Documente Academic
Documente Profesional
Documente Cultură
One of these conditions is a power system fed by several generators and/or transformers in
parallel. If the neutral of only one source is grounded, it is possible for the zero-sequence
impedance of the grounded source to exceed the effective positive-sequence impedance of
the several sources in parallel.
Another such condition may occur where power is distributed to remote facilities by an
overhead line without a metallic ground-return path. In this case, the return path for
ground-fault current is through the earth, and even though both the neutral of the source
and the non-conducting parts at the load may be grounded with well-made electrodes, the
ground-return path includes the impedance of both of these ground electrodes. This
impedance may be significant. Another significant source of zero-sequence impedance is
the large line-to-ground spacing of the overhead line.
The advantages and disadvantages of the various methods of grounding are summarized in
Table 1-1.