Sunteți pe pagina 1din 10

Physical Layer Measurement Report

Date: 23/01/2014 03:27:06 p.m.


Description: Automatically recorded Snapshot from Commissioning Wizard.

Fieldbus Type: FOUNDATION Fieldbus


Segment Tag: SegmentoSALA(2B)RemoteRIO

Measurement Equipment

Type: DM-AM
Serial Number: 01280221269002
Software Revision: 1.3.0.2
DTM Revision: 2.1.1.1971

Result: Commissioned, Excellent

Legend

Excellent All values are within the specification limit with an adequate safety margin
Good The value is within the specification limits but the safety margin is reduced
Out of Specification The value exceeds the allowed range

Limits used for this classification are listed on the last page of this report

Diagnostic Messages

(238) Status is Excellent

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 1


7 Field Devices detected

Min Max
Value Addr Result Value Addr Result
Segment Voltage: 28.8V - Excellent 28.8V - Excellent
Unbalance: - 2% - Excellent - 2% - Excellent
Noise: 24mV 16 Excellent 34mV 22 Excellent
Jitter: 0.7µs 16 Excellent 1.9µs 24 Excellent
Signal Level: 785mV 24 Excellent 940mV 23 Excellent

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 2


Field Device Details

Address: 16
Tag:
Polarity: Standard

Min Max
Value Result Value Result
Noise: 24mV Excellent 29mV Excellent
Jitter: 0.7µs Excellent 0.8µs Excellent
Signal Level: 896mV Excellent 901mV Excellent

Complete Frame

Start

End

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 3


Address: 20
Tag: 5150-PIT-00418

Device ID: 0011512051110113075438-460002449


Manufacturer: Emerson Process Management
Device Type: Rosemount 2051
Device Function: Pressure Transmitter

Polarity: Standard

Min Max
Value Result Value Result
Noise: 24mV Excellent 29mV Excellent
Jitter: 1.6µs Excellent 1.7µs Excellent
Signal Level: 803mV Excellent 804mV Excellent

Complete Frame

Start

End

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 4


Address: 21
Tag: 5140-PIT-00415

Device ID: 0011512051110113151041-450003057


Manufacturer: Emerson Process Management
Device Type: Rosemount 2051
Device Function: Pressure Transmitter

Polarity: Standard

Min Max
Value Result Value Result
Noise: 24mV Excellent 29mV Excellent
Jitter: 1.5µs Excellent 1.7µs Excellent
Signal Level: 810mV Excellent 811mV Excellent

Complete Frame

Start

End

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 5


Address: 22
Tag: 5140-FE-00412

Device ID: 0011518732-EPM-RFD00696937333C5D


Manufacturer: Emerson Process Management
Device Type: Rosemount 8732E
Device Function: Magnetic Flow Transmitter

Polarity: Standard

Min Max
Value Result Value Result
Noise: 24mV Excellent 34mV Excellent
Jitter: 1.4µs Excellent 1.6µs Excellent
Signal Level: 926mV Excellent 928mV Excellent

Complete Frame

Start

End

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 6


Address: 23
Tag: 5130-LIT-00830

Device ID: 0011515400-EPM-0x817BFF53


Manufacturer: Emerson Process Management
Device Type: Rosemount 5400 Series
Device Function: Radar Level Transmitter

Polarity: Standard

Min Max
Value Result Value Result
Noise: 24mV Excellent 29mV Excellent
Jitter: 1.6µs Excellent 1.8µs Excellent
Signal Level: 938mV Excellent 940mV Excellent

Complete Frame

Start

End

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 7


Address: 24
Tag: 5130-LCV-00830

Device ID: 002000EDC2-DCM_FF_1EA83820


Manufacturer: EIM Controls Inc.
Device Type: DCM Fieldbus Actuator
Device Function: Electric Actuator

Polarity: Standard

Min Max
Value Result Value Result
Noise: 24mV Excellent 29mV Excellent
Jitter: 1.3µs Excellent 1.9µs Excellent
Signal Level: 785mV Excellent 796mV Excellent

Complete Frame

Start

End

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 8


Address: 25
Tag: 5120-FE-00307

Device ID: 0011518732-EPM-RFD006796369D72D9


Manufacturer: Emerson Process Management
Device Type: Rosemount 8732E
Device Function: Magnetic Flow Transmitter

Polarity: Standard

Min Max
Value Result Value Result
Noise: 24mV Excellent 29mV Excellent
Jitter: 1.4µs Excellent 1.6µs Excellent
Signal Level: 932mV Excellent 933mV Excellent

Complete Frame

Start

End

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 9


Defined limit values

Low Out of Spec. Low Good Excellent High Good High Out of Spec.
Voltage: < 9.0V 9.0 ... < 9.0V 9.0 ... 32.0V > 32.0 ... 32.0V > 32.0V
Unbalance: < -84% -84 ... < -60% -60 ... 60% > 60 ... 84% > 84%
Noise: - - <= 50mV > 50 ... 100mV > 100mV
Jitter: - - <= 2.4μs > 2.4 ... 3.2μs > 3.2μs
Signal Level: < 200mV 200 ... < 400mV 400 ... 1200mV - > 1200mV

Date: 23/01/2014 03:27:06 p.m. SegmentoSALA(2B)RemoteRIO Page: 10

S-ar putea să vă placă și