.4 225 30.4 225 30.4 225 30.4 225 30.4 225
24.6 180 24.6 180 24.6 180 24.6 180 24.6 180 24.6 180
89.1 500 89.1 500 89.1 500 89.1 500 89.1 500 89.1 500
89.1 500 89.1 500 89.1 500 89.1 500 89.1 500 89.1 500
54.5 305 54.5 305 54.5 305 54.5 305 54.5 305 54.5 305
42.9 250 42.9 250 42.9 250 42.9 250 42.9 250 42.9 250
32.1 198 32.1 198 32.1 198 32.1 198 32.1 198 32.1 198
JOHNSON CONTROLS 57
Technical Data
Form 201.26-NM1 (308)
ELECTRICAL DATA (CONT)
STANDARD EFFICIENCY W OPTIONAL EXTERNAL COMPRESSOR OVERLOADS
58 JOHNSON CONTROLS
Form 201.26-NM1 (308)
ELECTRICAL DATA (CONT)
SYSTEM # 1 SYSTEM # 2
RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA
JOHNSON CONTROLS 59
Technical Data
Form 201.26-NM1 (308)
ELECTRICAL DATA (CONT)
HIGH EFFICIENCY W OPTIONAL EXTERNAL COMPRESSOR OVERLOADS
60 JOHNSON CONTROLS
Form 201.26-NM1 (308)
ELECTRICAL DATA (CONT)
SYSTEM # 1 SYSTEM # 2
RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA
JOHNSON CONTROLS 61
Technical Data
Form 201.26-NM1 (308)
It is possible that multiple sources of power can be supplying the unit power panel. To prevent
serious injury or death, the technician should verify that NO LETHAL VOLTAGES are
present inside the panel AFTER disconnecting power, PRIOR to working on equipment.
The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at
or below freezing temperatures, can result in damage to the evaporator and unit as a result
of the chilled liquid freezing.
62 JOHNSON CONTROLS
Form 201.26-NM1 (308)
ELECTRICAL DATA
TABLE 8 – MICRO PANEL POWER SUPPLY
It is possible that multiple sources of power can be supplying the unit power panel. To pre- 5
vent serious injury or death, the technician should verify that NO LETHAL VOLTAGES are
present inside the panel AFTER disconnecting power, PRIOR to working on equipment.
The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at or
below freezing temperatures, can result in damage to the evaporator and unit as a result of
the chilled liquid freezing.
VOLTAGE RANGE
VOLTAGE CODE UNIT POWER MIN. MAX.
-17 200-3-60 180 220
-28 230-3-60 207 253
-40 380/415-3-60 342 440
-46 460-3-60 414 506
-50 380/415-3-50 342 440
-58 575-3-60 517 633
JOHNSON CONTROLS 63
Technical Data
Form 201.26-NM1 (308)
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory
Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, -46, add 1.3 amps;
-58, add 1 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included
in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not
recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at
ambient temperatures in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit, per N.E.C. Article 440-22.
5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps
for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, an
HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated
load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the
unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase
of the wire range specified. Actual wire size and number of wires per phase must be determined based on the
National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C.
Table 250-95. A control circuit grounding lug is also supplied.
8. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the
unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended
to be a Load Break Device.
9. Field Wiring by others which complies to the National Electrical Code & Local Codes.
LEGEND:
64 JOHNSON CONTROLS
Form 201.26-NM1 (308)
Instructions:
1) Start in correct power option table (switch, breaker, terminal block)
2) Match engineering guide value for Amperage
3) Match engineering guide value for wire range
4) Note corresponding ground wire range
JOHNSON CONTROLS 65
Technical Data
Form 201.26-NM1 (308)
LD12941
66 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LD12942
JOHNSON CONTROLS 67
Technical Data
Form 201.26-NM1 (308)
LD12943
68 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LD12944
JOHNSON CONTROLS 69
Technical Data
Form 201.26-NM1 (308)
LD 12925
70 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LD12932
JOHNSON CONTROLS 71
Technical Data
Form 201.26-NM1 (308)
LD12926
FIG. 24 - CONNECTION WIRING DIAGRAM, 4 COMPRESSOR UNIT
72 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LD12927
JOHNSON CONTROLS 73
Technical Data
Form 201.26-NM1 (308)
LD12933
74 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LD12934
JOHNSON CONTROLS 75
Technical Data
Form 201.26-NM1 (308)
LD12928
76 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LD12929
JOHNSON CONTROLS 77
Technical Data
Form 201.26-NM1 (308)
LD12935
78 JOHNSON CONTROLS
Form 201.26-NM1 (308)
LD12936
JOHNSON CONTROLS 79
Technical Data
Form 201.26-NM1 (308)
W -
J K
C H
F C X
O
R S
A D
Q V
B
YCWL
0056SE 0064SE 0074SE 0084SE 0094SE 0104SE 0118SE 0132SE 0064HE 0074HE 0084HE 0094HE 0118HE
(4 Comp)
W 34 5/8 34 5/8 33 13/16 33 13/16 33 13/16 33 13/16 33 13/16 33 13/16 33 13/16 33 13/16 33 13/16 33 27/32 33 27/32
H 64 15/32 64 15/32 68 29/32 68 29/32 72 9/32 71 25/32 71 25/32 74 1/2 67 19/32 74 5/8 74 19/32 76 19/32 76 1/2
L 119 5/8 119 5/8 125 15/16 125 15/16 125 15/16 124 1/8 124 1/8 123 5/16 124 3/8 123 5/16 125 11/16 121 3/4 123 5/16
A 14 1/2 14 1/2 14 1/2 14 1/2 14 1/2 14 1/2 14 1/2 14 1/2 14 1/2 14 1/2 14 1/2 15 15
B 29 29 29 29 29 29 29 29 29 29 29 30 30
C 4 1/2 4 1/2 4 1/2 4 1/2 4 1/2 4 1/2 4 1/2 5 9/16 4 1/2 4 1/2 4 1/2 5 9/16 5 9/16
D 15 17/32 15 17/32 15 17/32 15 17/32 11 25/32 15 17/32 15 17/32 16 1/32 11 25/32 16 1/32 16 1/32 16 1/32 16 1/32
E 6 5/8 6 5/8 6 5/8 6 5/8 6 5/8 6 5/8 6 5/8 8 5/8 6 5/8 8 5/8 8 5/8 8 5/8 8 5/8
F 35 15/32 35 15/32 35 15/32 35 15/32 35 15/32 38 1/2 38 1/2 40 35 15/32 40 40 42 42
G 29 29 29 29 29 29 29 29 29 29 29 29 29
J 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16 17 11/16
K 8 15/16 8 15/16 8 15/16 8 15/16 12 1/4 12 1/4 12 1/4 12 3/4 12 1/4 12 3/4 12 3/4 12 3/4 12 3/4
M 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8
N 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8 9 7/8
O 5 1/2 5 1/2 5 1/2 7 1/8 7 1/8 7 1/8 7 1/8 7 1/8 7 1/8 7 1/8 7 1/8 7 1/8 7 1/8
P 9 1/16 9 1/16 9 1/16 8 1/4 8 1/4 8 8 8 1/4 8 8 1/4 8 1/4 9 1/4 9 1/4
Q 5 1/8 5 1/8 5 1/8 5 1/8 5 1/8 5 1/8 5 1/8 5 7/32 5 1/8 5 1/8 5 1/8 5 3/16 5 3/16
R 42 1/4 42 1/4 42 1/4 42 1/4 42 1/2 42 1/2 42 1/2 41 1/2 42 1/2 41 1/2 41 1/2 41 1/2 41 1/2
S 42 1/4 42 1/4 42 1/4 42 1/4 42 1/2 42 1/2 42 1/2 41 1/2 42 1/2 41 1/2 41 1/2 41 1/2 41 1/2
T 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32
U 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32 50 29/32
V 56 7/8 56 7/8 56 7/8 56 7/8 56 7/8 56 7/8 56 7/8 57 5/16 56 7/8 56 7/8 56 7/8 57 27/32 57 27/32
X 30 3/8 30 3/8 30 3/8 30 3/8 32 32 32 33 1/4 32 33 1/4 33 1/4 35 1/4 35 1/4
AA 40 31/32 40 31/32 47 9/32 47 9/32 47 9/32 45 15/32 45 15/32 44 21/32 45 23/32 47 1/32 47 1/32 44 21/32 44 21/32
BB 50 50 50 50 50 50 50 50 50 50 50 50 50
80 JOHNSON CONTROLS
Form 201.26-NM1 (308)
L
NOTES: T
U
1. Recommended service clearances.
508mm) AA BB
915mm) M
1092mm)
mm)
either end
NPTI N
W
J K
E
G
C
F O
C P X
A
B
D
R S 5
Q V
JOHNSON CONTROLS 81
Technical Data
Form 201.26-NM1 (308)
UNIT DIMENSIONS - SI
L
T
NOTES:
1. Recommended service clearances. U AA BB (0,0)
508mm) M
915mm)
1092mm)
mm)
either end
W -
J K
C H
F C X
O
R S
A D
Q V
B
YCWL
0056SE 0064SE 0074SE 0084SE 0094SE 0104SE 0118SE 0132SE 0064HE 0074HE 0084HE 0094HE 0118HE
(4 Comp)
W 879.5 879.5 858.8 858.8 858.8 858.8 858.8 858.8 858.8 858.8 858.8 859.6 859.6
H 1637.5 1637.5 1750.2 1750.2 1835.9 1823.2 1823.2 1892.3 1716.9 1895.5 1894.7 1945.5 1943.1
L 3038.5 3038.5 3198.8 3198.8 3198.8 3152.8 3152.8 3132.1 3159.1 3132.1 3192.5 3092.5 3132.1
A 368.3 368.3 368.3 368.3 368.3 368.3 368.3 368.3 368.3 368.3 368.3 381.0 381.0
B 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 762.0 762.0
C 114.3 114.3 114.3 114.3 114.3 114.3 114.3 141.3 114.3 114.3 114.3 141.3 141.3
D 394.5 394.5 394.5 394.5 299.2 394.5 394.5 407.2 299.2 407.2 407.2 407.2 407.2
E 168.3 168.3 168.3 168.3 168.3 168.3 168.3 219.1 168.3 219.1 219.1 219.1 219.1
F 900.9 900.9 900.9 900.9 900.9 977.9 977.9 1016.0 900.9 1016.0 1016.0 1066.8 1066.8
G 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6 736.6
J 449.3 449.3 449.3 449.3 449.3 449.3 449.3 449.3 449.3 449.3 449.3 449.3 449.3
K 227.0 227.0 227.0 227.0 311.2 311.2 311.2 323.9 311.2 323.9 323.9 323.9 323.9
M 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8
N 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8 250.8
O 139.7 139.7 139.7 181.0 181.0 181.0 181.0 181.0 181.0 181.0 181.0 181.0 181.0
P 230.2 230.2 230.2 209.6 209.6 203.2 203.2 209.6 203.2 209.6 209.6 235.0 235.0
Q 130.2 130.2 130.2 130.2 130.2 130.2 130.2 132.6 130.2 130.2 130.2 131.8 131.8
R 1073.2 1073.2 1073.2 1073.2 1079.5 1079.5 1079.5 1054.1 1079.5 1054.1 1054.1 1054.1 1054.1
S 1073.2 1073.2 1073.2 1073.2 1079.5 1079.5 1079.5 1054.1 1079.5 1054.1 1054.1 1054.1 1054.1
T 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0
U 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0 1293.0
V 1444.6 1444.6 1444.6 1444.6 1444.6 1444.6 1444.6 1455.7 1444.6 1444.6 1444.6 1469.2 1469.2
X 771.5 771.5 771.5 771.5 812.8 812.8 812.8 844.6 812.8 844.6 844.6 895.4 895.4
AA 1040.6 1040.6 1200.9 1200.9 1200.9 1154.9 1154.9 1134.3 1161.3 1194.6 1194.6 1134.3 1134.3
BB 1270.0 1270.0 1270.0 1270.0 1270.0 1270.0 1270.0 1270.0 1270.0 1270.0 1270.0 1270.0 1270.0
82 JOHNSON CONTROLS
Form 201.26-NM1 (308)
L
NOTES: T
U
1. Recommended service clearances.
508mm) AA BB
915mm) M
1092mm)
mm)
either end
NPTI N
W
J K
E
G
C
F O
C P X
5
A D
B R S
Q V
JOHNSON CONTROLS 83
Technical Data
Form 201.26-NM1 (308)
84 JOHNSON CONTROLS
Form 201.26-NM1 (308)
JOHNSON CONTROLS 85
Technical Data
Form 201.26-NM1 (308)
ISOLATOR INFORMATION
ONE INCH DEFLECTION SPRING ISOLATORS CROSS-REFERENCE
Illustration shows single spring CIP-B or CIP-C mount.
SBC
HCL
MAX BOLT
DIA. - MBD
Slot Width - SW
All springs have additional
HCW
travel to solid equal to 50%
of the rated deflection.
FOR UNITS WITH ALL POINT LOADS LESS THAN 1404 LBS (637 KG)
Weight Range (lbs) Weight Range (kg) Model Number Color
239 to 384 lbs 108 to 174 kg CIP-B- Red
384 to 639 lbs 174 to 290 kg CIP-B- White
639 to 851 lbs 290 to 386 kg CIP-B- Blue
851 to 1064 lbs 386 to 483 kg CIP-B- Gray
1064 to 1404 lbs 483 to 637 kg CIP-B- Black
FOR UNITS WITH ANY POINT LOAD ABOVE 1404 LBS (637 KG)
Weight Range (lbs) Weight Range (kg) Model Number Color
Up to 851 lbs Up to 386 kg CIP-C- Black
851 to 1149 lbs 386 to 521 kg CIP-C- Yellow
1149 to 1489 lbs 521 to 675 kg CIP-C- Black
1489 to 1786 lbs 675 to 910 kg CIP-C- Yellow w/ Red
1786 to 2028 lbs 910 to 920 kg CIP-C- Yellow w/ Green
2028 to 2254 lbs 920 to 1022 kg CIP-C- Red w/ Red
2254 to 2936 lbs 1022 to 1332 kg CIP-C- Red w/ Green
86 JOHNSON CONTROLS
Form 201.26-NM1 (308)
ENGLISH
Size D H L t W BC CS MBD
ND-C 2 9/16 2 3/ 4 5 1/ 2 1/ 4 2 5/16 4 1/80 1/2- 13 x 1” 1/ 2 “
ND-D 3 3/ 8 2 3/ 4 6 1/ 4 5/16 4 5 1/2- 13 x 1” 1/ 2 “
ND-DS 4 1/ 2 4 3/ 4 7 3/ 8 1/ 4 5 1/80 6 1/80 1/2- 13 x 1” 1/ 2 “
SI
ND-C 65.1 69.9 139.7 6.4 58.7 101.9 1/2- 13 x 1” 1/ 2 “
ND-D 85.7 69.9 158.8 7.9 101.6 127 1/2- 13 x 1” 1/ 2 “
ND-DS 114.3 120.7 187.3 6.4 127.3 152.7 1/2- 13 x 1” 1/ 2 “
JOHNSON CONTROLS 87
Technical Data
Form 201.26-NM1 (308)
1. Floor or steel frame should be level and smooth. 5. Complete piping and fill equipment with water,
refrigerant, etc.
2. For pad installations, isolators do not normally
require bolting. If necessary, anchor isolators to 6. Turn leveling bolt of first isolator four full revolu-
floor through bolt holes in the base plate. tions and proceed to each mount in turn.
Isolators must be bolted to the sub- 7. Continue turning leveling bolts until the equipment
structure and the equipment must be is fully supported by all mountings and the equip-
bolted to the isolators when outdoor ment is raised free of the spacer blocks or shims.
equipment is exposed to wind forces. Remove the blocks or shims.
88 JOHNSON CONTROLS
Form 201.26-NM1 (308)
SLRS
5
HCL Adjustment
HCW L Bolt
W
ENGLISH
SIZE H t D E L HCL W HCW MBD
2-C2 8 1/2 3/8 5/8 1 3/8 14 12 1/4 5 1/4 3 1/ 2 5/8 “
SI
SIZE H t D E L HCL W HCW MBD
2-C2 215.9 9.5 15.9 34.9 355.6 311.2 133.4 88.9 5/8 “
JOHNSON CONTROLS 89
Technical Data
Form 201.26-NM1 (308)
Adjustment
Bolt
LD10568
90 JOHNSON CONTROLS
Form 201.26-NM1 (308)
SECTION 6 – COMMISSIONING
Inspection Fans
Inspect unit for installation damage. If found, take Check that all fans are free to rotate and are not 6
action and/or repair as appropriate. damaged. Ensure blades are at the same height when
rotated. Ensure fan guards are securely fixed.
Refrigerant Charge
Isolation / Protection
Packaged units are normally shipped as standard
with a full refrigerant operating charge. Check that Verify all sources of electrical supply to the unit are
refrigerant pressure is present in both systems and taken from a single point of isolation. Check that
that no leaks are apparent. If no pressure is present, a the maximum recommended fuse sizes given in the
leak test must be undertaken, the leak(s) located and Technical Data Section has not been exceeded.
repaired. Remote systems and units are supplied with
a nitrogen holding charge. These systems must be Control Panel
evacuated with a suitable vacuum pump/recovery unit Check the panel to see that it is free of foreign
as appropriate to below 500 microns. materials (wire, metal chips, etc.) and clean out if
required.
Do not liquid charge with static water in the cooler.
Care must also be taken to liquid charge slowly to Power Connections
avoid excessive thermal stress at the charging point.
Once the vacuum is broken, charge into the condenser Check that the customer power cables are connected
coils with the full operating charge as given in the correctly to the terminal blocks or optional circuit
Technical Data Section. breaker. Ensure that connections of power cables
within the panels to the circuit breaker or terminal
Service and Oil Line Valves blocks are tight.
Open each compressor suction, economizer, and Grounding
discharge service valve. If valves are of the back-seat
type, open them fully (counterclockwise) then close Verify that the unit’s protective ground terminal(s)
one turn of the stem to ensure operating pressure are properly connected to a suitable grounding point.
is fed to pressure transducers. Open the liquid line Ensure that all unit internal ground connections are
service valve and oil return line ball valve fully in tight.
each system.
JOHNSON CONTROLS 91
Commissioning
Form 201.26-NM1 (308)
Supply Voltage Flow rates and pressure drops must be within the
Verify that the site voltage supply corresponds to the limits given in the Technical Data Section. Operation
unit requirement and is within the limits given in the outside of these limits is undesirable and could cause
Technical Data Section. damage.
Flow Switch
Verify a chilled water flow switch is correctly fitted in
the customer’s piping on the cooler outlet, and wired
Switch Settings into the control panel correctly using shielded cable.
Assure the chiller ON/OFF Unit Switch at the There should be a straight run of at least 5 pipe
bottom of the keypad is OFF. Place the optional diameters on either side of the flow switch. The flow
circuit breaker handle on the panel door to ON. The switch should be connected to terminals 2 and 13 in
customer’s disconnection devices can now be set to the panel.
ON.
Temperature Sensor(s)
Verify the control panel display is illuminated. Assure
Ensure the leaving liquid temperature sensor is coated
the system switches under the SYSTEM SWITCHES
with heat conductive compound (Part No. 013-00890-
Key are in the OFF position.
000) and is inserted to the bottom of the water outlet
Compressor Heaters sensor well in the cooler. This sensor also provides
some freeze protection and must always be fully
Verify the compressor heaters are energized. If the inserted in the water outlet sensor well.
ambient temperature is above 96 °F (36 °C) the
compressor heaters must be on for at least 8 hours
before start-up to ensure all refrigerant liquid is driven
out of the compressor and the oil. If the ambient
temperature is below 86 °F (30 °C), allow 24 hours.
Water System
Verify the chilled liquid system has been installed
correctly, and has been commissioned with the correct
direction of water flow through the cooler. The inlet
should be at the refrigerant piping connection end of
the cooler. Purge air from the top of the cooler using
the plugged air vent mounted on the top of the cooler
body.
92 JOHNSON CONTROLS
Form 201.26-NM1 (308)
JOHNSON CONTROLS 93
Commissioning
Form 201.26-NM1 (308)
TABLE 10 – SETPOINTS ENTRY LIST The chilled liquid setpoint may need
OPTIONS to be temporarily lowered to ensure
Display Language all compressors cycle “on.”
Sys 1 Switch
Sys 2 Switch
Chilled Liquid
* Ambient Control
Local/Remote Mode
Control Mode
Display Units
* Lead/Lag Control This unit uses scroll compressors
* Fan Control N/A which can only operate in one direc-
Manual Override tion. Failure to observe this will lead
Current Feedback
** Soft Start
to compressor failure.
** Unit Type
** Refrigerant Type
** Expansion Valve Type
COOLING SETPOINTS 6. Turn system 1 “OFF” and system 2 “ON” (refer
Cooling Setpoint to Option 2 under “UNIT KEYS” section for more
Range
information on system switches).
EMS-PWM Max. Setpoint
PROGRAM
Discharge Pressure Cutout Place the Unit Switch in the control panel to the
Suct. Pressure Cutout “ON” position. As each compressor cycles “ON”,
Low Amb. Temp. Cutout
ensure that the discharge pressure rises and the
Leaving Liquid Temp. Cutout
Anti-Recycle Time suction pressure decreases. If this does not oc-
Fan Control On Pressure N/A cur, the compressor being tested is operating in
Fan Differential Off Pressure N/A the reverse direction and must be corrected. After
Total # of Compressors verifying proper compressor rotation, turn the
* Number of Fans/System N/A Unit Switch to “OFF”.
* Unit/Sys Voltage
Unit ID
The chilled liquid setpoint may need
* NOT ON ALL MODELS to be temporarily lowered to ensure all
** VIEWABLE ONLY
compressors cycle “ON”.
4. Put the unit into Service Mode (as described under
the Control Service and Troubleshooting section)
and cycle each condenser fan to ensure proper
rotation.
5. Prior to this step, turn system 2 “OFF” and system
1 “ON” (refer to Option 2 under “Unit Keys”
section for more information on system switches).
Connect a manifold gauge to system 1 suction and
discharge service valves.
Place the Unit Switch in the control panel to the
“ON” position. As each compressor cycles on,
ensure that the discharge pressure rises and the
suction pressure decreases. If this does not oc-
cur, the compressor being tested is operating in
the reverse direction and must be corrected. After
verifying proper compressor rotation, turn the
Unit Switch to “OFF.”
94 JOHNSON CONTROLS
Form 201.26-NM1 (308)
CHECKING SUPERHEAT AND SUBCOOLING Assure that superheat is set at a minimum of 10 °F (5.56
The subcooling temperature of each system can be °C) with a single compressor running on each circuit.
calculated by recording the temperature of the liquid
line at the outlet of the condenser and subtracting it from 2. Record the suction temperature, suction pressure,
the liquid line saturation temperature at the liquid stop suction saturation temperature, and superheat of
valve (liquid line saturation temp. is converted from a each system below:
temperature/pressure chart).
Example: SYS 1 SYS 2
Liquid line pressure = Suction Temp = _______ _______ °F
325 PSIG converted to temp. 101 °F Suction Pressure = _______ _______ PSIG
minus liquid line temp. - 86 °F
Saturation Temp = _______ _______ °F
Subcooling = 15 °F
Superheat = _______ _______ °F
The subcooling should be adjusted to 15 °F at design
LEAK CHECKING
conditions.
1. Leak check compressors, fittings, and piping to
1. Record the liquid line pressure and its correspond- ensure no leaks.
ing temperature, liquid line temperature and
subcooling below: If the unit is functioning satisfactorily during the initial
operating period, no safeties trip and the compressors
SYS 1 SYS 2 cycle to control water temperature to setpoint, the chiller
Liq Line Press = _______ _______ PSIG is ready to be placed into operation.
Saturated Temp = _______ _______ °F
Liq Line Temp = _______ _______ °F
Subcooling = _______ _______ °F
6
After the subcooling is verified, the suction superheat
should be checked. The superheat should be checked
only after steady state operation of the chiller has been
established, the leaving water temperature has been pulled
down to the required leaving water temperature, and the
unit is running in a fully loaded condition. Correct superheat
setting for a system is 10 °F – 15 °F (5.56 °C – 8.33 °C)
18” (46 cm) from the heat exchanger.
JOHNSON CONTROLS 95
Commissioning
Form 201.26-NM1 (308)
1. For the chiller system to run, the Flow Switch must 5. If demand requires, the lag system will cycle
be closed, any remote cycling contacts must be on with the same timing sequences as the lead
closed, the Daily Schedule must not be scheduling system after the lead system has run for five min-
the chiller off, and temperature demand must be utes. Refer to the section on Capacity Control for
present. a detailed explanation of system and compressor
staging.
2. When power is applied to the system, the micropro-
cessor will start a 2 minute timer. This is the same 6. As the load decreases below setpoint, the compres-
timer that prevents an instantaneous start after a sors will be shut down in sequence. This will occur
power failure. at intervals of either 60, 30, or 20 seconds based
on water temperature as compared to setpoint, and
3. At the end of the 2 minute timer, the microproces- control mode. See the section on Capacity Control
sor will check for cooling demand. If all conditions for a detailed explanation.
allow for start, a compressor on the lead system
will start and the liquid line solenoid will open. 7 When the last compressor in a “system” (two or
Coincident with the start, the anti-coincident timer three compressors per system), is to be cycled
will be set and begin counting downward from “60” off, the system will initiate a pump-down. Each
seconds to “0” seconds. “system” has a pump-down feature upon shut-off.
On a non-Safety, non-Unit Switch shutdown, the
If the unit is programmed for Auto Lead/Lag, the LLSV will be turned off and the last compressor
system with the shortest average run-time of the will be allowed to run until the suction pressure
compressors will be assigned as the “lead” system. falls below the suction pressure cutout or for 180
A new lead/lag assignment is made whenever all seconds, whichever comes first.
systems shut down.
96 JOHNSON CONTROLS
Form 201.26-NM1 (308)
00065VIP
The YORK MicroComputer Control Center is a The IPU and I/O boards are assembled to function as a
microprocessor based control system designed to provide single microprocessor controller requiring no additional
the entire control for the liquid chiller. The control logic hardware. The IPU II board contains a coldfire
embedded in the microprocessor based control system microprocessor and is the controller and decision
will provide control for the chilled liquid temperatures, maker in the control panel. The I/O board handles all
as well as sequencing, system safeties, displaying status, of the chiller I/O (Inputs and Outputs). System inputs
and daily schedules. The MicroComputer Control Center from pressure transducers and temperature sensors are
consists of four basic components, 1) IPU II & I/O connected to the I/O board. The I/O board contains a
Boards, 2) transformer, 3) display and 4) keypad. The processor capable of reading the inputs and controlling
keypad allows programming and accessing setpoints, the outputs. It communicates through the transition
pressures, temperatures, cutouts, daily schedule, options, header with the IPU II microprocessor. 7
and fault information.
The I/O board circuitry multiplexes the analog inputs,
Remote cycling, demand limiting and chilled liquid digitizes them, and constantly scans them to keep watch
temperature reset can be accomplished by field supplied on the chiller operating conditions. The input values are
contacts. transmitted serially to the IPU II microprocessor board.
From this information, the IPU II then issues commands
Compressor starting/stopping and loading/unloading to the I/O board relay outputs to control contactors,
decisions are performed by the microprocessor to solenoids, etc. for Chilled Liquid Temperature Control
maintain leaving or return chilled liquid temperature. and to react to safety conditions. The I/O board
These decisions are a function of temperature deviation converts logic signals to operate relay outputs to 115
from setpoint. VAC levels used by motor contactors, fan contactors,
solenoid valves, etc. to control system operation. The
A Master ON/OFF switch is available to activate or low voltage side of all relay coils on the I/O board are
deactivate the unit. powered by +12V.
JOHNSON CONTROLS 97
Unit Controls
Form 201.26-NM1 (308)
and linear voltage regulators located on the I/O and IPU Display Messages may show characters indicating
II boards. These voltages are used to operate integrated “greater than” (>) or “less than” (<). These characters
circuitry on the board. The 40 Character Display and indicate the actual values are greater than or less than
unit sensors (transducers and temp sensors) are supplied the limit values which are being displayed.
power for the micro board +5V supply. 24V AC is
rectified, but not regulated, to provide unregulated +30 Keypad
VDC to supply all of the digital inputs. The 12 button non-tactile keypad allows the user
to retrieve vitals system parameters such as system
The IPU II board contains one green “Power” LED
pressures, temperatures, compressor running times
to indicate that the board is powered up and one red
and starts, option information on the chiller, and
“Status” LED to indicate by blinking that the processor
system setpoints. This data is useful for monitoring
is operating.
chiller operation, diagnosing potential problems,
troubleshooting, and commissioning the chiller.
The I/O board contains one green “Power” LED to
indicate that the board is powered up and one red
It is essential the user become familiar with the use of the
“Status” LED to indicate by blinking that the processor
keypad and display. This will allow the user to make full
is operating. The I/O board also contains two sets of
use of the capabilities and diagnostic features available.
Receiver/Transmit LED’s, one for each available serial
communication port. The receive LED’s are green, and
Battery Back-up
the Transmit LED’s are red.
The IPU II contains a Real Time Clock integrated circuit
A jumper on the I/O board selects 4-20mA or 0-10 chip with an internal battery backup. The purpose of
VDC as the input type on the remote temperature reset this battery backup is to assure any programmed values
analog input. (setpoints, clock, cutouts, etc.) are not lost during a
power failure regardless of the time involved in a power
cut or shutdown period.
Unit switch
A unit ON/OFF switch is just underneath the keypad. Transformer
This switch allows the operator to turn the entire unit A 75 VA, 120/24VAC 50/60Hz transformer is provided
“OFF” if desired. The switch must be placed in the “ON” to supply power to the Microprocessor Board, which in
position for the chiller to operate. turn rectifies, filters, and regulates as necessary to supply
power to the display, sensors, and transducers.
Display
The 40 Character Display (2 lines of 20 characters) Single System Select and Programming
# of Compressors
is a liquid crystal display used for displaying system
parameters and operator messages. The control software is common between single (1) and
dual (2) system units. A jumper is installed between
The display in conjunction with the keypad, allows the terminals 13 and 17 on the user terminal block to
operator to display system operating parameters as well configure a unit for a single system. Dual (2) system
as access programmed information already in memory. chillers do not have a jumper installed. The jumper is
The display has a lighted background for night viewing only checked by the micro on powerup.
and for viewing in direct sunlight.
The total number of compressors is programmable under
When a key is pressed, such as the OPER DATA key, the Program Key. Dual (2) system chillers can have 4,
system parameters will be displayed and will remain 5, or 6 compressors.
on the display until another key is pressed. The system
parameters can be scrolled with the use of the ↑ (UP)
and ↓ (DOWN) arrow keys. The display will update all
information at a rate of about 1 a second.
98 JOHNSON CONTROLS
Form 201.26-NM1 (308)
“STATUS” KEY
00066VIP
R E MO T E C O N T R O L L E D
Unit Status S H U T D OWN
Pressing the STATUS key will enable the operator to
determine current chiller operating status. The messages The REMOTE CONTROLLED SHUTDOWN message
displayed will include running status, cooling demand, indicates that either an ISN system or RCC has turned
fault status, external cycling device status. The display the unit “OFF”, not allowing it to run.
will be a single message relating to the highest priority
message as determined by the micro. Status messages D A I L Y S C H E D U L E
fall into the categories of General Status and Fault S H U T D OWN
Status.
The following General, Safety, and Warning messages The DAILY SCHEDULE SHUTDOWN message
are displayed when the STATUS key is pressed. indicates that the daily/holiday schedule programmed
Following each displayed message is an explanation is keeping the unit from running.
pertaining to that particular message. REMOTE STOP 7
NO RUN PERM
General Status Messages
In the case of messages which apply to individual REMOTE STOP NO RUN PERM shows that either
systems, SYS 1 and SYS 2 messages will both be the flow switch is open or a remote start/stop contact is
displayed and may be different. In the case of single open in series with the flow switch. These contacts are
system units, all SYS 2 messages will be blank. connected to J13-5. A 3-second delay is built into the
software to prevent nuisance shutdowns due to erroneous
U N I T SW I T C H O F F signals on the run permissive input.
S H U T D OWN
S Y S 1 S Y S SW I T C H O F F
This message informs the operator that the UNIT switch S Y S 2 S Y S SW I T C H O F F
on the control panel is in the OFF position which will
not allow the unit to run. SYS SWITCH OFF tells that the system switch under
OPTIONS is turned “OFF”. The system will not be
allowed to run until the switch is turned back on.
JOHNSON CONTROLS 99
Unit Controls
Form 201.26-NM1 (308)
S Y S 1 S U C T L I M I T I N G
The COMPS RUNNING message indicates that the S Y S 2 S U C T L I M I T I N G
respective system is running due to demand. The “X”
will be replaced with the number of compressors in that When this message appears, suction pressure limiting is
system that are running. in effect. The suction pressure limit is a control point that
limits the loading of a system when the suction pressure
S Y S 1 A R T I M E R X X S drops to within 15% above the suction pressure cutout.
S Y S 2 A R T I M E R X X S On a standard system programmed for 44 PSIG/3.0 Bar
suction pressure cutout, the micro would inhibit loading
The anti-recycle timer message shows the amount of of the affected system with the suction pressure less than
time left on the respective systems anti-recycle timer. or equal to 1.15 * 44 PSIG/3.0 Bar = 50 PSIG/3.5 Bar.
This message is displayed when the system is unable to The system will be allowed to load after 60 seconds
start due the anti-recycle timer being active. and after the suction pressure rises above the suction
pressure load limit point.
S Y S 1 A C T I M E R X X S
S Y S 2 A C T I M E R X X S S Y S 1 L O A D L I M I T X X %
S Y S 2 L O A D L I M I T X X %
The anti-coincidence timer is a software feature that
guards against 2 systems starting simultaneously. This This message indicates that load limiting is in effect and
assures instantaneous starting current does not become the percentage of the limiting in effect. This limiting
excessively high due to simultaneous starts. The micro could be due to the load limit/pwm input, ISN or RCC
limits the time between compressor starts to 1 minute controller sending a load limit command.
regardless of demand or the anti-recycle timer being
timed out. The anti-coincidence timer is only present M A N U A L
on two system units. O V E R R I D E
S Y S 1 P U M P I N G D OWN S Y S 1 L OW S U C T P R E S S
S Y S 2 P U M P I N G D OWN S Y S 2 L OW S U C T P R E S S
The PUMPING DOWN message indicates that a The Suction Pressure Cutout is a software cutout that
compressor in the respective system is presently in the helps protect the chiller from an evaporator freeze-up
process of pumping the system down. When pumpdown should the system attempt to run with a low refrigerant
is initiated on shutdown, the liquid line solenoid or EEV charge or a restriction in the refrigerant circuit.
will close and a compressor will continue to run. When
the suction pressure decreases to the suction pressure Repeated starts after resetting a low
cutout setpoint or runs for 180 seconds, whichever suction pressure fault will cause evapo-
comes first, the compressor will cycle off. rator freeze-up. Whenever a system
locks out on this safety or any safety,
Fault Safety Status Messages
immediate steps should be taken to
Safety Status messages appear when safety thresholds identify the cause.
in the unit have been exceeded. Safeties are divided
into two categories – system safeties and unit safeties. At system start, the cutout is set to 10% of programmed
System safeties are faults that cause the individual value. During the next 3 minutes the cutout point is
system to be shut down. Unit safeties are faults that cause ramped up to the programmed cutout point. If at any time
all running compressors to be shut down. Following are during this 3 minutes the suction pressure falls below the
display messages and explanations. ramped cutout point, the system will stop. This cutout is
completely ignored for the first 30 seconds of system run
System Safeties time to avoid nuisance shutdowns, especially on units
System safeties are faults that cause individual systems that utilize a low pressure switch in place of the suction
to be shut down if a safety threshold is exceeded for 3 pressure transducer.
seconds. They are auto reset faults in that the system
will be allowed to restart automatically after the fault After the first 3 minutes, if the suction pressure falls
condition is no longer present. However, if 3 faults on below the programmed cutout setting, a “transient
the same system occur within 90 minutes, that system protection routine” is activated. This sets the cutout at
will be locked out on the last fault. This condition is then 10% of the programmed value and ramps up the cutout
7
a manual reset. The system switch (under OPTIONS over the next 30 seconds. If at any time during this 30
key) must be turned off and then back on to clear the seconds the suction pressure falls below the ramped
lockout fault. Fault messages will be displayed whenever cutout, the system will stop.
a system is locked out.
S Y S 1 M P / H P C O F A U L T
S Y S 1 H I G H D S C H P R E S S Y S 2 M P / H P C O F A U L T
S Y S 2 H I G H D S C H P R E S
The internal motor protector opens at 185 °F – 248 °F During the 30 minute timeout, the MP/HPCO INHIB
(85 °C – 120 °C) and auto resets. On 60 Hz chillers, the message will be displayed. The MP/HPCO FAULT
mechanical HP switch opens at 500 PSIG ±8 PSIG and will only be displayed after 3 shutdowns in 90 minutes,
automatically closes at 375 PSIG ±10 PSIG. indicating the system is locked out and will not
restart.
On 50Hz chillers, the manual reset HP switch opens at
503 PSIG (34.7 barg). On systems with a second tool S Y S 1 H I G H M T R C U R R
reset cutout, the tool reset HP switch opens at 532 PSIG S Y S 2 H I G H M T R C U R R
(36.7 barg).
When the SYSTEM CURRENT FEEDBACK option is
The compressor is also equipped with a discharge installed and selected (Option 11 under OPTIONS Key
temperature sensor for the purpose of sensing internal Current Feedback), this safety will operate as follows.
scroll temperature. This sensor protects the scrolls If the actual feedback voltage of the system proportional
from overheating due to inadequate cooling that may to currents exceeds the programmed trip voltage for 5
occur when refrigerant charge is low, or superheat is seconds, the system will shutdown.
too high.
This safety will shut down a system if either suction
When the sensor senses a high temperature, it opens the temperature or suction pressure sensors read out of
motor protector circuit in the compressor causing the range high or low. This condition must be present for 3
compressor to shut down. seconds to cause a system shutdown. The safety locks
out a system after the first fault and will not allow
During the first two faults an MP/HP INHIBIT message automatic restarting.
will be displayed and the system will not be locked
out. Only after the third fault in 90 minutes will the
MP/HPCO FAULT message be displayed.
Unit Safeties U N I T F A U L T :
Unit safeties are faults that cause all running compressors H I G H M T R C U R R
to be shut down. Unit faults are auto reset faults in that
the unit will be allowed to restart automatically after the When the CURRENT FEEDBACK ONE PER UNIT
fault condition is no longer present. option is selected under the OPTIONS Key, the unit will
U N I T F A U L T :
shut down when the voltage exceeds the programmed
L OW A M B I E N T T E M P
trip voltage for 5 seconds.
I N C O R R E C T
U N I T T Y P E
System X
No Cooling load System X HIGH MTR CURR
(Optional) Incorrect Unit Type
System X Comps Run (Unit Warning Message)
System X AR Timer
LD11297A
Manual Overide Status
DISPLAY/PRINT KEYS
00067VIP
The DISPLAY/PRINT keys allow the user to retrieve With the “UNIT TYPE” set as a liquid chiller (no jumper
system and unit information that is useful for monitoring to J11-12), the following list of operating data screens
chiller operation, diagnosing potential problems, are viewable under the OPER DATA key in the order that
troubleshooting, and commissioning the chiller. they are displayed. The ↓ (DOWN) arrow key scrolls
through the displays in the order they appear below:
System and unit information, unit options, setpoints,
and scheduling can also be printed out with the use of The chiller MUST be set to be a liquid
a printer. Both real-time and history information are
7
chiller (no jumper to J11-12). DO
available. NOT operate the chiller if not properly
set up.
Oper Data Key
The OPER DATA key gives the user access to unit and
system operating parameters. When the OPER DATA
key is pressed, system parameters will be displayed and
L C H L T = 4 6 . 2 ° F
remain on the display until another key is pressed. After
R C H L T = 5 7 . 4 ° F °
pressing the OPER DATA key, the various operating data
screens can be scrolled through by using the ↑ (UP) and This display shows chilled leaving and return liquid
↓ (DOWN) arrow keys or the ENTER/ADV key located temperatures. The minimum limit on the display for
under the “ENTRY” section. these parameters are 2.2 °F (-19 °C). The maximum
limit on the display is 140 °F (60 °C).
System 2 information will only be dis-
played for 2 system units. A M B I E N T A I R T E M P
= 8 7 . 5 ° F
S Y S X S P = 7 2 . 1 P S I G C O O L I N G D E M A N D
D P = 2 2 7 . 0 P S I G 2 O F 8 S T E P S
These displays show suction and discharge pressures The display of COOLING DEMAND indicates the
for each system. The discharge pressure transducer is current “step” in the capacity control scheme when in
optional on some models. Return Water Control Mode. The number of available
steps are determined by how many compressors are in
If the optional discharge transducer is not installed, the the unit. In the above display, the “2” does not mean
discharge pressure would display 0 PSIG (0 barg). that two compressor are running but only indicates that
the capacity control scheme is on step 2 of 8. Capacity
The minimum limits for the display are: Control is covered in more detail in this publication
Suction Pressure: 0 PSIG (0 barg) which provides specific information on compressor
Discharge Pressure: 0 PSIG (0 barg)
staging (for Return Water Control only).
The maximum limits for the display are:
Suction Pressure: 400 PSIG (27.58 barg) T E M P E R R O R X X X . X ° F
Discharge Pressure: 650 PSIG (44.82 barg) T E M P R A T E X X X . X ° F / M
SY S X H O U R S 1 = X X X X X
2 = X X X X X, 3 = X X X X X The COOLING DEMAND message will be replaced
with this message when Leaving Chilled liquid control
S Y S X S T A R T S 1 = X X X X X is selected. This message indicates the temperature
2 = X X X X X, 3 = X X X X X error and the rate of change of the chilled liquid
temperature.
The above two messages will appear sequentially for
L E A D S Y S T E M I S
each system. The first display shows accumulated
S Y S T E M N U M B E R 2
running hours of each compressor for the specific
system. The second message shows the number of starts
for each compressor on each system. This display indicates the current LEAD system. In this
example system 2 is the LEAD system, making system
Run times and starts will only be dis- 1 the LAG system. The LEAD system can be manually
selected or automatic. Refer to the programming under
played for the actual number of sys-
the “OPTIONS” key. The Lead System display will only
tems and compressors on the unit.
appear on a two system unit.
E V A P O R A T O R H E A T E R * R e f e r t o t h e s e c t i o n o n O P E R AT I N G
S T A T U S I S = X X X CONTROLS.
E V A P O R A T O R WA T E R
If the micro is programmed for CURRENT FEEDBACK
P U M P S T A T U S = X X XX
NONE, no current display will appear.
S Y S X C OM P S T A T U S
The evaporator pump dry contacts are energized when
1 = X X X 2 = X X X 3 = X X X
any compressor is running, or the unit is not OFF on the
Daily Schedule and the UNIT switch is on, or the unit
has shutdown on a Low Leaving Chilled Liquid fault. S Y S X R U N T I M E
However, even if one of above is true, the pump will not X X - X X - X X - X X D - H - M - S
run if the micro panel has been powered up for less than
30 seconds or if the pump has run in the last 30 seconds S Y S X L L S V I S O N
to prevent pump motor overheating. H O T G A S S O L I S O F F
E V A P P U M P T O T A L R U N
H O U R S = X X X X X S Y S X F A N S T A G E 3
There are several types of remote systems that can The second message indicates the system run time in
be used to control or monitor the unit. The following days – hours – minutes – seconds. Please note that this
messages indicate the type of remote control mode is not accumulated run time but pertains only to the
active: current system cycle.
NONE – no remote control active. Remote monitoring The third message indicates the system, and whether the
may be via ISN. liquid line solenoid or EEV pilot solenoid and hot gas
solenoid are being turned on by the microboard. Please
note that hot gas is not available for system 2, so there
ISN – YORK Talk via ISN allows remote load limiting
is no message pertaining to the hot gas solenoid when
and temperature reset through an ISN system.
system 2 message is displayed.
LOAD LIM – Load limiting enabled using contact The fourth message indicates the stage of condenser fan
closure. operation that is active. This message does not apply to
a YCWL chiller and is displayed as a result of the use of
PWM TEMP – EMS temperature reset software common to both YCA and YCW chillers.
See the section on Condenser Fan Control in the UNIT TABLE 12 – OPERATION DATA
OPERATION section for more information.
Oper Data Key
The fifth message displays current as sensed by the
optional current feedback circuitry. The display reads
out in amps along with the DC feedback voltage from Leaving & Chilled Liquid Temps
the module. Current is calculated by:
Ambient Air Temperature
225A • Actual Volts
5 Volts System 1 Discharge & Suction Pressure
Individual displays will be present for each system, if *System X Accumulated Hours
CURRENT FEEDBACK ONE PER SYSTEM is pro-
grammed under the OPTIONS Key. Combined compres- *System X Accumulated Starts
sor current for each system is displayed.
Load and Unload Timers
Oper Data Quick Reference List
Cooling Demand Steps
The following table is a quick reference list for (Return Chilled Liquid Control Only)
information available under the OPER DATA key.
Temp Rate & Temp Error
(Leaving Chilled Liquid Control Only)
Print Key
The PRINT key allows the operator to obtain a printout UNIT DATA
RETURN LIQUID TEMP 58.2 DEGF
of real-time system operating data or a history printout LEAVING LIQUID TEMP 53.0 DEGF
of system data at the “instant of the fault” on the last six DISCHARGE AIR TEMP 55.3 DEGF
faults which occurred on the unit. An optional printer is COOLING RANGE 42.0 +/- 2.0 DEGF
HEATING RANGE 122.0 +/- 2.0 DEGF
required for the printout. SYS 1 SETPOINT 70 +/- 3 PSIG
SYS 2 SETPOINT 70 +/- 3 PSIG
Operating Data Printout REMOTE SETPOINT 44.0 DEGF
AMBIENT AIR TEMP 74.8 DEGF
Pressing the PRINT key and then OPER DATA key LEAD SYSTEM SYS 2
allows the operator to obtain a printout of current system EVAPORATOR PUMP ON
EVAPORATOR HEATER OFF
operating parameters. When the OPER DATA key is ACTIVE REMOTE CONTROL NONE
pressed, a snapshot will be taken of system operating LAST DEFROST SYS X DURATION XXXS
conditions and panel programming selections. This data TIME TO SYS X DEFROST XX MIN
BIVALENT DELAY REMAINING XX MIN
will be temporarily stored in memory and transmission UNIT XXX.X AMPS X.X VOLTS
of this data will begin to the printer. A sample Operating SOFTWARE VERSION C.M02.13.00
Data printout is shown below. (Note: Not all values are
SYSTEM 1 DATA
printed for all models. Not all data applies to a YCWL COMP STATUS 1=OFF 2=OFF 3=OFF
chiller.) RUN TIME 0- 0- 0- 0 D-H-M-S
TIME YYYYYYY 0- 0- 0- 0 D-H-M-S
LAST STATE YYYYYYY
YORK INTERNATIONAL CORPORATION SUCTION PRESSURE 105 PSIG
MILLENNIUM LIQUID CHILLER DISCHARGE PRESSURE 315 PSIG
SUCTION TEMPERATURE 46.0 DEGF
UNIT STATUS SAT SUCTION TEMP 34.0 DEGF
2:04PM 01 OCT 07 SUCTION SUPERHEAT 12.0 DEGF
COOLER INLET REFRIG 31.6 DEGF
SYS 1 NO COOLING LOAD DEFROST TEMPERATURE 52.8 DEGF
SYS 2 COMPRESSORS RUNNING 2 LIQUID LINE SOLENOID OFF
MODE SOLENOID OFF
OPTIONS HOT GAS BYPASS VALVE OFF
CHILLED LIQUID WATER CONDENSER FAN STAGE OFF
AMBIENT CONTROL STANDARD EEV OUTPUT 0.0 %
LOCAL/REMOTE MODE
CONTROL MODE
REMOTE
LEAVING LIQUID
SYSTEM XXX.X AMPS X.X VOLTS 7
LEAD/LAG CONTROL AUTOMATIC SYSTEM 2 DATA
FAN CONTROL AMB & DSCH PRESS COMP STATUS 1=ON, 2=OFF, 3=ON
CURRENT FEEDBACK NONE RUN TIME 0-0-1-46 D-H-M-S
POWER FAILURE RESTART AUTOMATIC TIME YYYYYYY 0-0-0-0 D-H-M-S
SOFT START ENABLED LAST STATE YYYYYYY
EXPANSION VALVE THERMOSTATIC SUCTION PRESSURE 110 PSIG
REMOTE TEMP RESET 4 TO 20 MA DISCHARGE PRESSURE 320 PSIG
SUCTION TEMPERATURE 49.3 DEGF
PROGRAM VALUES SAT SUCTION TEMP 36.0 DEGF
DSCH PRESS CUTOUT 570 PSIG SUCTION SUPERHEAT 13.3 DEGF
SUCT PRESS CUTOUT 80 PSIG COOLER INLET REFRIG 31.6 DEGF
SUCT PRESS CUT COOLING 42 PSIG DEFROST TEMPERATURE 52.8 DEGF
SUCT PRESS CUT HEATING 31 PSIG LIQUID LINE SOLENOID ON
LOW AMBIENT CUTOUT 25.0 DEGF MODE SOLENOID ON
LEAVING LIQUID CUTOUT 25.0 DEGF CONDENSER FAN STAGE 3
ANTI RECYCLE TIME 600 SECS EEV OUTPUT 63.2%
FAN CONTROL ON PRESS 425 PSIG SYSTEM XXX.X AMPS X.X VOLTS
FAN DIFF OFF PRESS 125 PSIG
NUMBER OF COMPRESSORS 6 DAILY SCHEDULE
NUMBER OF FANS PER SYSTEM 4 S M T W T F S *=HOLIDAY
UNIT TRIP VOLTS 3.0 SUN START=00:00AM STOP=00:00AM
REFRIGERANT TYPE R-22 MON START=00:00AM STOP=00:00AM
DEFROST INIT TEMP 41.0 DEGF TUE START=00:00AM STOP=00:00AM
DEFROST INITIATION TIME 60MIN WED START=00:00AM STOP=00:00AM
DEFROST TERMINATION TIME 3MIN THU START=00:00AM STOP=00:00AM
BIVALENT HEAT DELAY TIME 30 MIN FRI START=00:00AM STOP=00:00AM
REMOTE UNIT ID PROGRAMMED 2 SAT START=00:00AM STOP=00:00AM
YORK HYDRO KIT PUMPS 1 (410a) HOL START=00:00AM STOP=00:00AM
PUMP TOTAL RUN HOURS XXXXX (410a)
History Printout D I S P L A Y S A F E T Y S H U T-
D OWN N O . 1 ( 1 TO 9 )
Pressing the PRINT key and then the HISTORY key
allows the operator to obtain a printout of information
relating to the last 9 Safety Shutdowns which occurred. While this message is displayed, the ↑ (UP) arrow key can be
The information is stored at the instant of the fault, used to select any of the six history buffers. Buffer number
regardless of whether the fault caused a lockout to 1 is the most recent, and buffer number 6 is the oldest Safety
occur. The information is also not affected by power Shutdown that was saved.
failures (long-term internal memory battery backup
is built into the circuit board) or manual resetting of a After selecting the shutdown number, pressing the ENTER
fault lock-out. key displays the following message which shows when the
shutdown occurred.
When the HISTORY key is pressed, a printout is S H U T D OWN O C C U R R E D
transmitted of all system operating conditions which 0 3 : 5 6 P M 2 9 J A N 0 2
were stored at the “instant the fault occurred” for each of
the 9 Safety Shutdowns buffers. The printout will begin
with the most recent fault which occurred. The most The ↑ (UP) and ↓ (DOWN) arrow keys are used to scroll
recent fault will always be stored as Safety Shutdown forward and backward through the history buffer to
No. 1. identically formatted fault information will then display the shutdown conditions stored at the instant the
be printed for the remaining Safety Shutdowns. fault occurred. The ↓ (DOWN) arrow key scrolls through
the displays in the order they appear below:
Information contained in the Safety Shutdown buffers is
very important when attempting to troubleshoot a system U N I T F A U L T :
problem. This data reflects the system conditions at the L OW L I Q U I D T E M P
instant the fault occurred and often reveals other system
conditions which actually caused the safety threshold
to be exceeded. Displays the type of fault that occurred.
A M B I E N T C O N T R O L L OW A M B I E N T T E M P
X X X X X X X X X X C U T O U T = X X X . X ° F
Displays the type of Ambient Control; Standard or Low Displays the programmed Low Ambient Cutout.
Ambient.
L E A V I N G L I Q U I D T E M P
C U T O U T = X X X . X ° F
L O C A L / RE MO T E MO D E
X X X X X X X X X
Displays the Leaving Liquid Temp. Cutout
programmed.
Displays Local or Remote control selection.
F A N C O N T R O L O N
C O N T R O L MO D E P R E S S U R E = X X X P S I G
L E A V I N G L I Q U I D
Displays the programmed Fan On Pressure.
Displays the type of chilled liquid control; Leaving or
Return. F A N D I F F E R E N T I A L OFF
P R E S S U R E = PS I G
L E A D / L A G C O N T R O L
X X X X X X X X This message does not apply to a YCWL chiller.
Y O R K H Y D R O
M A N U A L O V E R R I D E MO D E
X X X X X X X X X
K I T P U M P S = X 7
Displays whether Manual Override was Enabled or Indicates the Pump Control option is selected.
Disabled.
L C H L T = X X X . X ° F
C U R R E N T F E E D B A C K R C H L T = X X X . X ° F
X X X X X X X X X X X X X X X X
Displays the Leaving and Return chilled Liquid
Displays type of Current Feedback utilized. Temperature at the time of the fault.
S O F T S T A R T S E T P O I N T = X X X . X ° F
X X X X X X X R A N G E = + / - ° F
Displays whether the optional European Soft Start was Displays the programmed Setpoint and Range, if
installed and selected. the chiller is programmed for leaving chilled liquid
control.
D I S C H A R G E P R E S S U R E
C U T O U T = X X X X P S I G S E T P O I N T = X X X . X ° F
R A N G E = + X X . X ° F
Displays the programmed Discharge Pressure Cutout.
Displays the programmed Setpoint and Range, if the
S U C T I O N P R E S S U R E chiller is programmed for return chilled liquid control.
C U T O U T = X X X X P S I G
A M B I E N T A I R T E M P
= X X X . X ° F
Displays the programmed Suction Pressure Cutout.
Displays the Ambient Temp. at the time of the fault.
JOHNSON CONTROLS 111
Unit Controls
Form 201.26-NM1 (308)
E V A P O R A T O R WA T E R
P U M P S T A T U S X X X X This message does not apply to a YCWL chiller.
S Y S X S P = X X X X P S I G D I S P L A Y S A F E T Y S H U T -
D P = X X X X P S I G D OWN N O . 1 ( 1 T O 6 )
Displays the system Suction and Discharge Pressure of After the ↓ (DOWN) arrow key is pressed again, the
the time of the fault. software version will appear.
S Y S X S U C T = X X X . X ° F
C O N T R O L C. M X X. Z Z. Y Y
S A T S U C T = X X X . X ° F
I / O C. M X X. 1 8. Y Y
“ENTRY” KEYS
00068VIP 7
The ENTRY Keys allows the user to view, change Enter/adv Key
programmed values. The ENTRY keys consist of an ↑ (UP)
The ENTER/ADV key must be pushed after any change
arrow key, ↓ (DOWN) arrow key, and an ENTER/ADV
is made to the cooling setpoints, daily schedule, safety
key.
setpoints, chiller options, and the clock. Pressing this key
“enters” the new values into memory. If the ENTER/
Up and Down Arrow Keys
ADV key is not pressed after a value is changed, the
Used in conjunction with the OPER DATA, HISTORY, changes will not be “entered” and the original values
COOLING SETPOINTS, SCHEDULE/ADVANCE will be used to control the chiller.
DAY, OPTIONS and CLOCK keys, the ↑ (UP) and ↓
(DOWN) arrow keys allow the user to scroll through Programming and a description on the use of the ↑ (UP)
the various data screens. Refer to the section on arrow key, and ↓ (DOWN) arrow, and ENTER/ADV
“DISPLAY/PRINT” keys for specific information on the keys are covered in detail under the SETPOINTS, and
displayed information and specific use of the ↑ (UP) and UNIT keys.
↓ (DOWN) arrow keys.
The ↑ (UP) arrow key, and ↓ (DOWN) arrow key are also
used for programming the control panel such as changing
numerical or text values when programming cooling
setpoints, setting the daily schedule, changing safety
setpoints, chiller options, and setting the clock.
“SETPOINTS” KEYS
00069VIP
Programming of the cooling setpoints, daily schedule, Leaving Chilled Liquid Control
and safeties is accomplished by using the keys located
under the SETPOINTS section. S E T P O I N T = 4 5 . 0 ° F
R A N G E = +/- 2 . 0 ° F
The three keys involved are labeled COOLING
SETPOINTS, SCHEDULE/ADVANCE DAY, and
The above message shows the current chilled water
PROGRAM.
temperature SETPOINT at 45.0 °F (notice the cursor po-
sitioned under the number 0). Pressing either the ↑ (UP)
Following are instructions for programming the
or ↓ (DOWN) arrow will change the setpoint in .5 °F
respective setpoints. The same instruction should be increments. After using the ↑ (UP) or ↓ (DOWN) arrow
used to view the setpoints with the exception that the keys to adjust to the desired setpoint, the ENTER/ADV
setpoint will not be changed. key must be pressed to enter this number into memory
and advance to the RANGE SETPOINT.
Cooling Setpoints
Entry of the setpoint will be indicated by the cursor mov-
The Cooling Setpoint and Range can be programmed by
ing under the current RANGE setpoint. The ↑ (UP) and
pressing the COOLING SETPOINTS key. The cooling ↓ (DOWN) arrow keys are used to set the RANGE, in
mode (leaving chilled liquid or return chilled liquid) will .5 °F increments, to the desired RANGE setpoint. After
be displayed for a few seconds, and the setpoint display adjusting the setpoint, the ENTER/ADV key must be
entry screen will appear. pressed to enter the data into memory.
In return chilled liquid control, the range no longer has Pressing the COOLING SETPOINTS a third time will
a +/- X.X °F, but only a + X.X °F RANGE setpoint. bring up the display that allows the Maximum EMS-
This indicates that the setpoint is not centered within PWM Temperature Reset to be programmed. This
the RANGE but could be described as the bottom of message is shown below.
the control range. A listing of the limits and the pro- M A X E M S - PWM R E MO T E
grammable values for the COOLING SETPOINTS are T E M P R E S E T = + 2 0 ° F
shown in Table 13.
The SETPOINT and RANGE displays just described The Temp Reset value is the maximum allowable remote
were based on LOCAL control. If the unit was pro- reset of the temperature setpoint. The setpoint can be
grammed for REMOTE control (under the OPTIONS reset upwards by the use of an Energy Management
key), the above programmed setpoints would have no System or from the Temperature Reset Option Board. See
effect. page 129 for a detailed explanation of this feature.
When in return chilled liquid temperature control, the As with the other setpoints, the ↑ (UP) arrow and ↓
micro will turn all compressors off at setpoint and will (DOWN) arrow keys are used to change the Temp Reset
turn compressors on as return chilled liquid tempera- value. After using the ↑ (UP) and ↓ (DOWN) arrows to
ture rises. All compressors will be on at setpoint + the adjust to the desired setpoint, the ENTER/ADV key must 7
range. If the range equals the temperature drop across be pressed to enter this number into memory.
the evaporator when fully loaded, the leaving chilled
liquid temperature will remain near the setpoint + or – a SCHEDULE/ADVANCE DAY KEY
few degrees as the chiller loads and unloads according The SCHEDULE is a seven day Daily Schedule that
to return chilled liquid temperature. allows one start/stop time per day. The schedule can be
programmed Monday through Sunday with an alternate
Both LEAVING and RETURN control are described in holiday schedule available. If no start/stop times are
detail under the section on CAPACITY CONTROL. programmed, the unit will run on demand, providing the
chiller is not shut off on a unit or system shutdown. The
Remote Setpoint Control Daily Schedule is considered “not programmed” when
the times in the schedule are all zeros (00:00 AM).
Pressing the COOLING SETPOINTS key a second
time will display the remote setpoint and cooling
To set the schedule, press the SCHEDULE/ADVANCE
range. This display automatically updates about every
DAY key. The display will immediately show the
2 seconds. Notice that these setpoints are not “locally”
following display.
programmable, but are controlled by a remote device
such as an ISN control, remote reset option board, or
MO N S T A R T = 0 0 : 0 0 A M
remote PWM signal. These setpoints would only be valid
S T O P = 0 0 : 0 0 A M
if the unit was operating in the REMOTE mode.
PROGRAM KEY L OW A M B I E N T T E M P
There are several operating parameters under the C U T O U T = 2 5 . 0 ° F
PROGRAM key that are programmable. These setpoints
can be changed by pressing the PROGRAM key, and The LOW AMBIENT TEMP CUTOUT allows the user
then the ENTER/ADV key to enter Program Mode. to select the chiller outside ambient temperature cutout
Continuing to press the ENTER/ADV key will display point. If the ambient falls below this point, the chiller
each operating parameter. While a particular parameter will shut down. Restart can occur when temperature rises
is being displayed, the ↑ (UP) and ↓ (DOWN) arrow 2 °F (1.11 °C) above the cutout setpoint.
keys can be used to change the value. After the value is
changed, the ENTER/ADV key must be pressed to enter L E A V I N G L I Q U I D T E M P
the data into memory. Table 14 shows the programmable C U T O U T = 3 6 . 0 ° F
limits and default values for each operating parameter.
The LEAVING LIQUID TEMP CUTOUT protects
Following are the displays for the programmable values the chiller from an evaporator freeze-up. Anytime the
in the order they appear: leaving chilled liquid temperature drops to the cutout
point, the chiller shuts down. Restart will be permitted
d D I S C H A R G E P R E S S U R E when the leaving chilled liquid temperature rises 2 °F
C U T O U T = 3 9 5 P S I G (1.11 °C) above the cutout setpoint.
DISCHARGE PRESSURE CUTOUT is the discharge When water cooling mode is programmed (OPTIONS
pressure at which the system will shutdown as monitored key), the value is fixed at 36.0 °F (2.22 °C) and cannot
by the optional discharge transducer. This is a software be changed. Glycol cooling mode can be programmed
shutdown that acts as a backup for the mechanical high to values listed in Table 14.
pressure switch located in the refrigerant circuit. The
system can restart when the discharge pressure drops A N T I R E C Y C L E T I M E R
= 6 0 0 S E C
40 PSIG (2.76 barg) below the cutout point.
If the optional discharge pressure transducer is not The programmable anti-recycle timer assures that
installed, this programmable safety would not apply. systems do not short cycle, and the compressor motors
It should be noted that every system has a mechanical have sufficient time to dissipate heat after a start. 7
high pressure cutout that protects against excessive This timer is programmable under the PROGRAM
high discharge pressure regardless of whether or not the key between 300 – 600 seconds. Whenever possible,
optional discharge pressure is installed. to reduce cycling and motor heating, the anti-recycle
timer should be adjusted as high as possible. The
S U C T I O N P R E S S U R E programmable anti-recycle timer starts the timer when
C U T O U T = 80 . 0 P S I G the first compressor in a system starts. The timer begins
to count down. If all the compressors in the circuit cycle
The SUCTION PRESSURE CUTOUT protects the off, a compressor within the circuit will not be permitted
chiller from an evaporator freeze-up. If the suction to start until the anti-recycle timer has timed out. If the
pressure drops below the cutout point, the system will lead system has run for less than 5 minutes, 3 times
shut down. Typically, the cutout should be set to 80 PSIG in a row, the anti-recycle timer will be extended to 10
(5.52 Bars) form water cooling. minutes, if currently programmed for < 10 minutes.
F A N C O N T R O L O N
There are some exceptions when the
P R E S S U R E = XX X P S I G
suction pressure is permitted to tem-
porarily drop below the cutout point.
Does not apply to YCWL.
Details are explained under the topic
of SYSTEM SAFETIES. F A N D I F F E R E N T I A L O F F
PR E S S U R E = XX X P S I G
T O T A L N U M B E R O F N U M B E R O F F A N S
C OM P R E S S O R S = 6 P E R S Y S T E M = X
R E M O T E U N I T I D
Unit Trip Volts
P R O G R A M M E D = X
For total chiller high current trip programming on
460VAC chillers: When communications is required with a BAS or
OptiView Panel, individual unit IDs are necessary for
• Add the sum of all the the compressor and fan
communications with specific chillers on a single RS-
RLA’s in the chiller.
485 line. ID 0-7 is selectable.
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be
programmed.
UNIT/SYSTEM TRIP VOLTS CURRENT FEEDBACK 0.5 Volts 4.5 Volts 2.5 Volts
REMOTE UNIT ID — 0 7 0
* The minimum discharge pressure allowed is 235 PSIG. The Fan Differential Off Pressure High Limit will be lowered (reduced) to
prevent going below 235 PSIG based on where the fan control On Pressure is programmed.
Leaving Liquid
EMS - PWM Temperature
Remote Temp Cutout
Reset Setpoint
Anti-Recycle
Table 15
Table 16 provides a quick reference of the setpoints list for the Setpoints Keys.
Timer
Fan Control
On-Pressure
(Not applicable to a YCWL)
Fan Differential
Off-Pressure
(Not applicable to a YCWL)
Total Numbers
of
Compressors
Number of
Fans Per System
SYS / Unit
Trip Volts Option
Remote Unit ID
LD07404c
“UNIT” KEYS
OPTIONS
CLOCK
00070VIP
D I S P L A Y L A N G U A G E C H I L L E D L I Q U I D
E N G L I S H WA T E R
English, Spanish, French, German, and Italian can be The chilled liquid is water. The Cooling Setpoint can be
programmed. programmed from 40 °F to 70 °F (4.4 °C to 21.1 °C)
or
Option 2 – System Switches: (two system units C H I L L E D L I Q U I D
only)
G L Y C O L
(Single System Display is similar)
S Y S 1 SW I T C H O N The chilled liquid is glycol. The Cooling Setpoint can
S Y S 2 SW I T C H O N be programmed from 10 °F to 70 °F (-12.2 °C to 21.1
°C).
A M B I E N T C O N T R O L D I S P L A Y U N I T S
S T A N D A R D I M P E R I A L
The low ambient cutout is adjustable from 25 °F to 60 °F This mode displays system operating values in Imperial
(-3.9 °C to 15.6 °C). units of °F or PSIG.
or
or
A M B I E N T C O N T R O L
L OW A M B I E N T D I S P L A Y U N I T S
S I
The low ambient cutout is programmable down to 0 °F This mode displays system operating values in Scientific
(-17.8 °C). A low ambient kit MUST be installed for International Units of °C or barg.
this option to be chosen. If the kit is NOT installed,
and low ambient is selected, low pressure faults and Option 8 – Lead/Lag Type (two system units
compressor damage may occur. only):
Option 5 – Local/Remote Control Type: L E A D / L A G C O N T R O L
M A N U A L S Y S 1 L E A D
L O C A L / R E MO T E MO D E L
L O C A L
SYS 1 selected as lead compressor. SYS 1 lead option
MUST be chosen if Hot Gas Bypass is installed.
When programmed for LOCAL, an ISN or RCC control or
can be used to monitor only. The micro panel will operate
on locally programmed values and ignore all commands L E A D / L A G C O N T R O L
from remote devices, or through the RS-485 inputs. The M A N U A L S Y S 2 L E A D
chiller will communicate and send data to the remote
monitoring devices. SYS 2 selected as lead compressor.
or or
L O C A L / R E MO T E MO D E L E A D / L A G C O N T R O L
R E MO T E A U T OM A T I C
This mode should be selected when an ISN or RCC Lead/lag between systems may be selected to help
control is to be used to control the chiller. This mode equalize average run hours between systems on
will allow the ISN to control the following items: chillers with 2 refrigerant systems. Auto lead/lag
Remote Start/Stop, Cooling Setpoint, Load Limit, and allows automatic lead/lag of the two systems based
History Buffer Request. If the unit receives no valid on an average run hours of the compressors in each
ISN transmission for 5 minutes, it will revert back to system. A new lead/lag assignment is made whenever
the locally programmed values. all compressors shut down. The micro will then assign
Option 6 – Unit Control Mode: the “lead” to the system with the shortest average run
time.
C O N T R O L MO D E
R E T U R N L I Q U I D Option 9 – Condenser Fan Control Mode:
M A N U A L O V E R R I D E MO D E S O F T S T A R T
E N A B L E D D I S A B L E D
Manual Override Mode is enabled. This is a service SOFT START “DISABLED” MUST be selected on all
function and when enabled, will allow the unit to chillers.
start when shut down on the Daily Schedule. It will This message may not be viewable on non-European
automatically be disabled after 30 minutes. chillers.
Expansion valve type, thermostatic or electronic If the update resulted in an error, the original program
may be selected under Service Mode. Expansion will still be active. When an error occurs, assure the
valve type is displayed under the OPTIONS key, but correct Flash Card was utilized. Incorrect chiller
is only programmable in Service Mode. YCAL 0019 software will cause an error. If this is not the case, the
– 0066 chillers will typically always be equipped with Flash Card is most likely defective or the IPU and I/O
thermostaic expansion valves. combo board is bad.
F L A S H C A R D U P D A T E
E N A B L E D
Pump Control is utilized to operate the optional onboard The displays for this PUMP SELECTION option should
pump kit or to control an external pump through dry only appear if “YORK HYDRO KIT PUMPS = 2” are
contacts 23 and 24. To use this option, the following selected under Option 19. Presently, this option should
selection should be made in the Service Mode: not be used.
Y O R K H Y D R O CLOCK
K I T P U M P S = 1
The CLOCK display shows the current day, time, and
date. Pressing the CLOCK key will show the current
When YORK HYDRO KIT PUMPS = 1, the controls day, time, and date.
will be closed to run the pumps whenever any one of
the following conditions are true: It is important that the date and time be correct,
• Low Leaving Chilled Liquid Fault otherwise the Daily Schedule will not function as desired
• Any compressor is running if programmed. In addition, for ease of troubleshooting
via the History printouts, the day, time, and date should
• Daily Schedule is ON and Remote Stop is
be correct.
closed.
To change the day, time, and date press the CLOCK
Even if one of the above conditions
key. The display will show something similar to the
are true, the pump will not run if the following:
chiller has been powered up for less
than 30 seconds; or if the pump has T O D A Y I S F R I 0 8 : 5 1 A M
run in the last 30 seconds to prevent 2 5 J A N 0 2
pump overheating.
The line under the F is the cursor. If the day is correct,
E X T E R N A L press the ENTER/ADV key. The cursor will move under
E V A P P U M P the 0 in 08 hours. If the day is incorrect, press the ↑
(UP) or ↓ (DOWN) arrow keys until the desired day is
displayed and then press the ENTER/ADV key at which 7
EXTERNAL EVAP PUMP should be selected if an time the day will be accepted and the cursor will move
external pump is being controlled with the chiller pump under the first digit of the “2 digit hour”. In a similar
contacts. The operation will be the same as YORK manner, the hour, minute, meridian, month, day, and
HDRO KIT PUMPS = 1 year may be programmed, whenever the cursor is under
the first letter/numeral of the item. Press the ↑ (UP) or
The following option should not be selected. ↓ (DOWN) arrow keys until the desired hour, minute,
meridian; day, month, and year are displayed. Pressing
Y O R K H Y D R O the ENTER/ADV Key will save the valve and move the
K I T P U M P S = 2 cursor on to the next programmable variable.
Options Key
Expansion Valve Type
(press Options Key
to adv.) (Thermoplastic or Electric)
(Programmed under Service
Display Language Mode, Viewable Only)
Must be programmed
System Switches for Thermostatic
on/off
Flash Card Update
Chilled Liquid Type
(water or glycol)
Remote Temp Reset
Ambient Control
Pump Control
(standard or low)
Pump Selection
Local/Remote Mode
Display Units
(English or Metric)
Unit Type
(”Chiller” MUST be Selected
Via No Jumper Installed
(Viewable Only)
Refrigerant Type
R-410A
(Programmed under Service Mode)
Viewable Only)
Fig. 28 provides a quick reference list for the Unit key setpoints. LD07405d
To initiate the start sequence of the chiller, all run The setpoint, when programmed for Leaving Chilled
permissive inputs must be satisfied (flow/remote start/ Liquid Control, is the temperature the unit will control
stop switch), and no chiller or system faults exist. to within +/- the (control) cooling range. The Setpoint
High Limit is the Setpoint plus the Cooling Range. The
The first phase of the start sequence is initiated by the Setpoint Low Limit is the Setpoint minus the Cooling
Daily Schedule Start or any Remote Cycling Device. If Range. Fig. 18 should be utilized to aid in understanding
the unit is shut down on the Daily Schedule, the chilled the following description of Leaving Chilled Liquid
water pump microboard contacts (TB8 6-7) will close Control.
to start the pump when the Daily Schedule start time
has been reached. Once flow has been established and If the leaving chilled liquid temperature is above the
the flow switch closes, capacity control functions are Setpoint High Limit, the lead compressor on the lead
initiated, if the remote cycling contacts wired in series system will be energized along with the liquid line
with the flow switch are closed. solenoid. Upon energizing any compressor, the 60
second Anti-Coincidence timer will be initiated to
It should be noted that the chilled water pump contacts prevent multiple compressors from turning on.
(TB8 6-7) are not required to be used to cycle the chilled
water pump. However, in all cases the flow switch must If after 60 seconds of run-time the leaving chilled liquid
be closed to allow unit operation. temperature is still above the Setpoint High Limit,
the next compressor in sequence will be energized.
The control system will evaluate the need for cooling Additional compressors will be energized at a rate of
by comparing the actual leaving or return chilled liquid once every 60 seconds if the chilled liquid temperature
temperature to the desired setpoint, and regulate the remains above the Setpoint High Limit and the chilled
leaving or return chilled liquid temperature to meet that liquid temperature is dropping less than 3 °F/min. The
desired setpoint. lag system will not be allowed to start a compressor until
the lead system has run for 5 minutes.
SUCTION PRESSURE LIMIT CONTROLS
If the chilled liquid temperature falls below the Setpoint
The anticipatory controls are intended to prevent the High Limit but is greater than the Setpoint Low Limit,
unit from ever actually reaching a low-pressure cutout. loading and unloading do not occur. This area of control
Loading is prevented, if the suction pressure drops below is called the control range.
1.15 x suction pressure cutout (15% below the cutout).
Loading may reoccur after suction pressure rises above If the chilled liquid temperature drops to between
the unload point and a period of one minute elapses. This Setpoint Low Limit and 0.5 °F (.28 °C) below the
control is only operable if the optional suction pressure Setpoint Low Limit, unloading (a compressor turns off)
transducers are installed. occurs at a rate of 1 every 30 seconds. If the chilled liquid 8
temperature falls to a value greater than 0.5 °F (.28 °C)
DISCHARGE PRESSURE LIMIT CONTROLS below the Setpoint Low Limit but not greater than 1.5 °F
(.83 °C) below the Setpoint Low Limit, unloading occurs
The discharge pressure limit controls unload a system at a rate of 20 seconds. If the chilled liquid temperature
before it reaches a safety limit due to high load or dirty falls to a value greater than 1.5 °F (.83 °C) below the
condenser coils. The micro monitors discharge pressure Setpoint Low Limit, unloading occurs at a rate of 10
and unloads a system, if fully loaded, by one compressor seconds. If the chilled liquid temperature falls below
when discharge pressure exceeds the programmed cutout 1 °F above the low chilled liquid temperature cutout,
minus 10 PSIG (0.69 barg). Reloading will occur when unloading occurs at a rate of 10 seconds if it is greater
the discharge pressure on the affected system drops than 10 seconds.
to 85% of the unload pressure and 10 minutes have
In water cooling mode on R-410A chillers, the minimum
elapsed.
low limit of the control range will be 40.0ºF. For leaving
This control is only applicable if optional discharge chilled liquid temperature setpoint and control range
pressure transducers are installed. combinations that result in the low limit of the control
range being below 40.0ºF, the low limit will be reset
to 40.0ºF and the difference will be added to the high
limit. This will result in a control range the same size as
programmed but not allow the unit to run below 40.0ºF.
This control will not affect glycol chillers.
JOHNSON CONTROLS 127
Unit Operation
Form 201.26-NM1 (308)
Hot gas, if present, will be the final step of capacity. Hot microprocessor will increase the setpoint high limit
gas is energized when only a single compressor is running according to the chart below, with a maximum value
and LWT<SP. Hot gas is turned off as temperature rises allowed of 50 °F (See Fig. 30).
when LWT>SP + CR/2. If temperature remains below
the setpoint low limit on the lowest step of capacity, the If adding the setpoint adjust value to the setpoint high
micro will close the liquid line solenoid, after turning limit causes the setpoint high limit to be greater than 50
off hot gas, and pump the system down before turning °F, the setpoint high limit will be set to 50 °F, and the
off the last compressor in a system. difference will be added to the setpoint low limit.
The leaving chilled liquid setpoint is programmable Once a system runs for greater than 5 minutes, the
from 40 °F to 70 °F (4.4 °C to 21.1 °C) in water chilling
setpoint adjust will be set back to 0. This will occur
mode and from 10 °F to 70 °F (-12.2 °C to 21.1 °C) in
glycol chilling mode. In both modes, the cooling range while the system is still running.
can be from +/-1.5 °F to +/-2.5 °F (+/-.83 °C to 1.39
On a hot water start, once a system starts, it will turn on all Once the second system starts a compressor on a 2
compressors before the next system starts a compressor. system chillers, the micro will attempt to equally load
The microprocessor will sequence compressors within each system as long as the system is not limiting or
each circuit to maximize individual compressor run time pumping down. Once this occurs, loading and unloading
on individual compressors within a system to prevent will alternate between systems, loading the lead system
short cycling. first or unloading the lag system first.
RETURN CHILLED LIQUID CONTROL As an example of compressor staging (refer to Table 19),
a chiller with six compressors using a Cooling Setpoint
Return chilled liquid control is based on staging the programmed for 45 °F (7.20 °C) and a Range Setpoint
compressors to match the cooling load. The chiller will of 10 °F (5.56 °C). Using the formulas in Table 20, the
be fully loaded when the return water temperature is control range will be split up into six (seven including
equal to the Cooling Setpoint plus the Range. The chiller hot gas) segments, with the Control Range determining
will be totally unloaded (all compressors off) when the the separation between segments. Note also that the
return water temperature is equal to the Cooling Setpoint Cooling Setpoint is the point at which all compressors
(See sample in Table 16). At return water temperatures are off, and Cooling Setpoint plus Range is the point
between the Cooling Setpoint and Cooling Setpoint all compressors are on. Specifically, if the return water
plus Range, compressor loading and unloading will be temperature is 55 °F (12.8 °C), then all compressors
determined by the formulas in Table 17. will be on, providing full capacity. At nominal gpm, this
would provide approximately 45 °F (7.2 °C) leaving
Return Chilled Liquid Control MUST water temperature out of the evaporator.
only be used when constant chilled
If the return water temperature drops to 53.4 °F (11.9
liquid flow is ensured.
°C), one compressor would cycle off leaving five
compressors running. The compressors would continue
The RANGE MUST always be pro- to cycle off approximately every 1.7 °F (.94 °C), with
grammed to equal the temperature the exception of hot gas bypass. Notice that the hot
drop across the evaporator when the gas bypass would cycle on when the return water
chiller is “fully loaded”. Otherwise, temperature dropped to 46.25 °F (7.9 °C). At this point
chilled liquid temperature will over or one compressor would be running with hot gas.
under shoot. Variable flow must never
be used in return chilled liquid mode. Should the return water temperature rise from this
point to 46.7 °F (8.2 °C), the hot gas bypass would shut
Normal loading will occur at intervals of 60 seconds off, still leaving one compressor running. As the load
according to the temperatures determined by the formulas. increased, the compressors would stage on every 1.7
Unloading will occur at a rate of 30 seconds according °F (.94 °C).
to the temperatures determined in the formulas used
to calculate the on and off points for each step of Also note that Table 17 not only provides the formulas
capacity. for the loading (ON POINT) and unloading (OFF
POINT) of the system, the “STEP” is also shown in the
tables. The “STEP” is the incriment in the sequence
The return chilled liquid setpoint is programmable from
of the capacity control scheme that can be viewed
8
40 °F to 70 °F (4.4 °C to 21.1 °C) in water chilling mode
and from 10 °F to 70 °F (-12.2 °C to 21.1 °C) in glycol under the OPER DATA key. Refer to the section on the
chilling mode. In both modes, the cooling range can be DISPLAY/PRINT keys for specific information on the
from 4 °F to 20 °F (2.2° to 11.1 °C). OPER DATA key.
RETURN CHILLED LIQUID SYSTEM LEAD/LAG from starting 2 times in a row. The micro will not attempt
AND COMPRESSOR SEQUENCING to equalize run time on individual compressors within
A lead/Lag option may be selected to help equalize a system.
average run hours between systems with 2 refigerant
systems. This may be programmed under the OPTIONS Each compressor in a system will be assigned an
key. Auto Lead/Lag of the 2 systems based on average arbitrary number 1, or 2. The non-running compressor
run hours of the compressors in each system. Manual within a system with the lowest priority number will
Lead/Lag selects specifically the sequence which the always be the next compressor to start. The running
micro starts the systems. compressor with priority number 1 will always be the
next compressor to shut off. Whenever a compressor is
The micro will sequence compressors load and unload shut off, the priority numbers of all compressors in each
systems according to Table 18. The microprocessor will system will be decreased by 1 with the wrap around.
lead/lag compressors within each circuit to maximize This control scheme assures the same compressor does
individual compressor run time for the purpose of not repeatedly cycle on and off.
lubrication. It will also prevent the same compressor
(English) Example:
(6 sec. - 1) (10°F/10) = 5°F Reset Local Chilled Liquid Setpoint = 45 °F (7.22 °C)
*Max Reset Value = 20 °F (11.11 °C)
So...the new chilled liquid setpoint = 45°F + 5°F= Input Signal = 6VDC
50°F. This can be viewed by pressing the Cooling
(English)
Setpoints key twice. The new value will be displayed
°Reset = 6VDC x 20 °F = 12 °F Reset
as “REM SETP = 50.0°F.”
10
New Setpoint = 45 °F + 12 °F = 57 °F
(Metric)
(6 sec - 1) * (5.56°C/10) = 2.78°C (Metric)
Reset Cooling Setpoint = 7.22°C + 2.78°C = °Reset = 6VDC x 11. 11 °C = 6.67 °C Reset
10.0°C 10
New Setpoint = 7.22 °C + 6.67 °C = 13.89 °C
So...the new reset Cooling Setpoint = 7.22 °C + 2.78°C
* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” setpoint
= 10°C. This can be viewed by pressing the Cooling value described in the programming section under Cooling Setpoints.
Setpoints key twice. The new value will be displayed Programmable values are from 2 °F to 40 °F (1.11 °C to 11.11
as “REM SETP = 10.0°C.” °C).
The Remote Reset Option allows the Control Center °Reset = (mA signal - 4) x (*Max Reset Value)
of the unit to reset the chilled liquid setpoint using a 16
0 - 10VDC input, or a 4-20mA input connected to CTB1 Example:
Local Chilled Liquid Setpoint = 45° (7.22 °C)
terminals A- and A+. Whenever a reset is called for, the
*Max Reset Value = 10 °F (5.56 °C)
change may be noted by pressing the Cooling Setpoints Input Signal = 12 mA
key twice. The new value will be displayed as “REM
SETP = XXX °F.” This reset value is always added to (English)
the locally programmed chilled liquid setpoint, meaning °Reset = 8mA x 10 °F = 5 °F Reset
this function never lowers the chilled liquid setpoint 16 8
below the locally programmed value. Setpoint = 45 °F + 5 °F = 50 °F
If a 0 - 10VDC signal is supplied, it is applied to (Metric)
terminals A+ and A-, and jumper JP1 on the I/O board °Reset = 8mA x 5.56 °C = 2.78 °C Reset
must be inserted between pins 2 and 3. To calculate 16
the reset chilled liquid setpoint for values between 0VDC Setpoint = 7.22 °C + 2.78 °C = 10.0 °C
and 10VDC use the following formula:
Pressing the ↑ (UP) arrow key will energize the liquid SERVICE MODE – ANALOG & DIGITAL
line solenoid valve and “OFF” will change to “ON” in INPUTS
the display as the LLSV is energized. Energizing and
de-energizing outputs may be useful during trouble- After entering Service Mode (PROGRAM ↑↑ ↓↓),
shooting. all digital and analog inputs to the microboard can be
viewed by pressing the OPER DATA key. After pressing
SERVICE MODE – CHILLER CONFIGURATION the OPER DATA key, the ↑ (UP) arrow and ↓ (DOWN)
arrow keys are used to scroll through the analog and
After the Outputs are displayed, the next group of
digital inputs.
displays relate to chiller configuration and start/hour
counters. Data logging, soft start, refrigerant type, pump Following is the order of analog and digital inputs that
control selection and expansion valve type all must be will appear when sequenced with the ↓ (Down) arrow
programmed to match actual chiller configuration. key:
(analog inputs)
Soft start (disabled), Refrigerant Type SYS 1 SUCT PRESSURE
(R410A), and Expansion Valve Type UNIT TYPE
(Thermostatic), and North American SYS 1 *DISCH PRESSURE
Feature (Enabled) MUST be properly SYS 1** SUCTION TEMP.
programmed or damage to compres- SYS 2** SUCTION TEMP.
sors and other system components AMBIENT AIR TEMP.
may result. LEAVING LIQUID TEMP.
RETURN LIQUID TEMP.
Following is a list of chiller configuration selections, in SYS 2 SUCTION PRESSURE
order of appearance: SYS 2 SPARE
DATA LOGGING MODE = : DO NOT MODIFY SYS 2 *DISCH PRESSURE
DATA LOGGING TIMER = : DO NOT MODIFY
SYS 1 MTR VOLTS
SOFT START
SYS 2 MTR VOLTS
REFRIGERANT TYPE
(digital inputs)
EXPANSION VALVE TYPE
PWM TEMP RESET INPUT
REMOTE TEMP RESET OPTION LOAD LIMIT INPUT
REMOTE INPUT SERVICE TIME FLOW SW / REM START
FEATURE SET SPARE
SINGLE SYSTEM SELECT
PUMP CONTROL SELECTION
SYS 1 MP / HPCO INPUT
SYS 1 HOURS SYS 2 MP / HPCO INPUT
SYS 2 HOURS * The discharge pressure transducer is optional on some models.
SYS 1 STARTS ** The suction temp. sensor is on EEV units only.
SYS 2 STARTS
The analog inputs will display the input connection,
The last displays shown on the above list are for the ac-
the temperature or pressure, and corresponding input
cumulated run and start timers for each system. All val-
voltage such as:
ues can also be changed using the ↑ (UP) and ↓ (Down)
arrow keys, but under normal circumstances would not
S Y S 1 S U C T P R J 7 - 1 0
be required or advised. After the last start display, the
2 . 1 V D C = 8 1 P S I G
micro will display the first programmable value under
the PROGRAM key.
This example indicates that the system 1 suction
pressure input is connected to plug 7 – pin 10 (J7-10)
on the I/O board. It indicates that the voltage is 2.1
volts dc which corresponds to 81 PSIG (5.6 bars)
suction pressure.
The digital inputs will display the input connection and TABLE 21 – I/O DIGITAL OUTPUTS
ON/OFF status such as: TB7-2 SYS 1 Compressor 1
TB7-3 SYS 1 Liquid Line Solenoid Valve
F L OW SW / R E M S T A R T
TB7-4 SYS 1 Compressor 2
J 13 - 5 I S O N
TB7-5 SYS 1 Compressor 3
This indicates that the flow switch/remote start input is TB7-7 SYS 1 Hot Gas Bypass Valve
connected to plug 13- pin 5 (J13-5) on the microboard, TB10-2 SYS 2 Compressor 1
and is ON (ON = +30VDC unregulated input, OFF = TB10-3 SYS 2 Liquid Line Solenoid Valve
0VDC input on digital inputs). TB10-4 SYS 2 Compressor 2
TB10-5 SYS 2 Compressor 3
CONTROL INPUTS/OUTPUTS TB7-8 SYS 1 Condenser Fan Output 1 (N/A)
Tables 27 through 30 are a quick reference list providing TB7-9 SYS 1 Condenser Fan Output 2 (N/A)
the connection points and a description of the inputs and TB7-10 SYS 1 Condenser Fan Output 3 (N/A)
outputs respectively. All input and output connections TB10-8 SYS 2 Condenser Fan Output 1 (N/A)
pertain to the connections at the microboard.
TB10-9 SYS 2 Condenser Fan Output 2 (N/A)
TABLE 20 – I/O DIGITAL INPUTS TB10-10 SYS 2 Condenser Fan Output 3 (N/A)
TB8-2 Evaporator Heater
J13-2 Unit ON/OFF Switch
TB8-3 SYS 1 Alarm
J13-3 Load Limit Stage 2 on 3, 5 & 6 Comp. Units
TB9-2 SYS 2 Alarm
J13-4 Load Limit Stage 1
TB8-6 & 7 Evaporator Pump Starter
J13-5 Flow Switch and Remote Start/Stop
TB10-7 SYS 2 Hot Gas Bypass Valve
J13-6 Spare
Single System Select TABLE 22 – I/O ANALOG INPUTS
J13-7
(Jumper = Single Sys, No Jumper = Two Sys)
SYS 1 Suction Transducer
CR1
J13-8 J7-10 -or-
(Sys 1 Motor Protector/High Pressure Cutout)
SYS 1 Low Pressure Switch
CR2
J13-10 Unit Type: Chiller = NO Jumper J11-12 to +24 VDC
(Sys 2 Motor Protector/High Pressure Cutout)
J11-12 YCUL Condensing Unit = Jumper J11-12 to +24 VDC
(Do NOT Use)
J7-11 SYS 1 Discharge Pressure Transducer (Optional)
J6-9 Ambient Air Temp. Sensor
J6-7 Leaving Chilled Liquid Temp. Sensor
J6-8 Return Chilled Liquid Temp. Sensor
SYS 2 Suction Pressure Transducer
J9-10 -or-
SYS 2 Low Pressure Switch
J9-11
SYS 2 Discharge Pressure Transducer
(Optional)
9
J7-12 Unit/SYS 1 Voltage
J9-12 SYS 2 Voltage
J11-11 Remote Temperature Reset
MICROBOARD LAYOUT
TB1
TB7
J3
TB8
J5
IPU
BOARD
TB9
J6
J7
J8
TB10
J9
J10
J14 JP1
J13 J11
J12
LD12721
Digital Inputs
Refer to the unit wiring diagram. All digital inputs are Typically, voltages of 24 – 36VDC could be measured
connected to J13-1 of the I/O board. The term “digital” for the DC voltage on the digital inputs. This voltage
refers to two states – either on or off. As an example, is in reference to ground. The unit case should be suf-
when the flow switch is closed, 30 volts DC will be ficient as a reference point when measuring digital input
applied to J13, pin 5 (J13-5) of the I/O board. If the voltages.
flow switch is open, 0 volts DC will then be present at
J13-5. Analog Inputs – Temperature
Refer to the unit wiring diagram. Temperature inputs are
Pin 1 of J13 is an unregulated 30VDC source used to connected to the microboard on plug J6. These analog
supply the DC voltage to the various user contacts, Unit inputs represent varying DC signals corresponding to
Switch, flow switch, etc. This DC source is factory wired varying temperatures. All voltages are in reference to
to CTB1, terminal 13. Any switch or contact used as a the unit case (ground). Following are the connections
digital input would be connected to this terminal, with for the temperature sensing inputs:
the other end connecting to its respective digital input on
the microboard. Any time a switch or contact is closed,
30VDC would be applied to that particular digital input.
Any time a switch or contact is open, 0VDC would be
applied to that particular digital input.
TABLE 24 – ENTERING/LEAVING CHILLED LIQUID Liquid & Refrigerant Sensor Test Points
TEMP. SENSOR, TEMPERATURE/VOLTAGE
CORRELATION
(Table 24)
Entering Chilled Liquid Sensor
VOLTAGE J6-5 = +5VDC regulated supply to sensor.
TEMP °F (Signal Input TEMP °C J6-8 = VDC input signal to the I/O board. See
to Return) Table 24 for voltage readings that correspond
10 1.33 -12 to specific liquid temperatures.
12 1.39 -11 J6-2 = drain (shield connection = 0VDC) Return
14 1.46 -10
Leaving Chilled Liquid Temperature Sensor
16 1.51 -9
18 1.58 -8 J6-4 = +5VDC regulated supply to sensor.
J6-7 = VDC input signal to the microboard. See
20 1.65 -7
Table 24 for voltage readings that correspond
22 1.71 -6
to specific liquid temperatures.
24 1.78 -4 J6-1 = drain (shield connection = 0VDC) Return
26 1.85 -3
28 1.91 -2
30 1.98 -1
32 2.05 0
34 2.12 1
36 2.19 2
38 2.26 3
40 2.33 4
42 2.40 6
44 2.47 7
46 2.53 8
48 2.60 9
50 2.65 10
52 2.73 11
54 2.80 12
56 2.86 13
58 2.92 14
60 2.98 16
62 3.05 17
64 3.11 18
66 3.17 19
68 3.23 20
70 3.29 21
72 3.34 22
74 3.39 23
76 3.45 24
78 3.5 26
80 3.54 27
TEST POINTS:
Suction Pressure:
System 1: ...............................................Microboard J7-10 to J7-9
System 2: ...............................................Microboard J9-10 to J9-9
Discharge Pressure:
System 1: ...............................................Microboard J7-11 to J7-7
System 2: ...............................................Microboard J9-11 to J9-7
JOHNSON CONTROLS 141
Service and Troubleshooting
Form 201.26-NM1 (308)
The suction transducers have a range from 0 to 400 PSIG Digital Outputs
(27.5 barg). The output will be linear from 0.5VDC to
Refer to the unit wiring diagram and Fig. 32. The digital
4.5VDC over the 400 PSIG (27.5 barg) range. Following
outputs are located on TB7, TB8, and TB9 and TB-10 of
is a formula that can be used to verify the voltage output
the microboard. ALL OUTPUTS ARE 120VAC with the
of the transducer. All voltage reading are in reference to
exception of TB8-6 to TB8-7 which are the contacts that
ground (unit case).
can be used for a remote evaporator pump start signal.
The voltage applied to either of these terminals would
V = (Pressure in PSIG x .02) + .5
or be determined by field wiring.
V = (Pressure in barg x .29) + .5
Each output is controlled by the microprocessor by
where V = dc voltage input to micro switching 120VAC to the respective output connection
Pressure = pressure sensed by transducer energizing contactors, evaporator heater, and solenoids
according to the operating sequence (see Fig. 32).
Following are the I/O board connections for the Suction
Transducer: 120VAC is supplied to the I/O board via connections
at TB7-1, TB7-6, TB10-1, TB10-6, TB8-1 and TB9-1.
System 1 Suction Transducer Fig. 32 illustrates the relay contact architecture on the
J7-5 = +5VDC regulated supply to transducer. microboard.
J7-10 = VDC input signal to the microboard. SYS 1
TB7-2 COMP 1
See the formula above for voltage readings that
correspond to specific suction pressures. TB7-3 LLSV 1
J7-9 = +5VDC return TB7
SYS 1
TB7-4 COMP 2
J7-1 = drain (shield connection = 0VDC)
SYS 1
TB7-5 COMP 3
TB10-3 LLSV 2
TB10
SYS 2
TB10-4 COMPR 2 (5)
SYS 2
TB10-5 COMPR 3 (6)
SYS 2
TB10-7 HGSV
TB10-8
TB10
TB10-9
TB10-10
TB8-6 EVAP
TB8-7 PUMP
TB8
HEAT EXCH
TB8-2 HEATER
LD12722A
TB3-3 TXD 2 RD 9
TB3-2 CTS 5 CTS
TB3-5 GND 7 SG
LD12723
TROUBLESHOOTING
TABLE 26 – TROUBLESHOOTING
5. Defective IPU II & I/O Board 5. Replace IPU II & I/O Board
or the Display Board. or the Display Board.
Contact YORK
Service before
Replacing circuit
Boards!
TROUBLESHOOTING (CONT’D)
TROUBLESHOOTING (CONT’D)
LACK OF COOLING EFFECT 1. Fouled evaporator surface. 1. Contact the local YORK
Low suction pressure will service representative.
be observed.
SECTION 10 – MAINTENANCE
It is the responsibility of the equipment owner to provide OPERATING PARAMETERS
maintenance on the system. Regular checks of the system should be preformed to
ensure that operating temperatures and pressures are
IMPORTANT within limitations, and that the operating controls are set
If system failure occurs due to improper maintenance within proper limits. Refer to the Operation, Start-Up,
during the warranty period, JOHNSON CONTROLS and Installation sections of this manual.
will not be liable for costs incurred to return the system
to satisfactory operation. The following is intended only ON-BOARD BATTERY BACK-UP
as a guide and covers only the chiller unit components. U5 is the Real Time Clock chip located on the 031-
It does not cover other related system components 02630 IPU II board that maintains the date/time and
which may or may not be furnished by YORK. System stores customer programmed setpoints. The Real Time
components should be maintained according to the Clock is a 128K bram, P/N 031-02565-000. The IPU
individual manufacture’s recommendations as their II board must have JP1 installed when the 128K bram
operation will affect the operation of the chiller. is installed.
ISN CONTROL
Received Data (Control Data)
TABLE 28 – ISN TRANSMITTED DATA
The unit receives 8 data values from the ISN. The first
4 are analog values and the last 4 are digital values. ISN
CHARACTER TYPE DATA
PAGE
These 8 data values are used as control parameters
when in REMOTE mode. When the unit is in LOCAL Leaving Chilled
P11 8-11 Analog
Liquid Temp.
mode, these 8 values are ignored. If the unit receives no
Return Chilled
valid ISN transmission for 5 minutes it will revert back P12 12-15 Analog
Liquid Temp.
to all local control values. Table 27 lists the 5 control
P13 16-19 Analog ----
parameters. These values are found under feature 54
on the ISN. P14 20-23 Analog ----
SYS 1 Suction
P15 24-27 Analog
TABLE 27 – ISN RECEIVED DATA Temp. (EEV Only)
P16 28-31 Analog Ambient Air Temp.
ISN
CONTROL DATA SYS 1 Suction
PAGE
P17 32-35 Analog Superheat
SETPOINT
P03 (EEV Only)
COOLING
SYS 1 Run Time
P04 LOAD LIMIT STAGE (0,1, 2) P18 36-39 Analog
(Seconds)
P05 –
P06 – P19 40-43 Analog SYS 1 Suction
Pressure
START/STOP COMMAND
P07
(0 = STOP, 1 = RUN) SYS 1 Discharge
P20 44-47 Analog
P08 — Pressure
P09 — P21 48-51 Analog ----
HISTORY BUFFER REQUEST P22 52-55 Analog ----
P10
(0 = CURRENT DATA, 1 = LAST HISTORY DATA)
SYS 1 EEV
P23 56-59 Analog Output %
(EEV Only)
Transmitted Data
SYS 1
P24 60-63 Analog
After receiving a valid transmission from the ISN, the Anti-Recycle Timer
unit will transmit either operational data or history buffer Anti-Coincidence
P25 64-67 Analog
data depending on the “History Buffer Request” on Timer
ISN PAGE 10. Data must be transmitted for every ISN P26 68-71 Analog
SYS 2 Suction
page under feature 54. If there is no value to be sent to Temp. (EEV Only)
a particular page, a zero will be sent. Tables 29 and 30 SYS 2 Run Time
P27 72-75 Analog
show the data values and page listings for this unit. (Seconds)
SYS 2
P28 76-79 Analog
Suction Pressure
ISN PAGES listed are ENG PAGE
SYS 2
REFERENCES and must be decoded P29 80-83 Analog
Discharge Pressure
to the corresponding PAGE REF P30 84-87 Analog ----
point map related to the communica- P31 88-91 Analog ----
tions protocol type utilized. The latest SYS 2
point map information is listed on the P32 92-95 Analog Suction Superheat
Johnson Controls Group Equipment (EEV Only)
Integration website. SYS 2
P33 96-99 Analog
Anti-Recycle Timer
ISN ISN
CHARACTER TYPE DATA CHARACTER TYPE DATA
PAGE PAGE
Evaporator Heater SYS 1 Condenser
P38 110 Digital P61 133 Coded
Status Fan Stage
Evaporator Pump P62 134 Coded ----
P39 111 Digital
Status
SYS 2 Condenser
P63 135 Coded
SYS 1 Fan Stage
P40 112 Digital
Comp. 2 Run
P64 136 Coded ----
SYS 2
P41 113 Digital Unit Control Mode
Comp. 2 Run
(0=Leaving Water,
SYS 1 Liquid Line 1=Return Water,
P42 114 Digital Solenoid Valve or P65 137 Coded 2=Discharge Air,
EEV Pilot Solenoid 3=Suction Press.,
SYS 1 Hot Gas 4=Cooling
P43 115 Digital 5=Heating)
Bypass Valve
SYS 1 P66 138-141 Analog Anti-Recycle Timer
P44 116 Digital
Comp. 2 Run Leaving Chilled Liquid
P67 142-145 Analog
SYS 2 Temp. Cutout
P45 117 Digital
Comp. 2 Run Low Ambient
P68 146-149 Analog
SYS 2 Liquid Line Temp. Cutout
P46 118 Digital Solenoid Valve or P69 150-153 Analog ----
EEV Pilot Solenoid
Low Suction
P70 154-157 Analog
Lead System Pressure Cutout
P47 119 Digital
(0=SYS 1, 1=SYS 2)
High Discharge
P71 158-161 Analog
SYS 1 Pressure Cutout
P48 120 Digital
Comp.3 Run
P72 162-165 Analog Setpoint
SYS 2
P49 121 Digital P73 166-169 Analog Cooling Range
Comp. 3 Run
P74 170-173 Analog ----
Chilled Liquid Type
P50 122 Digital P75 174-177 Analog ----
(0=Water, 1=Glycol)
Ambient Control Mode SYS 1 Discharge
P51 123 Digital (0=Std. Ambient, P76 178-181 Analog Temp.
1=Low Ambient) (EEV Only-Optional)
Local/Remote SYS 1 Discharge
Control Mode P77 182-185 Analog Superheat
P52 124 Digital (EEV Only- Optional)
(0=Local,
1=Remote) SYS 2 Discharge
Units P78 186-189 Analog Temp.
P53 125 Digital (EEV Only- Optional)
(0=Imperial, 1= SI)
Lead/Lag Control SYS 2 Discharge
P54 126 Digital Mode P79 190-193 Analog Superheat
(0=Manual,1= Remote) (EEV Only- Optional)
P55 127 Digital ---- P80 194 Digital ---- 10
* SYS 1 P81 195 Digital ----
P56 128 Coded
Operational Code P82 196 Digital ----
* SYS 1 P83 197 Digital ----
P57 129 Coded
Fault Code
P84 198 Digital ----
* SYS 2
P58 130 Coded
Operational Code
* SYS 2
P59 131 Coded
Fault Code
P60 132 Coded ----
Data can be read and in some cases modified using In some cases, BACnet parameters may need to be
a serial communication BACnet or Modbus network modified. Modification is accomplished by pressing
connection. This information allows communications of the PROGRAM, DOWN ARROW, DOWN ARROW,
chiller operating parameters and external control changes DOWN ARROW, DOWN ARROW, and ENTER keys
to setpoint, load limiting, and start/stop commands. in sequence. The list below shows the displays for the
values that may be modified:
P1 STOP BITS
X
The table below shows the minimum, maximum, and default values.
The table below shows the real time error numbers and a description of each.
10
Chiller data that can be read and modified using specific Modbus Register Addresses; and the data associated with
the addresses, is outlined in the following description:
R410-A
PRESSURE TEMPERATURE CHART
NOTES
10