8 7 6 5 4 3 2 1

REVISIONS
ZONE REV ECR DESCRIPTION BY DATE APPR APPR DATE

FL500 - - - - - - - - - 0 800000027815 PRODUCTION RELEASE WJE 12JUN18 BM 20JUN18

Sensitivity Time Delay Housing Cable Entry


1(Std)100% 1 2 SECOND DELAY 1(Std)STAINLESS STEEL 1(Std)2x3/4" NPT
2 75% 2 4 SECOND DELAY 2 2x25mm
3 50% 3 8 SECOND DELAY
4(STD)10 SECOND DELAY
D Approvals D
1(Std)FM/CSA/ATEX/IECEx Mounting Bracket
RELAY STATE - NC 0 Without Bracket
1 LATCH ALARM/NON-LATCH WARN DE-ENERGIZED NO CHARGE 1(STD)With Bracket (p/n 71370-1)
2 LATCH ALARM/NON-LATCH WARN ENERGIZED NO CHARGE
3 LATCH ALARM/LATCH WARN DE-ENERGIZED NO CHARGE
4 LATCH ALARM/LATCH WARN ENERGIZED NO CHARGE
5(Std)NON-LATCH ALARM/NON-LATCH WARN DE-ENERGIZED NO CHARGE
6 NON-LATCH ALARM/NON-LATCH WARN ENERGIZED NO CHARGE
7 NON-LATCH ALARM/LATCH WARN DE-ENERGIZED NO CHARGE
8 NON-LATCH ALARM/LATCH WARN ENERGIZED

Alarm Output
1 4-20mA SOURCE CURRENT,RELAYS,SINGLE MODBUS,HART off
2 4-20mA SINK CURRENT,RELAYS,SINGLE MODBUS,HART off
3(Std)3.5 mA HART,SOURCE CURRENT,RELAYS,SINGLE MODBUS
4 3.5 mA HART,SINK CURRENT,RELAYS,SINGLE MODBUS
5 1.25 mA HART,SOURCE CURRENT,RELAYS,SINGLE MODBUS
6 1.25 mA HART,SINK CURRENT,RELAYS,SINGLE MODBUS

5.00
127

C C
2X #8-32 INTERNAL
CHASSIS GROUND

ALARM

10
FAULT 2

11 12 13 14
RESET
FAULT C NOT USED

9
FAULT 1 NOT USED

8
DATA - ALARM

7
TEST

15
DATA + ALARM HIGH 2

16
4.40
NOT USED ALARM HIGH 1

17 18 19 20
4.97
0-20mA

4
ALARM HIGH C

111.76 +24 VDC

3
ALARM LOW C

126.24 COM ALARM LOW 1

2
(24V-RETURN)
ALARM LOW 2

1
CHASSIS

TB1 TB2

6.40
162.47 2X 3/4-14 NPT
(M25 ADAPTER OPTIONAL)

B B

LOCKING SCREW #8-32 EXTERNAL THRU HOLE FOR TAG


(5 mm HEX DRIVE) CHASSIS GROUND

.39 UNLESS OTHERWISE SPECIFIED The information and technical data disclosed by this document may be used and disseminated only for the purposes and to the extent
9.91 specifically authorized by General Monitors, Inc. in writing. Such information and technical data are proprietary to General Monitors, Inc. and
MOUNTING PIN THIRD ANGLE PROJECTION
may not be used or disseminated except as provided in the foregoing sentence.
4.33 DRAWN WJE 03MAY18
DIMENSIONS L.VLAGEA 02MAY18 LAKE FOREST, CA, USA
109.98 CHK'D.

INCH[mm] ENGR. B.MONAHAN 02MAY18 GALWAY, IRELAND


3. ENCLOSURE FINISH:
- STAINLESS STEEL PASSIVATED, RED POLYESTER (TGIC) POWDER COAT
CUSTOMER _________________________ TITLE:
A 2. DETECTOR WEIGHT: P.O. NO. _________________________ INSTALLATION OUTLINE A
- STAINLESS STEEL ENCLOSURE: 9.4 lb [4.3 kg]
GM NO. ___________________________ DRAWING, FL500
1. DIMENSIONS ARE FOR REFERENCE ONLY.
LOCATION _________________________ DRAWING NO.: LIFECYCLE STATE: REV:
NOTES: UNLESS OTHERWISE SPECIFIED 712907 712902 TAG NO. __________________________
712906 Production 0
NEXT ASSY USED ON TOTAL NO. OF UNITS _______________
SCALE: NTS MODEL: FL500 SHEET 1 OF 2

8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1

WIRING 5.00 9.36


POSITION TB1 POSITION TB2 127 237.85

10 FAULT 2 11 ALARM
RESET
D 9 FAULT C 12 NOT USED D
8 FAULT 1 13 NOT USED

7 DATA- 14 ALARM
TEST
6 DATA+ 15 ALARM HIGH 2
5 NOT USED 16 ALARM HIGH 1
4 0-20 mA 17 ALARM HIGH C
3 +24VDC 18 ALARM LOW C

2 COM 19 ALARM LOW 1


(24V-RETURN 6.40
1 CHASSIS 20 ALARM LOW 2 162.47

8.31
211.02

C C

2.01
51
17mm WRENCH/SOCKET
REQUIRED FOR TIGHTENING

4X .24
6
3.35
85

B B

MAXIMUM WIRE LENGTH TO


INSTRUMENT FOR A +24 VDC SUPPLY
(MAXIMUM 20 OHM LOOP)

AWG
2
mm Feet Meters

A 14 2.08 6588 2013


LAKE FOREST, CA, USA
GALWAY, IRELAND A
16 1.31 4146 1266
The information and technical data disclosed by this document may be used and disseminated only for the
18 0.823 2608 796 purposes and to the extent specifically authorized by General Monitors, Inc. in writing. Such information and
technical data are proprietary to General Monitors, Inc. and may not be used or disseminated except as
20 0.519 1642 501 provided in the foregoing sentence.

22 0.33 1055 321 DRAWING NO.: LIFECYCLE STATE: REV:

712906 Production 0
SCALE: NTS MODEL: FL500 SHEET 2 OF 2