5 BAR]
FEATURES
• High-flow-rate valve valve bore is equipped with a rubber seal to contain the
• 4.0” [100 mm] grooved valve outlet connection extinguishing agent under pressure within the cylinder.
• Calibrated Pressure Gauge An orifice in the axis of the piston allows cylinder
• Over-pressure safety device (PRD) pressure to equalize on the top and bottom of the
• 4-way “lift-base” for ease of shipping and installation piston. The pressurized area at the top of the piston is
• Manual, Electric or Pressure operated greater than the area at the bottom of the piston. The
(Pneumatic) Actuation net force seals the piston against the valve seat. When
• Optional Equipment the cylinder pressure on the top of the piston is relieved
- Liquid-level indicator (by means of automatic or manual activation) there is
- Pressure Supervisory Switch only pressure acting against the bottom of the piston
- Discharge Pressure Switch and the piston slides to its full open position. This
- Cylinder Floorstrap allows the agent to discharge through the distribution
piping network connected to the valve outlet. A siphon
The Cylinder Assembly is equipped with a 4.0” [100 tube is built into the cylinder assembly. The siphon
mm] stainless steel, differential pressure-type valve with tube is straight, allowing the cylinder to be installed in a
a 4.0” [100 mm] grooved male outlet. A piston in the vertically upright orientation (valve on top).
ASSEMBLY P/N CYLINDER SIZE (NOMINAL) MAXIMUM FILL MINIMUM FILL VALVE SIZE (NOMINAL)
FTF 000490 1300 lb (490 L) 1297 lb (588 kg) 260 lb (118 kg) 4.0” (100 mm)