Documente Academic
Documente Profesional
Documente Cultură
Q.1 The per unit values of positive, negative and zero sequence reactance of a network at fault
are 0.16, 0.14 and 0.2. Determine the fault current if fault is double line to ground (L-L-G).
Q.2 Derive an expression for maximum momentary current, if transient takes place on a
transmission line. Also, explain doubling effect with the help of waveform of short circuit
current on a transmission line.
Q.3 Deduce the expression for fault current in single line to ground fault. An 11 kV, 25 MVA
Synchronous Generator has positive, negative and zero sequence reactances of 0.12, 0.12 and
0.08 pu, respectively. The generator neutral grounded through a reactance of 0.03 pu. A
single line-to-ground fault occurs at the generator terminals. Determine the fault current and
the line-to-line voltages. Assume that the generator was unloaded before the fault.
Q.4 100 MVA, 11 kV generator having Z1 = Z2 = Z0 = 0.1 pu and Zn = 0.05 pu, Zf = 0.05 pu.
Single line to ground fault occurs in 'a' phase. Find (i) fault current in per unit, (ii) actual fault
current, (iii) short circuit MVA and (iv) short circuit MVA in per unit.
Q.5 Explain the switching operation in a series R-L circuit.
Q.6 Two generators rated at 11 kV, 5 MVA having 5% reactance connected through a
transmission line having reactance of 0.4 Ω/Φ/km. Both the transformers rated at 8 MVA, 11
kV/33 kV and a reactance of 4%. Choose MVA base as 8 MVA and 11 kV. A short circuit
occurs at the midpoint of the transmission line shown in figure 1, then find fault MVA and
fault current. (length of line is 50 km)
Q.7 A 25 MVA, 13.2 kV alternator with solidly grounded neutral has a sub-transient reactance of
0.25 pu. The negative and zero sequence reactances are 0.35 and 0.1 pu, respectively.
Determine the fault current and line to line voltages at the fault when double line to ground
fault occurs at the terminals of the alternator. Deduce also the expression used for calculating
fault current.
Q.9 Two generators A and B are identical and rated 11 kV, 10 MVA and have a transient
reactance of 20% at their own MVA base. Two transformers T1 and T2 are also identical and
are rated 5 MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie line
is 100 km long and has a reactance of 0.1 ohms/km. A 3 – phase fault occurs at distance of
25 km from one end of the line when the system is on no load but at rated voltage. Determine
fault MVA and fault current. Choose base MVA as 10 MVA and base kV of the generator
side 11 kV and for transmission line as 66 kV.
Q.10 A 3 – phase, star connected alternator is rated 30 MVA, 13.8 kV and has a reactance
values: X1 = 0.25 pu; X2 = 0.35 pu and X0 = 0.10 pu. The neutral of the alternator is solidly
grounded. Determine the alternator line currents when a double line to ground fault occurs on
its terminals. Assume that the alternator is unloaded and is operating at rated voltage when
the fault occurs.
Unit – 2
MCQ Questions (2/3 Marks)