Sunteți pe pagina 1din 12

TECHNICAL

TB-226
BULLETIN
Model NCM300 Zone Control System

LEAVE THIS BULLETIN ON THE JOB SITE FOR FUTURE REFERENCE


The New NCM300 panel provides intelligent control of Heat 14
21
28 40
43
46 130
140
150
C3 D1 R4 R8
ZONE 3
Pump or Conventional forced air zoning systems at a MOTOR 7 35 37 49 120 160 R5 SUPPLY
AIR
M6 OFF 42 34 52 110 170 R10 SENSOR
maximum of three zones using motorized dampers and M4
STAGING
W2 TIMER
LOW TEMP
LIMIT
HIGH TEMP
LIMIT U2 R9
2
M2 R7 R6
practically any off-the-shelf thermostat. With features like M1 NCM-300 D2
R70 1
C4
Automatic changeover, Timed or Thermostatic staging, ZONE 2
MOTOR
K1
D3
C8 U1
R69 ZONE 3
T'STAT
R28 RESET U3 R13

NCM300 Ver 2.3


Field selectable Features and Supply air Sensing capability, M6 R14 R17 R19 C

Copyright EWC/ACI 2006


C9
M4 R16 R23 W/E

ALL rights reserved


the NCM300 provides the highest level of performance and M2 K2 R21
C7
R24 O/B
M1 D4 R20 Y
R25
versatility in a non-expandable zone control panel. Perfect ZONE 1
R26
R22
C5 U4 R29 R
R27 G
for new construction and retro-fit applications. M6
MOTOR
K3
R317
R30
R34
D5 R66 ZONE 2
M4 R32 T'STAT
Zone Capacity Controls two or three air zones with M2 C1 C2
Z1
R36
C6 R33 C
M1 R38 W/E
24vac Power Open/Close or Spring F1
D6
OFF < > ON
R37
R40
R39 O/B
24 VAC HP < SYSTEM > GAS
Y
Assisted motorized dampers. T'FORMER R35
HC < TSTATS > HP
OFF < PURGE ASST > ON
R42
R
R 90 < PURGE > 120 S
R43
K4 0 < FAN DLY > 45 S R41 G

Compatible Will control 1 stage Heat Pumps with C


D7 O < RV > B
OFF < SAS > ON
U5
R44
R44 GAS < FAN > HYDRO
R47 ZONE 1
HVAC Systems Electric auxiliary heat. Will also control SYSTEM U6 R49
T'STAT
W2/E R45 C
K5
1 & 2 stage Gas or Oil furnaces. Also W1/B D8 LED1 STATUS
R48
R48
W/E
O R52 O/B
LED2 SUPPLY AIR LIMIT
Straight Electric furnaces or Hydronic Y
R51 R54
Y
R53 LED4 ZONE 3 OPEN R55
G R
Heat with 1stage air conditioning. RH
K6
D9 LED3 ZONE 2 OPEN
R54
G
R57 R55
RC LED6 ZONE 1 OPEN ONE
R56 R50
Compatible The NCM300 is compatible with C
LED5 W2 / E R61
ZONE
R63
Thermostats most single stage Heat/Cool type RC/RH
LINK
K7
D10
LED7 W1 / B
R62

Thermostats. Two stage Heat Pump LED8 COMPRESSOR


R
R65

LED9 FAN CONTROLS INC.


Thermostats can be used if staging CONTROL SYSTEM Englishtown, NJ

by temperature is desired. Hard Figure 1. NCM300 panel


Wired, Power Robbing or Battery
Powered type thermostat models Thermal The NCM300 has a 2.5amp thermal circuit
can be used. Breaker breaker in place of a fuse that protects the
NCM300 from shorted circuits in the
Automatic The NCM300 panel features automatic thermostat and damper field wiring. It will
Heat/Cool changeover from any thermostat not protect against shorts in the HVAC
Changeover allowing for individual zone comfort system wiring. DO NOT exceed a 60va
from the zoned HVAC system. transformer to power the panel.
NOTE: When the circuit breaker is tripped it will
The STATUS LED blinks slowly during get hot and all of the panel LED’s will stop
Status LED functioning. To reset the breaker, locate the
normal operation to indicate the micro
short by removing all wires connected to the
processor is operating properly. panel, one at a time. When the shorted wire is
removed the panel will resume normal
System LEDs A total of 9 LED’s indicate the system operation. Now you must repair or replace the
status and mode of operation. shorted wire before you re-connect it.

Operating TEMPERATURE: -20° to 160°F (-29° to


LEDs labeled Zone 1 thru Zone 3 71°C)
Damper LEDs Conditions
indicate which dampers are energized HUMIDITY: 0% - 95% RH Non-Condensing.
to open.

Operating INPUT VOLTAGE: 19-30VAC 60 Hz Indoor Fan Any zone can activate the indoor fan
Power Transformer 40-60VA MAX. NEC Class 2. Control and only the dampers in zones calling
CURRENT DRAW: Max 14VA @ 24VAC. for continuous fan operation will open.
OVER-CURRENT PROTECTION: 2.5 Continuous fan operation will only
amp or 60VA. occur when there are no active or
pending heat or cool demands.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com

P/N 090375A0226 REV. F Copyright © 2006 - 2009, EWC Controls Inc. ALL Rights Reserved
Built-In Timer The panel has built-in timers that
RESET Momentarily pressing the RESET button
Settings insure safe HVAC system operations. BUTTON clears the built-in timers controlling the
*Start-up Delay Timer 4 minutes, fixed. Start-up timer, Minimum run timer, Short
*Minimum Run Timer 2 minutes, fixed. cycle timer, W2 timer, Supply air sensor
*Short Cycle Timer 2 minutes, fixed. RESET timer and the Changeover timer. This
Reset the CPU enables you to test the installation faster.
*Changeover Timer 4 minutes, fixed. anytime you make
dip-switch changes Caution should be observed when using
*Opposing System 20 . minutes, fixed. to the NCM300 panel! this button.
Service Timer
DO NOT use a sharp
*Second Stage Off or 7 to 42 object to press the Pressing the RESET button for 7
Heating Timer minutes, adjustable. button! Your finger
seconds will reset the CPU.
tip will work fine.
TIMER DEFINITIONS
Start-Up Delay Upon initial power up or after a Selecting the Options Using the DIP Switches
Timer power failure, the panel will not start 8 DIP switches allow you to select the features specific
the equipment for 4 minutes. to your very own zoned HVAC system.
Minimum Run When a call is activated, the zone Select the type of HVAC system the
Timer HP < SYSTEM > GAS
panel will run the HVAC system in that panel will control. Heat Pump (HP) or
mode for a minimum of 2 minutes. Gas/Oil/Hydronic with A/C. (GAS)
Short Cycle When the HVAC system is satisfied,
Timer the zone panel will not resume the HC < TSTATS > HP Select the type of Thermostats you
same call for a minimum of 2 minutes. will use. Select HC for conventional
Heat/Cool type thermostats or select
Changeover At the end of a call, a 4 minute timer is HP for Heat Pump type thermostats.
Timer started and the zone panel will not
switch to the opposite mode of OFF<PURGE ASST>ON Select ON to allow the NCM300 to operate
the fan during the 90/120 second purge
operation until the timer has expired.
cycle. Works in both heat and cool mode.
Opposing A 20 minute delay must expire, or the Set the switch to OFF to allow the system
System active zone(s) must satisfy, before to operate on it’s own fan purge cycle.
the panel will honor a thermostat
Service Timer demand to changeover to the Select a purge time of 90 seconds or 120
90< PURGE >120s
opposite mode of system operation. seconds. The damper(s) on the last zone
2nd Stage calling will be held open for that time while
The W2 TIMER sets the total amount
Heating Timer all other zone dampers remain closed.
of time delay before second stage
21 heating is energized. 1st stage heat Select 45 seconds to allow the hot
14 28 0< FAN DLY > 45S
will stay energized when 2nd stage water or steam coil to heat up before
7 35
heat activates. If desired turn the the fan starts. Select 0 seconds and
OFF 42 Timer OFF and let your heat pump the fan will start immediately upon a
STAGING
W2 TIMER thermostats stage up for you. call for heat. Switch # 8 must be set
Heating and Cooling to HYDRO for this feature to work!
Limit Settings The Heating Limit potentiometer sets 0 < RV > B
140 Select O or B for the type of
the supply air temperature at which
130 150 Reversing Valve operation of your
the heating is cycled off and the fan
120 160 heat pump.
continues to run until, the supply air
110 170 OFF < SAS > ON Select ON if you are using a Supply
temperature has dropped below the
HIGH TEMP Air Sensor with the NCM300. Select
LIMIT heating limit set point. 3 Minutes min.
OFF if you have not installed a sensor.
The Cooling Limit potentiometer sets
43
40 46 the supply air temperature at which GAS< FAN >HYDRO Select the GAS position when setting
37 49 the cooling is cycled off and the fan up for gas or heat pump systems.
continues to run until, the supply air Select HYDRO when setting up for
34 52
temperature has risen above the Straight Electric or Hydronic
LOW TEMP
LIMIT cooling limit set point. 3 Minutes min. (Steam/Hot Water) heating systems.

2 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
WIRING INSTRUCTIONS
WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO
AVOID ELECTRIC SHOCK OR EQUIPMENT DAMAGE. ALL WORK SHOULD BE PERFORMED TO LOCAL AND NATIONAL
CODES AND ORDINANCES. USE 18 AWG SOLID COPPER, COLOR-CODED, MULTI-CONDUCTOR THERMOSTAT CABLE.

Thermostat The NCM300 zone control panel requires standard 1 stage heat/cool thermostats in all zones, regardless
Wiring of the application. 2nd stage heat output is controlled by an adjustable timer on the panel. If you prefer,
the NCM300 will also work with any off the shelf 2 stage Heat Pump Thermostat. 2nd stage heat will then
be thermostatically controlled. Typical thermostat wiring diagrams are shown below.

HEAT/COOL THERMOSTATS HEAT PUMP THERMOSTATS

MODEL EWT-3707 MODEL EWT-3707


B C W1 E O Y1 R G W2 L B C W1 E O Y1 R G W2 L
ZONE *
T'STAT **
ZONE
C T'STAT
W/E C *
O/B W/E
Y O/B
R Y
G R
ONE G
ZONE ONE
* Common wire not required if batteries are used. ZONE * Common wire not required if batteries are used.
** Field installed jumper.
Figure 2a. Model EWT-3707: Configured for 1 heat 1 Figure 2c. Model EWT-3707: configured for 2 heat 1 cool
cool (SS1 mode). See thermostat
instructions for further details. heat pump (HP1 mode). See thermostat
instructions for further details.

WIRELESS THERMOSTAT: RECIEVER MODULE TOUCHSCREEN THERMOSTAT


MODEL EWT-3900 MODEL EWT-3102
C W1 L W2 Y1 R G E O B S1 S2 L Y2 C W2 E O/B Y1 R G

ZONE
T'STAT
**
C ZONE
T'STAT
W/E C *
O/B W/E
Y O/B
R Y
G R
G
Figure 2b. Model EWT-3900: Wireless Thermostat.
Configured for 1 heat 1 cool (SS1 mode). * Common wire not required if batteries are used.
Field installed jumper.
Can be configured for heat pump. See **
Figure 2d. Model EWT-3900 Wireless Thermostat:
Configured for 2 heat 1 cool heat pump (HP1
Mode). See thermostat instructions for further
Details.
NOTE: The New NCM300 allows the user to install Heat Pump thermostats on all zones. This allows the user to over-
ride the W2 Timer and energize the auxiliary heat via thermostatic demand! You may still use regular Heat/Cool type
thermostats with a Heat Pump system and use the W2 Timer to energize the auxiliary heat. Doing so may save more
energy. This new design simplifies the thermostat selection process and allows the installer to easily adapt the
NCM300 to most residential applications.

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-635-8646 E-Mail- info@ewccontrols.com 3
System Wiring Typical heat pump system wiring with electric
The NCM300 panel was designed to be easy to understand
Heat Pump resistance backup heat. Wire up the reversing
and wire up. We have provided several typical field wiring with O or B Type valve to either O or W1/B, depending on your
diagrams to review. Your actual field wiring may vary. Notice Reversing Valve type of system. Applies to air cooled or
that you may now connect the 24vac “C” common terminal
geothermal / ground source HVAC systems.
from the HVAC system to the NCM300 “system” terminal
block. This provides a convenient place to reference the
HVAC system 24vac common wire and helps to simplify the
AIR HANDLER
troubleshooting process. WITH 1 0R 2 STAGE
ELECTRIC RESISTANCE
BACKUP HEAT NCM300
Typical gas/electric system showing 1 HEAT PUMP
Single or 2 stage heating. Note the jumper 1 STAGE
W1 W1
Transformer
(link) between RC and RH. There is SYSTEM
Gas/Electric
no need to install your own jumper. X/W W2 W2 W2/E
Systems W1/B
Y Y Y * O
Y
Oor B G
G G
GAS/OIL
Furnace
NCM300 R R R
RH
RC
OUTDOOR
CONDENSING
1or2 STAGE C C C C
UNIT SYSTEM
W2 W2 W2/E RC/RH
W1 W1 W1/B LINK
Y Y1 Y1
O
Y
C G G G

R
RH * Connect either the O or the W1/B.
R RC
In a typical O type reversing valve system, there
C
C C will not be a connection to the W1/B terminal!
RC/RH Figure 3c.
NOTE: You may connect the ‘C’ common LINK
terminal from the HVAC system to the NCM300
to make troubleshooting a little easier.
Your Oil furnace may not provide factory isolation for
Two the Primary Burner Control. Simply cut the Rc/Rh link
Figure 3a.
Transformer on the NCM300 and wire up to the Fan Center as
Note: Your Hydronic Air Handler may include a W terminal.
Oil Heating shown. Then run the T&T connections to the Rh and
That means it may have it’s own isolation circuit. If you can Systems the W1/B terminals to complete the control wiring.
confirm this, simply connect the W1/B terminal to the W
terminal on the air handler. Do not cut the Rc/Rh Link. Wire TYPICAL Fan Center NCM300
Two up your Boiler Control or Circulator Control to the isolation OUTDOOR TERMINAL
Transformer contacts or wires provided in the air handler. (Follow dashed CONDENSING BLOCK
SYSTEM
Hydronic Heat lines)The fan is controlled via time delay relay inside the air UNIT

Systems handler or use the Fan Hydro switch on the NCM300. W2/E
Y Y W1/B
TYPICAL Hydronic Y G
O
G
Air Handler Y
NCM300 R
TERMINAL C R G
RH
OUTDOOR BLOCK C C
CONDENSING RC
SYSTEM C
UNIT
W W
W2/E
Y Y W1/B
RC/RH
Y G G
O
Y
LINK

C R R G
RH
C C RC YOU MUST cut
C the Rc/Rh link
T T
OEM provided
ISOLATION RC/RH
TERMINALS LINK
OR WIRES

OIL T
TYPICAL BOILER or BURNER
DO NOT cut FURNACE
PRIMARY
PRIMARY BURNER CONTROL T
the Rc/Rh link CONTROL
BOILER CONTROL
CIRCULATOR
RELAY OR HOT T
WATER ZONE VALVE
CONNECTION T

Figure 3b. Figure 3d.


4 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-635-8646 E-Mail- info@ewccontrols.com
DAMPER WIRING
Note: All zone dampers default to the "OPEN"
2 Wire Spring Return Motor Wiring
position after a purge delay has occurred.
Dampers also default “OPEN” during
changeover & short cycle delays, and when EWC Controls
Spring Return Motor Wiring
all zone demands are satisfied, and no MA-ESR
signals are detected from the thermostats.
REFERENCE THESE DIAGRAMS PRIOR TO M6
INSTALLATION AND POWER WIRING. DOING SO WILL {
Either one M4
SAVE TIME AND LABOR LATER ON. Not both
M2
NC NO C M M
M1
ZONE DAMPER MOTOR
Auxilary
TERMINAL BLOCK SPDT
End Switch
DESIGNATION & FUNCTION Dry Contacts
Rated for
ZONE
24vac only
MOTOR A Spring Open Damper is wired to M1 & M6
.
A Spring Close Damper is wired to M1 & M4
Terminal M6 24vac to Close a damper(s) M6
Terminal M4 24vac to Open a damper(s) M4
Figure 5
Terminal M2 Constant 24vac HOT M2
Terminal M1 Common 24vac M1

ZONE
MOTOR

. 1 4 6
M6
Figure 4a
M4
All Models ND & URD Damper Wiring M2
M1
ZONE
MOTOR

M6
1 4 6

1 4 6

M4
M2
M1

Multiple ND or URD
1 4 6

Figure 4b Damper Wiring on a


Single Zone Terminal
1 4 6

NO 3
ZONE
MOTOR Block
M6
M4
C 1
1 4 6

M2
M1
Figure 6
NC 2 COIL
24 vac
R1 Isolation Relay
1 4 6

SPDT action with 24 vac coil On all these dampers and most older style
Relay is shown de-energized.
All dampers are closed. dampers, including competitor’s dampers,
always wire up number to number.
H L1
1 4 6

To Line Voltage
Provide over current
C L2
protection Do not overload the NCM300 Thermal
Separate 24 vac
Transformer
Circuit Breaker. Use a 24vac UL listed
Multiple Damper Wiring on a Single Zone, using a Separate Transformer
and an Isolating Relay. Maximum of 6 dampers per 40 va transformer. transformer at 60va maximum power
Figure 4c rating!
5
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
SERVICE GUIDE
Some Helpful All voltage measurements on the Check 24VAC Measure 24VAC at all damper M1 and
Guidelines NCM300 panel should be made with Power M2 terminals and all T-stat R and C
the ground lead of your meter on terminals. See Table 1 if any of these
terminal “C” of the 24VAC input voltages are incorrect.
terminals.
HVAC System If the HVAC LED indicators are
All voltage measurements at the HVAC
Not Responding responding properly, but the system
System Terminal Block (W1/B, O, Y, Properly appears to be malfunctioning, check
W2/E & G) should be made with the
that the HVAC system is wired correctly
meter’s ground lead on the terminal
and that the DIP switches have been
“C” at the HVAC system block.
properly set.
Using the LED The STATUS LED should blink at
Indicators 1second on / 1 second off, to indicate If the HVAC LEDs are not responding
the microprocessor is operating properly, check the calls on each zone
properly. thermostat. If the calls indicate that the
HVAC system should be activated and
The SUPPLY AIR LIMIT LED will is not, press the RESET switch to
illuminate if the panel senses a cancel the timers. Also check that the
discharge temperature in excess of the DIP switches have been properly set. If
high or low limit set points. The LED will the problem persists, see Table 3 for
blink rapidly if the sensor is open, trouble shooting help.
shorted or disconnected. The panel
will function normally but with no Table 1. Detecting 24VAC Shorts
supply air temperature control until the
open or short is repaired. Detecting All LED’s will be off and the panel
24vac Shorts will appear to be dead! you will
The Zone Damper LED’s will measure 24VAC at the transformer
illuminate to indicate which dampers terminals R & C, but not at any damper
should be open. M1&M2 terminals, or any zone
The W1/B LED indicates that the panel thermostat R & C terminals.
CAUTION: The thermal breaker will be
is in the 1st stage heating mode or, the
hot to the touch.
“B” type reversing valve output is
active. Remove the power to the panel and
Isolating
The W2/E LED indicates 2nd stage 24vac Shorts allow the thermal poly fuse to cool
heat or Emergency heat has been down.
energized.
Remove the wire at each zone
The COMPRESSOR LED indicates thermostat R terminal and test if the
the compressor is energized. short still persists by restoring power to
the zone panel and testing as
The FAN LED indicates the fan is
described above. If the short dis-
energized.
appears, check the zone thermostat
wiring and the thermostat itself. This
Dampers Not If the Zone LED indicators are
applies if the thermostat requires the
Responding illuminated but the dampers appear to 24 volt (C)common, or the R wire could
Properly be malfunctioning, check the damper be shorted to the building ground.
field wiring.
If the short still persists disconnect all
If the ZONE LED’s are not responding
the wires at each damper terminal (M1,
properly, check the calls on each zone M2, M4 & M6). Restore power and test
thermostat. If the calls indicate a as described above. If the short clears,
damper should be energized and is check the damper wiring and the
not, press the RESET button to cancel dampers for shorts with a continuity
the timers. If the problem persists, see tester. If the short still persists, call the
Table 2 for service help. technical support hot-line.

6
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
Table 2. Detecting Damper Problems
Damper LED On Check the damper wiring to insure it Testing Damper For a RDN/SMDL/BMDL damper,
But Damper Not is correctly wired. Be sure the wires Motors connect 24VAC common to terminal
Responding are secured in the terminals. Test the 1, and 24VAC to terminals 2 and 4.
damper motor to insure it is properly The damper should open. Remove
operating. If the problem still persists, 24VAC from terminal 4 and the
contact technical support. damper should close.
For a BMD/SMD/ND/URD damper,
Check that the STATUS LED is connect 24VAC common to terminal
NCM300 1, and 24VAC to terminal 4 and the
Damper LED blinking. If it is not, the panel may be in
damper should open. Remove
Not Responding a shutdown mode due to a short in the
24VAC from terminal 4 and apply
field wiring. See Table 1. Detecting 24VAC to terminal 6 and the damper
24vac shorts. should close.
Press the RESET for 1 second to For a power close spring open
clear any time delay(s) that may be damper, connect 24VAC to the two
keeping the call off and the damper motor “M” terminals, and the damper
from not responding. should CLOSE. Remove the 24VAC
and the damper should OPEN. For a
Check the voltage at each zone power open damper, the action will
thermostat terminal W, Y and G be reversed.
terminals to insure the damper should
be activated.
If the problem still persists, call the
technical support hot-line.

Table 3. Detecting Heating, Cooling and Fan Problems

Panel LEDS Check the HVAC wiring to insure it is Press the RESET button for 1 second to clear
On But System correctly wired. Be sure the wires are the time delay that may be preventing the
Not Responding secured in the terminals. Check that call. The panel could be in minimum run
there is 24VAC at the Rc and Rh time, short cycle delay, changeover delay or
terminals. Use the HVAC system opposite system timing mode.
common (C) for the ground lead of
your meter. Check that Rh and Rc are If the system still does not respond, measure
connected if the system uses a single the voltage at each zone thermostat terminal
transformer. W/E, Y, & G to insure they are correct and a
call is in order.
For a gas/electric system test the
HVAC by shorting terminals Rh and
W1/B together to activate the heater, Measuring Heat/Cool thermostats will apply 24vac to
Rc to Y to activate the compressor and Thermostat the W/E terminal during a heating call.
Rc to G to activate the fan. If the HVAC Voltages During a cooling call, 24vac is applied to
system has responded properly, call both Y & G. During a continuous fan call,
EWC technical support. 24VAC is applied to the G terminal.

For a heat pump system test the Be sure the Rc and Rh terminals at the
heating by jumping terminals Rc to Y, thermostats are jumped together if your
W1/B and G. For a cooling test jump specific installation requires it.
Rc to Y, O and G. Heat Pump thermostats will apply 24vac to Y
Check that the STATUS LED is and G during a 1st stage heating call. 24vac
LEDs and will be applied to W/E during a 2nd stage
System Not blinking to insure the computer is
operating properly, press and hold call. In Emergency mode, 24vac is applied to
Responding W/E & G. During a cooling call, 24vac is
the RESET button for 7 seconds to
reboot the CPU. applied to Y, G & O.

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com 7
21 43 140 C3 D1 R4 R8
14 28 40 46 130 150
ZONE 3
R5 SUPPLY
MOTOR 7 35 37 49 120 160
AIR
M6 OFF 42 34 52 110 170 R10 SENSOR
STAGING LOW TEMP HIGH TEMP
M4 W2 TIMER LIMIT LIMIT U2 R9
2
M2 R7 R6
M1 NCM-300 D2

C4
R70 1
K1 R69
ZONE 2 C8 U1 ZONE 3
D3
MOTOR RESET T'STAT
R28 U3 R13

NCM300 Ver 2.3


M6 R14 R17 R19 C

Copyright EWC/ACI 2006


C9
M4 R16 R23 W/E

ALL rights reserved


R21 C7
M2 K2
R24 O/B
D4 R20
M1 R25 Y
R22
R26 C5 U4 R29 R
ZONE 1
MOTOR R27
R30
G
R317
M6 K3
R66 R34 ZONE 2
D5
M4 R32 T'STAT
Z1
M2 C1 C2 R36 R33 C
C6
M1 R38 W/E
R40
F1 R37
OFF < > ON R39 O/B
D6
24 VAC HP < SYSTEM > GAS
T'FORMER R35
HC < TSTATS > HP R42 Y
R OFF < PURGE ASST > ON
R43 R
90 < PURGE > 120 S
K4 0 < FAN DLY > 45 S R41 G
D7 O < RV > B
U5
C OFF < SAS > ON R44
R44 GAS < FAN > HYDRO
R47 ZONE 1
SYSTEM U6 T'STAT
R49
W2/E R45 C
K5 R48
W1/B D8 LED1 STATUS W/E
R48
O R52 O/B
R51 LED2 SUPPLY AIR LIMIT R54
Y Y
R53 LED4 ZONE 3 OPEN R55
G R
K6 R54
RH D9 LED3 ZONE 2 OPEN G
R57 R55
RC LED6 ZONE 1 OPEN ONE
R56 R50
C R61
ZONE
LED5 W2 / E
K7 R63
RC/RH LED7 W1 / B
D10 R62
LINK
LED8 COMPRESSOR R65
R
LED9 FAN CONTROLS INC.
CONTROL SYSTEM Englishtown, NJ

Blow-up view of NCM300 showing Factory Dip Switch settings.


OFF < > ON
HP < SYSTEM > GAS
HC < TSTATS > HP
RECORD YOUR OWN DIP SWITCH OFF < PURGE ASST > ON
SETTINGS HERE 90 < PURGE > 120 S
0 < FAN DLY > 45 S
Use a pencil and shade the boxes O < RV > B
that correspond to your settings! OFF < SAS > ON
GAS < FAN > HYDRO

8 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
HEAT / COOL Sensor
URD/ND
ESR
Damper WIRING DIAGRAM TYPICAL THERMOSTAT
Model NCM-300 Control Panel 72
FAN
21 43 140 C3 D1 R4 R8 HEAT OFF COOL ON AUTO
14 28 40 46 130 150

C NO NC M M
ZONE 3
35 37 49 120 160 R5 SUPPLY W Y R G
MOTOR 7
AIR
M6 OFF 42 34 52 110 170 R10 SENSOR
STAGING LOW TEMP HIGH TEMP
M4 W2 TIMER LIMIT LIMIT U2 2
{ M2
R9
R7 D2 R6
URD M1 NCM-300 R70 1
Damper C4
K1
ZONE 2 C8 U1
R69 ZONE 3
D3
MOTOR T'STAT
R28 RESET R13

1 4 6
U3
M6 R14 R17 R19 C
C9
M4 R16 R23 W/E
C7
M2 K2 R21 O/B
R24
M1 D4 R20 Y
R22 R25 TYPICAL THERMOSTAT
ND R26 C5 U4 R29 R
ZONE 1
Damper MOTOR R27 G 68
R30

ALL rights reserved


R317
K3 FAN

Copyright EWC/ACI 2006


M6 R34 ZONE 2
D5 R66 HEAT OFF COOL ON AUTO

1 4 6
M4 R32 T'STAT

NCM300 Ver 2.3


Z1 W Y R G
M2 C1 C2 R36 C
C6 R33
M1 R38 W/E
R40
F1 R37
OUTDOOR OFF < > ON R39 O/B
D6
TRANSFORMER 24 VAC HP < SYSTEM > GAS
CONDENSING T'FORMER R35
HC < TSTATS > HP R42 Y
UNIT 24V, 40VA
OFF < PURGE ASST > ON R
R 90 < PURGE > 120 S
R43
K4 0 < FAN DLY > 45 S R41 G
D7 O < RV > B
OFF < SAS > ON
U5
C R44
Y R44 GAS < FAN > HYDRO
R47 ZONE 1
SYSTEM U6 T'STAT
R49
C W2/E R45 C
K5 R48
W1/B D8 LED1 STATUS W/E
R48 TYPICAL THERMOSTAT
O R52
LED2 O/B
R51 SUPPLY AIR LIMIT R54
Y Y 74
R53 LED4 ZONE 3 OPEN R55
G R
K6 R54 FAN
RH LED3 ZONE 2 OPEN HEAT OFF COOL ON AUTO
D9 G
R55

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
RC R57 W Y R G
R56 LED6 ZONE 1 OPEN R50 ONE
C R61
ZONE
LED5 W2 / E
W2 W2 R63
K7
RC/RH LED7 W1 / B
D10 R62
LINK
W1 W1 LED8 COMPRESSOR R65
R
LED9 FAN CONTROLS INC.
Y1 Y1
CONTROL SYSTEM Englishtown, NJ
G G

R R
RC/RH
C C JUMPER All wiring should be done to local and WARNING: THESE PANELS ARE DESIGNED FOR
national codes and ordinances. Use color- USE WITH 24VAC. DO NOT USE OTHER

E-Mail- info@ewccontrols.com
GAS/OIL or coded, multi-conductor wire. Wire number to VOLTAGES! USE CAUTION TO AVOID ELECTRIC
ELECTRIC number or letter to letter on each control. SHOCK OR EQUIPMENT DAMAGE.
Furnace
1or2 STAGE

9
10
HEAT PUMP Sensor
URD/ND
ESR Typical Heat Pump
Damper WIRING DIAGRAM Thermostat
70
Model NCM-300 Control Panel FAN
HEAT OFF COOL ON AUTO

21 43 140 C3 D1 R4 R8
14 28 40 46 130 150

C NO NC M M
ZONE 3
35 37 49 120 160 R5 SUPPLY C W2/E O/B R G
MOTOR 7 Y
AIR
M6 OFF 42 34 52 110 170 R10 SENSOR
STAGING LOW TEMP HIGH TEMP
{ M4 W2 TIMER LIMIT LIMIT U2 2
R9
M2 R7 D2 R6
URD M1 NCM-300 R70 1
Damper C4
K1
ZONE 2 C8 U1
R69 ZONE 3
D3
MOTOR T'STAT
R28 RESET U3 R13

1 4 6
M6 R14 R17 R19 C
C9
M4 R16 R23 W/E
C7 Typical Heat Pump
M2 K2 R21 O/B
R24
M1 D4 R20 Y Thermostat
R22 R25
ND R26 C5 U4 R29 R
ZONE 1 72
MOTOR R27 G
R30

ALL rights reserved


Damper R317 FAN
K3 HEAT OFF COOL ON AUTO

Copyright EWC/ACI 2006


M6 R34 ZONE 2
D5 R66
M4 R32 T'STAT

1 4 6
NCM300 Ver 2.3
Z1
M2 C1 C2 R36 C
C6 R33 C W2/E O/B Y R G
M1 R38 W/E
R40
F1 R37
HEAT PUMP OFF < > ON R39 O/B
D6
1 STAGE TRANSFORMER 24 VAC HP < SYSTEM > GAS
T'FORMER R35 R42 Y
24V, 40VA HC < TSTATS > HP
OFF < PURGE ASST > ON R
R 90 < PURGE > 120 S
R43
K4 0 < FAN DLY > 45 S R41 G
X/W D7 O < RV > B
OFF < SAS > ON
U5
C R44
R44 GAS < FAN > HYDRO
O R47 ZONE 1
SYSTEM U6 T'STAT
R49
W2/E R45 C Typical Heat Pump
K5 R48
Y W1/B D8 LED1 STATUS W/E Thermostat
R48
O R52
LED2 O/B
R R51 SUPPLY AIR LIMIT R54
Y Y 74
R53 LED4 ZONE 3 OPEN R55 FAN
G R HEAT OFF COOL ON AUTO
C K6 R54
W1 W1 RH D9 LED3 ZONE 2 OPEN G
R55

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
RC R57
R56 LED6 ZONE 1 OPEN R50 ONE
C ZONE C W2/E O/B Y R G
W2 W2 LED5 W2 / E R61
K7 R63
O O RC/RH LED7 W1 / B
D10 R62
LINK
LED8 COMPRESSOR R65
Y Y R
LED9 FAN CONTROLS INC.
G G CONTROL SYSTEM Englishtown, NJ

R R

C C RC/RH
JUMPER
All wiring should be done to local and WARNING: THESE PANELS ARE DESIGNED FOR
AIR HANDLER
WITH 1 0R 2 STAGE

E-Mail- info@ewccontrols.com
national codes and ordinances. Use color- USE WITH 24VAC. DO NOT USE OTHER
ELECTRIC RESISTANCE
BACKUP HEAT coded, multi-conductor wire. Wire number to VOLTAGES! USE CAUTION TO AVOID ELECTRIC
number or letter to letter on each control. SHOCK OR EQUIPMENT DAMAGE.
P/N 090375A0206 REV C
TM

Forced Air Zone Controls


SUPPLY AIR SENSOR OPERATIONS AND ONE ZONE FEATURE CONTROL
A Supply Air Sensor can be used to limit supply air The One Zone feature allows the homeowner to
temperatures and prevent over heating of the control all the zones from a single thermostat by using
equipment during the heating cycle or coil freeze- an optional switch connected to the One Zone
terminal shown below. A homeowner can switch to
up during cooling cycles. Wire the sensor as
One Zone control when they leave for vacation or as a
shown below and set dip switch #7 to the ON night setback mode, and the Zone 1 thermostat will
position. (See Page 2) control all zones. All zone dampers will respond to the
The Supply air sensor installs into the supply air Zone 1thermostat. Use Part # VAC.
plenum or downstream of the evaporator coil or One Zone can also be used in commercial
heat exchanger and monitors the discharge air applications with a programmable thermostat in Zone
temperature in heating and cooling modes. The 1 and non-programmable thermostats in all other
zones, thus satisfying the requirements of California
actual temperature is relayed backed to the
Title 24.
microprocessor. When the temperature exceeds
or falls below the HEAT or COOL limit set points, Substantial energy savings and equipment protection
can be obtained with proper use of the One Zone
the microprocessor will de-energize all HEAT or
feature and the supply air sensor.
COOL outputs for a minimum of 3 minutes. It also
energizes the FAN, if it is not already running, to
help dissipate the heat or warm up the evaporator ZONE 1
T'STAT
coil. Refer to the Data sheet that comes with the
C
Supply Air Sensor. W/E ON

There is no differential built in to the sensor! Once O/B OFF

Y
the supply air temperature rises or falls to a safe R O N E ZO N E M O D E

value and, the 3 minute time delay has expired, G


ONE
the microprocessor will restore the HEAT or ZONE
COOL outputs. The FAN will de-energize or stay See Technical Bulletin #TB-212
for exact wiring connections.
running, depending on the mode of operation
and the application.
One Zone Mode Commercial Grade
SUPPLY via the Zone 1 Thermostat
Model AIR SENSOR Thermostat ZONE THERMOSTAT
SAS SENSOR
#1
2
C W1 Y R G UNOCC / OCC

1 ZONE 1
T'STAT
C
Supply air temperature sensor.
W/E
140 43 O/B
130 150 40 46
Y
120 160 37 49 R
110 170 34 52 G
HIGH TEMP LOW TEMP ONE
LIMIT LIMIT
ZONE
Adjustable Heating & Cooling limit potentiometers

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com 11
Congratulations on purchasing and successfully installing your new NCM300 Zone Control
system. The NCM300 is certainly easy to setup and install. But should you find the need for a
little assistance, remember that you can call our toll free technical support hotline when you
are on the job site! @ 800-446-3110. Please have a multi-meter, pocket screwdriver and wire
cutters handy.

If you just have some questions about the NCM300 or any other Ultra-Zone product, call us at
732-446-3110. Monday thru Friday, 8:00am - 5:00pm Eastern Time.

Thank You

FIELD NOTES:

12 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com

S-ar putea să vă placă și