Documente Academic
Documente Profesional
Documente Cultură
TB-226
BULLETIN
Model NCM300 Zone Control System
Operating INPUT VOLTAGE: 19-30VAC 60 Hz Indoor Fan Any zone can activate the indoor fan
Power Transformer 40-60VA MAX. NEC Class 2. Control and only the dampers in zones calling
CURRENT DRAW: Max 14VA @ 24VAC. for continuous fan operation will open.
OVER-CURRENT PROTECTION: 2.5 Continuous fan operation will only
amp or 60VA. occur when there are no active or
pending heat or cool demands.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
P/N 090375A0226 REV. F Copyright © 2006 - 2009, EWC Controls Inc. ALL Rights Reserved
Built-In Timer The panel has built-in timers that
RESET Momentarily pressing the RESET button
Settings insure safe HVAC system operations. BUTTON clears the built-in timers controlling the
*Start-up Delay Timer 4 minutes, fixed. Start-up timer, Minimum run timer, Short
*Minimum Run Timer 2 minutes, fixed. cycle timer, W2 timer, Supply air sensor
*Short Cycle Timer 2 minutes, fixed. RESET timer and the Changeover timer. This
Reset the CPU enables you to test the installation faster.
*Changeover Timer 4 minutes, fixed. anytime you make
dip-switch changes Caution should be observed when using
*Opposing System 20 . minutes, fixed. to the NCM300 panel! this button.
Service Timer
DO NOT use a sharp
*Second Stage Off or 7 to 42 object to press the Pressing the RESET button for 7
Heating Timer minutes, adjustable. button! Your finger
seconds will reset the CPU.
tip will work fine.
TIMER DEFINITIONS
Start-Up Delay Upon initial power up or after a Selecting the Options Using the DIP Switches
Timer power failure, the panel will not start 8 DIP switches allow you to select the features specific
the equipment for 4 minutes. to your very own zoned HVAC system.
Minimum Run When a call is activated, the zone Select the type of HVAC system the
Timer HP < SYSTEM > GAS
panel will run the HVAC system in that panel will control. Heat Pump (HP) or
mode for a minimum of 2 minutes. Gas/Oil/Hydronic with A/C. (GAS)
Short Cycle When the HVAC system is satisfied,
Timer the zone panel will not resume the HC < TSTATS > HP Select the type of Thermostats you
same call for a minimum of 2 minutes. will use. Select HC for conventional
Heat/Cool type thermostats or select
Changeover At the end of a call, a 4 minute timer is HP for Heat Pump type thermostats.
Timer started and the zone panel will not
switch to the opposite mode of OFF<PURGE ASST>ON Select ON to allow the NCM300 to operate
the fan during the 90/120 second purge
operation until the timer has expired.
cycle. Works in both heat and cool mode.
Opposing A 20 minute delay must expire, or the Set the switch to OFF to allow the system
System active zone(s) must satisfy, before to operate on it’s own fan purge cycle.
the panel will honor a thermostat
Service Timer demand to changeover to the Select a purge time of 90 seconds or 120
90< PURGE >120s
opposite mode of system operation. seconds. The damper(s) on the last zone
2nd Stage calling will be held open for that time while
The W2 TIMER sets the total amount
Heating Timer all other zone dampers remain closed.
of time delay before second stage
21 heating is energized. 1st stage heat Select 45 seconds to allow the hot
14 28 0< FAN DLY > 45S
will stay energized when 2nd stage water or steam coil to heat up before
7 35
heat activates. If desired turn the the fan starts. Select 0 seconds and
OFF 42 Timer OFF and let your heat pump the fan will start immediately upon a
STAGING
W2 TIMER thermostats stage up for you. call for heat. Switch # 8 must be set
Heating and Cooling to HYDRO for this feature to work!
Limit Settings The Heating Limit potentiometer sets 0 < RV > B
140 Select O or B for the type of
the supply air temperature at which
130 150 Reversing Valve operation of your
the heating is cycled off and the fan
120 160 heat pump.
continues to run until, the supply air
110 170 OFF < SAS > ON Select ON if you are using a Supply
temperature has dropped below the
HIGH TEMP Air Sensor with the NCM300. Select
LIMIT heating limit set point. 3 Minutes min.
OFF if you have not installed a sensor.
The Cooling Limit potentiometer sets
43
40 46 the supply air temperature at which GAS< FAN >HYDRO Select the GAS position when setting
37 49 the cooling is cycled off and the fan up for gas or heat pump systems.
continues to run until, the supply air Select HYDRO when setting up for
34 52
temperature has risen above the Straight Electric or Hydronic
LOW TEMP
LIMIT cooling limit set point. 3 Minutes min. (Steam/Hot Water) heating systems.
2 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
WIRING INSTRUCTIONS
WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO
AVOID ELECTRIC SHOCK OR EQUIPMENT DAMAGE. ALL WORK SHOULD BE PERFORMED TO LOCAL AND NATIONAL
CODES AND ORDINANCES. USE 18 AWG SOLID COPPER, COLOR-CODED, MULTI-CONDUCTOR THERMOSTAT CABLE.
Thermostat The NCM300 zone control panel requires standard 1 stage heat/cool thermostats in all zones, regardless
Wiring of the application. 2nd stage heat output is controlled by an adjustable timer on the panel. If you prefer,
the NCM300 will also work with any off the shelf 2 stage Heat Pump Thermostat. 2nd stage heat will then
be thermostatically controlled. Typical thermostat wiring diagrams are shown below.
ZONE
T'STAT
**
C ZONE
T'STAT
W/E C *
O/B W/E
Y O/B
R Y
G R
G
Figure 2b. Model EWT-3900: Wireless Thermostat.
Configured for 1 heat 1 cool (SS1 mode). * Common wire not required if batteries are used.
Field installed jumper.
Can be configured for heat pump. See **
Figure 2d. Model EWT-3900 Wireless Thermostat:
Configured for 2 heat 1 cool heat pump (HP1
Mode). See thermostat instructions for further
Details.
NOTE: The New NCM300 allows the user to install Heat Pump thermostats on all zones. This allows the user to over-
ride the W2 Timer and energize the auxiliary heat via thermostatic demand! You may still use regular Heat/Cool type
thermostats with a Heat Pump system and use the W2 Timer to energize the auxiliary heat. Doing so may save more
energy. This new design simplifies the thermostat selection process and allows the installer to easily adapt the
NCM300 to most residential applications.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-635-8646 E-Mail- info@ewccontrols.com 3
System Wiring Typical heat pump system wiring with electric
The NCM300 panel was designed to be easy to understand
Heat Pump resistance backup heat. Wire up the reversing
and wire up. We have provided several typical field wiring with O or B Type valve to either O or W1/B, depending on your
diagrams to review. Your actual field wiring may vary. Notice Reversing Valve type of system. Applies to air cooled or
that you may now connect the 24vac “C” common terminal
geothermal / ground source HVAC systems.
from the HVAC system to the NCM300 “system” terminal
block. This provides a convenient place to reference the
HVAC system 24vac common wire and helps to simplify the
AIR HANDLER
troubleshooting process. WITH 1 0R 2 STAGE
ELECTRIC RESISTANCE
BACKUP HEAT NCM300
Typical gas/electric system showing 1 HEAT PUMP
Single or 2 stage heating. Note the jumper 1 STAGE
W1 W1
Transformer
(link) between RC and RH. There is SYSTEM
Gas/Electric
no need to install your own jumper. X/W W2 W2 W2/E
Systems W1/B
Y Y Y * O
Y
Oor B G
G G
GAS/OIL
Furnace
NCM300 R R R
RH
RC
OUTDOOR
CONDENSING
1or2 STAGE C C C C
UNIT SYSTEM
W2 W2 W2/E RC/RH
W1 W1 W1/B LINK
Y Y1 Y1
O
Y
C G G G
R
RH * Connect either the O or the W1/B.
R RC
In a typical O type reversing valve system, there
C
C C will not be a connection to the W1/B terminal!
RC/RH Figure 3c.
NOTE: You may connect the ‘C’ common LINK
terminal from the HVAC system to the NCM300
to make troubleshooting a little easier.
Your Oil furnace may not provide factory isolation for
Two the Primary Burner Control. Simply cut the Rc/Rh link
Figure 3a.
Transformer on the NCM300 and wire up to the Fan Center as
Note: Your Hydronic Air Handler may include a W terminal.
Oil Heating shown. Then run the T&T connections to the Rh and
That means it may have it’s own isolation circuit. If you can Systems the W1/B terminals to complete the control wiring.
confirm this, simply connect the W1/B terminal to the W
terminal on the air handler. Do not cut the Rc/Rh Link. Wire TYPICAL Fan Center NCM300
Two up your Boiler Control or Circulator Control to the isolation OUTDOOR TERMINAL
Transformer contacts or wires provided in the air handler. (Follow dashed CONDENSING BLOCK
SYSTEM
Hydronic Heat lines)The fan is controlled via time delay relay inside the air UNIT
Systems handler or use the Fan Hydro switch on the NCM300. W2/E
Y Y W1/B
TYPICAL Hydronic Y G
O
G
Air Handler Y
NCM300 R
TERMINAL C R G
RH
OUTDOOR BLOCK C C
CONDENSING RC
SYSTEM C
UNIT
W W
W2/E
Y Y W1/B
RC/RH
Y G G
O
Y
LINK
C R R G
RH
C C RC YOU MUST cut
C the Rc/Rh link
T T
OEM provided
ISOLATION RC/RH
TERMINALS LINK
OR WIRES
OIL T
TYPICAL BOILER or BURNER
DO NOT cut FURNACE
PRIMARY
PRIMARY BURNER CONTROL T
the Rc/Rh link CONTROL
BOILER CONTROL
CIRCULATOR
RELAY OR HOT T
WATER ZONE VALVE
CONNECTION T
ZONE
MOTOR
. 1 4 6
M6
Figure 4a
M4
All Models ND & URD Damper Wiring M2
M1
ZONE
MOTOR
M6
1 4 6
1 4 6
M4
M2
M1
Multiple ND or URD
1 4 6
NO 3
ZONE
MOTOR Block
M6
M4
C 1
1 4 6
M2
M1
Figure 6
NC 2 COIL
24 vac
R1 Isolation Relay
1 4 6
SPDT action with 24 vac coil On all these dampers and most older style
Relay is shown de-energized.
All dampers are closed. dampers, including competitor’s dampers,
always wire up number to number.
H L1
1 4 6
To Line Voltage
Provide over current
C L2
protection Do not overload the NCM300 Thermal
Separate 24 vac
Transformer
Circuit Breaker. Use a 24vac UL listed
Multiple Damper Wiring on a Single Zone, using a Separate Transformer
and an Isolating Relay. Maximum of 6 dampers per 40 va transformer. transformer at 60va maximum power
Figure 4c rating!
5
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
SERVICE GUIDE
Some Helpful All voltage measurements on the Check 24VAC Measure 24VAC at all damper M1 and
Guidelines NCM300 panel should be made with Power M2 terminals and all T-stat R and C
the ground lead of your meter on terminals. See Table 1 if any of these
terminal “C” of the 24VAC input voltages are incorrect.
terminals.
HVAC System If the HVAC LED indicators are
All voltage measurements at the HVAC
Not Responding responding properly, but the system
System Terminal Block (W1/B, O, Y, Properly appears to be malfunctioning, check
W2/E & G) should be made with the
that the HVAC system is wired correctly
meter’s ground lead on the terminal
and that the DIP switches have been
“C” at the HVAC system block.
properly set.
Using the LED The STATUS LED should blink at
Indicators 1second on / 1 second off, to indicate If the HVAC LEDs are not responding
the microprocessor is operating properly, check the calls on each zone
properly. thermostat. If the calls indicate that the
HVAC system should be activated and
The SUPPLY AIR LIMIT LED will is not, press the RESET switch to
illuminate if the panel senses a cancel the timers. Also check that the
discharge temperature in excess of the DIP switches have been properly set. If
high or low limit set points. The LED will the problem persists, see Table 3 for
blink rapidly if the sensor is open, trouble shooting help.
shorted or disconnected. The panel
will function normally but with no Table 1. Detecting 24VAC Shorts
supply air temperature control until the
open or short is repaired. Detecting All LED’s will be off and the panel
24vac Shorts will appear to be dead! you will
The Zone Damper LED’s will measure 24VAC at the transformer
illuminate to indicate which dampers terminals R & C, but not at any damper
should be open. M1&M2 terminals, or any zone
The W1/B LED indicates that the panel thermostat R & C terminals.
CAUTION: The thermal breaker will be
is in the 1st stage heating mode or, the
hot to the touch.
“B” type reversing valve output is
active. Remove the power to the panel and
Isolating
The W2/E LED indicates 2nd stage 24vac Shorts allow the thermal poly fuse to cool
heat or Emergency heat has been down.
energized.
Remove the wire at each zone
The COMPRESSOR LED indicates thermostat R terminal and test if the
the compressor is energized. short still persists by restoring power to
the zone panel and testing as
The FAN LED indicates the fan is
described above. If the short dis-
energized.
appears, check the zone thermostat
wiring and the thermostat itself. This
Dampers Not If the Zone LED indicators are
applies if the thermostat requires the
Responding illuminated but the dampers appear to 24 volt (C)common, or the R wire could
Properly be malfunctioning, check the damper be shorted to the building ground.
field wiring.
If the short still persists disconnect all
If the ZONE LED’s are not responding
the wires at each damper terminal (M1,
properly, check the calls on each zone M2, M4 & M6). Restore power and test
thermostat. If the calls indicate a as described above. If the short clears,
damper should be energized and is check the damper wiring and the
not, press the RESET button to cancel dampers for shorts with a continuity
the timers. If the problem persists, see tester. If the short still persists, call the
Table 2 for service help. technical support hot-line.
6
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
Table 2. Detecting Damper Problems
Damper LED On Check the damper wiring to insure it Testing Damper For a RDN/SMDL/BMDL damper,
But Damper Not is correctly wired. Be sure the wires Motors connect 24VAC common to terminal
Responding are secured in the terminals. Test the 1, and 24VAC to terminals 2 and 4.
damper motor to insure it is properly The damper should open. Remove
operating. If the problem still persists, 24VAC from terminal 4 and the
contact technical support. damper should close.
For a BMD/SMD/ND/URD damper,
Check that the STATUS LED is connect 24VAC common to terminal
NCM300 1, and 24VAC to terminal 4 and the
Damper LED blinking. If it is not, the panel may be in
damper should open. Remove
Not Responding a shutdown mode due to a short in the
24VAC from terminal 4 and apply
field wiring. See Table 1. Detecting 24VAC to terminal 6 and the damper
24vac shorts. should close.
Press the RESET for 1 second to For a power close spring open
clear any time delay(s) that may be damper, connect 24VAC to the two
keeping the call off and the damper motor “M” terminals, and the damper
from not responding. should CLOSE. Remove the 24VAC
and the damper should OPEN. For a
Check the voltage at each zone power open damper, the action will
thermostat terminal W, Y and G be reversed.
terminals to insure the damper should
be activated.
If the problem still persists, call the
technical support hot-line.
Panel LEDS Check the HVAC wiring to insure it is Press the RESET button for 1 second to clear
On But System correctly wired. Be sure the wires are the time delay that may be preventing the
Not Responding secured in the terminals. Check that call. The panel could be in minimum run
there is 24VAC at the Rc and Rh time, short cycle delay, changeover delay or
terminals. Use the HVAC system opposite system timing mode.
common (C) for the ground lead of
your meter. Check that Rh and Rc are If the system still does not respond, measure
connected if the system uses a single the voltage at each zone thermostat terminal
transformer. W/E, Y, & G to insure they are correct and a
call is in order.
For a gas/electric system test the
HVAC by shorting terminals Rh and
W1/B together to activate the heater, Measuring Heat/Cool thermostats will apply 24vac to
Rc to Y to activate the compressor and Thermostat the W/E terminal during a heating call.
Rc to G to activate the fan. If the HVAC Voltages During a cooling call, 24vac is applied to
system has responded properly, call both Y & G. During a continuous fan call,
EWC technical support. 24VAC is applied to the G terminal.
For a heat pump system test the Be sure the Rc and Rh terminals at the
heating by jumping terminals Rc to Y, thermostats are jumped together if your
W1/B and G. For a cooling test jump specific installation requires it.
Rc to Y, O and G. Heat Pump thermostats will apply 24vac to Y
Check that the STATUS LED is and G during a 1st stage heating call. 24vac
LEDs and will be applied to W/E during a 2nd stage
System Not blinking to insure the computer is
operating properly, press and hold call. In Emergency mode, 24vac is applied to
Responding W/E & G. During a cooling call, 24vac is
the RESET button for 7 seconds to
reboot the CPU. applied to Y, G & O.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com 7
21 43 140 C3 D1 R4 R8
14 28 40 46 130 150
ZONE 3
R5 SUPPLY
MOTOR 7 35 37 49 120 160
AIR
M6 OFF 42 34 52 110 170 R10 SENSOR
STAGING LOW TEMP HIGH TEMP
M4 W2 TIMER LIMIT LIMIT U2 R9
2
M2 R7 R6
M1 NCM-300 D2
C4
R70 1
K1 R69
ZONE 2 C8 U1 ZONE 3
D3
MOTOR RESET T'STAT
R28 U3 R13
8 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
HEAT / COOL Sensor
URD/ND
ESR
Damper WIRING DIAGRAM TYPICAL THERMOSTAT
Model NCM-300 Control Panel 72
FAN
21 43 140 C3 D1 R4 R8 HEAT OFF COOL ON AUTO
14 28 40 46 130 150
C NO NC M M
ZONE 3
35 37 49 120 160 R5 SUPPLY W Y R G
MOTOR 7
AIR
M6 OFF 42 34 52 110 170 R10 SENSOR
STAGING LOW TEMP HIGH TEMP
M4 W2 TIMER LIMIT LIMIT U2 2
{ M2
R9
R7 D2 R6
URD M1 NCM-300 R70 1
Damper C4
K1
ZONE 2 C8 U1
R69 ZONE 3
D3
MOTOR T'STAT
R28 RESET R13
1 4 6
U3
M6 R14 R17 R19 C
C9
M4 R16 R23 W/E
C7
M2 K2 R21 O/B
R24
M1 D4 R20 Y
R22 R25 TYPICAL THERMOSTAT
ND R26 C5 U4 R29 R
ZONE 1
Damper MOTOR R27 G 68
R30
1 4 6
M4 R32 T'STAT
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
RC R57 W Y R G
R56 LED6 ZONE 1 OPEN R50 ONE
C R61
ZONE
LED5 W2 / E
W2 W2 R63
K7
RC/RH LED7 W1 / B
D10 R62
LINK
W1 W1 LED8 COMPRESSOR R65
R
LED9 FAN CONTROLS INC.
Y1 Y1
CONTROL SYSTEM Englishtown, NJ
G G
R R
RC/RH
C C JUMPER All wiring should be done to local and WARNING: THESE PANELS ARE DESIGNED FOR
national codes and ordinances. Use color- USE WITH 24VAC. DO NOT USE OTHER
E-Mail- info@ewccontrols.com
GAS/OIL or coded, multi-conductor wire. Wire number to VOLTAGES! USE CAUTION TO AVOID ELECTRIC
ELECTRIC number or letter to letter on each control. SHOCK OR EQUIPMENT DAMAGE.
Furnace
1or2 STAGE
9
10
HEAT PUMP Sensor
URD/ND
ESR Typical Heat Pump
Damper WIRING DIAGRAM Thermostat
70
Model NCM-300 Control Panel FAN
HEAT OFF COOL ON AUTO
21 43 140 C3 D1 R4 R8
14 28 40 46 130 150
C NO NC M M
ZONE 3
35 37 49 120 160 R5 SUPPLY C W2/E O/B R G
MOTOR 7 Y
AIR
M6 OFF 42 34 52 110 170 R10 SENSOR
STAGING LOW TEMP HIGH TEMP
{ M4 W2 TIMER LIMIT LIMIT U2 2
R9
M2 R7 D2 R6
URD M1 NCM-300 R70 1
Damper C4
K1
ZONE 2 C8 U1
R69 ZONE 3
D3
MOTOR T'STAT
R28 RESET U3 R13
1 4 6
M6 R14 R17 R19 C
C9
M4 R16 R23 W/E
C7 Typical Heat Pump
M2 K2 R21 O/B
R24
M1 D4 R20 Y Thermostat
R22 R25
ND R26 C5 U4 R29 R
ZONE 1 72
MOTOR R27 G
R30
1 4 6
NCM300 Ver 2.3
Z1
M2 C1 C2 R36 C
C6 R33 C W2/E O/B Y R G
M1 R38 W/E
R40
F1 R37
HEAT PUMP OFF < > ON R39 O/B
D6
1 STAGE TRANSFORMER 24 VAC HP < SYSTEM > GAS
T'FORMER R35 R42 Y
24V, 40VA HC < TSTATS > HP
OFF < PURGE ASST > ON R
R 90 < PURGE > 120 S
R43
K4 0 < FAN DLY > 45 S R41 G
X/W D7 O < RV > B
OFF < SAS > ON
U5
C R44
R44 GAS < FAN > HYDRO
O R47 ZONE 1
SYSTEM U6 T'STAT
R49
W2/E R45 C Typical Heat Pump
K5 R48
Y W1/B D8 LED1 STATUS W/E Thermostat
R48
O R52
LED2 O/B
R R51 SUPPLY AIR LIMIT R54
Y Y 74
R53 LED4 ZONE 3 OPEN R55 FAN
G R HEAT OFF COOL ON AUTO
C K6 R54
W1 W1 RH D9 LED3 ZONE 2 OPEN G
R55
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
RC R57
R56 LED6 ZONE 1 OPEN R50 ONE
C ZONE C W2/E O/B Y R G
W2 W2 LED5 W2 / E R61
K7 R63
O O RC/RH LED7 W1 / B
D10 R62
LINK
LED8 COMPRESSOR R65
Y Y R
LED9 FAN CONTROLS INC.
G G CONTROL SYSTEM Englishtown, NJ
R R
C C RC/RH
JUMPER
All wiring should be done to local and WARNING: THESE PANELS ARE DESIGNED FOR
AIR HANDLER
WITH 1 0R 2 STAGE
E-Mail- info@ewccontrols.com
national codes and ordinances. Use color- USE WITH 24VAC. DO NOT USE OTHER
ELECTRIC RESISTANCE
BACKUP HEAT coded, multi-conductor wire. Wire number to VOLTAGES! USE CAUTION TO AVOID ELECTRIC
number or letter to letter on each control. SHOCK OR EQUIPMENT DAMAGE.
P/N 090375A0206 REV C
TM
Y
the supply air temperature rises or falls to a safe R O N E ZO N E M O D E
1 ZONE 1
T'STAT
C
Supply air temperature sensor.
W/E
140 43 O/B
130 150 40 46
Y
120 160 37 49 R
110 170 34 52 G
HIGH TEMP LOW TEMP ONE
LIMIT LIMIT
ZONE
Adjustable Heating & Cooling limit potentiometers
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com 11
Congratulations on purchasing and successfully installing your new NCM300 Zone Control
system. The NCM300 is certainly easy to setup and install. But should you find the need for a
little assistance, remember that you can call our toll free technical support hotline when you
are on the job site! @ 800-446-3110. Please have a multi-meter, pocket screwdriver and wire
cutters handy.
If you just have some questions about the NCM300 or any other Ultra-Zone product, call us at
732-446-3110. Monday thru Friday, 8:00am - 5:00pm Eastern Time.
Thank You
FIELD NOTES:
12 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com