Sunteți pe pagina 1din 6

1

EXPERIENCES WITH WIDE AREA COORDINATED


CONTROL OF FACTS DEVICES AND HVDC IN A
REAL TIME ENVIRONMENT
Dirk Westermann, Senior Member IEEE, Hubert Sauvain

trol network controllers. This yields a wide area control


Abstract – This paper outlines practical experiences from system (WACS) which is seen as a powerful concept to
the application of a wide area monitoring and control system ensure safer and more reliable system operation even in
in a real network environment. After outline a general archi- case of multiple fast network controllers (see also [6]).
tecture for system control, results of first prototype application Most of the application studies for WACS have been
for optimal power flow and damping control will be presented. carried out on a software simulation basis, where some
The last part of the paper focuses on the impact of data quality
within the communication system.
essential real world real-time constraints are difficult to
analyze. In order to study these particular boundary
Index Terms – Wide area monitoring, wide area control, conditions, a WACS has been setup within a reduced
power flow controllers, high voltage direct current, coordi- scale model of a part of the Swiss transmission grid. In
nated control, addition, this model contains fast network controllers
(Unified Power Flow Controller, Phase Angle Regula-
I. INTRODUCTION tors and High Voltage Direct Current Systems) which
are subjected to be coordinated and controlled by means
During the last years phasor measurement unit
of the WACS.
(PMU) based wide area monitoring systems (WAMS)
This paper outlines the general approach of WACS
have been evolved far beyond basic protection functions
architecture suitable to fulfill the coordinated control
[1]. Today WAMS technology is seen as a powerful
requirements as outlined above. As a first instantiation
technology platform enabling dozens of new application
some aspects of the proposed Three-Layer-Architecture
in power system control and operation (e.g. [2]-[5]).
for coordinated network operation, selected applications
In particular, certain coordinated control functions of
will be investigated with respect to their implementation
network controller like conventional phase angle regula-
in a real time simulation system. Results of comprehen-
tors, FACTS devices or HVDC systems are enabled by
sive lab tests will be given and discussed. They result
WAMS. In particular against the background of in-
from prototype implementation of certain control func-
creased amount of transcontinental energy transmission
tions covering various methods with respect to real time
WAMS can be used to avoid adverse interactions be-
constraints. The key technology is closed loop control
tween network controllers. Consequently, the WAMS
of network controller with WACS. Different control
technology can be seen as a platform for more secure
objectives like loss minimization, voltage profile or
operation of interconnected power systems. The opera-
damping control have been applied. The last part of the
tion of today’s interconnected power systems with cor-
paper will provide a closer look at the sensitivity of the
ridors to transmit bulk energy between different states
communication systems to data transmission distur-
demands the operation of the existing transmission as-
bances, i.e. how the quality of control might be im-
sets at their limits. On top of the aforementioned appli-
pacted.
cations, WAMS platform be can taken to setup a super-
visory system that allows for new energy management
functions. In particular, this applies to those areas, II. THREE-LAYER-ARCHITECTURE
which are supervised by different SCADA/EMS sys- Operation of network controllers in interconnected
tems within an interconnected power system. power systems is a very complex task in three dimen-
The next step towards an overall control system is to sions: control structure design, control objective defini-
operate the WAMS in closed loop mode in order to con- tion and data availability. With respect to comprehen-
sive system control all dimensions are of equal impor-
tance. Control structure design and control objective
Prof. Dr. Dirk Westermannn, Technical University of Ilmenau,
Institute of Electric Power and Control Engineering,
definition strongly depends on the application area. If it
P.O.Box 10 05 65, D-98684 Ilmenau, Germany comes to applications in interconnected power systems
(e-mail: dirk.westermann@tu-ilmenau.de) a coordinated operation is of utmost importance. This
underlines the need for a control system architecture
Prof. Hubert Sauvain, University of Applied Sciences HES-SO,
avoiding adverse controller interactions while covering
Pérolles 80, CH-1705 Fribourg, Switzerland
(e-mail: hubert.sauvain@eif.ch) all time ranges of operation (e.g. [7]).
2

Most of the approaches have been based on the as- The network comprises several generators, built as syn-
sumption of an ideal functioning of the network control chronous machines. For system studies typical faults
system (data availability) and the existence of suitable can be applied to the system at each node and / or on the
objective functions. Today the control objectives are lines at predefined locations. The scale of the model is
subjected to rapid changes. In the light of power market 1 kVA for 100 MVA and 400 V for rated voltage of the
deregulation the power flow objectives may change original system.
from loss minimization to maximum import capacity
from one operation cycle to another. Not least because
Fribourg
the advent of PMU technology and TCP/IP based com- 5
munication in substations (IEC 61850, [8]) – which will

L10
L9
PMU Schiffenen
become standard for system wide communication as
4
well – a comprehensive architecture covering the whole
range of application areas is needed. One approach cov-

< HVDC
ering all dimension of system control is a Three-Layer-

PFC
L8
Architecture (TLA) [9] (Figure 1).
PMU PMU

L6
L7
3 Payerne 1 Hauterive
L4

HVDC BtB
L5 EOS
PFC
Cleuson

Offline Applications Online Applications


HVDC >

L3
2 PMU

L2
L1
Montbovon

Network Layer

Figure 2: Topology of the transmission network

Economic Layer In order to study the impact of all kind of fast net-
work controllers the two power flow controllers (PFCs)
have been set up on a UPFC basis [10], [11]. The series
voltage capabilities of the UPFC have been designed to
be 60V / 3 per phase at 7.5 A line current. The follow-
Measurement Layer ing operation modes are available:
 reactive power compensation (shunt source)
Figure 1: General concept of the Three-Layer-Architecture  open loop current control (fixed series source)
The general concept of TLA is to consider the com-  closed loop current control (controlled series vol-
munication system (measurement layer), the system tage with P and Q set points)
economic state (economic layer) and the network state  Special control software allows the UPFC to oper-
(network layer) at the same time. While considering all ate like a conventional phase shifting transformer
three systems, time deficiencies inherent to each subsys- since most of the power flow control applications in
tem, can be incorporated in the controller design. Based interconnected power systems are based on this
on this all-embracing system view online and offline type of device.
applications can be tuned accordingly. As a conse- In order to study the behavior of embedded HVDC
quence, multi objective controller coordination becomes two types of schemes have been integrated into the net-
more precise. work. As reference for a parallel operation, a HVDC
transmission line has been integrated between Montbo-
III. LABORATORY SETUP von and Schiffenen. The shorter line between Montbo-
A. Network Model von and Payerne comprises a model of a HVDC Back to
Back (BtB) scheme, which can be considered as HVDC
The network model that has been built for real time based network controller. Both HVDC schemes are us-
simulation represents the power grid of the region of ing voltage source converter technology.
Fribourg in Switzerland according to Figure 2.
This analog simulation environment has already been B. Wide Area Control System
used for various WAMS and WACS application studies In the basic concept of a WAMS the PMUs are
[10]. The connection to the high voltage transmission placed in substations to allow observation of a part of
system at EOS Cleuson can be interpreted as slack node. the power system under any operation condition. For the
3

supervision and control of the network model up to four


PMUs have been used. They are integrated in the net- 
f  x, u    apiloss  b i  ci  
 
i
work model and synchronized by a conventional GPS (1)
signal. The data processing is based on the software   d u j  u ref
j 2
 eu j
i
PSG delivered by ABB [12], [13]. The phasor informa-
tion is provided to an application and control server, The first part of this function represents the cost of
where the control algorithms and general analysis func- losses and the cost of overload situations. The second
tions are executed (Figure 3). sum stands for a description of costs related to voltage
Wide Area Control System variations. The weighting factors a to e are utilized to
adjust the importance of each criterion (Table 1).
HVDC BtB 1 PMU
< HVDC Table 1: Overview on weighting factors according to [14]
2 PMU
HVDC > Factor Objective
3 PMU
PFC a minimization of active power losses
CAN Bus

4 PMU
PFC b keeping line loadings below 90%
c keeping line loadings below 100%
d minimization of voltage deviations from ref-
erences
e keeping bus voltages within acceptable lim-
Wide Area Monitoring
its
Application & Control
(LabView / MATLAB) (PSG)
In reference to the proposed TLA this application is
Figure 3: General structure of the wide area control systems an excellent example of how the economic layer and the
The lab control is realized by LabView software; network layer can be combined. The measurement layer
higher analysis and control applications are utilizing is considered in the lab realization of the coordinated
MATLAB environment. The control signals are distri- power flow controller approach as well. In the lab envi-
buted to the network controllers via a controller area ronment the PMU deliver the actual loading status of
network bus (CAN Bus). For the analysis of the com- the network. Topology status, network controller status
munication with respect to its sensitivity against data and control objectives are manually pre-adjusted. This
transmission errors, the PMU bus structure has been models the real application frame, where the operator
split up into two independent paths. This reflects a more defines the actual control target. By extracting data from
realistic situation of data transmission from remote loca- the SCADA system, topology status and PFC status can
tions. be derived automatically. Based on these information
the setpoint optimization comprises a topology proces-
IV. APPLICATION STUDIES sor, the optimal power flow instance and a module for
result verification. In the utilized setup these routines
Out of the wide range of potential application scena- have been realized in MATLAB (Figure 4).
rios for a WACS those have been chosen, which are
considered to be of significant importance:
 Coordinated control of phase angle controllers Topology Setpoint Ctrl
Status (MATLAB)
 Power oscillation damping with embedded HVDC Setpoints
The control objectives of the network controllers PFC Topology PFC
have been chosen according to the TLA. Based on in- Status Processing
stallation locations of PMUs, physical (network) and Control Load Flow
economical constraints have to be taken into account. Objective Optimization
To complement the investigations of these two applica- User
Actual Result Information
tions cases the third application study will focus on the
impact of disturbances on data transmission. Loading Verification
(PMU)
A. Coordinated control of phase angle regulators
Figure 4: Overall structure of the coordinated control realiza-
The algorithms for coordinated control of network tion as realized in the lab environment
controllers has been adopted from [14] since this ap-
proach shows optimal performance with respect to As results of this calculation a new set of setpoints is
coordinated controller setpoint settings for steady state processed and uploaded to the device controllers. For
load flow determination. In brief, the basic idea is to run the sake of simplicity, i.e. to study the impact on the AC
an optimal power flow utilizing all setpoint definition network controllers, the HVDC schemes have been dis-
of network controllers as controlled variables. The fol- abled (BtB operated in bypass mode). For the basic
lowing objective function will be used: functionality test, the objective lies on minimizing the
network losses while having a balanced voltage profile
4

throughout the system. The weighting factors have been


PMU
chosen accordingly: Controller Setpoint
Measurement
a =106, b = 103, c = 105, d = 104 and e = 5.102.
Figure 5 shows the change in node voltage profile 2 3
with respect to the bus voltages without optimization. HVDC BtB
1,5%
Change in node voltage

1,0%

0,5% Network
Equivalent
0,0%

-0,5% Figure 7: General system equivalent for the application of a


damping controller for the HVDC scheme
-1,0% In this configuration the most simple control system
1 2 3 4 5 configuration has been chosen – a PI control structure
Node Number (Figure 8). The parameters have been tuned according
to the network representation as shown in Figure 7.
Figure 5: Change in node voltage as a results of the power
flow optimization Kp +
It is obvious that a net increase of the average node Setpoint
voltage is the result out of loss and loading optimiza- Ki z +
tion. The loading of the particular lines is decreased in z-1
general (Figure 6). PMU
Measurement
20,0% Figure 8: Simple control structure utilized for damping con-
trol of the HVDC scheme
10,0%
Change in Line Loading

The advantage of the lab environment is to excite


0,0% power oscillations under controlled conditions. In gen-
-10,0% eral there are two options to model power oscillations:
-20,0%  Tune the controllers in the system and arrange the
system topology to excite oscillations after a pre-
-30,0% defined disturbance.
-40,0%  Modulate the signal of the torque control at one of
the generators in the system – supposing that the
-50,0%
generators are driven by controlled machines.
1 2 3 4 5 6 7 8 9 10 For this study the second option has been taken since
Line Number
the frequency of the oscillations can be directly adjusted
by the torque control of the system. A complex mathe-
Figure 6: Change in line loading as a result of the power flow matical model of laboratory system for tuning purposes
optimization is not needed in this case. The monitoring of power os-
The optimization algorithm not only minimizes the cillations by WAMS provides the input signal for damp-
loading impact by reactive power flow but also takes ing control. Due to the time delay in data transmission
advantage of the slack node contribution to the entire and processing the corresponding input signal is sub-
load flow pattern. In total an entire loss reduction could jected to some minor deficiencies as shown in Figure 9.
be achieved by 1.6%. It should be mentioned that loss 0,6
reduction could be achieved by a proper selection of 0,4
weighting factors in the objective function. It can be 0,2
p23 [pu]

shown that losses increase for the sake of a more ba- 0


lanced voltage profile. -0,2
-0,4
B. Power oscillation damping with embedded HVDC -0,6
The concept of embedded HVDC allows handling a 2500 4500 6500 8500 10500
HVDC scheme like a “regular” network controller for t [ms]
e.g. power oscillation damping purposes. The objective Figure 9: Power oscillation as monitored by a wide area
of the case study presented here is to show the basic monitoring system
functionality of such a setup in a lab environment utiliz- With some appropriate signal rehashing this power
ing measurement signals from PMUs. The basic setup flow measurement signal is suitable enough to be used
of the studied configuration is shown in Figure 7. for damping control purposes. Even though the most
5

simple control system setup has been used for the damp- to the processing unit) impact the quality of PMU based
ing control realization the magnitude of the power oscil- system wide control ? In order to investigate this repre-
lation between node 2 and 3 can significantly be re- sentative scenario the four PMUs have been connected
duced (Figure 10). to two different OPC servers. Each OPC server is con-
nected by means of TCP/IP to the central data collection
and processing unit. One of the data channels is sub-
2DPmax

jected to typical disturbances (Figure 12).


OPC 1 OPC 2
1 PMU PMU 3
3 min
2 PMU PMU 4

Setpoint Power Controller Controller


Oscillation active inactive Disturbance
TCP / IP
w/o ctrl.
Figure 10: Power flow from nodes 2 to 3 with and without
damping control
Data Collection &
The investigated scenario comprises a regular set- Processing
point control mode of the DC scheme. After approx-
Figure 12: System setup for the investigation of disturbances
imately 2 min of normal operation the power oscilla- in the measurement layer
tions are excited (3 min). Then the damping control be-
comes active for around the same amount of time. The time critical information is the angle information
In a second simulation run, certain disturbances on of voltages and currents at the PMU location. Therefore,
the measurement layer occurred. The resulting bad qual- the angle signal has been utilized as reference to eva-
ity of input signals for the control system leads to major luate the impact of disturbances. As reference serves the
disturbances in the power flow of the line. These distur- angle difference between node 4 and node 2 (see equ.
bances are almost of same magnitude then the original (2)).
power oscillations to be damped (Figure 11). T0  DT
1
D ref 
DT 
T0
4 (t )   2 (t ) dt
(2)
2DPmax

j i ( t )
 i (t ) : u i (t )  ui (t )e
Four typical disturbances in a packet switching net-
5 min work have been investigated (Table 2). “Delay” a de-
termined packet delay. “Jitter” considers a “Delay” plus
a random delay for each packet in a defined time inter-
Damping controller Disturbance in val. “Package loss” described the probability of loosing
active measurement a packet during the transmission. Finally the “Reduced
data bandwidth” criterion describes the effect of data channel
Figure 11: Power flow from node 2 to 3 with and without overload resulting in a bandwidth reduction for data
damping control; impact of artificial disturbances transmission (Figure 13).
in data transmission
Table 2: List of disturbances subjected to the dedicated communi-
Dedicated data supervision has not been applied in cation channel
this application study. Nevertheless, this tremendous
impact shows the importance of input data quality and Disturbance Parameter
motivates a sensitivity analysis of the communication Delay 10ms .. 500ms
system as described in the next section. Jitter 80ms  20ms; 100ms  50ms
C. Sensitivity analysis of the communication system Package loss 0.1% .. 1.0%
Sensitivity of the communication system against dis- Reduced bandwidth 19.2kB .. 250kB
turbances in the data communication system is consi-
dered as key factor for the quality of the overall control The result of the communication system analysis
system. As shown in the second case study, system be- shows measurement errors below 4% except for the
havior can turn out to be even worse when utilizing “extreme” situations of 500ms packet delay, a huge Jit-
faulty input signals. When generalizing the setup of a ter and abnormally low bandwidth limitation.
wide area communication system at least two different
OPC servers are processing data from (remote) loca-
tions. Consequently, the question is: How will a distur-
bance on the data channel (from one of the OPC servers
6

REFERENCES
[1] Bhargava, B.; Rodriguez, G.: „Monitoring the power
grid“, Transmission & Distribution World, December
2004
[2] Korba, P; Larsson, M; Rehtanz, Ch.: “Detection of Os-
cillations in Power Systems using Kalman Filtering
Techniques”, IEEE Conference on Control Applications,
2003
[3] Larsson, M.; Rehtanz, Ch.; Westermann, D.: “Improve-
ment of Cross-border Trading Capabilities through
Wide-area Control of FACTS”, BULK POWER
SYSTEM DYNAMICS AND CONTROL – VI, Cortina
d’Ampezzo, Italy, August 2004
[4] Junce, D.; Zexiang, C.: “Mixed Measurements State
Estimation Based on Wide-Area Measurement System
and Analysis”, T&D Conference and Exhibition: Asia
and Pacific, 2005 IEEE/PES, 2005
[5] Westermann, D.; John, A.: “Demand Matching Wind
Power Generation With Wide-Area Measurement and
Demand-Side Management”, IEEE Transactions on
Energy Conversion, Vol. 22, Iss. 1, March 2007
Figure 13: Relative measurement error for certain disturbances [6] Tomsovic, K.; Bakken, D.E.; Venkatasubramanian, V.;
in data transmission within the measurement layer Bose, A.: “Designing the next generation of real-time
control, communication, and computations for large
V. CONCLUSION power systems”, Proceedings of the IEEE, Vol. 93 , Iss.
5, May 2005
The advantage of a wide area control system results
[7] Rehtanz, Ch.; Westermann, D.: “Non-intrusive control
from direct utilization of network state variables without
system architecture for AC power transmission”, Pro-
slow intermediate software modules. As comprehensive ceedings of the 7th international conference on AC-DC
approach for system wide control a Three-Layer- Power Transmission, IEE, London, England, 2001
Architecture has been introduced, where WACS can be [8] Brand, K.-P.: “The standard IEC 61850 as prerequisite
identified as one key component. for intelligent applications in substations”, Power Engi-
In a reduced scale power system setup two different neering Society General Meeting, June 2004
application areas of WACS have been analyzed: Coor- [9] Westermann, D.: “System Wide Control assuring Stabili-
dinated control of network controllers with optimal ty”, IEEE Workshop on Power System Stability – New
power flow and damping control with embedded Challenges and Solutions, Dättwil, Switzerland, No-
HVDC. In the first application the basic functionality in vember 2006
laboratory setup has been demonstrated. For the realiza- [10] Westermann, D.; Sauvain, H.: “Experience with wide
tion some software modules had to be developed, which Area Monitoring and Facts Control in a Real Time Si-
have to satisfy some real time requirements as well. mulator”, PowerTech, St Petersburg , Russia, 2005
This particular point has not been studied here and is [11] Pellerin, M.: "Démonstrateur pour FACTS”; Conférence
subjected to future research work. EPF, Montpellier, 2002
In a second application study the basic damping be- [12] Rehtanz, Ch.; Larsson, M.; Zima, M.; Bertsch, J.: “Sys-
havior of a HVDC scheme utilizing PMU measurement tem for wide-area protection control and optimization
values has been shown. It could be seen that the prere- based on phasor measurements”, Power System and
quisite for a proper functioning of a damping control is Communication Systems Infrastructure for the Future
a high data quality delivered by the WACS. In case of Conference, Beijing, China, 2002
disturbances, the controller might even deteriorate the [13] ABB Product Description: “Wide Area Measurement,
overall system performance. This effect has motivated Monitoring, Protection and Control”, 2003
the third case study, where the impact of disturbances [14] Glanzmann, G.; Andersson, G.: “Coordinated Control
on the data transmission has been analyzed. As time Facts Devices based on Optimal Power Flow”, North
critical signal the angle difference between nodes has American Power Symposium (NAPS), Ames, USA,
been considered in detail. As expected it could be 2005
shown that only large disturbances lead to significant
measurement errors. Future work has to be carried out,
to provide mechanisms for the detection of large distur-
bances in the data channel. This is considered as one
key issue for the realization of WACS.

S-ar putea să vă placă și