Documente Academic
Documente Profesional
Documente Cultură
It may be because of that detail that many people incorrectly appiy the rules from this chapter. Be sure to pay careful attention to
the details, and be sure that you make your instaliation in compliance with the rules in the Code, not just in the manner that you
may have been taught or because "it's always been done that way." This is especially true when it comes to appiying the Tables.
Violations of the rules for wiring methods found in Chapter 3 can result in problems with power quality and can lead to fire, shock,
and other hazards.
The type of wiring method you'll use depends on several factors: Job specifications, Code requirements, the environment, need,
and cost are among them.
Chapter 3 begins with rules that are common to most wiring methods [Article 300], it then covers conductors [Article 310], and
enclosures [Articles 312 and 314]. The articles that follow become more specific and deal more in-depth with individua! wiring
methods such as specific types of cables [Articles 320 through 340] and varióos raceways [Articles 342 through 390]. The chapter
winds up with Article 392, a support system, and the final articles [Articles 394 through 398] for open wiring.
Notice as you read through the varióos wiring methods that the Code attempts to use similar subsection numbering for similar
topics from one article to the next, using the same digits after the decimal point in the section number for the same topic. This
makes it easier to lócate specific requirements in a particular article. For example, the rules for securing and supporting can be
found in the section that ends with .30 of each article. In addition to this, you'll find a "uses permitted" and "uses not permitted"
section in nearly every article.
• Article 300—Wiring Methods. Article 300 contains the general requirements for all wiring methods included in the
NEC, except for signaling and Communications systems, which are covered in Chapters 7 and 8.
• Article 310—Conductors for General Wiring. This article contains the general requirements for conductors, such as
insulation markings, ampacity ratings, and conductor use. Article 310 doesn't apply to conductors that are part of flex-
ible cords, fixture wires, or conductors that are an integral part of equipment [90.6 and 300.1 (B)].
• Article 312—Cabinets, Cutout Boxes, and Meter Socket Enclosures. Article 312 covers the instaliation and con-
struction specifications for cabinets, cutout boxes, and meter socket enclosures.
• Article 314—Outlet, Device, Pulí and Junction Boxes, Conduit Bodies, Fittings, and Handhole Enclosures.
Instaliation requirements for outlet boxes, pulí and junction boxes, as well as conduit bodies, and handhole enclosures
are contained in this article.
• Article 330—Metal-Ciad Cable (Type MC). Metal-dad • Understand what's available for doing the work.
cable endoses insulated conductors in a metal sheath • Recognize raceway types that have special Code require-
of either corrugated or smooth copper or aluminum ments.
tubing, or spiral interlocked steel or aluminum. The phys- • Avoid buying a raceway that you can't install due to NEC
ical characteristics of Type MC cable make it a versatile requirements you can't meet with that particular wiring
wiring method permitted in almost any location and for method.
almost any application. The most commonly used Type
Here's a brief overview of each one:
MC cable is the interlocking kind, which looks similar to
armored cable or flexible metal conduit. • Article 342—Intermedíate Metal Conduit (Type IMC).
Intermedíate metal conduit is a circular metal raceway
• Article 334—Nonmetallic-Sheathed Cable (Type NM).
with the same outside diameter as rigid metal conduit.
Nonmetallic-sheathed cable endoses two, three, or four
The wall thickness of intermedíate metal conduit is less
insulated conductors, 14 AWG through 2 AWG, within a
than that of rigid metal conduit, so it's a greater interior
nonmetallic outer jacket. Because this cable is nonme-
cross-sectional área for holding conductors. Intermedíate
tallic, it contains a sepárate equipment grounding con-
metal conduit is lighter and less expensive than rigid
ductor. Nonmetallic-sheathed cable is a common wiring
metal conduit, but it's permitted in all the same locations
method used for residential and commercial branch cir-
as rigid metal conduit. Intermedíate metal conduit aiso
cuits. Many electricians cali this plastic-sheathed cable
uses a different steel alloy, which makes it stronger than
"Romex®."
rigid metal conduit, even though the walls are thinner.
274 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring Methods and Materials Chapter 3
• Article 348—Flexible Metal Conduit (Type FMC). • Article 362—Electrical Nonmetallic Tubing (ENT).
Flexible meta! conduit is a raceway of circular cross Electrical nonmetallic tubing is a pliable, corrugated, cir-
section made of a heücally wound, interlocl<ed metal cular raceway made of PVC. It's often called "Smurf Pipe"
strip of either steel or aluminum. It's commonly called or "Smurf Tube," because it was available only in blue
"Greenfieid" or "Flex." when it carne out and at the time the children's cartoon
characters "The Smurfs," were popular. It's now available
• Article 350—Liquidtight Flexible Metal Conduit (Type
in múltiple colors such as red and yellow as well as blue.
LFMC). Liquidtight flexible metal conduit is a raceway
of circular cross section with an outer liquidtight, non- • Article 376—Metal Wireways. A metal wireway is a
metallic, sunlight-resistant jacket over an inner flexible sheet metal trough with hinged or removable covers for
metal core, with associated couplings, connectors, and housing and protecting electrical conductors and cable, in
fittings. It's listed for the instaliation of electric conduc- which conductors are placed after the wireway has been
tors. Liquidtight flexible metal conduit is commonly called installed as a complete system.
"Sealtite®" or simply "liquidtight." Liquidtight flexible
• Article 380—Multioutlet Assemblies. A multiout-
metal conduit is of similar construction to flexible metal
let assembiy is a surface, flush, or freestanding raceway
conduit, but it has an outer thermoplastic covering.
designed to hold conductors and receptacles. It's assem-
• Article 352—Rigid Polyvinyl Chioride Conduit (Type bled in the fieId or at the factory.
PVC). Rigid polyvinyl chioride conduit is a nonmetallic
• Article 386—Surtace Metal Raceways. A surface metal
raceway of circular cross section with integral or associ-
raceway is a metallic raceway intended to be mounted
ated couplings, connectors, and fittings. It's listed for the
to the surface with associated accessories, in which con-
instaliation of electrical conductors,
ductors are placed after the raceway has been installed
• Article 356—Liquidtight Flexible Nonmetallic Conduit as a complete system.
(Type LFNC). Liquidtight flexible nonmetallic conduit is
• Article 388—Surface Nonmetallic Raceways. A sur-
a raceway of circular cross section with an outer liquid-
face nonmetallic raceway is intended to be surface
tight, nonmetallic, sunlight-resistant jacket over an inner
mounted with associated accessories. Conductors are
flexible core, with associated couplings, connectors, and
placed inside after the raceway has been installed as a
fittings. It's listed for the instaliation of electrical conduc-
complete system.
tors. LFNC is available in three types:
- Type LFNC-A (orange). A smooth seamiess inner core
Cable l^ay
and cover bonded together with reinforcement layers
inserted between the core and covers. • Article 392—Cable Trays. A cable tray system is a unit
or assembiy of units or sections with associated fittings
- Type LFNC-B (gray). A smooth inner surface with inte-
that form a structural system used to secureiy fasten or
gral reinforcement within the conduit wall.
support cables and raceways. A cable tray isn't a race-
- Type LFNC-C (black). A corrugated interna! and exter-
way; it's a support system for raceways, cables, and
na! surface without integral reinforcement within the
enclosures.
conduit wall.
Mike HoiVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
ARTICLE
301
lIIiI Wiring Methods
INTRODUCTION TO ARTICLE 300—WIRING METHODS
Article 300 contains the general requirements for ail wiring methods included in the NEC. However, the article doesn't appty to
Communications systems, which are covered in Chapter 8, except when Article 300 is specifically referenced in Chapter 8.
This article is primarily concerned with how to install, route, spiice, protect, and secure conductors and raceways. How well you conform
to the requirements of Article 300 will generally be evident in the finished work, because many of the requirements tend to determine the
appearance of the instaliation.
Because of this, it's often easy to spot Article 300 problems if you're looking for Code violations. For example, you can easily see when
someone runs an equipment grounding conductor outside a raceway instead of grouping all conductors of a circuit together, as required by
300.3(B).
A good understanding of Article 300 will start you on the path to correctly installing the wiring methods included in Chapter 3. Be sure to
carefully consider the accompanying illustrations, and refer to the definitions in Article 100 as needed.
300.1 Scope.
• CATV, 820.3
• Class 2 and 3 Circuits, 725,3
I The r
• Communications Cables and Raceways, 800.133(A)t2)
• FireAlarm Circuits, 760.3 I applV
Figure 300-1
(B) Integral Parts of Equipment. The requirements contained in
Article 300 don't apply to the internal parts of electrical equipment.
Author's Comment: Industry practico is to describe raceways
Figure 300-1
using inch sizes, such as y2 in., 2 in., and so on; however, the
(C) Trade Sizes. Designators for raceway trade sizes are given in proper reference (2005 NEC change) is to use "Trade Size Vz''
Table 300.1 (C). or "Trade Size 2." In this textbook we use the term "Trade Size."
ve Figure 300-3
Figure 300-2
278 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring Methods
4 8 0 V Circuit
6 0 0 V Insulation
Associated E q u i p m e n t
Class 2 and 3 Circuits Reclassified as Class 1 (A) Cables and Raceways Through Wood Members. When the fol-
725.130(A) Ex 2
lowing wiring methods are installed through wood members, they
must comply with (1) and (2). Figure 300-11
Figure 300-11
PV systeiTi conductors. both de and ac^ are perriiiUed_tg
be installed in the s a m e raceways. outlet and junction
^ boxes. or similar fittings. but must be entirely
independent of non-PV system wiring [690.4(8)].
(1) Holes In Wood Members. Hotes through wood framing members
for the above cables or raceways must be not less than VA in. from
Figure 300-10
the edge of the wood member. If the edge of the hole is less than VA
in. from the edge, a '/e in. thick steel píate of sufficient length and
300.4 Protection Against Physical Damage. Con- width must be installed to protect the wiring method from screws and
damage [110.27(6)].
Ex 1: A steel piafe isn't required to protect rigid metal conduit, inter-
medíate metal conduit, PVC conduit, or electrical metallic tubing.
280 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring IVIethods 300.4
Ex 2: A listed and marked steel píate less than /w in. thick that pro- R a c e w a y s a n d Cables Through W o o d M e m b e r s
vides equal or better protection against nail or screw penetration is Notches in W o o d
300.4(A)(2) Ex 2
permitted. Figure 300-12
Ex: A listed and marked steel píate less than A in. thick that pro- Protection Against Physical D a m a g e
Cables Parallel to Framing M e m b e r s and Furring Strips
vides equal or better protection against nail or screw penetration is
300.4(D)
permitted.
Framing
" Member
(C) Behind Suspended Ceilings. Wiring metliods, such as cables or
raceways, installed behind paneis designed to allow access must be
Cable must be at Ieast I V i in. from the
supported in accordance with its applicable article. Figure 300-15
e d g e of a framing m e m b e r or furring
strip, or be protected by a steel píate.
Furring Framing
Suspended Strip Member
Wiring installed behind paneis C o p y r i í * M11. «ww M Í I B U D U con.
Ceiling
designed to allow a c c e s s m u s t
be supported in a c c o r d a n c e Figure 300-16
with its applicable article.
(D) Cables and Raceways Parallel to Framing Members and Ex 3: A Usted and marked steel píate less than /le ¡n. thick that pro-
Furring Strips. Cables or raceways run parallel to framing members vides equal or better protection against nail or screw penetration is
nails or screws, by installing the wiring method so it isn't less than (E) Wiring Under Roof Decking. Cables, raceways, and enclosures
VA in. from the nearest edge of the framing member or furring strip. under metal-corrugated sheet roof decking must not be located
If the edge of the framing member or furring strip is less than 1 '/4 in. within VÁ in. of the roof decking, measured from the lowest surface
away, a Vie in. thick steel píate of sufficient length and width must be of the roof decking to the top of the cable, raceway. or box. In addi-
installed to protect the wiring method from screws and nails. Figure tion, cables, raceways, and enclosures aren't permitted in concealed
300-16 locations of metal-corrugated sheet decking type roofíng.
282 Mike Holt's lllustrated Guide to Understanding the 2011 Nationai Electrical Code, Volume 1
Wiring IVIethods 300.5
and intermedíate metal conduit • An insulated fitting isn't required for a grounding electrode.
Figure 300-18
(F) Cables and Raceways Installed in Grooves. Cables and race-
ways installed in a groove must be protected by a '/le in. thick steel
píate or sieeve, or by VA in. of free space.
Protection Against Physical D a m a g e
R a c e w a y Terminations
Author's Comment: An example is Type NM cable installed in 300.4(G)
a groove cut into the Styrofoam-type insulation building block
structure and then covered with wallboard.
Ex 2: A listed and marked steel píate less than /le in. thick that pro-
vides equal or better protection against nail or screw penetration is
permitted.
A bushing isn't required for a
(G) Insulating Fittings. If raceways contain insulated circuit conduc- grounding electrode c o n d u c t o r
tors 4 AWG and larger that enter an enclosure, the conductors must 1
be protected from abrasión during and after instaliation by a fitting Figure 300-18
identified to provide a smooth, rounded insulating surface, such as an
insulating bushing. Figure 300-17
Ex: Insulating bushings aren't required if a raceway terminates in a
threaded raceway entry that provides a smooth, rounded, or flared
Protection of Insulated Circuit Conductors Bushing surface for the conductors. An example would be a meter hub fitting
Identified Insulated Fittings Not
300.4(G) Required oraMeyer's hub-type fitting.
4 AWG
and L A R G E R P V C - 352.46
6 AWG E N T - 362.46
and SMALLER
Copyright 2011. uvww MikeHolt com
Figure 300-17
Street
Driveway 24 in. 24 in. 24 in. I24in.
Parking Lot
Driveways
One - Two
Family
Solid Rock
¡ 1 8 ín: |l8ln. Jl8in. t 12 in.
o
cae
With not Less than
2in. of Concrete Raceway On>y I Raceway Onty I
Spiices within a n u n d e r g r o u n d
enclosure must be a p p r o v e d
Author's Comment: The cover requirements contained in
for w e t locations.
300.5 don't apply to the following signaling, Communications,
and other power-limited wiring systems: Figure 300-20
CowrtBM2011
• CATV, 90.3
• Class 2 and 3 Circuits, 725.3
• Communications Cables and Raceways, 90.3
Figure 300-21
• Fire Alarm Circuits, 760,3
• Optical Fiber Cables and Raceways, 770.3
284 Mike HoiVs Iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring IVIethods 300.5
Ex 2: Type MC Cable Usted for direct burial is permitted under a build- V: 18 in. Cover'...I
y : ' 18 in. Cover
ing without instaliation in a raceway [330.10(A)(5)]. Figure 300-22
Figure 300-23
Figure 300-22
^ | y ^ Type U F o r U S E
^ ^ ^ ^ • ^ ^ Single C o n d u c t o r
(D) Protecting Underground Cables and Conductors. Direct-buried
conductors and cables such as Types MC, UF, and USE must be pro-
tected from damage in accordance with (1) through (4).
(2) Conductors Entering Buildings. Conductors that enter a building Figure 300-24
(F) Backfill. Backfill material for underground wiring must not U n d e r g r o u n d Installations
Grouping of Conductors
damage the underground cable or raceway, or contribute to the corro- 300.5(1)
sión of the metal raceway.
Mike HoiVs iiiustrated Guide to Understanding tlie 2011 National Electrical Code, Volume 1
Wiring Methods 300.6
(J) Earth Movement. Direct-buried conductors, cables, or raceways Protection Against Corrosión and Deterioration
300.6
that are subject to movement by settiement or frost musí be arranged
to prevent damage to conductors or equipment connected to the
wiring.
sieeve for the innerducts. having a system of organic coatings marked "Raintight," "Rainproof,"
"Innerduct" and "outerduct" are terms usually associated or "OutdoorType," can be installed outdoors.
with optical fiber cable installations. while "unitduct" comes with
(3) In Concrete or in Direct Contact with the Earth. Ferrous metal
factory installed conductors. All of these come in various sizes.
raceways, cable armor, boxes, cable sheathing, cabinets, elbows,
Galvanized hgid metal conduit, Schedule 40 and Schedule 80
couplings, nipples, fittings, supports, and support hardware can be
PVC, HDPE conduit and nonmetallic underground conduit with
installed in concrete or in direct contact with the earth, or in áreas
conductors (NUCC) are common wiring methods used with
subject to severe corrosive influences if made of material approved
directional boring installations.
for the condition, or if provided with corrosión protection approved for
the condition.
300.6 Protection Against Corrosión and Deteriora-
tion. Raceways, cable trays, cablebus, cable armor, boxes. cable Author's Comment Galvanized steel electrical metallic tubing can
sheathing, cabinets, elbows, couplings, fittings, supports, and support be installed in concrete at grade level and in direct contact with the
hardware must be suitable for the environment. Figure 300-27 earth, but supplementary corrosión protection is usually required
(UL White Book, Guide Information for Electrical Equipment, vmN.
(A) Ferrous Metal Equipment. Ferrous metal raceways, enclosures,
ul.com/regulators/2008_WhiteBook.pdf). Electrical metallic tubing
cables, cable trays, fittings, and support hardware must be protected
can be installed in concrete above the ground floor slab generally
against corrosión by a coating of listed corrosion-resistant material.
without supplementary corrosión protection. Figure 300-28
Where conduit is threaded in the field, the threads must be coaíed
with an approved eiectrically conductive, corrosion-resistant com- (B) Aluminum Equipment. Aluminum raceways, cable trays, cable-
pound, such as coId zinc. bus, cable armor, boxes, cable sheathing, cabinets, elbows, cou-
plings, nipples, fittings, supports, and support hardware embedded or
Author's Comment: Nonferrous metal raceways, such as alu-
encased in concrete or in direct contact with the earth must be pro-
minum rigid metal conduit, don't have to meet the provisions of
vided with supplementary corrosión protection.
this section.
Protection Against Corrosión (1) Exposed to Sunlight. If exposed to sunlight, the materiais must
Raceways in Concrete or Direct Contact with Earth
r 300.6(A)(3) ^ be listed or identified as sunlight resistant.
Galvanized E M T in a ground floor slab or Author's Comment: See the definitions of "Exposed" and
in direct contact with the earth requires "Location, Wet" in Article 100.
supplemental corrosión protection.
(C) Nonmetallic Equipment. Nonmetallic raceways, cable trays, Note: Areas where acids and alkali Chemicals are handied and
stored may present corrosive conditions, particularty when wet or
cablebus, boxes, cables with a nonmetallic outer jacket and internal
damp. Severe corrosive conditions may aiso be present in portions
metal armor or jacket, cable sheathing, cabinets, elbows, couplings, of meatpacking plants, tanneries, glue houses, and some stables; in
nipples, fittings, supports, and support hardware must be made of installations immediately adjacent to a seashore or swimming pool,
spa, hot tub, and fountain áreas; in áreas where chemical deicers
material identified for the condition, and must comply with (1) and (2).
are used; and in storage celfars or rooms for hides, casings, fertilizer,
Figure 300-29 sait, and bulk Chemicals.
Figure 300-29
Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring Methods 300.10
Electric
Seal-Off Fitting Conductors
Violation
Not Required or Cables
Expansión
Fitting
Okay
O p e n i n g is not a r a c e w a y
CcpyrighlZOlO
¥fwwMikeHollcom Water
VIOLATION
N M cable isn't
suitable for a
wet location
[334.12(B)(4)]. Short sections of r a c e w a y s used for support
or protection of cables aren't required to be
Insulated conductors and cables installed in eiectrically continuous or c o n n e c t e d t o an
raceways located in w e t locations must be e q u i p m e n t g r o u n d i n g conductor [250.86 Ex 2]
listed for use in w e t locations.
Figure 300-36
Electrical Continuity
300.10
300.11 Securing and Supporting.
Panel
Outlet (A) Secured in Place. Raceways, cable assemblies, boxes, cabinets,
and fittings must be secureiy fastened in place. The ceiling-support
wires or ceiling grid must not be used to support raceways and cables
(power, signaling, or Communications). However, independent support
wires that are secured at both ends and provide secure support are
permitted. Figure 300-37
Effective Ground-Fault Ground
Current Path Fault
Figure 300-37
Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring Methods 300.11
Author's Comment: Outlet boxes [314.23(D)] and luminaires Raceways Used for Support
can be secured to the suspended-ceiling grid if secureiy fas- 300.11 (B)
tened to the ceiling-framing members by mechanical means
such as bolts, screws, or rivets, or by the use of clips or other
^ L_
securing means identified for use with the type of ceiling-fram-
ing member{s) used [410.36(B)].
Equipment controlled
by a Class 2 circuit.
Cable supported by a
Independent support wires used for support can b e ] raceway is permitted.
attached to the nonfire-rated assembiy. These support
wires must be distinguishable by color, tagging. etc.
Copyright » 1 1 . www.MiksHott.i Class 2 cables can be supported by the raceway that
supplies power to the equipment controlled by the cable.
Figure 300-38
Figure 300-40
Mechanical Continuity
300.12 Ex 1
Violation Furnace
Figure 300-41
300.12 Mechanical Continuity. Raceways and cable Short sections of raceways used t o provide support
or protection of cable from physical d a m a g e aren't
sheaths must be mechanically continuous between boxes, cabinets, required to be mechanically continuous.
and fittings. Figure 300-42
Figure 300-43
Mechanical Continuity
300.12
Mechanical Continuity
O p e n - B o t t o m Equipment
300.12 Ex 2
B 1 .
OKAY —
i
Figure 300-44
continuous [250.86 Ex 2 and 300.10 Ex 1]. Figure 300-43 bottom switchboard, the raceway, inciuding the end fitting, can't
rise more than 3 in. above the bottom of the switchboard enclo-
Ex 2: Raceways at the bottom of open-bottom equipment, such sure [408.5].
as switchboards, motor control centers, and transformers, aren't
required to be mechanically secured to the equipment. Figure 300-44
Mike Hoit's Iliustrated Guide to Understanding the 2011 National ElecMcal Code, Volume 1
Wiring IVIethods 300.13
300.13 Spiices and PIgtalls. Author's Comment: Tfie opening of tlie ungrounded con-
ductors, or tlie neutral conductor of a 2-wire circuit during the
A) Conductor Spiices. Spiices must be in enclosures as per 300.15
repiacement of a device, doesn't cause a safety hazard, so pig-
and aren't permitted in raceways, except as permitted by 376.56, taillng these conductors isn't required [110.14(B)].
386.56, or 388.56. Figure 300-45
CAUTION: If the continuity of the neutral conductor
of a multiwire circuit is interrupted (oponed), the
resultant over- or undervoltage can cause a fire and/
Spiices in R a c e w a y
or destruction of electrical equipment
300.13(A)
wiring device. In these applications the neutral conductors must be R = 36 ohms (12 ohms + 24 ohms)
spiiced together, and a pigtail must be provided for the wiring device. l = 240V/36ohms
Figure 300-46
L1
L1 " T " 600W
i L2 TV 120V TV
24Q: 240V
H.D. T2&1 , V2
12Í1 120V 1200W
Vi ! I Hair Dryer
L2-*- _ j — — »
Copynghl 2011, *w*.Mit<eHo« rom
Parallel Circuit
er Connection Caution: If the u n g r o u n d e d conductors o f a multiwire
Voltage Drop of circuit aren't terminated to different phases or lines,
Televisión = 120V the currents on the neutral conductor won't cancel,
Voltage Drop of but will a d d , which can c a u s e a d a n g e r o u s overload
Hair Dryer = 1 2 0 V on the neutral conductor.
L e n g t h of Free Conductor
300.14
Figure 300-48
294 Mike HoiVs iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring Methods 300.15
Figure 300-53
300.15 Boxes or Conduit Bodies. A box must be installed
at each spiice or termination point, except as permitted for: Figure
300-52 Author's Comment: Boxes aren't required for the following sig-
naling and Communications cables or raceways: Figure 300-54
• Cabinet or Cutout Boxes, 312.8
• Conduit Bodies, 314.16(C) Figure 300-53 • • CATV. 90.3 ' ^
Spiice and Termination Points (C) Raceways for Support or Protection. When a raceway is used
Control, Signal, a n d Communications Circuits
for the support or protection of cables, a fitting to reduce the potential
for abrasión must be placed at the location the cables enter the race-
way. Figure 300-56
Reception A r e a
I A bbox
( isn't
30Q.15{C)
required.
\r R o o m
Figure 300-54
Fittings and Connectors. Fittings can only be used with the specific
wiring methods for which they're listed and designed. For example,
Type NM cable connectors must not be used with Type AC cable, and
electrical metallic tubing fittings must not be used with rigid metal
conduit or intermedíate metal conduit, unless listed for the purpose. Figure 300-56
Figure 300-55
272 E M T
Connector VIOLATION
Fittings are permitted only
\
on the wiring method f o r
which they're listed. A fitting is permitted in lieu of a box or
conduit body w h e r e the conductors aren't
TA R M C spiiced or terminated within the fitting and
Copynghl 2011. www.UiksHoiI com
the fitting is accessible after instaliation.
Figure 300-55
296 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring Methods 300.17
(G) Underground Spiices. A box or conduit body isn't required where Spiice and Termination Points
Handhole Enclosure
a spiice is made underground if the conductors are spiiced with a
300.15(L)
spiicing device listed for direct burial. See 110.14(B) and 300.5(E).
ÉÉHlhhHíliWÉlWlÉf
{!) Enclosures. A box or conduit body isn't required where a spiice
is made in a cabinet or in cutout boxes containing switches or over-
current devices if the spiices or taps don't fill the wiring space at any
crass section to more than 75 percent, and the wiring at any cross
section doesn't exceed 40 percent. See 312.8 and 404.3(B). Figure
300-58
Figure 300-59
Spiice and Termination Points
Switch/Circuit Breaker Enclosure
300.15(1) 300.16 Raceway or Cable to Open or Concealed
Wiring.
Author's Comments:
Figure 300-58 • When all conductors in a raceway are the same size and of
the same insulation type, the number of conductors permitted
can be determined byAnnex C.
Author's Comment: See the definitions of "Cabinet" and
"Cutout Box" in Article 100. • When different size conductors are installed in a race-
way, conductor fill is limited to the percentages in Table 1 of
(L) Handhole Enclosures. A box or conduit body isn't required for Chapter 9. Figure 300-60
must be accomplished by the use of fittings listed as suitable for 1 Conductor 53%
wet locations [110.14{B) and 314.30(C)]. 2 Conductors 31%
3 or more 40%
One Conductor
Raceway
5 3 % Fill
24 i n . o r Less:
6 0 % Fill
Note 4
Two Conductors
3 1 % Fill
Cable is Treated
OQD) a s 1 Conductor Table 5 Table 8 Table 8
Three o r More 5 3 % Fill, Note 9 10THHN 10 A W G 10 A W G
Conductors (Solid/Stranded) Bare Stranded
Bare Solid
4 0 % Fill Cop/nght 2011. www WikeHoA com
Area Area Area
W h e n conductors are installed in a raceway, 0.0211 in.2 0.008 in.2 0.011 in.2
conductor fill is limited to the above percentages. CopyfigM 2011. woMJMMHoa com
Figure 300-61
298 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring IVIethods 300.19
Inserting Conductors in R a c e w a y
Step 1: Determine ttie total área of conductors
Complete Runs
[Ctiapter9, Table 5]: 300.18(A)
500 THHN 0.7073 x3= 2.1219 in.^
250 THHN 0.3970 X 1 - 0.3970 in.^
3 THHN 0.0973 X 1 - + 0.0973 in.^
VIOLATION
Total Area = 2.6162 in.' R a c e w a y s must
be complete prior
Step 2: Select the raceway at 40 percent fill to the instaliation
of conductors.
[Chapter 9, Table 4]:
R a c e w a y Sizing
300.17 Figure 300-65
Figure 300-64
Ex: Short sections of raceways used for the protection of cables from
physical damage aren't required to be installed complete between
outlet, junction, or spiicing points.
Author's Comment: The weight of long vertical runs of con- Magnetic materiais naturally resist the rapidly changing mag-
ductors can cause the conductors to actually drop out of the netic fields. The resulting friction produces its own additional
raceway if they aren't properiy secured. There have been many heat—hysteresis heating—in addition to eddy current heating.
cases where conductors in a vertical raceway were released A metal which offers high resistance is said to have high mag-
from the pulling "basl^et" or "grip" {at the top) without being netic "permeability." Permeability can vary on a scale of 100 to
secured, and the conductors fell down and out of the raceway, 500 for magnetic materiais; nonmagnetic materiais have a per-
injuring those at the bottom of the instaliation. meability of one.
Simply put, the molecules of steel and iron align to the polar-
ity of the magnetic field and when the magnetic field reverses,
300.20 Induced Currents In Ferrous Metal Enclo-
the molecules reverse their polarity as well. This bacl<-and-forth
sures and Raceways.
alignment of the molecules heats up the metal, and the more
(A) Conductors Grouped Together. To minimize induction heating the current flows, the greater the heat rises in the ferrous metal
of ferrous metal raceways and ferrous metal enclosures for alternat- parts. Figure 300-68
ing-current circuits, and to maintain an effective ground-fault cur-
rent path, all conductors of a circuit must be installed in the same
Induced Currents in Ferrous Metal Parts
raceway, cable, trench, cord, or cable tray. See 250.102(E), 300.3(B), Hysteresis Heating
300.5(1), and 392.8(0). Figure 300-67 Ferrous Metal
(not a l u m i n u m )
O n e Cycle - AC
300 Mike HoiVs iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring IVIethods 300.21
(B) Single Conductors. When single conductors are installed in non- S p r e a d of Fire or Products of Combustión
300.21
metallic raceways as permitted in 300.5(1) Ex 2, the inductive heat-
ing of the metal enclosure must be minimized by the use of aluminum
locknuts and by cutting a slot between the individual holes through
which the conductors pass. Figure 300-69
'PHASE^ V^ÍhASeN
Figure 300-70
(>ipyñSlW20ii,wi«v<.Mi*eHoitc«ii \
S p r e a d of Fire or Products of C o m b u s t i ó n
Author's Comment: Aluminum conduit, locknuts, and enclo- 300.21 Note
sures carry eddy currents, but because aluminum is nonferrous, 16in.^ • 16 in.
it doesn't heat up [300.20(B) Note], VIOLATION Top View
24 in.
300.21 Spread of Fire or Products of Combustión.
Electrical circuits and equipment must be installed in such a way VIOLATION 7 1! Top View
that the spread of fire or products of combustión won't be substan- 24 in.^
tially increased. Openings into or through fire-rated walls, floors, and
ceilings for electrical equipment must be fire-stopped using meth- OKAY b p View
ods approved by the authority having jurisdiction to maintain the fire-
2 4 in. CapyrtoH 20ia www.MkeHoUcom
resistance rating of the fire-rated assembiy. Figure 300-70 Outlet boxes installed on opposite sides of a fire-rated
assembiy must have a horizontal separation not less
than 24 in. unless listed for closer spacing or protected
by fire-resistant "putty pads."
Figure 300-71
Author's Comments: (B) Ducts Specifically Fabricated for Environmental Air. If neces
sary for direct action upon, or sensing of, the contained air, Type MC
• Boxes installed in fire-resistance-rated assemblies must be
cable that has a smooth or corrugated impervious metal sheath with-
listed for the purpose. If steel boxes are used, they must be
out an overall nonmetallic covering, electrical metallic tubing, flexi-
secured to the framing member, so cut-in type boxes aren't
permitted (UL White Book, Guide Information for Electrical ble metallic tubing, intermedíate metal conduit, or rigid metal conduit
Equipment, www.ul,com/regulators/2008_WhiteBook.pdf). without an overall nonmetallic covering can be installed in ducts spe-
cifically fabricated to transport environmental air. Flexible metal con-
• This rule aiso applies to control, signaling, and Communications
duit in lengths not exceeding 4 ft can be used to connect physically
cables or raceways.
adjustable equipment and devices within the fabricated duct.
- CATV, 820.26
Equipment is only permitted within the duct specifically fabricated to
- Communications, 800.26
transport environmental air if necessary for the direct action upon, or
- Control and Signaling, 725.25
sensing of, the contained air. Equipment, devices, and/or illumination
- FireAlarm,760.3(A)
are only permitted to be installed in the duct if necessary to facilítate
- Optical Fiber, 770.26
maintenance and repair. Figure 300-73
- Sound Systems, 640.3(A)
(A) Ducts Used for Dust, Loóse Stock, or Vapor. Ducts that trans-
port dust, loóse stock, or vapors must not have any wiring method VIOLATION
installed within them. Figure 300-72 Ducts specifically fabricated to transport
environmental air aren't permitted to contain
any wiring unless necessary for direct action
or sensing of the contained air.
Ducts Used for Dust, Loóse Stock, or Vapor
300.22(A) C o p y r l ^ 2011. www.UtoHoKxom
Figure 300-73
5S¿
pose of which isn't air handiing.
O
Note 1: The spaces above a suspended ceiling or below a raised
floor used for environmental air are examples of the type of space to
Copyright 2011. www.hfikvHoK com which this section applies. Figure 300-74
Figure 300-72 Note 2: The phrase "other space used for environmen-
tal air (plenum)" correlatas with the term "plenum" in NFPA
90A, Standard for tt\e Instaliation of Air-Conditioning and
Ventilating Systems, and other mechanical codes where the
ceiling cavity plenum is used for return air purposes, as well
as some other air-handling spaces.
302 Mike Hoit's iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring Methods 300.22
i
environmental air (plenums)." - CATV, 820.179(A)
Cop™MZ011,ww*.MiKeHoB.com \ RaíSCd FlOOr - Communications, 800.21
I I \ ^ (not in ITE room) | ^ - Control and Signaling, 725.154(A)
- FireAlarm, 760.7
Environmental Air Space (Plenum) ^
- Optical Fiber Cables and Raceways, 770.113(0)
Figure 300-74 - Sound Systems, 640.9(C) and 725.154(A)
• Any wiring method suitable for the condition can be used in
Author's Comment: For the purpose of this book, when a space not used for environmental air-handling purposes.
the NEC references "other space used for environmental air Figure 300-77
(plenum)," the term cavity plenum space' will be used.
Suspended Air
Ceiling Handler
Figure 300-75
Space Not Used for Environmental Air (3) Equipment. Electrical equipment with metal enclosures is permit-
Wiring Methods Permitted
300.22(C)(1) ted to be installed in cavity plenum space.
1
air-handling purposes has no wiring Environmental
method restrictions. Air Space
(Ptenum)
I
Copyright 2011. www MikaHoH.coni
Figure 300-77
Electrical equipment with
metal enclosures is
permitted in plenum space.
(2) Cable Tray Systems. C o p y n ) ^ 1011. www UfteHoK cMn
(a) Metal Cable Tray Systems. Metal cable tray systems can be
installed to support the wiring methods and equipment permitted by Figure 300-79
this section. Figure 300-78
304 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Wiring Methods 300.23
Panels Designed to A l l o w A c c e s s
300.23
^ . ^
Equipment Behind
Removable Panels
R e m o v a b l e Panel
Copyright 2011. «iww MiKehtoll.com
Figure 300-80
People often make errors in appiying the ampacity tables contained in Article 310. If you study the explanations carefully, you'll avoid
common errors such as appiying Table 310.15(B)(17) when you should be appiying Table 310.15(B)(16).
Why so many tables? Why does Table 310.15(B)(17) list the ampacity of 6 THHN as 105 amperes, yet Table 310.15(B)(16) lists the same
conductor as having an ampacity of only 75 amperes? To answer that, go back to Article 100 and review the definition of ampacity. Notice
the phrase "conditions of use." These tables set a máximum current valué at which premature failure of the conductor insulation shouldn't
occur during normal use, under the conditions described in the tables.
The designations THHN, THHW, RHH, and so on, are insulation types. Every type of insulation has a limit to how much heat it can withstand.
When current flows through a conductor, it creates heat. How well the insulation around a conductor can dissipate that heat depends on
factors such as whether that conductor is in free air or not. Think about what happens when you put on a sweater, a jacket, and then a
coat—all at the same time. You heat up. Your skin can't dissipate heat with all that clothing on nearly as well as it dissipates heat in free air
The same principal applies to conductors.
Conductor insulation aiso fails with age. That's why we conduct cable testing and take other measures to predict failure and replace certain
conductors (for example, feeders or critical equipment conductors) while they're still within design specifications. But conductor insulation
failure takes decades under normal use—and it's a maintenance issue. However, if a conductor is torced to exceed the ampacity listed in
the appropriate table, and as a result its design temperature is exceeded, insulation failure happens much more rapidly—often catastrophi-
cally. Consequently, exceeding the allowable ampacity of a conductor is a serióos safety issue.
PART I. GENERAL í ü Dry and Damp Locations. Insulated conductors typically used in
dry and damp locations include THHN, THHW, THWN, or THWN-2.
310.1 Scope. Article 310 contains the general requirements for
conductors, such as insulation markings, ampacity ratings, and their Author's Comment: Refer to Table 310.104 for a complete list
use. This article doesn't apply to conductors that are an integral part of conductors that may be installed in dry or damp locations.
of equipment [90.7 and 300.1 (B)].
(C) Wet Locations. Insulated conductors typically used in wet loca-
tions include:
PART II. INSTALLATION (2) Types THHW, THWN, THWN-2, XHHW, or XHHW-2
310.10 Uses Permitted. Conductors described in 310.104 can Author's Comment: Refer to Table 310.104 for a complete list
be used in any oí the wiring methods recognized in Chapter 3 as per- of conductors that may be installed in wet locations.
mitted in ms Code [110.8].
306 Mike HoiVs iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Conductors for General Wiring 310.10
Figure 310-2
(3) Be the same size in circular mil área (minimum 1/0 AWG).
Figure 310-1 (4) Have the same type of insulation (like THHN).
(2) Covered with insulating material, such as tape or sieeving mate- (3) Sepárate Raceways or Cables. Raceways or cables containing
riais that are listed as being sunlight resistant or marked as being parallel conductors must have the same electrical characteristics and
sunlight resistant. the same number of conductors. Figure 310-3
R a c e w a y s containing parallel
conductors must have the s a m e
Conductors in Parallel
electrical characteristics and t h e
Conductor A m p a c i t y Adjustment
s a m e n u m b e r of conductors. 310.10(H)(4)
Conductors in Parallel
E q u i p m e n t Grounding Conductor
Conductors in Parallel - Sepárate Cables or Raceways
310.10{H)(5}
310.10(H)(3)
2 - 3 A W G C U , 101 f t l o n g CopyOBWaOll
T h e e q u i p m e n t grounding conductor in each
raceway is sized to 250.122 b a s e d o n t h e rating
For current to be evenly distributed between of the overcurrent device. 6 0 0 A = 1 A W G
the individual parallel conductors, each conductor
(within a parallel set) must be identical to each other. Figure 310-6
Figure 310-4
308 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Conductors for General Wiring 310.15
Author's Comment: The minimum 1/0 AWG paraliei conduc- (2) Conductor Ampacity—Lower Rating. Where more than one
tor size rule of 310.10(H) doesn't apply to equipment grounding ampacity applies for a given circuit length, the lowest valué must be
conductors. used. Figure 310-8
5 current-carrying conductors
Ambient Temperature 110°F
Conductor Ampacity
The máximum current, in a m p e r e s , a conductor Higher Rating
can carry continuously, under the conditions of use
310.15(A)(2)Ex
[310.15] without exceeding its temperature rating.
60 ft
Figure 310-7 55 ft 5ft
Í
Ambient j¡£,^._^,jr* ^ Conductor
Conductor
The higher ampacity can be used if the length of the Temperature J f f W B ^ B l H Bundiing ¿wWfTS^
lower ampacity isn't more than 10 ft, a n d it isn't longer If the ambient temperature is If the n u m b e r of current-
than 10 percent o f t h e higher ampacity length. above 86°F or below 78°F, the carrying conductors
conductor ampacity changes. exceeds 3, the conductor
[Table 310.15(B)(2)(a)]. ampacity decreases
Figure 310-10
Copynghl 201V www.MkeHott com [Table 310.15(B)í3j(a)].
Rgure 310-11
(3) Insulation Temperature LImitation. Conductors must not be
used where the operating temperature exceeds that designated for
the type of insulated conductor involved.
Conductor A m p a c i t y - Temperature Correction Adjustment
310.15(B)(2)(a)
Note 1: The insulation temperature rating of a conductor [Table
310.104(A)] is the máximum temperature a conductor can withstand R a c e w a y o n roof with four 10 T H W N - 2 . T h e ambient
over a prolongad time period without serious degradation. The main temperature is 150°F (90°F + 60°F [310.15(B)(3)(c)].
factors to consider for conductor operating temperature include:
rsi
(2) Heat generated internally in the conductor—load current flow.
(3) The rate at which generated heat dissipates into the ambient
médium.
10 T H W N - 2 rated 40A, TbI 310.15(B)(16) at 90°C
(4) Adjacent load-carrying conductors have the effect of raising Ampacity = 4 0 A x 0.58 x 0.80
Ampacity = 18.56A
the ambient temperature and impeding heat dissipation [Table
310.15(B)(3)(a)]. üá-i . .-.
Figure 310-12
Note 2: See 110.14(0(1) for the temperature limitation of
terminations.
(2) Conductor Ampacity Ambient Temperature Correction. When
(B) Ampacity Table. The allowable conductor ampacities listed in conductors are installed in an ambient temperature other than 78°F
Table 310.15(B)(16) are based on conditions where the ambient tem- to 86°F, the ampacities listed in Table 310.15(B)(16) must be cor-
perature isn't over 86°F, and no more than three current-carrying rected in accordance with the multipliers listed in Table 310.15(B)(2)
conductors are bundied together. Figure 310-11 M : Figure 310-13
310 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Conductors for General Wiring 310.15
50 or less 10 or less 1.20 1.15 Cable. Where four or more current-carrying power conductors are in
a raceway longer than 24 in. [310.15(B){3)(a)(3)], or where cables are
51-59T 11-15°C 1.15 1.12
bundied for a length longer than 24 in., the ampacity of each conduc-
60-68°F 16-20°C 1.11 1.08
tor must be reduced in accordance with Table 310.15(B)(3)(a).
69-77°F 21-25°C 1.05 1.04
168-176T 76-80'^C 0.00 0.41 'Number of conductors is the total number of conductors in the raceway or
cable adjusted in accordance with 310.15(B)(5) and (6).
177-185T 81-85°C 0,00 0.29
Figure 310-16
Figure 310-14
Conductor A m p a c i t y - Table 310.15{B)(16)
A d j u s t m e n t Factor - A C and M C Cables
310.15(B)(3)(a)(4)
Conductor A m p a c i t y A d j u s t m e n t Factor
310.15(B)(3)(a) and Table 310.15(B)(16) Ampacity adjustment doesn't apply
to Type AC or MC cable when:
Raceway contains 4 current-carrying (a) Cable has no outer jacket.
conductors. T h e Table 310.15(B)(3)(a) fb) Each cable has no more than
adjustment factor is 0.80. three current-carrying conductors.
fe) The conductors are 12 AWG copper
(d) No more than 20 current-carrying
conductors are installed without
maintaining spacing for a continuous
length longer than 24 in.
(1) Conductor ampacity adjustment of Table 310.15(B)(3)(a) does not (c) The conductors are 12 AWG copper, and
apply to conductors installed in cable trays, 392.80 apply.
(d) No more than 20 current-carrying conductors (ten 2-wire cables
(2) Conductor ampacity adjustment of Table 310.15(B)(3)(a) does not or six 3-wire cables) are installed without maintaining spacing for
apply to conductors in raceways having a length not exceeding a continuous length longer than 24 in.
24 in. Figure 310-16
Mike Hoit's iiiustrated Guide to Understanding ttie 2011 Nationai Eiectricai Code, Voiume 1
Conductors for General Wiring 310.15
(5) Ampacity adjustment of 60 percent applies to conductors within Circular R a c e w a y s Exposed to Sunlight on Roofs
A m b i e n t Temperature Adjustments
Type AC or Type MC cable without an overall outer jacket under 310.15(B)(3}(c)
the following conditions: Ambient
The raceway is 3 / 4 in. above Temperature
(fa) The number of current-carrying conductors exceeds 20. the roof, so a d d 4 0 O F to the is 9 0 ° F
ambient temperature.
(c) The cables are stacked or bundied longer than 24 in. without
spacing being maintained. 8 THWN-2
Ampacity?
(c) Circular Raceways Exposed to Sunlight on Rooftops. When
appiying ampacity adjustment correction factors, the ambient temper-
ature adjustment contained in Table 310.15{B)(3)(c) is added to the Table 310.15(B)(16) ampacity, 8 T H W N - 2 = 55A
Adjusted Temperature:
outdoor ambient temperature for conductors installed in circular race-
90OF + 40OF [Table 310.15{B)(3}(c)] = 130OF
ways exposed to direct sunlight on or above rooftops to determine Temp Con-ection Factor = 0.76 [Table 310.15{B)(2)(a)]
the applicable ambient temperature for ampacity correction factors N e w A m p a c i t y = 5 5 A x 0.76 = 41.80A
in Table 310.15(B)(2)(a) or Table 310.15(B)(2)(b). Figures 310-18 and
Figure 310-19
310-19
Neutral Conductors From the S a m e Circuit (c) The neutral conductor of a 4-wire, three-phase, 120/208\ or
310.15(B)(5)(a)
277/480V wye-connected system is considered a current-carry-
ing conductor for conductor ampacity adjustment of 310.15(B)(3)
120/240V
(a) if more than 50 percent of the neutral load consista of nonlin-
earloads.Figure310-22
15A ih5A
100A
Neutral conductors that carry only unbalanced Nonlinear
current from other conductors f r o m the s a m e circuit
aren't considered current-carrying conductors.
Figure 310-20
Figure 310-22
Author's Comment: When a 3-wire circuit is supplied from a
4-wire. three-phase, 120/208V or 277/480V wye-connected
system, the neutral conductor carries approximately the same
Author's Comment: Nonlinear loads supplied by a 4-wire,
current as the ungrounded conductors. Figure 310-21
three-phase, 120/208V or 277/480V wye-connected system
can produce unwanted and potentially hazardous odd triplen
harmonio currents (3rd, 9th, 15th, and so on) that can add on
Neutral Conductor of a 3-Wire Circuit the neutral conductor. To prevent fire or equipment damage
From a W y e 4-Wire System from excessive harmonio neutral current, the designer should
310.15(B)(5)(b)
120/208V or 277/480V consider increasing the size of the neutral conductor or install-
ing a sepárate neutral for each phase. For more information,
Current-Carrying Conductor visit www.MikeHolt.com, click on the "Tecbnical" link, then the
"Power Quality" link. Aiso see 210.4(A} Note, 220.61 Note 2,
T h e neutral conductor o f a and 450.3 Note 2.
3-wire circuit from a 4-wire,
w y e system is considered a
current-carrying conductor. (6) Grounding Conductors. Grounding and bonding conductors
aren't considered current carrying. Figure 310-23
Determine the neutral current.
(7) Dweiling Unit Feeder/Service Conductors. For individual dweil-
I NEUTRAL = J{L2^ + L32) - (L2 X L3)
314 Mike Hoit's Iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Conductors for General Wiring 310.15
Copvrtghl»1l,w«M.KHi*Hall.com
2 3 5 A Calculated Load
CAUTION: Because the service neutral conductor is
4/0 A W G Service a n d
Feeder Conductors Wt^ required to serve as the effective ground-fault cur-
rent path, it must be sized so it can safety carry the
máximum fault current likely to be imposed on it [ 110.10 and
250.4(A)(5)]. This is accomplished by sizing the neutral con-
For individual dweiling units of one-family, two-family, ductor In accordance with Table 250.66, based on the área of
and multifamily dweiling units, Table 310.15(B)(7) c a n the largest ungrounded service conductor [250.24(C)(1)].
be used to size 3-wire, single-phase, 120/240V service
or feeder conductors that supply all loads that are part
of, or associated with, the dweiling unit.
— Rubber
— H = (one H) 750C Insulation
f W e t Locations
i
(D) Insulated. Conductors must be insulated except where specific
2 90°C in Wet/Dry Locations permission allows them to be covered or bare. Figure 310-31
Nylon Jacket or Equivalent
W e t Locations
Figure 310-29
310.106 Conductors
(A) Minimum Size Conductors. The smallest conductor permitted for
branch circuits for residential, commercial, and industrial locations is
14 AWG copper, except as permitted elsewhere in this Code.
318 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Conductors for General Wiring 310.110
U n g r o u n d e d conductors must
Types of Equipment Grounding Conductors be clearly distinguishable from
250.118 neutral a n d equipment
grounding conductors.
An equipment g r o u n d i n g conductor
can be any o n e or a combination of
the types listed in 250.118.
N M Cable
For all such enclosures, certain requirements apply—-regardiess of the use. For example, you must cover any openings, protect conductors
from abrasión, and allow sufficient bending room for conductors.
Notice that Article 408 covers switchboards and panelboards, with primary emphasis on the interior, or "guts" while the cabinet that would be
used to endose a panelboard is covered here in Article 312. Therefore you'll find that some important considerations such as wire-bending
space at termináis of panelboards are included in this article.
Article 312 covers the instaliation and construction specifications for cabinets, cutout boxes. and meter socket enclosures. [312.1].
Author's Comment: A cabinet is an enclosure for either surface mounting or flush mounting and provided with a frame in which a door may
be hung. A cutout box is designed for surface mounting with a swinging door [Article 100]. The industry ñame for a meter socket enclosure
is "meter can."
312.1 Scope. Article 312 covers the instaliation and construc- Cabinets, Cutout B o x e s , and Meter C a n s
312.1
tion specifications for cabinets, cutout boxes, and meter socket enclo-
Screw/Bolt C o v e r Meter Socket
sures. Figure 312-1 Hinged Cover
Enclosure
Figure 312-1
320 Mike HoiVs Iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Cabinets, Cutout Boxes, and Meter Socket Enclosure 312.5
312.2 Damp or Wet Locations. (A) Unused Openings. Openings intended to provide entry for con-
ductors must be adequately closed. Figure 312-3
Enclosures in damp or wet locations must prevent moisture or water
from entering or accumulating wittiin the enclosure, and must be
weatherproof. When the enclosure is surface mounted in a wet loca- U n u s e d R a c e w a y and Cable Openings
tion, the enclosure must be mounted with not less than a in. air 312.5(A)
space between it and the mounting surface. See 300.6(D).
£x; The Va in. air space isn 't required for nonmetaiiic equipment, race-
ways, or cables.
U n u s e d cable or r a c e w a y o p e n i n g s must be closed
312.3 installed in Walls. Cabinets or cutout boxes installed with a fitting that provides equivalent protection.
Figure 312-4
Figure 312-2
(C) Cable Termination. Cables must be secured to the enclosure with Cable Termination N o t Required
312.5(0) Ex
fittings designed and listed for the cable. See 300.12 and 300.15.
Figure 312-5
Figure 312-6
(d) The raceway is sealed. or tapping off to other enclosures, switches, or overcurrent devices
where all of the following conditions are met:
(e) Each cable sheath extends not less than J4 in. into the
panelboard. (D The total área of the conductors at any cross section doesn't
exceed 40 percent of the cross-sectional área of the space.
(f) The raceway ís properiy secured.
Figure 312-7
(g) Conductor fill is limited to Chapter 9, Table 1 percentages.
322 Mike HoiVs iiiustrated Guide to Understanding tiie 2011 Nationai Eiectricai Code, Volume 1
Cabinets, Cutout Boxes, and IVIeter Socket Enclosure
Switch and Overcurrent Device Enclosures Switch and Overcurrent Device Enclosures
Spiices. Taps. and Feed-Through Conductors Spiices and Taps
312.8(11 312.812).
. J d
A n enclosure can be used as a
raceway if the conductors don't fill |f-T
the wiring space to more than 4 0 % .
H
! Spiices and taps can be installed in a n
i enclosure if the spiices or taps don't
fill the wiring space to more than 7 5 % .
Copyn((m2011,ww*MrteHa«rom " ^ ^ ^ J
Copyrtaht 2D11, wwwMikeHo«.corn
Figure 312-7
Figure 312-9
Article 314 provides guidance for selecting and installing outlet and device boxes, pulí and junction boxes, conduit bodies, and handhole
enclosures. Information in this article will help you size an outlet box using the proper cubic-inch capacity as well as calculating the mini-
mum dimensions for larger pulí boxes. There are limits on the amount of weight that can be supported by an outlet box and rules on how
to support a device or outlet box to various surfaces. This article will help you understand these type of rules so that your instaliation will be
compliant with the NEC. As always, the clear illustrations in this unit will help you visualize the finished instaliation.
PART I. SCOPE AND GENERAL 314.3 Nonmetallic Boxes. Nonmetallic boxes can only be
used with nonmetallic cables and raceways.
314.1 Scope. Article 314 contains the instaliation requirements
for outlet boxes, conduit bodies, pulí and junction boxes, and hand- Ex 1: Metal raceways and metal cables can be used with nonmetal-
hole enclosures. Figure 314-1 lic boxes ifall raceways are bonded together in the nonmetallic box
324 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Outlet, Device, Pulí and Junction Boxes; Conduit Bodies; and Handhole Enclosures 314.16
Metal B o x e s (A) Box Volume Calculations. The volume of a box includes the total
314.4 volume of its assembled parts, inciuding plaster rings, extensión rings,
and domed covers that are either marked with their volume in cubic
inches (cu in.), or are made from boxes listed in Table 314.16(A).
Figure 3 1 4 - 4
Figure 3 1 4 - 4
14 2.00
12 2.25
Eacti c o n d u c t o r of a
spiice is c o u n t e d a s o n e .
Box Fill Calculations - Fixture W i r e s
314.16(B)(1) Ex
326 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Outlet, Device, Pulí and Junction Boxes; Conduit Bodies; and Handhole Enclosures 314.16
Cable or R a c e w a y
CONNECTORS
O Conductors
Internal Cable
CLAMPS
1 Conductor
(3) Support Fitting Volume. Each luminaire stud or luminaire hickey Each multigang-device yoke counts as two conductor volumes for
counts as a single conductor volume in accordance with Table each gang, based on the largest conductor that terminates on the
314.16(B), based on the largest conductor that enters the box. Figure device in accordance with Table 314.16(B). Figure 314-12
314-10
Luminaire Hickey 3/8 in. Mounting Each multigang device yoke counts a s two conductor
1 Conductor S t e m (not c o u n t e d ) v o l u m e s for e a c h g a n g based on t h e largest conductor
that terminates o n t h e device.
CopvTignt 2011. www.MikeHol1.com
Figure 314-12
Figure 314-10
Author's Comment: Luminaire stems don't need to be counted Author's Comment: A device that's too wide for mounting in
as a conductor volume. a single-gang box, as described in Table 314.16(A), is counted
based on the number of gangs required for the device.
(4) Device Yoke Volume. Each single-gang device yoke (regard-
less of the ampere rating of the device) counts as two conductor vol-
umes, based on the largest conductor that terminates on the device in
accordance with Table 314.16(B). Figure 314-11
Answer: (b) 5
H o w m a n y 14 A W G
conductors can be a d d e d ? Question: How many 12 AWG conductors can be spiiced ina15
cu in. conduit body? Figure 314-15
CopyrtgW 2011. W¥íw M*>Ho«.com
(^4 (b)6 (0 8 10
Step 1. Volume of box/ring: 30.3 + 3.6 c u in. = 33.9 c u i n .
Step 2. Volume of existing conductors/devices = 22.5 c u i n . Answer: (b) 6 conductors (15 cu in./2.25 cu in.)
Step 3. Space remaining: 33.9 - 22.5 = 11.4 c u in.
Step 4 . Number of 14 A W G a d d e d : 11.4/2.0 c u in. = 5 12AWG = 2.25 cu in. [Table 314.16(B)[
15cuin./2.25cuin. =6
Figure 314-14
328 Mike HoiVs Iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Outlet, Device, Pulí and Junction Boxes; Conduit Bodies; and Handhole Enclosures 314.17
Conduit Body - Conductor Spiices Author's Comment Unused cable or raceway openings in
314.16(C)(2) electrical equipment must be effectively closed by fittings that
provide protection substantially equivalent to the wall of the
equipment [110.12(A)]. Figure 314-17
y * " —
Six 12 A W G Conductors (15 c u in./2.25 c u in.)
Plug Filler
CopyTig(it2011 www.Mit>eHol1.<
Figure 314-15
Copyri^2(M1
W e e p (drain) holes, ventilation openings,
a n d other legitímate openings are permitted.
(3) Short-Radius Conduit Bodies. Capped elbows, handy ells, and
sen^ice-entrance elbows aren't permitted to contain any spiices. U n u s e d cable or r a c e w a y o p e n i n g s must be closed with
fittings that provide equivalent protection [110.12(A)].
Figure 314-16
Figure 314-17
Figure 314-16
Figure 314-18
The sheath of type cable must extend not less than Va in. into the Boxes R e c e s s e d in Walls or Ceilings
314.20
nonmetallic box.
Noncombustible
Author's Comment: Two Type NM cables can terminate in a
Finished Surface
single cable clamp, if the clamp is listed for this purpose.
Nonmetallic Single G a n g Box - N M Cable B o x e s , plaster rings, extensión rings, or listed extenders
314.17(0) Ex must have the front edge set back no more than V4 in.
from t h e noncombustible finished surface.
Figure 314-20
Metal
Studs
B o x e s R e c e s s e d in Walls or Ceilings
374.20
Combustible
Finished Surface
330 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Outlet, Device, Pulí and Junction Boxes; Conduit Bodies; and Handhole Enclosures 314.23
(2) Braces. Metal braces no less than 0.02 in. thick and wood bracos
Surface Extensions
not less than a nominal 1 in. x 2 in. can support a box.
314.22
ao.c
(C) Finished Surface Support. Boxes can be secured to a finished
surface {drywail or plaster walls or ceilings) by clamps, anchors, or
fittings identified for the purpose. Figure 314-25
Extensión Surface
Ring Extensión
Figure 314-23
(A) Surface. Boxes can be fastened to any surface that provides ade- B o x e s can be s e c u r e d t o a finished surface by
quate support. c l a m p s , anchors, or fittings identified for the purpose.
(B) structural Mounting. Boxes can be supported from a structural Figure 314-25
member of a building or supported from grade by a metal, plástic, or
wood brace.
(D) Suspended-Ceiling Support. Outlet boxes can be supported
(1) Nails and Screws. Nails or screws can be used to fasten boxes,
to the structural or supporting elements of a suspended ceiling, if
provided the exposed threads of screws are protected to prevent
secureiy fastened by one of the following methods;
abrasión of conductor insulation.
(1) Celling-Framing Members. An outlet box can be secured to sus- Box Support - I n d e p e n d e n t Support W i r e s
314.23(D)(2)
pended-ceiling framing members by boits, screws, rivets, clips, or
other means identified for the suspended-ceiling framing member(s).
Independent support wires
Figure 314-26 can be used to secure
electrical wiring [300.11 (A)].
36 in.
Author's Comment: If framing members of suspended-ceiling
systems are used to support luminaires, they must be secureiy T w o t h r e a d e d IMC o r R M C can support an
fastened to each other and must be secureiy attached to the outlet box without devices or luminaires, if
building structure at appropriate intervals. In addition, luminaires e a c h raceway is supported within 3 6 in., or
must be attached to the suspended-ceiling framing members
36 in. within 18 in. if all conduits are o n one side.
with screws, bolts, rivets, or clips listed and identified for such
use [410,36(B)].
Author's Comment: See 300.11 (A) on the use of independent (2) Rigid metal conduit, Type RMC
support wires to support raceways and cables.
(3) Rigid polyvinyl chioride conduit, Type PVC
(E) Raceway—Boxes and Conduit Bodies Vl/ithout Devices or (4) Reinforced thermosetting resin conduit, Type RTRC
Luminaires. Two intermedíate metal or rigid metal conduits, threaded
(5) Electrical metallic tubing, Type EMT
wrenchtight into the enclosure, can be used to support an outlet box
that doesn't contain a device or luminaire, if each raceway is sup- (F) Raceway—Boxes and Conduit Bodies with Devices or
ported within 36 in. of the box or within 18 in. of the box if all conduit Luminaires. Two intermedíate metal or rigid metal conduits, threaded
enfries are on the same side. Figure 314-28 wrenchtight into the enclosure, can be used to support an outlet box
containing devices or luminaires, if each raceway is supported within
Ex: Conduit bodies are permitted to be supported by any of the follow-
18 in. of the box. Figure 314-29
ing wiring methods:
Mike HoiVs iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Outlet, Device, Pulí and Junction Boxes; Conduit Bodies; and Handhole Enclosures 314.23
(H) Pendant Boxes. (A) Nonmetallic or Metallic. Nonmetallic covers are permitted on
any box, but metal covers are only permitted if they can be con-
(I) Flexible Cord. Boxes containing a hub can be supported from a
nected to an equipment grounding conductor of a type recognized in
cord connected to fittings that prevent tensión from being transmitted
250.118, in accordance with 250.110 [250.4(A)(3)]. Figure 314^32
to joints or termináis [400.10]. Figure 314-30
É
p
Figure 314-32
Figure 314-30
314.27 Outlet Box. (2) Luminaire Outlets in the Ceiling. Boxes for a luminaire in a ceil-
ing must be designed to support a luminaire weighing a minimum of
(A) Boxes at Luminaire Outlets.
50 Ib. Luminaires weighing more than 50 Ib must be supported inde-
f1) Luminaire Outlets in the Wall. Boxes for a luminaire in a wall pendently of the outlet box unless the outlet box is listed and marked
must be designed for the purpose and marked on the interior of the for the máximum weight to be supported. Figure 314-35
box to indícate the máximum weight of the luminaire if other than 50
Ib. Figure 314-33
Luminaire and Lampholder Outlets in Ceiling
314.27(Am
Figure 314-33
(B) Floor Box. Floor boxes must be specifically listed for the purpose.
Figure 314-36
Ex: A wall-mounted luminaire weighing no more than 6 Ib can be sup-
ported to a device box or plaster ring secured to a device box. Figure
314-34 Floor Outlet B o x
314.27(8}
Figure 314-36
A wall-mounted luminaire or lampholder weighing no m o r e
than 6 Ib can be supported to a device box or plaster ring.
Figure 314-34
334 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Outlet, Device, Pulí and Junction Boxes; Conduit Bodies; and Handhole Enclosures 314.28
(C) Ceiling Paddie Fan Box. Outlet boxes for a ceiling paddie fan Outlet B o x e s for Utilization Equipment
314.27(0) Ex
must be listed and marked as suitable for the purpose, and must not
support a fan weighing more than 70 Ib. Outlet boxes for a ceiling
paddie fan that weighs more than 35 Ib must include the máximum
weight to be supported in the required marking. Figure 314-37
Figure 314-38
Fan outlet boxes must be listed,
marked as suitable for the
purpose, and can't support a
314.28 Boxes and Conduit Bodies for Conductors 4
fan that weighs more than 70 Ib.
AWG and Larger. Boxes and conduit bodies containing conduc-
Paddie fans over 70 Ib must b e tors 4 AWG and larger that are required to be insulated must be sized
supported independently of the box.
so the conductor insulation won't be damaged. Figure 314-39
Figure 314-37
Í
ported independently of the outlet box, Ceiling paddie fans over junction boxes, and conduit
70 Ib must be supported independently of the outlet box. bodies w h e n conductor sizes
4 A W G and larger are used.
1 ¡
Where spare, separately switched, ungrounded conductors are pro-
vided to a ceiling-mounted outlet box, in a location acceptable for a A n g l e Pulís U Pulís
Ex: When conductors enter an enclosure with a removable cover, the Pulí Box, Junction Box, a n d Conduit Body Covers
314.28(C)
distance from where the conductors enter to the removable cover
must not be less than the bending distance as listed in Table 312.6(A)
for one conductor per terminal. Figure 314-47
Dimensión D
500 kcmil = 6 i n . T h e metal r a c e w a y and enclosure is t h e equipment i
g r o u n d i n g conductor to w h i c h the covers connect. •
Figure 314-48
mum size of conductors. Power distribution biocks in pulí and junction boxes must:
(1) Be listed as a power distribution block.
(B) Conductors in Pulí or Junction Boxes. Pulí boxes or junction (2) Be installed in a box with dimensions not smaller than
specifiedin.íhe instaliation instructjons.of the block,
boxes with any dimensión over 6 ft must have all conductors cabled f3) Comply with 312.6 for wire-bending space at termináis
or racked in an approved manner. (4) Have no uninsulated exposed live parts. wtiether the
junction/pull box cover is on or off.
(C) Covers. Pulí boxes, junction boxes, and conduit bodies must have
Figure 314-49
a cover suitable for the conditions. Nonmetallic covers are permitted
on any box, but metal covers are only permitted if they can be con-
nected to an equipment grounding conductor of a type recognized in (3) Wire-Bending Space. The junction box is sized so that the wire-
250.118, in accordance with 250.110 [250.4(A)(3)]. Figure 314-48 bending space requirements of 312.6 can be met.
(E) Power Distribution Block. Power distribution biocks installed in (4) Live Parts. Exposed live parts on the power distribution block
junction boxes over 100 cu in. must comply with the following: Figure aren't present when the junction box cover is removed.
314-49
(5) Through Conductors. Where the junction box has conductors that
(1) Instaliation. Be listed as a power distribution block. don't terminate on the power distribution block(s), the through con-
ductors must be arranged so the power distribution block termináis
(2) Size. Be installed in a box not smaller than required by the instal-
are unobstructed following instaliation.
iation instructions ofthe power distribution block.
Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Outlet, Device, Pulí and Junction Boxes; Conduit Bodies; and Handhole Enclosures 314.30
Accessible by \
d Removing Ceiling Panels p ¡ ^
Copyright 20i 1. -ww. WkeHoW.com
Figure 314-50
Figure 314-53
340 Mike Hoit's Iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
ARTICLE
Interlocked Spiral (4) Embedded in plaster or brick, except in damp or wet locations.
Metal Sheath Bonding Strip
(5) Air voids where not exposed to excessive moisture or dampness.
A fabricated assembiy of conductors in a flexible Note: The "Uses Permitted" isn't an all-inclusive list, which indicates
interiocked metal armor with an internal bonding strip that other suitable uses are permitted if approved by the authority
in intímate contact with the armor for its entire length. having jurisdiction.
CopyrigM ?011. www MikeHok com
(3) In air voids of masonry block or tile walls where such walls are If the edge of the hole is less than I V i in. from the edge, a
exposed or subject to excessive moisture or dampness. V\b in. thick steel píate of sufficient length and width must be
installed to protect the wiring method from screws and nails.
(4) Where exposed to corrosive conditions.
Figure 320-3B
Coo*"gm2Cil *w*M*eHoncom
Notch (if permitted) |
[300.4(A)(2)]
Steel Píate Required
Figure 320-2
Figure 320-3
342 Mike HoiVs Iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Armored Cable (Type AC) 320.30
Figure 320-5
(A) Cables Run Across the Top of Floor Joists. Where run across
Máximum
the top of floor joists, or across the face of rafters or studding within 4V2ft
7 ft of floor or floor joists, the cable must be protected by substantial
guard sthps that are at Ieast as high as the cable. If this space isn't
accessible by permanent stairs or ladders, protection is required only
within 6 ft of the nearest edge of the scuttie hole or attic entrance. I Copyright 2011
I www.MkeHolLcom
(A) General. Type AC cable must be supported and secured by Sta- metal framing members are considered supported if support doesn't
ples, cable ties, straps, hangers, or similar fittings, designed and exceed 4^2 ft. Figure 320-7
(B) Securing. Type AC cable must be secured within 12 in. of every the cable is:
outlet box, junction box, cabinet, or fitting, and at intervals not exceed- (1) Fished through concealed spaces in finished buildings or struc-
ing 4V2 ft. Figure 320-6
tures, if support is impracticable; or
Listed A C
^ J2
Cable Fitting
(2) Not more than 2 ft long at termináis where flexibility is necessary; An insulating anti-short bushing, sometimes called a "redhead," must
or be installed at all Type AC cable terminations. The termination fitting
must permit the visual inspection of the anti-short bushing once the
(3) Not more than 6 ft long from the last point of cable support to
cable has been installed. Figure 320-10
the point of connection to a luminaire or other piece of electrical
equipment within an accessible ceiling. Type AC cable fittings are
permitted as a means of cable support. Figure 320-8
A C Cable - B o x e s a n d Fittings
Anti-Short Bushing
A C Cable - Unsupported in Accessible Ceilings 320.40
320.30(D)(3)
Last Point of
A n insulating anti-short bushing must '
X X ^ X . ^ Cable Support p ^ ^ >
be installed at cable terminations.
1 /
Figure 320-8
Author's Comments:
344 mke Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Armored Cable (Type AC) 320.108
Author's Comments:
• Conductors 4 AWG and larger that enter an enclosure must
be protected from abrasión during and after instaliation by • The best method of cutting Type AC cable is to use a tool spe-
a fitting that provides a smooth, rounded, insulating surface, cially designed for the purpose, such as a rotary armor cutter.
such as an insulating bushing unless the design of the box,
• When cutting Type AC cable with a hacksaw, be sure to cut
fitting, or enclosure provides equivalent protection in accor-
only one spiral of the cable and be careful not to nick the con-
dance with 300.4(6).
ductors; this is done by cutting the cable at an angle, Breaking
the cable spiral (bending the cable very sharply), then cutting
320.80 Conductor Ampacity. the cable with a pair of dikes isn't a good practice.
must be sized to the termination temperature rating in accordance cable must provide an adequate path for fault current as required by
with 110.14(C)(1). Figure 320-11 250.4(A)(5) or 250.4(B)(4) to act as an equipment grounding conduc-
tor. Figure 320-12
T y p e A C Cable
Ampacity in Thermai Insulation
320.80(A) A C Cable - Equipment G r o u n d i n g Conductor
320.108
\
conductor in a c c o r d a n c e with 250.118(8).
330.2 Definition.
Metal-Ciad Cable (Type MC). A factory assembiy of insulated cir- PART II. INSTALLATION
cuit conductors, with or without optical fiber members, enclosed in
330.10 Uses Permitted.
an armor of interlocking metal tape or a smooth or corrugated metal-
lic sheath. Figure 330-1 (A) General Uses.
Metal-Ciad Cable (Type M C Cable) (2) In power, lighting, control, and signal circuits
330.2 Definition
(3) Indoors or outdoors
(7) In a raceway
Figure 330-1 (11) In wet locations, if any of the following are met:
346 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
I-Clad Cable (Type MC) 330.17
a. The metallic covering is impervious to moisture. 330.17 Through or Parallel to Framing Members.
Type MC cable installed through or parallel to framing members or
b. A moisture-impervious jacket is provided under the metal
furring strips must be protected against physical damage from pen-
covering.
etration of screws or nails by maintaining a VA in. separation, or by
c. The insulated conductors under the metallic covering are installing a suitable metal píate in accordance with 300.4(A) and (D).
listed for use in wet locations and a corrosion-resistant
jacket is provided over the metallic sheath. Author's Comments:
(12' If single-conductor cables are used, all circuit conductors must • 300.4(A)(1) Drilling Holes in Wood Members. When drilling
be grouped together to minimize induced voltage on the sheath holes through wood framing members for cables, the edge of
[300.3(B)]. the holes must be not less than VA in. from the edge of the
wood member Figure 330-2A
(B) Specific Uses. If the edge of the hole is less than VA in. from the edge, a
VÍ6 in. thick steel píate of sufficient length and width must be
(1) Cable Tray. Type MC cable installed in a cable tray must comply
installed to protect the wiring method from screws and nails.
with 392.10, 392.12, 392.10(E). 392.10(L), 392.10(N), 392.30ÍA),
Figure 330-2B
392.46, and 392.56.
• 300.4(A)(2) Notching Wood Members. If notching of wood
(2) Direct Buried. Direct-buried cables must be protected in accor- framing members for cables is permitted by the building code,
with 300.5. a '/e in. thick steel píate of sufficient length and width must
be installed to protect the cables and raceways from screws
(3) Installed as Service-Entrance Cable. Type MC cable is permit-
and nails. Figure 330-2C
ted for service entráñeos, when installed in accordance with 230.43.
• 300.4(D) Cables Parallel to Framing Members and Furring
(4) Installed Outside of Buildings or Structures. Type MC cable Strips. Cables installed parallel to framing members or furring
installed outside oí buildings or structures must comply with 225.10, strips must be protected where likely to be penetrated by nails
396.10, and 396.12. or screws. The wiring method must be installed so it's at Ieast
11/4 in. from the nearest edge of the framing member or fur-
Note: The "Uses Permitted" isn't an all-inclusive list, which indicates ring strips, or a '/e in. thick steel píate must protect it. Figure
that other suitable uses are permitted if approved by the authority
330-3
having jurisdiction.
(2) Exposed to the destructive corrosive conditions in (a) or (b), unless Bored Hole, [300.4(A)(1)]
the metallic sheath or armor is resistant or protected by material VÁ in. or M o r e ,
No Steel Píate Required
resistant to the conditions:
(a) Direct burial in the earth or embedded in concrete unless identi- ^.r^-*^, I B o r e d Hole. r300.4(A)í1)]
fied for the application. ^ Less T h a n 1 Vi i n .
Steel Píate Required
(b) Exposed to cinder filis, strong chiorides, caustic alkalis, or vapors
of chiorine or of hydrochioric acids.
Notch (if permitted)
[300.4(A){2)]
Steel Píate Required
Copyright 2011. www.MlktHoa com
Figure 330-2
Inner E d g e
of Bend
Figure 330-3
0.50 in.
O.D.
330.23 In Accessible Attics or Roof Spaces. lype MC
cable installed in accessible attics or roof spaces must comply with Radius
320.23. 3.50 in.
T h e Radius of the Curve
Author's Comments: 7 X 0.50 in. = 3.50 in.
• On the Surface of Floor Joists, Rafters, or Studs. In attics and T h e radius of the inner edge o f the curve must not
be less than 7 times t h e diameter of the cable.
roof spaces that are accessible, substantial guards must pro-
tect cables installed across the top of floor joists, or across
Figure 330-4
the face of rafters or studding within 7 ft of floor or floor joists.
If this space isn't accessible by permanent stairs or ladders,
protection is required only within 6 ft of the nearest edge of
330.30 Securing and Supporting.
the scuttie hole or attic entrance [320.23(A)].
(A) General. Type MC cable must be supported and secured by Sta-
• Along the Side of Framing Members [320,23(B)]. When Type
MC cable is installed on the side of rafters, studs, or floor ples, cable ties, straps, hangers, or similar fittings designed and
joists, no protection is required if the cable is installed and installed so as not to damage the cable.
supported so the nearest outside surface of the cable or
(B) Securing. Type MC cable with four or less conductors sized no
raceway is at Ieast V/A in. from the nearest edge of the fram-
larger than 10 AWG, must be secured within 12 in. of every outlet box,
ing member where nails or screws are likely to penétrate
junction box, cabinet, or fitting and at intervals not exceeding 6 ft.
[300.4(0)].
Figure 330-5
Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
330.80 Metal-ciad Cable (Type MC)
330.80 Conductor Ampacities. Conductor ampacity is cal- M C Cable - Equipment Grounding Conductor
culated on the 90°C insulation rating of the conductors; however, the
conductors must be sized to the termination temperature rating in
accordance with 110.14{C)(1).
Copynghl 20)1. w w w . M ¡ k e H o « - c o m
Figure 330-10
Mike HaiVs liiustrated Guide to Understanding the 2011 National Electrical Code, Volume
ARTICLE
Nonmetallic-Sheathed
334 Cable (Types NM and NMC)
INTRODUCTION TO ARTICLE 334—NONMETALLIC-SHEATHED CABLE (TYPES NM AND NMC)
Nonmetallic-Sheathed cable is flexible, inexpensive, and easily installed. It provides very limited physical protection for the conductors, so
the instaliation restrictions are strict. Its low cost and relativa ease of instaliation make it a common wiring method for residential and com-
mercial branch circuits. In the field, Type NM cable is typically referred to as "Romex®."
334.2 Definition.
Nonmetallic-Sheathed Cable (Types NM and NMC). A wiring method ^m^NlG NM-B 600V
that endoses hwo or more insulated conductors, 14 AWG through 2
AWG, within a nonmetallic jacket.
• NM cable has insulated conductors enclosed within an A wiring m e t h o d that e n d o s e s two, three, or four
overall nonmetallic jacket. insulated conductors (14 A W G to 2 A W G ) within a n
outer nonmetallic jacket.
• NMC cable has insulated conductors enclosed within an
overall, corrosión resistant, nonmetallic jacket. Figure Copyngm 2011. www IMieHon com
334-1
Figure 334-1
PART II. INSTALLATION (2) Multifamily dweilings permitted to be of Types III, IV, and V con-
struction. Figure 334-4 _
334,10 Uses Permitted. Type N M and Type N M C cables can
be used in the following:
(1) One- and two-family dweilings of any height, and their attached/
detached garages or storage buildings. Figures 334-2 and
334^3
Figure 334-4
El ¡LMÍ
I
352 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Nonmetallic-Sheathed Cable (Types NM and NMC) 334.15
Author's Comment: See the definition of "Concealed" in Article (6) In motion picture studios.
100.
(7) In storage battery rooms.
Note 1: Building constructions are defined in NFPA 220-2006,
(8) In hoistways, or on elevators or escalators.
Standard on Types of Building Construction the applicable building
code,or both. (9) Embedded in poured cement, concrete, or aggregate.
Note 2: See Annex E for the determination of building types [NFPA (10) In any hazardous location, except where permitted by 501.10(6)
220, Table 3-1]. (3). 502.10(B)(3), and 504.20.
334.12 Uses Not Permitted. (B) Type NM. Type NM cables must not be used under the following
conditions, or in the following locations:
(A) Types NM and NMC.
(1) If exposed to corrosive fumes or vapors.
(1) In any dweiling or structure not specifically permitted in
334.10(1), (2), and (3). (2) If embedded in masonry, concrete, adobe, fill, or plaster
(2) Exposed in dropped or suspended ceilings in other than one- and (3) In a shallow chase in masonry, concrete, or adobe and covered
two-family and multifamily dweilings. Figure 334-6 with plaster, adobe, or similar finish.
N M Cable - S u s p e n d e d Ceilings
334.12(A)(2) N M Cable - Wet Location
334.12(B)(4) Exposed to
Weather
Direct-Buried ^
Cable or R a c e w a y
Concrete in direct
contact with earth.
In other than a dweiling unit,
VIOLATION
N M cable isn't permitted to
be run e x p o s e d within a
s u s p e n d e d ceiling.
VIOLATION
Type N M cable isn't suitable for
H
use in wet or d a m p locations.
Figure 334-7
(B) Protected from Physical Damage. Nonmetallic-sheathed cable Type NM cable installed on a wall of an unfinished basement or crawl
must be protected from physical damage by rigid metal conduit, inter- space subject to physical damage must be protected in accordance
medíate metal conduit, Schedule 80 PVC conduit, Type RTRC-XW con- with 300.4, or be installed in a raceway with a nonmetallic bushing
duit, electrical metallic tubing, guard strips, or other means approved or adaptar at the point where the cable enters the raceway, and the
by the authority having jurisdiction. NM cable must be secured within 12 in. of the point where the cable
enters the raceway. Figure 334-9
Author's Comment: When installed in a raceway, the cable
must be protected from abrasión by a fitting installed on the end
of the raceway [300.15(C)]. N M Cable Run on Walls
Unfinished B a s e m e n t
334.15(0)
Type NMC cable installed in shallow chases in masonry, concrete, or
adobe, must be protected against nails or screws by a steel píate not
Secure the cable within
less than Vie in. thick [300.4{F)] and covered with plaster, adobe, or 12 in. o f t h e raceway.
similar finish.
Type NM cable must be protected in accordance
with 300.4 or installed in a raceway that has a non-
Author's Comment: If Type NM cable is installed in a metal metallic bushing or adaptor where the cable enters.
raceway, the raceway isn't required to be connected to an
equipment grounding conductor [250.86 Ex 2 and 300.12 Ex]. The cable sheath must extend
into the box at Ieast % in.
354 Mike HoiVs iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Nonmetallíc-Sheathed Cable (Types NM and NMC) 334.30
VA
VA B o r e d Hole, [300.4(A)(1)]
VA in. or More,
No Steel Píate Required
B o r e d Hole, [300.4(A)(1)]
Less T h a n VA in. j ,
Steel Píate R e q u i r e d '
I I I
• Steel Píate for N o t c h e s | Radius
in W o o d [300.4(A)(2)] 2.50 in.
11 I ' 1 T h e Radius of the Curve
5 X 0.50 in. = 2.50 in.
Copyrtghl 2011. www Mlk.HoH com
Figure 334-13
Figure 334-11
Two-wire (fíat) Type NM cable isn't permitted to be stapled on edge. N M Cable - Securing a n d Supporting
334.30
Figure 334-14
Figure 334-14
Note: See 314.17(C) for support where nonmetallic boxes are used.
(2) Not more than AV? ft of unsupported cable is permitted from the
last point of support within an accessible ceiling for the connec- 334.80 Conductor Ampacity. Conductor ampacity is caicu
tion of luminaires or equipment. lated on the 90°C insulation rating of the conductor in accordance
with Table 310.15(B)(16), however the conductors must be sized to
Author's Comment: Type NM cable isn't permitted as a the termination temperature rating of 60°C.
wiring method above accessible ceilings, except in dweilings
[334.12(A){2)].
356 Mike Hoit's Iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Nonmetallic-Sheathed Cable (Types NM and NMC) 334.80
Question: Wtiat size Type NM cable is required to supply a 9.60 If múltiple Type NM cables pass through the same wood framing
'i^K 240V, single-phase fixed space heater with a 3A blower opening that's to be sealed with thermai insulation, caulking, or
wtof? The termináis are rated 75%. Figure 334-17 sealing foam, the allowable ampacity of each conductor must be
adjusted in accordance with Table 310.15(B)(3)(a). Figure 334-18
(aj2AWG (b)4AWG (c)6AWG (d)8AWG
Figure 334-18
NM Cable - Conductor Ampacity
334.80
9.6kW Heat
Author's Comment: This requirement has no effect on conduc-
3AFan
tor sizing if you bundie no more than nine current-carrying 14
(40A + 3A) = 4 3 A or 12 AWG conductors together. For example, three 14/2 cables
4 3 A x 1.25 = 53.75A
6 A W G Rated 5 5 A and one 14/3 cable (nine current-carrying 1 4 THHN conductors)
at 60°C are bundied together in a dry location, the ampacity for each
conductor (25A at 90°C, Table 310.15(B)(16)) is adjusted by a
Copyright 70 percent adjustment factor [Table 310.15(B)(3)(a)].
Figure 334-17
358 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
ARTICLE
Service-Entrance Cable
338 (Types SE and USE)
INTRODUCTION TO ARTICLE 338—SERVICE-ENTRANCE CABLE (TYPES SE AND USE)
Sen/ice-entrance cable is a single conductor or muíticonductor assembiy with or without an overall moisture-resistant covering. This cable
is used primarily for services not over GOOV, but can aiso be used for feeders and branch circuits when the limitations of this article are
observed.
PART L GENERAL Type SE. SE and SER cables have a flame-retardant, moisture-resis-
tant covering and are permitted only in aboveground installations.
338.1 Scope. Article 338 covers the use, instaliation, and con-
These cables are permitted for branch circuits or feeders when
struction specifications of service-entrance cable, Types SE and USE.
installed in accordance with 338.10(8).
338.2 Definitions.
Author's Comment: SER cable is SE cable with an insulated
Service-Entrance Cable. Service-entrance cable is a single or muíti- neutral, resulting in three insulated conductors with an uninsu-
conductor assembiy, with or without an overall covering, used primar- lated equipment grounding conductor. SER cable is round, while
ily for services not over eoov. Figure 338-1 2-wire SE cable is fíat.
Service-Entrance Cable underground use; its covering is moisture resistant, but not fíame
338.2 Definition retardan!.
A single or muíticonductor assembiy with o r
without an overall covering used primarily for
Author's Comment: USE cable isn't permitted to be installed
services not over 600V.
indoors [338.10(B)], except single-conductor USE dual rated as
Aboveground RHH/RHW.
(2) Uninsulated Conductor. SE cable is permitted for branch circuits The máximum conductor temperature rating can be used [310.15(6)
and feeders if the insulated conductors are used for circuit wiring, (2)] for ampacity adjustment and correction purposes, but when
and the uninsulated conductor is only used for equipment grounding installed in thermai insulation the conductors must be sized in
purposes. Figure 338-2 accordance with Table 310.15(B)(16) 60°C rated conductor column.
360 Mike HoiVs Iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
ARTICLE
Underground Feeder
and Branch-Circuit
340 Cable (Type UF)
INTRODUCTION TO ARTICLE 340--UNDERGR0UND FEEDER AND BRANCH-CIRCUIT CABLE
(TYPE UF)
UF cable is a moisture-, fungus-, and corrosion-resistant cable suitable for direct burial in the earth.
340.12 Uses Not Permitted. Author's Comment: UF cable isn't permitted in ducts or cavity
plenum spaces [300.22], or in patient care áreas [517.13].
(1) As services [230.43].
Figure 3 4 0 - 2
362 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
ARTICLE
ntermediate Metal
342 Conduit (Type IMC)
INTRODUCTION TO ARTICLE 342—INTERMEDIATE METAL CONDUIT (TYPE IMC)
Intermedíate metal conduit (IMC) is a circular metal raceway with an outside diameter equal to that oí rigid metal conduit. The wall thick-
ness of intermedíate metal conduit is less than that of rigid metal conduit (RMC), so it's a greater interior cross-sectional área for containing
conductors. Intermedíate metal conduit is lighter and less expensive than rigid metal conduit, but it can be used in all of the same loca-
tions as rigid metal conduit. Intermedíate metal conduit aiso uses a different steel alloy that makes it stronger than rigid metal conduit, even
though the walls are thinner. Intermedíate metal conduit is manufactured in both galvanized steel and aluminum; the steel type is much
more common.
PART I. GENERAL Author's Comment: The type of steel from which intermedíate
metal conduit is manufactured, the process by which it's made,
342.1 Scope, Article 342 covers the use, instaliation, and con- and the corrosión protection applied are all equal, or superior, to
struction specifications of intermedíate metal conduit and associated that of rigid metal conduit.
fittings.
Compression Set S c r e w (C) Cinder Fill. IMC can be installed ín or under cinder fill subject
to permanent moisture when protected on all sides by 2 ín. of non-
cínder concrete; where the conduit isn't less than 18 ín. under the
\ : \ _,.„^ti fill; or where protected by corrosión protection judged suitable for the
Threadless IMC Fittings condition.
CopyngM 2011. www UikeHoll con)
Figure 342-1
(D) Wet Locations. Support fittings, such as screws, straps, and so Author's Comment: See 300.17 for additional examples on
forth, installed in a wet location must be made of corrosion-resistant how to size raceways when conductors aren't all the same size.
342.14 Dissimilar Metals. If practical, contact with dissimi- 342.26 Number of Bends (360°). To reduce the stress
lar metáis should be avoided to prevent the deterioration of the metal and friction on conductor insulation, the máximum number of bends
because of galvanic action. Aluminum fittings and enclosures, how- (inciuding offsets) between pulí points must not exceed 360°. Figure
ever, are permitted with steel intermedíate metal conduit. 342-2
(B) Máximum. Intermedíate metal conduit larger than trade size 4 90°
Figure 342-2
Question: How many 10 THHN conductors can be installed in
trade size 11MC?
364 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Intermedíate Metal Conduit (Type IMC) 342.30
Auttior's Comment: It's a commonly accepted practice to ream IMC - Secureiy Fastened to Structural Members
small raceways with a screwdriver or the backside of pliers. 342.30(A)(2l
However, when the raceway is cut with a three-wheel pipe
cutter, a reaming tool is required to remove the sharp edge of
the indented raceway. When conduits are threaded in the field,
the threads must be coated with an eiectrically conductive, cor- Coupling is O k a y Secured
rosion-resistant compound approved by the authority having
jurisdiction, in accordance with 300.6(A).
Máximum Máximum
5ft 5ft
342.30 Securing and Supporting. intermedíate metal
conduit must be installed as a complete system in accordance with
W h e r e structural m e m b e r s don't permit fastening within
300.18 [300.10 and 300.12], and it must be secureiy fastened in 3 ft of termination, it must be secured within 5 ft.
place and supported in accordance with (A) and (B).
Copyngnt 2011 <vwvt WikeHoll.coni
(1J Fastened within 3 ft of each outlet box, junction box, device box,
(B) Supports.
cabinet, conduit body, or other conduit termination. Figure 342-3
(1) General. Intermedíate metal conduit must generally be supported
at intervals not exceeding 10 ft.
I M C - Support of Straight R u n s
342.30{B){2)
Trade Size 1 I M C
Intermedíate metal conduit must be secureiy fastened Table 344.30(B)(2)
within 3 ft of every box, cabinet, or termination fitting. 12 ft B e t w e e n Supports
C o p y n ^ 301 \. Mnn>MikeHo«.com
¡2) When structural members don't permit the raceway to be secured Figure 342-5
within 3 ft of a box or termination fitting, the raceway must be
secured within 5 ft of the termination. Figure 342-4
H Exposed vertical risers c a n conduit ends unless listed for the purpose.
Upto
H be supported at intervals not 2 0 ft
exceeding 20 ft if firmiy (B) Running Threads. Running threads aren't permitted for the con-
supported and secured at t h e nection of couplings, but they're permitted at other locations. Figure
top and bottom of the riser.
342-7
Running
Thread
Figure 342-6
r/
Boxes or Enclosures
(4) Horizontal Runs. Conduits installed horizontally in bored or
punched holes in wood or metal framing members, or notches in
wooden members are considered supported, but the raceway must
be secured within 3 ft of termination. B iw I
VIOLATION
Copyright 2011. www.MlkeHon.com
Figure 342-7
366 fñlke Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Intermedíate Metal Conduit (Type IMC) 342.46
Figure 342-8
PART I. GENERAL Author's Comment: When the mechanical and physical char-
acteristics of rigid metal conduit are desired and a corrosive
344.1 Scope. Article 344 covers the use, instaliation, and con- environment is anticipated, a PVC-coated raceway system is
struction specifications of rigid metal conduit and associated fittings. commonly used. This type of raceway is frequently used in the
petrochemical industry, The common trade ñame of this coated
344.2 Definition. raceway is "Plasti-bond®," and it's commonly referred to as "Rob
Roy conduit." The benefits of the improved corrosión protec-
Rigid Metal Conduit (Type HMC). A listed metal raceway of circu-
tion can be achieved only when the system is properiy installed.
lar cross section with integral or associated couplings, listed for the
Joints must be sealed in accordance with the manufacturer's
instaliation of electrical conductors, and used with listed fittings to
instructions, and the coating must not be damaged with tools
provide electrical continuity. Figure 344-1
such as benders, pliers, and pipe wrenches. Couplings are avail-
able with an extended skirt that can be properiy sealed after
instaliation.
Rigid Metal Conduit (Type R M C )
344.2 Definition
344.6 Listing Requirements. Rlgld metal conduit, elbows,
couplings, and associated fittings must be listed.
Figure 344-1 (2) Red Brass. Red brass rigid metal conduit is permitted for direct
burial and swimming pool applications.
368 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Rigid Metal Conduit (Type RMC) 344.26
(A) Mínimum. Rigid metal conduit smaller than trade size ¥2 must not To reduce t h e stress and friction on
conductor insulation, the total a m o u n t
be used. of bends (inciuding offsets) between
pulí points can't e x c e e d 360o.
(B) Máximum. Rigid metal conduit larger than trade size 6 must not
150
be used. There's no m á x i m u m
15°
distance b e t w e e n pulí points.
344.22 Number of Conductors. Raceways must be large
— P u l í Points \r—-^^ o
enough to permit the instaliation and removal of conductors without
o
damaging the conductors' insulation. When all conductors in a race-
way are the same size and insulation, the number of conductors per-
mitted can be found in Annex C for the raceway type.
Figure 344-2
Author's Comment: There's no máximum distance between Author's Comment: Fastening is required within 3 ft of termi-
pulí boxes because this is a design issue, not a safety issue. nations, not within 3 ft of each coupling.
Coupling is O k a y ; Secured
344.30 Securing and Supporting. Rígid metal conduit
must be installed as a complete system in accordance with 300.18
[300.10 and 300.12], and it must be secureiy fastened in place and
supported in accordance with (A) and (B). Máximum Máximum
5ft 5ft
(A) Secureiy Fastened. RMC must be secured in accordance with
one of the following: Figure 344-3 W h e r e structural m e m b e r s don't permit fastening within
3 ft of termination, it must be secured within 5 ft.
• Fastened within 3 ft of each outlet box, junction box, device
box, cabinet, conduit body, or other conduit termination. Copyright 2011, ww*.M*eHoir com
Figure 344-4
R M C - Secureiy Fastened
344.30(A)
(B) Supports.
3ft 3ft
Termination Termination (1) General. Rigid metal conduit must be supported at intervals not
exceeding l O f t .
lOft
Copynghl 2011. www MiUHoll com
12 ft*
Figure 344-3
iy4-iK2 14ft
2-2^/2 16ft
3 and larger 20 ft
370 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Rigid Metal Conduit (Type RMC) 344.42
R M C - Support of Straight Runs Author's Comment: Rigid metal conduit must be provided with
344.30(B)(2) expansión fittings if necessary to compénsate for thermai expan-
sión and contraction [300.7(B)]. The expansión characteristics
Trade Size 1 R M C
for metal raceways are determined by multipiying the valúes
Table 344.30(B)(2)
12 ft Between Supports from Table 3 5 2 . 4 4 by 0.20, and the expansión characteristics
for aluminum raceways is determined by multipiying the valúes
from Table 3 5 2 . 4 4 by 0 . 4 0 [300.7 Note].
i Figure 344-5 Author's Comment: Loóse locknuts have been found to burn
clear before a fault was cleared because loóse connections
increase the impedance of the fault current path.
(3) Vertical Risers. Exposed vertical nsers for fixed equipment can
be supported at intervals not exceeding 20 ft, if the conduit is made
If buried in masonry or concrete, threadless fittings must be the con-
up with threaded couplings, firmiy supported, secureiy fastened at the
crete-tight type. If installed in wet locations, fittings must be listed for
top and bottom of the riser, and if no other means of support is avail-
use in wet locations, in accordance with 314.15(A).
able. Figure 344-6
Threadless couplings and connectors must not be used on threaded
conduit ends, unless listed for the purpose.
R M C - Support of Vertical Risers
344.30(B)(3) (B) Running Threads. Running threads aren't permitted for the con-
nection of couplings, but they're permitted at other locations. Figure
344-7
T h r e a d e d Coupling
R M C - Running T h r e a d s
Exposed vertical risers c a n 344.42(B)
be supported at intervals not
exceeding 20 ft if firmiy
supported and secured at the
top and bottom of the riser.
344.130 Standard Lengths. The standard length of RMC is Conductors 4 A W G and larger must be protected by a
10 ft inciuding an attached coupling, and each end must be threaded. fitting that provides a s m o o t h , r o u n d e d , insulating surface,
Longer or shorter lengths with or without a coupling and threaded or such a s an insulating bushing [300.4(G)].
372 Mike Hoit's iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
ARTICLE
Flexib
348 (Type
INTRODUCTION TO ARTICLE 348~-FLEXIBLE METAL CONDUIT (TYPE FMC)
Flexible metal conduit (FMC), commonly called "Greenfieid" or "flex," is a raceway of an interlocked metal strip of either steel or alumi-
num. It's primarily used for the final 6 ft or less of raceways between a more rigid raceway system and equipment that moves, shakes, or
vibrates. Examples of such equipment include pump motors and industrial machinery.
348.1 Scope. Article 348 covers the use, instaliation, and con- (A) Minimum. Flexible metal conduit smaller than trade size ¥2
struction specifications for flexible metal conduit and associated fit- must not be used, except trade size V?. can be used for the following
tings. applications:
(7) If subject to physical damage. c. For luminaire tap connections, in accordance with 410.117(C).
(3) In manufactured wiring systems, 604.6(A). 348.24 Bends. Bends must be made so that the conduit won't
be damaged, and its interna! diameter won't be effectively reduced.
(4) In hoistways, 620.21 (A)(1).
The radius of the curve of the inner edge of any field bend must not
(5) As part of a listed luminaire assembiy in accordance with be less than shown in Table 2, Chapter 9 using the column "Other
410.137(C). Bends."
(B) Máximum. Flexible metal conduit larger than trade size 4 must
348.26 Number of Bends (360°). To reduce the stress
not be used.
and friction on conductor insulation, the máximum number of bends
348.22 Number of Conductors. (inciuding offsets) between pulí points must not exceed 360°.
Trade Size Vz and Larger Flexible metal conduit must be large Author's Comment: There's no máximum distance between
enough to permit the instaliation and removal of conductors without pulí boxes because this is a design issue, not a safety issue.
damaging the conductors' insulation. When all conductors in a race-
way are the same size and insulation, the number of conductors per-
348.28 Trimming. The cut ends of flexible metal conduit must
mitted can be found in Annex C for the raceway type.
be trimmed to remove the rough edges, but this isn't necessary if fit-
tings are threaded into the convolutions.
Trade Size Va. The number and size of conductors in trade size ¥& flex-
ible metal conduit must comply with Table 348.22.
374 Mike HoiVs liiustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Rexible Metal Conduit (Type FMC) 348.60
F M C - Horizontal Support
348.30(B)
Figure 348-3
Metal Max. 4V2ft
Wood
Studs Between
Studs
Framing
f/; 5 n for trade sizes V2 tfirougfi VA Members
S e e 250.118(5)
376 Mike HoiVs iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Liquidtight Flexible Meta
ARTICLE
Listed f
350.2 Definition. LFMC ^
Fittings
Liquidtight Flexible Metal Conduit (Type LFMC). A raceway of circu-
lar cross section, having an outer liquidtight, nonmetallic, sunlight-
resistant jacket over an inner flexible metal core, with associated
A circular raceway having an outer
connectors and fittings for the instaliation of electric conductors. liquidtight, nonmetallic, sunlight-resistant
Rgure 350-1 jacket over a n inner flexible metal core.
Author's Comment: According to 348.20(A), LFMC smaller Author's Comment: See 300.17 for additional examples on
than trade size Yi is permitted for tfie following: how to size raceways when conductors aren't all the same size.
378 Mike HoiVs liiustrated Guide to Understanding the 2011 National Electncal Code, Volume 1
Liquidtight Flexible Metal Conduit (Type LFMC) 350.60
L F M C - Secureiy F a s t e n e d Ex 4: Lengths not exceeding 6 ft from the last point where the race-
350.30(A) way is secureiy fastened can be unsecured within an accessible ceil-
ing for luminaire(s) or other equipment.
I
350.60 Grounding and Bonding. If flexibility ¡s necessary
LFMC must be secureiy fastened within 1 ft of to minimize the transmission of vibration from equipment or to pro-
termination and at intervals not exceeding 4V2 ft.
vide flexibility for equipment that requires movement after instalia-
tion, an equipment grounding conductor of the wire type must be
Figure 350-3 installed with the circuit conductors in accordance with 250.118(6),
based on the rating of the circuit overcurrent device in accordance
Ex 2: If flexibility is necessary after instaliation, unsecured lengths with 250.122. Figure 350-5
from the last point where the raceway is secureiy fastened must not
exceed: Figure 350-4
L F M C - Equipment G r o u n d i n g Conductor
(1) 3 ñ for trade sizes Vz through VA Flexibility Required After Instaliation
350.60
(2) 4 ft for trade sizes VÁ through 2
(3) 5 ft for trade sizes 2Á and larger II
Figure 350-5
M á x i m u m of 1 ft From
Tennination [350.30(A)]
If flexibility isn't necessary after instaliation, and vibration isn't a
V/a L F M C , M á x i m u m Unsecured Length is 3 ft concern, the metal armor of flexible metal conduit can serve as an
equipment grounding conductor if the circuit conductors contained in
the raceway are protected by an overcurrent device rated 20A or less,
and the combined length of the flexible metal raceway in the same
Copyngnt 2011. www.MUieHMt com
ground-fault return path doesn't exceed 6 ft [250.118(6)].
Rigió Polyvinyl Chioride Conduit (PVC). A rigid nonmetallic conduit of (A) Concealed. PVC conduit can be concealed within walls, floors, or
circular cross section with integral or associated couplings, listed for ceilings, directly buried or embedded in concrete in buildings of any
the instaliation of electrical conductors and cables. Figure 352-1 height.
Schedule 4 0 P V C (D) Wet Locations. PVC conduit is permitted in wet locations such as
with Integral Coupling
dairies, laundries, canneries, car washes, and other áreas frequently
washed or in outdoor locations. Support fittings such as straps,
Copyngni ^ 1 V www klkMott c o n P V C Fittings
screws, and bolts must be made of corrosion-resistant materiais, or
A rigid nonmetallic conduit with a circular cross must be protected with a corrosion-resistant coating, in accordance
section with integral or associated couplings.
with 300.6(A).
Figure 352-1 (E) Dry and Damp Locations. PVC conduit is permitted in dry and
damp locations, except where limited in 352.12.
380 Mike HoiVs iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Rjgjd Polyvinyl Chioride Conduit (TYPE PVC) 352.12
Exposed. Schedule 40 PVC conduit is permitted for exposed loca- (G) Underground. PVC conduit installed underground must comply
where not subject to physical damage. Figure 352-2 with the burial requirements of 300.5.
P V C in Exposed Locations nonmetallic conduit bodies that aren't larger than the largest trade
352.10(F) size of an entering raceway. These conduit bodies can't support lumi-
naires or other equipment, and aren't permitted to contain devices,
other than spiicing devices permitted by 110.14(B) and 314.16(C)(2).
Figure 352-2
Note: PVC Schedule 80 conduit is identified for use in áreas subject Conductors rated at a temperature higher than
to physical damage. Figure 352-3 the listed temperature rating of P V C conduit
must not be operated at a temperature above
the raceway's listed temperature rating.
(B) Support of Luminaires. PVC conduit must not be used for the
Schedule 8 0 P V C is identified for use
in áreas subject to physical d a m a g e . support of luminaires or other equipment not described in 352.1 OtH).
(0) Physical Damage. Schedule 40 PVC conduit must not be installed Cables can be installed in PVC conduit, as long as the number of
if subject to physical damage, unless identified for the application. cables doesn't exceed the allowable percentage fill specified in Table
1, Chapter 9.
Author's Comment: PVC Schedule 80 conduit is identified for
use in áreas subject to physical damage [352.10(F) Note]. 352.24 Bends. Raceway bends must not be made in any manner
that would damage the raceway, or significantly change its intemal
(D) Ambient Temperature. PVC conduit must not be installed if the
diameter (no kinks). The radius of the curve of the inner edge of any
ambient temperature exceeds 50°C (122°F). field bend must not be less than shown in Table 2, Chapter 9.
352.20 Trade Size. Author's Comment: Be sure to use equipment designed for
(A) Minimum. PVC conduit smaller than trade size must not be heating the nonmetallic raceway so it's pliable for bending (for
example, a "hot box"). Don't use open-flame torches.
used.
(B) Máximum. PVC conduit larger than trade size 6 must not be used.
352.26 Number of Bends (360°). To reduce the stress
and friction on conductor insulation, the máximum number of bends
352.22 Number of Conductors. Raceways must be large
(inciuding offsets) between pulí points must not exceed 360°. Figure
enough to permit the instaliation and removal of conductors with-
352-5
out damaging the conductors' insulation, and the number of conduc-
tors must not exceed that permitted by the percentage fill specified in
Table 1, Chapter 9.
P V C - N u m b e r of B e n d s
When all conductors in a raceway are the same size and insulation, 352.26
382 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Rigid Polyvinyl Cliloride Conduit (TYPE PVC) 352.44
|A) Secured. PVC conduit must be secured within 3 ft of every box, P V C - Expansión Fitting
Straight Run B e t w e e n 352.44
cabinet, or termination fitting, such as a conduit body. Figure 352-6 Two Secureiy
M o u n t e d Elbows
Expansión Fitting
P V C - Securing a n d Supporting
352.30
Figure 352-7
^2-1 3ft
VA-2 5ft
6fí
3^-5 7ft
6 8ft
sidered supported, but the raceway must be secured within 3 ft of E x p n - C o n t In. = (Length/100) x (Temp C h a n g e / 1 0 0 x 4.0)
tennination.
Figure 352-8
352.44 Expansión Fittings. If PVC conduit is installed in a
straight run between secureiy mounted items, such as boxes, cabi-
nets, elbows, or other conduit terminations, expansión fittings must
be provided to compénsate for thermai expansión and contraction of
tíie raceway in accordance with Table 352.44, if the length change is
determined to be VA in. or greater. Figure 352-7
Example: How much will a 25 fí run of PVC conduit contract 352.48 Joints. Joints, such as couplings and connectors, must
when it's located in an ambient temperature change of25°F? be made in a manner approved by the authority having jurisdiction.
Figure 352-10
Figure 352-9
384 Mike HoiVs iiiustrated Guide to Understanding tiie 2011 Nationai Electrical Code, Volume 1
Rigid Polyvinyl Chioride Conduit (TYPE PVC) 352.60
P V C - Grounding
352.60 Ex 2
Rgure 352-11
PART I. GENERAL (1) Type LFNC-A (orange color). A smooth seamiess inner core and
cover having reinforcement layers between the core and cover.
356.1 Scope. Article 356 covers the use, instaliation, and con-
struction specifications of liquidtight flexible nonmetallic conduit and (2) Type LFNC-B (gray color). A smooth inner surface with integral
associated fittings. reinforcement within the conduit wall.
(4) Directly buried in the earth, if listed and marked for this purpose.
386 Mike Hoit's Iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Liquidtight Flexible Nonmetallic Conduit (Type LFNC) 356.30
356.12 Uses Not Permitted. Question: How many 8 THHN conductors can be installed in
1) If subject to physicai damage. trade size ^ LFNC-B?
í2i If the combination of ambient and conductor temperature will pro- Answer: Six conductors [Annex C, Table C5]
(31 Longer than 6 ft, except if approved by the authority having juris-
Author's Comment: See 300.17 for additional examples on
diction as essential for a required degree of flexibility.
how to size raceways when conductors aren't all the same size.
(4} If the operating voltage of the contained conductors exceeds 600
volts, nominal. Cables can be installed in liquidtight flexible nonmetallic conduit, as
long as the number of cables doesn't exceed the allowable percent-
(5} In any hazardous location, except as permitted by 501.10(B),
age fill specified in Table 1, Chapter 9.
502.10(A) and (B),and 504.20.
(2) For tap connections to lighting fixtures as permitted by 356.26 Number of Bends (360''). To reduce the stress
410.117(0). and friction on conductor insulation, the máximum number of bends
(inciuding offsets) between pulí points must not exceed 360°.
(B) Máximum. Liquidtight flexible nonmetallic conduit larger than
trade size 4 isn't permitted.
Author's Comment: There's no máximum distance between
pulí boxes because this is a design issue, not a safety issue.
356.22 Number of Conductors. Raceways must be large
enough to permit the instaliation and removal of conductors without
damaging the insulation. When all conductors in a raceway are the 356.30 Securing and Supporting, LFNC-B (gray color)
same size and insulation, the number of conductors permitted can be must be secureiy fastened and supported in accordance with one of
found in Annex C for the raceway type. Figure 356-2 the following: Figure 356-3
L F N C - Secureiy F a s t e n e d
356.3Q{A)
L F N C - N u m b e r of C o n d u c t o r s
356.22
1 ftof
Termination
Máximum
of3ft •
A m á x i m u m of six 8 T H H N
conductors can b e installed in
Va LFNC-B [Table C.5].
When all conductors in a raceway are the s a m e size L F N C m u s t be secureiy fastened within 1 ft of
and insulation, the n u m b e r of conductors permitted termination a n d at intervals not exceeding 3 f t .
can be f o u n d in A n n e x C.
(1) The conduit must be secureiy fastened at intervals not exceeding 356.60 Equipment Grounding Conductor, if equipment
3 ft, and within 1 ft of termination when installed longer than 6 ft. grounding is required, a sepárate equipment grounding conductor of
the wire type must be installed within the conduit [300.2(B)]. Figure
(2) Securing or supporting isn't required if it's fished, installed in
356-^
lengths not exceeding 3 ft at termináis if flexibility is required, or
installed in lengths not exceeding 6 ft for tap conductors to lumi-
naires, as permitted in 410.117(0).
L F N C - Equipment Grounding Conductor
(3) Horizontal runs of liquidtight flexible nonmetallic conduit installed W h e r e Flexibility is Required
horizontally in bored or punched holes in wood or metal fram-
ing members, or notches in wooden members, are consid-
ered supported, but the raceway must be secured within 1 ft of
termination.
356.42 Fittings. Oniy fittings listed for use with liquidtight flexi-
ble nonmetallic conduit can be used [300.15]. Angle connector fittings
must not be used in concealed raceway installations. Straight liquid-
tight flexible nonmetallic conduit fittings are permitted for direct burial Figure 356-4
or encasement in concrete.
388 Mike HoiVs iiiustrated Guide to Understanding tt)e 2011 National Electrk)al Code, Volume 1
Electrical Metallic
ARTICLE
I
Installed in Concrete or Earth
358.10(B)
Threadless E M T Fittings
Figure 358-1
Figure 358-2
(4) In any hazardous location, except as permitted by 502.10, Question: How many 12 THHN conductors can be installed in ^
(5) For the support of luminaires or other equipment (like boxes), (a) 26 (b)28 (0 30 (d)32
except conduit bodies no larger than the largest trade size of the Answer: (a) 26 conductors [Annex C, Table C. 1]
tubing that can be supported by the raceway. Figure 358-3
390 Mike Hoit's iiiustrated Guide to Understanding tiie 2011 National Electrical Code, Volume 1
Electrical Metallic Tubing (Type EMT) 358.30
Author's Comment: There's no máximum distance between Ex 1: When structural members don't permit the raceway to be
pulí boxes because this is a design issue, not a safety issue. secured within Sñofa box or termination fitting, an unbroken race-
way can be secured within Sftofa box or termination fitting. Figure
358-7
E M T - Secureiy Fastened to Structural M e m b e r s Author's Comment: Conductors 4 AWG and larger that enter
358.30(A) Ex 1
an enclosure must be protected from abrasión, during and after
VIOLATION instaliation, by a fitting that provides a smooth, rounded, insu-
E M T must be unbroken lating surface, such as an insulating bushing, unless the design
between termination in this c a s e .
of the box, fitting, or enclosure provides equivalent protection, in
^ * ^ I
* > » * * * accordance with 300.4{G}. Figure 358-8
- * " — - ^ - " - ^ '^^^ • * * r-^
E M T - Bushings
300.4(G)
Máximum Máximum n
5ft 5ft
í
Where structural m e m b e r s don't pennlt fastening within
3 ft of the termination, E M T must be secured within 5 ft.
Fitting Termination
Copynghl 2011. « w » M*«Holl.com
Figure 35&-7
4 AWG 6 AWG
(B) Horizontal Runs. Electrical metallic tubing installed horizontally a n d Larger a n d Smaller
Bushing Bushing Not
in bored or punched holes in wood or metal framing members, or
Required Required
notches in wooden members, is considered supported, but the race-
way must be secured within 3 ft of termination.
CopyriOM 2011. «ww.hMieHoli.com
392 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Electrical Nonmetallic
ARTICLE
sprinkier System
(all floors)
uilding Over 3 Floors
362.10(2)
Ex: If a fire sprinkier system is installed on all floors, in accordance concrete slab provided fittings identified for the purpose are used.
with NFPA 13, Standard for the Instaliation of Sprinkier Systems, elec-
Author's Comment: Electrical nonmetallic tubing isn't permit-
trical nonmetallic tubing is permitted above a suspended ceiling that
ted in the earth [362.12(5)].
doesn't have a 15-minute finish rated thermai barrier material. Figure
362-6
Mike HoWs lllustrated Guide to Understanding the 2011 National Electncal Code, Volume 1
Electrical
E Nonmetallic Tubing (Type ENT) 362.12
Suspended Sprinkier S y s t e m
' i Ceiling (all floors)
. i ^ V " »
Figure 3 6 2 - 7
W h e n a fire sprinkier system is installed o n all (6) Exposed in buildings over three floors, except as permitted by
floors, E N T c a n b e installed a b o v e a s u s p e n d e d
362.10(2) and (5) Ex.
ceiling regardiess of the finish rating.
(7) In assembiy occupancies or theaters, except as permitted by
Figure 362-6 518.4 and 520.5.
(8) Exposed to the direct rays of the sun for an extended period,
(7) Electrical nonmetallic tubing is permitted in wet locations indoors, unless listed as sunlight resistant.
or in a concrete slab on or below grade, with fittings listed for the
purpose. Author's Comment: Exposing electrical nonmetallic tubing to
the direct rays of the sun for an extended time may result in the
(8) Listed prewired electrical nonmetallic tubing with conductors is
product becoming brittle, unless it's listed to resist the effects of
permitted in trade sizes V2, % and 1. ultraviolet (UV) radiation. Figure 3 6 2 - 8
(9) If subject to physical damage. Author's Comment: There's no máximum distance between
pulí boxes because this is a design issue, not a safety issue.
Author's Comment: Electrical nonmetallic tubing is prohibited
in ducts, cavity plenum spaces [300.22{C)], and patient care
362.28 Trimming. The cut ends of electrical nonmetallic tubing
área circuits in health care facilities [517.13(A)].
must be trimmed (inside and out) to remove the burrs and rough
edges. ,. • .
362.20 Trade Sizes.
Trimming electrical nonmetallic tubing is very easy; most of the burrs
(A) Minimum. Electrical nonmetallic tubing smaller than trade size Vi rub off with fingers, and a knife can be used to smooth the rough
isn't permitted. edges.
362.22 Number of Conductors. Raceways must be large 300.18 [300.10 and 300.12], and it must be secureiy fastened in
enough to permit the instaliation and removal of conductors with- place and supported in accordance with (A) and (B).
out damaging the conductors' insulation, and the number of conduc- (A) Secureiy Fastened. Electrical nonmetallic tubing must be secured
tors must not exceed that permitted by the percentage fill specified in within 3 ft of every box, cabinet, or termination fitting, such as a con-
Table 1, Chapter 9. duit body, and at intervals not exceeding 3 ft. Figure 362-9
When all conductors in a raceway are the same size and insulation,
the number of conductors permitted can be found in Annex C for the
raceway type. ENT - Secured and Supported
362.30(A)
Mike HoiVs Iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Electrical Nonmetallic Tubing (Type ENT) 362.60
(B) Horizontal Runs. Electrical nonmetallic tubing installed horizon- ENT - Equipment Grounding
tally in bored or punched holes in wood or metal framing members, or
notches in wooden members, is considered supported, but the race-
way must be secured within 3 ft of terminations.
Figure 3 6 2 - 1 0
Author's Comment: Follow the manufacturer's instructions for
the raceway, fittings, and glue, According to product listings, PVC
conduit fittings are permitted with electrical nonmetallic tubing.
Author's Comment: Both metal wireways and nonmetallic wireways are often called "troughs" or "gutters" in the field.
376.2 Definition. (2) In any hazardous locations, as permitted by other articles in the
Cade.
Metal Wireway. A sheet metal trough with hinged or removable
covers for housing and protecting electric conductors and cable, and (3) Wet locations where listed for the purpose.
in which conductors are placed after the wireway has been installed.
(4) Unbroken through walls, partitions, and floors.
Figure 376-1
A sheet metal trough with hinged or removable covers for 376.22 Number of Conductors and Ampacity. The
housing and protecting electnc wires and cable, and in which number of conductors and their ampacity must comply with 376.22{A)
conductors are placed after the wireway has been installed.
and (B).
398 Mike HoiVs iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Metal Wireways 376.56
Wireway - Number of Conductors Signaling and motor control conductors between a motor and its
starter used only for starting duty aren't considered current carrying
for conductor ampacity adjustment.
The máximum number of conductors permitted in a
wireway is limited to 20 percent of the cross-sectional
área of the wireway. 376.23 Wireway Sizing.
CBp|«igMM11
W i r e w a y Sizing
Conductor Bending Radius
376.23(A)
Rgure 376-2
Author's Comment: Spiices and taps must not fill more than
75 percent of the wiring space at any cross section [376.56].
Figure 376-4
Wireway - Conductor A m p a c i t y
376.22(B)
When more than 3 0 current-carrying conductors 376.30 Supports. Wireways must be supported in accordance
are installed in any cross-sectional área, conductor
with (A) and (B).
ampacity from Table 310.15(B){16) must be adjusted
in accordance with 310.15(B)(3)(a). (A) Horizontal Support. If installed honzontally, metal wireways must
be supported at each end and at intervals not exceeding 5 ft.
(4) Live Parts. Power distribution biocks must not have uninsulated
exposed live parts in the metal wireway after instaliation, whether or
not the wireway cover is installed. Figure 376-6
400 Mike HolVs lllustrated Guide to Understanding the 2011 National Eleotrical Code, Volume 1
ARTICLE
Author's Comment: A multioutlet assembiy is a surface, flush 380.12 Uses Not Permitted.
or freestanding raceway designed to hold conductors and recep-
(1) Concealed.
tacles assembled in the field or at the factory [Article 100].
Figure 380-1 (2) If subject to severe physical damage.
Figure 380-1
Surface Metal R a c e w a y s their packaging, which identify the type of surface metal race-
386.2 Definition way that can be used with the enclosure.
402 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrk)al Code, Volume 1
Surface Metal Raceways 386.60
Surface Metal Raceway - Dry Locations The ampacity adjustment factors of 310.15(B)(3)(a) don't apply to
386.10(1)
conductors installed in surface metal raceways if all of the following
conditions are met: Figure 386-3
Suspended Ceiling
386.22 Number of Conductors. The number of conduc- 386.60 Equipment Grounding Conductor. Surface metal
tors or cables installed in a surface metal raceway must not be more raceway fittings must be mechanically and eiectrically joined together
than the number for which the raceway is designed. Cables can be in a manner that doesn't subject the conductors to abrasión. Surface
installed in surface metal raceways as long as the number of cables metal raceways that allow a transition to another wiring method, such
doesn't exceed the allowable percentage fill specified in Table 1, as knockouts for connecting raceways, must have a means for the
Chapter 9. termination of an equipment grounding conductor. A surface metal
raceway is considered suitable as an equipment grounding conductor,
in accordance with 250.118(14).
404 Mike Holt's lllustrated Guide to Understanding the 2011 National Eléctrica! Code, Volume 1
ARTICLE
I I Cable Tray S y s t e m
I i 392.2 Definition
• If exposed to the direct rays of the sun, insulated conduc- • Coaxial Cables, 820.133{A){1)(b) Ex 1 I
tors and jacketed cables must be identified as being sunlight • Class 2 and 3 Cables, 725.136(6) and 725.136(1) I
resistant. The manufacturer must identify cable trays and • Communications Cables, 800.133(A)(2) Ex 1 I
associated fittings for their intended use. • Fire Alarm Cables, 760.136(0) I
• Optical Fiber Cables, 770,133(8) I
(A) Wiring Methods. Any wiring methods listed in Table 392.10(A) • Intrinsically Safe Systems Cables, 504.30(A)(2) Ex 1 I
can be installed in a cable tray. • Radio and Televisión Cables, 810.18(B) Ex 1 I
Wiring Method Article/Section (1) Where conditions of maintenance and supervisión ensure that '
only qualified persons service the installed cable tray system,
Armored Cable 320
single conductor cables can be installed in accordance with the
CATV cables 820
following;
CATV raceways 820
(a) 1/0 AWG and larger listed and marked for use in cable trays.
Class 2 & 3 cables 725
Communications cables 800 (c) Equipment grounding conductors must be 4 AWG and larger
Communications raceways 800 (C) Hazardous Locations. Cable trays in hazardous locations must
Electrical metallic tubing 358 contain only the cable types and raceways permitted by the M e for
Electrical nonmetallic tubing 362 the application
Intermedíate metal conduit 342 (D) Nonmetallic Cable Trays. In addition to the uses permitted else-
Liquidtight flexible metal conduit 350 where in Article 392, nonmetallic cable trays can be installed in corro-
sive áreas, and in áreas requiring voltage isolation.
Liquidtight flexible nonmetallic conduit 356
Optical fiber cables and raceways 770 392.18 Cable Tray installations
Polyvinyl chioride PVC conduit 352 (A) Complete System. Cable trays must be installed as a complete
Power and control tray cable 336 system, except mechanically discontinuóos segments between cable
406 Mike Holfs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Cable Trays 392.56
Through Partitions and Walls. Cable trays can extend through Boxes and conduit bodies attached to the bottom or side of a cable
lons and walls, or vertically through platforms and floors if the tray system must be fastened and supported in accordance with
llation is made in accordance with the firestopping requirements 314.23.
].21.
392.20 Cable and Conductor Instaliation
(E) Exposed and Accessible. Cable trays must be exposed and
accessible, except as permitted by 392.10(H). (C) Connected in Parallel. To prevent unbalanced current in the par-
allel conductors due to inductive reactance, all circuit conductors of a
(F) Adequate Access. Sufficient space must be provided and main-
parallel set [310.10(H)] must be bundied together and secured to pre-
taiíied about cable trays to permit adequate access for installing and
vent excessive movement due to fault current magnetic torces.
íPaintaining the cables.
(D) Single Conductors. Single conductors of a circuit not connected
(G) Raceways, Cables, and Boxes Supported from Cable Trays.
in parallel must be installed in a single layer, unless the conductors
h industrial facilities where conditions of maintenance and supervi-
are bound together.
sión ensure only qualified persons will service the instaliation, and if
the cable tray system is designed and installed to support the load, 392.22 Number of Conductors or Cables.
cable tray systems can support raceways, cables, boxes, and conduit
3. Figure 392-3 (A) Number of Muíticonductor Cables ín Cable Trays. The number
of muíticonductor cables, rated 2,000 volts or less, permitted in
a single cable tray must not exceed the requirements of this sec-
Cable Tray - Support Raceways a n d B o x e s tion. The conductor sizes herein apply to both aluminum and copper
392.18(G)
conductors.
I
Raceways, cables, boxes, and conduit bodies
t
can be supported to a cable tray w h e r e only
Cable Tray (1) Any Mixture of Cables. If ladder or ventilated trough cable
trays contain muíticonductor power or lighting cables, the máximum
number of cables must conform to the following:
(a) If all of the cables are 4/0 AWG and larger, the sum of the diam-
qualified persons will service t h e instaliation. eters of all cables must not exceed the cable tray width, and the
cables must be installed in a single layer.
For raceways terminating at the tray, a listed cable tray clamp or the manufacturer's instaliation instructions.
appropriate raceway article. or conductors exit a bushed raceway used for the support or protec-
tion of the conductors.
Raceways or cables running parallel to the cable tray system can be
attached to the bottom or side of a cable tray system. The raceway or 392.56 Cable Spiices. Spiices are permiüed in a cable tray if
cable must be fastened and supported in accordance with the appro- the spiice is accessible and insulated by a method approved by the
priate raceway or cable's Code article. authority having jurisdiction. Spiices can project above the side ralis
of the cable tray if not subject to physical damage. Figure 392-4
s p i i c e s in Cable Tray Metal cable trays containing Communications, data, and signaling
392.56 conductors and cables must be eiectrically continuous through listed
connections or the use of a bonding jumper not smaller than 10 AWG.
Cable Tray
Figure 392-6
Figure 392-4
Bonding Metal cable tray can be used as an (B) Serve as Equipment Grounding Conductor. Metal cable trays
I ; Conductor equipment grounding conductor
can serve as equipment grounding conductors where the following
where continuous maintenance and
supervisión ensure that only qualified requirements have been met [392.10(0)]:
persons service the cable tray.
(1) Cable tray sections and fittings are identified for grounding.
Figure 392-7
(4) Cable tray sections, fittíngs, and connected raceways are effec-
Figure 392-5
tively bonded to each other to ensure electrical continuity and the
capacity to conduct safely any fault current likely to be imposed
The metallic cable trays that support conductors must be bonded on them [250.96(A)]. This is accomplished by using bolted
together to ensure that they have the capacity to conduct safely any mechanical connectors or bonding jumpers sized in accordance
408 Mike HoiVs iiiustrated Guide to Understanding tiie 2011 Nationai Eiectricai Code, Voiume 1
Cable Trays 392.80
Figure 392-7
3 Practice Questions
These questions are based on tiie 2011 National 4. Where cables and nonmetallic raceways are installed parallel
Electrical Code. Please use ttie 2011 NEC Code bool< to to framing members, the nearest outside surface of the cable
answer tlie following questions. or raceway shall be the nearest edge of the framing
member where nails or screws are likely to penétrate.
1. Conductors shall be installed within a raceway, cable, or enclo- 5. When installed under metal-corrugated sheet roof decking, the
sure. rules for spacing from roof decking apply equally to rigid metal
conduit and intermedíate metal conduit.
(a) True
(b) False (a) True
(b) False
holes in metal members, the cable shall be protected by under a driveway oí a one-family dweiling?
which are installed in the opening prior to the instaliation of the (a) 6 in.
cable and which secureiy cover all metal edges. (b) 1 2 i n .
(a) listed bushings (c) 16 in.
(a) wet
(b) dry
(c) damp
(d) corrosive
410 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Practice Questions Article 300
Direct-buried service conductors that are not encased in 14. Where nonmetallic wiring methods are subject to exposure to
concrete and that are buried 18 in. or more below/ grade shall chemical solvents or vapors, they shall be inherently resistant
have their locahon identified by a warning ribbon placed in the to chemicals based upon their being .
trench at Ieast above the underground instaliation.
(a) listed for the chemical
(a) 6 in. (b) identified for the chemical
(b) 10in. (c) a and b
(c) 12in. (d) a or b
(d}18in.
19. Metal or nonmetallic raceways, cable armors, and cable 25. Electrical installations in hollow spaces, vertical shafts, and
sheaths between cabinets, boxes, fittings or other ventilation or air-handling ducts shall be made so that the
enclosures or outlets. possible spread of fire or products of combustión is not .
20. In multiwire branch circuits, the continuity of the 26. Equipment and devices shall only be permitted within ducts or
conductor shall not be dependent upon the device connections. plenum chambers specifically fabricated to transport environ-
mental air if necessary for their direct action upon, or sensing
(a) ungrounded
of, the .
(b) grounded
(c) grounding electrode (a) contained air
(d) a a n d b (b) air quality
(c) air temperature
(d) none of these
21. A box or conduit body shall not be required where cables enter
or exit from conduit or tubing that is used to provide cable
support or protection against physical damage. 27. shall be permitted to support the wiring methods and
equipment permitted to be used in other spaces used for envi-
(a) True
ronmental air (plenum).
(b) False
(a) Metal cable tray system
(b) Nonmetallic wireways
22. A bushing shall be permitted in lieu of a box or terminal where
(c) PVC conduit
the conductors emerge from a raceway and enter or terminate
(d) Surface nonmetallic raceways
at equipment such as open switchboards, unenclosed control
equipment, or similar equipment.
24. A vertical run of 4/0 AWG copper shall be supported at intervals 2. Where conductors in parallel are run in sepárate raceways, the
not exceeding . raceways shall have the same electrical characteristics.
412 Mike Hoit's iilustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Practice Questions Article 314
3. There are four principal determinants of conductor operating 8. THWN insulated conductors are rated .
temperature, one of which is generated internally in the
(a) 75°C
conductor as the result ot load current flow, inciuding funda-
(b) for wet locations
mental and harmonio currents.
(c) a and b
(a) friction (d) not enough information
(b) magnetism
(c) heat
9. The minimum size conductor permitted for branch circuits
(d) none of these
under 600V is AWG.
(a) 14
4. Each current-carrying conductor of a paralleled set of conduc-
(b) 12
tors shall be counted as a current-carrying conductor for the
(c) 10
purpose of appiying the adjustment factors of 310.15(B)(3)(a).
(d) 8
(a) True
(b) False
(a) True
1. According to the NEC, the volume of a 3 x 2 x 2 in. device box is
(b) False
(a) 8 cu in.
(b) 10 cu in.
(c) 12 cu in.
(d) 14 cu in.
2. When couníing the number of conductors in a box, a conductor 7. In completed installations, each outlet box shall have a .
running through the box with an unbrol^en loop or coil not less
(a) cover
than twice the minimum length required for free conductors
(b) faceplate
shall be counted as conductor(s).
(c) canopy
(a) one (d) any of these
(b) two
(c) three
(d) four 8. Listed outlet boxes to support ceiling-suspended fans ttiat
weigh more than Ib shall have the máximum allowable
weight marked on the box.
3. For the purposes of determining box fill, each device or utiliza-
(a) 35 Ib
tion equipment in the box which is wider than a single device
(b) 50 Ib
box counts as two conductors for each required for the
(c) 60 Ib
mounting.
(d) 70 Ib
(a) inch
(b) kilometer
(c) gang 9. Power distribution biocks shall be permitted in pulí and junction
(d) box ""^ boxes over 100 cubic inches when they comply with the provi-
sions of 314.28(E).
(a) True
4. Conduit bodies that are durably and legibly marked by the
(b) False
manufacturer with their volume can contain spiices, taps, or
devices.
(a) True 10. shall be installed so that the wiring contained can be
(b) False rendered accessible without removing any part of the building
or, in underground circuits, without excavating sidewaiks,
paving, or earth.
5. Noncombustible surfaces that are broken or incompleto around
(a) Boxes
boxes employing a flush-type cover or faceplate shall be
(b) Conduit bodies
repaired so there will be no gaps or open spaces larger than
(c) Handhole enclosures
at the edge of the box.
(d) all of these
{a)1/16in.
(b) 1/8 in.
(c) 1/4 in. 11. Conductors, spiices or terminations in a handhole enclosure
414 Mike HolVs lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Practice Questions Article 330
icie 320. Armored Cable (Type AC) Article 330. IVIetal-Clad Cable (Type MC)
Type cable is a fabricated assembiy of insulated 1. Type is a factory assembiy of insulated circuit conduc-
conductors in a flexible interlocked metallic armor. tors within an armor of interlocking metal tape, or a smooth or
corrugated metallic sheath.
(a) AC
(b) MC (a) AC
(c) NM (b) MC
(d) b and c (c) NM
(d) b and c
(a) 3ft
(b) 4ft (a) 3ft
{c)5ft (b) 4ft
(d)6tt (c) 6ft
(d) 8ft
(a) 2 f t
(b) 3ft
(c) 4V2ft
(d) 6ft
Article 334. Nonmetallic-Slieathed 6. For Type NM and NMC cable, the conductor ampacity used for
(a) in one- and two-family dweilings and their attached/ Article 338. Service-Entrance Cable (Types SE and USE)
detached garages or storage buildings
(b) multifamily dweilings permitted to be of Types III, IV, and V 1. Type SE cable shall be permitted to be used as in wiring
construction systems where all of the circuit conductors of the cable are of
(c) other structures permitted to be of Types III, IV, and V the thermoset or thermoplastic type.
construction, except as prohibited in 334.12.
(a) branch circuits
(d) any of these
(b) feeders
(c) a or b
(d) neither a or b
3. Type NM cable shall closely follow the surface ot the building
finish or running boards when run exposed.
416 Mike HoiVs Iliustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Practice Questions Article 344
2. Type UF cable can be used in commercial garages. 4. Threadless couplings approved for use with IMC in wet loca-
tions shall be .
(a) True
(b) False (a) rainproof
(b) listed for wet locations
(c) moistureproof
3. Type UF cable shall not be used where subject to physical
(d) concrete-tight
damage.
(a) True
(b) False Article 344. Rigid Metal Conduit (Type RMC)
(a) fíame retardant áreas subject to severe corrosive influences when protected by
(b) moisture, fungus, and corrosión resistant and judged suitable for the condition.
1. IMC can be installed in or under cinder fill subject to permanent 2. Aluminum fittings and enclosures can be used with
moisture . conduit where not subject to severe corrosive influences.
(a) where the conduit is not less than 18 in. under the fill (a) steel rigid metal
(b) when protected on all sides by 2 in. of noncinder concrete (b) aluminum rigid metal
(c) where protected by corrosión protection judged suitable for (c) PVC-coated rigid conduit only
the condition (d) a and b
(d) any of these
3. Trade size 1 IMC shall be supported at intervals not exceeding (a) raintight
(b) wet and damp location
(a) 8 f t (c) nonabsorbent
(b) 10ft (d) concrete-tight
(c) 12 ft
(d) 14ft
5. Each length of RMC shall be clearly and durably identified in Article 350. Liquidtight Flexible
every . Metal Conduit (Type LFMC)
(a) 3 f t
1. Liquidtight flexible metal conduit must be secureiy fastened by
(b) 5 f t
a means approved by the authority having jurisdiction within
(c) 10 ft
of termination.
(d) 20 ft
(a) 6 in.
(b) 1 0 i n .
3. Flexible metal conduit shall not be required to be where (a) is required after instaliation
fished between access points through concealed spaces in (b) is not required after instaliation
finished buildings or structures and supporting is impracti- (c) either a or d
cable. (d) is optional
(a) secured
(b) supported
(c) complete Article 352. Rigid Polyvinyl Chioride Conduit (Type PVC)
(d) (a) and (b)
1. PVC conduit shall be permitted for exposed work where subject
to physical damage if identified for such use.
4. In an FMC instaliation, connectors shall not be
(a) True
concealed.
(b) False
(a) straight
(b) angle
(c) grounding-type
(d) none of these
418 mke Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Questions Article 362
PVC conduit shall not be used , unless specifically 2. Bends in LFNC shall between pulí points.
permitted.
(a) not be made
(a) in hazardous (classified) locations (b) not be limited in degrees
(b) for the support of luminaires or other equipment (c) be limited to 360 degrees
(c) where subject to physical damage unless identified for such (d) be limited to 180 degrees
use
(d) allof these
2. When a building is supplied with a fire sprinkier system, ENT Article 376. I\1etal Wireways
can be installed above any suspended ceiling.
1. Metal wireways are sheet metal troughs with for
(a) True
housing and protecting electric conductors and cable.
(b) False
(a) removable covers
(b) hinged covers
3. ENT is not permitted in hazardous (classihed) locations, unless (c) a or b
permitted in other articles of the Code. (d) none of these
(a) True
(b) False
2. Wireways can pass transversely through a wall .
5. Cut ends of ENT shall be trimmed inside and to remove (a) 50 percent
rough edges. (b) 20 percent
(c) filed
(d) beveled
4. Where insulated conductors are deflected within a metal
wireway, the wireway shall be sized to meet the bending
6. Bushings or adapters shall be provided at ENT terminations to requirements corresponding to wire per terminal in
protect the conductors from abrasión, unless the box, fitting, or Table 312.6(A).
420 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1
Practice Questions Article 392
Article 380. IVIultioutlet Assembiy 5. Surface metal raceway enclosures providing a transition from
other wiring methods shall have a means for connecting a(n)
1. A multioutlet assembiy shall not be installed.
1. Unbroken lengths of surface metal raceways can be run 1. A cable tray is a unit or assembiy of units or sections and asso-
through dry . ciated fittings forming a system used to secureiy fasten
or support cables and raceways.
(a) walls
(b) partitions (a) structural
(c) floors (b) flexible
(d) all of these (c) movable
(d) secure
5. In industrial facilities where conditions of maintenance and 8. Metal cable trays containing only non-power conductors such
supervisión ensure that only qualified persons will service the as communication, data, signal, conductors and cables must be
instaliation, cable tray systems can be used to support . eiectrically continuous, through listed connections or the use of
an insulated stranded bonding jumper not smaller than .
(a) raceways
(b) cables (a) 12 AWG
{c} boxes and conduit bodies (b) 10 AWG
(d) allof these (c) 6AWG
(d) 4AWG
(a) in groups consisting of not more than three conductors per (a) an equipment grounding conductor
phase or neutral (b) special
(b) in groups consishng of not more than one conductor per (c) industrial
phase or neutral (d) all of these
(c) as individual conductors secureiy bound to the cable tray
(d) in sepárate groups
10. Cable trays shall .
422 Mike Holt's lllustrated Guide to Understanding the 2011 National Electrical Code, Volume 1