Sunteți pe pagina 1din 16

Part 1. Load Estimating | Chapter 2.

Design Conditions

CHAPTER 2. DESIGN CONDITIONS

This chapter presents the data from which the apparatus; use a moisture content corresponding to the
outdoor design conditions are established for various normal design wet-bulb temperature and 80 % rh for
localities and inside design conditions for various selecting the dehumidifier (dehydrator)
applications. The design conditions established Daily range is the average difference between the
determine the heat content of air, both outdoor and high and low dry-bulb temperatures for a 24-hr period
inside. They directly affect the load on the air on a design day. This range varies with local climate
conditioning equipment by influencing the transmission conditions.
of heat across the exterior structure and the difference
in heat content between the outdoor and inside air. For MAXIMUM DESIGN CONDITIONS-SUMMER
further details, refer to Chapters 5 and 6. Maximum summer design conditions are
recommended for laboratories and industrial
OUTDOOR DESIGN CONDITIONS – SUMMER applications where exceeding the room design
AND WINTER conditions for even short periods of time can be
The outdoor design conditions listed in Table 1 are detrimental to a product or process.
the industry accepted design conditions as published The maximum design dry-bulb and wet-bulb
in ARI Std. 530-56 and the 1958 ASHAE Guide. The temperatures are simultaneous peaks (not individual
conditions, as listed, permit a choice of outdoor dry- peaks). The moisture content is an individual peak, and
bulb and wet-bulb temperatures for different types of is listed only for use in the selection of separate cooling
applications as outlined below. and dehumidifying systems for closely controlled
spaces. Each of these conditions can be expected to
NORMAL DESIGN CONDITIONS – SUMMER be exceeded no more than 3 hours in a normal
Normal design conditions are recommended for use summer.
with comfort and industrial cooling applications where
it is occasionally permissible to exceed the design NORMAL DESIGN CONDITIONS – WINTER
room conditions. These outdoor design conditions are Normal winter design conditions are recommended
the simultaneously occurring dry-bulb and wet-bulb for use with all comfort and industrial heating
temperatures and moisture content, which can be applications. The outdoor dry-bulb temperature can be
expected to be exceeded a few times a year for short expected to go below the listed temperatures a few
periods. The dry-bulb is exceeded more frequently times a year, normally during the early morning hours.
than the wet-bulb temperature. And usually when the The annual degree days listed are the sum of all the
wet-bulb is lower than design. days in the year on which the daily mean temperature
When cooling and dehumidification (dehydration) falls below 65 F db, times the number of degrees
are performed separately with these types of between 65 F db and the daily mean temperature.
applications, use the normal design dry-bulb
temperature for selecting the sensible cooling
Part 1. Load Estimating | Chapter 2. Design Conditions

CORRECTIONS TO OUTDOOR DESIGN Solution:


CONDITIONS FOR TIME OF DAY AND Normal design conditions for New York in July at 3:00
TIME OFYEAR p.m. are 95 F db, 75 F wb (Table 1).
The normal design conditions for summer, listed in Daily range in New York City is 14 F db.
Table 1, are applicable to the month of July at about Yearly range in New York City = 95-0 = 95 F db.
3:00 P.M. Frequently, the design conditions at other Correction for time of day (12 noon) from Table 2:
times of the day and other months of the year must be Dry-bulb = -5 F
known. Wet-bulb = -1 F
Table 2 lists the approximate corrections on the dry- Correction for time of year (October) from Table 3:
bulb and wet-bulb temperatures from 8 a.m. to 12 p.m. Dry-bulb = -16 F
based on the average daily range. The dry-bulb Wet-bulb = -8 F
corrections are based on analysis of weather data, and Design conditions at 12 noon in October (approximate) :
the wet-bulb corrections assume a relatively constant Dry-bulb = 95-5-16 = 74 F
dewpoint throughout the 24-hr period. Wet-bulb = 75-1- 8 = 66 F
Table 3 lists the approximate corrections of the dry-
bulb and wet-bulb temperatures from March to INSIDE COMFORT DESIGN CONDITIONS-
November, based on the yearly range in dry-bulb SUMMER
temperature (summer normal design dry-bulb minus The inside design conditions listed in Table 4 are
winter normal design dry-bulb temperature). These recommended for types of applications listed. These
corrections are based on analysis of weather data and conditions are based on experience gathered from
are applicable only to the cooling load estimate. many applications, substantiated by ASHAE tests.
The optimum or deluxe conditions are chosen where
Example 1 – Corrections to Design Conditions costs are not of prime importance and for comfort
Given: applications in localities having summer outdoor design
A comfort application in New York City. dry-bulb temperatures of 90 F or less. Since all of the
Find: loads (sun, lights, people, outdoor air, etc.) do not peak
The approximate dry-bulb and wet-bulb temperatures at simultaneously for any prolonged periods, it may be
12:00 noon in October. uneconomical to design for the optimum conditions.
equipment. Applications of inherently high sen-sible
The commercial inside design conditions are heat factor (relatively small latent load) usually result in
recommended for general comfort air conditioning the most economical equipment selection if the higher
applications. Since a majority of people are dry-bulb temperatures and lower relative humidities are
comfortable at 75 F or 76 F db and around 45% to 50% used. Applications with low sensible heat factors (high
rh, the thermostat is set to these temperatures, and latent load) usually result in more economical
these conditions are maintained under partial loads. As equipment selection if the lower dry-bulb temperatures
the peak loading occurs (outdoor peak dry-bulb and and higher relative humidities are used.
wet-bulb temperatures, 100% sun, all people and lights,
etc.), the temperature in the space rises to the design INSIDE COMFORT DESIGN CONDITIONS-
point, usually 78 F db. WINTER
If the temperature in the conditioned space is forced For winter season operation, the inside design
to rise, heat will be stored in the building mass. Refer conditions listed in Table 4 are recommended for
to Chapter 3, “Heat Storage, Diversity and general heating applications. With heating, the
Stratification,” for a more complete discussion of heat temperature swing (variation) is below the comfort
storage. With summer cooling, the temperature swing condition at the time of peak heating load (no people,
used in the calculation of storage is the difference lights, or solar gain, and with the minimum outdoor
between the design temperature and the normal temperature). Heat stored in the building structure
thermostat setting. during partial load (day) operation reduces the required
The range of summer inside design conditions is equipment capacity for peak load operation in the same
provided to allow for the most economical selection of manner as it does with cooling.
.

INSIDE INDUSTRIAL DESIGN CONDITIONS required conditions and comfort conditions to maintain
Table 5 lists typical temperatures and relative high quality commensurate with low production cost.
humidities used in preparing, processing, and Generally, specific inside design conditions are
manufacturing various products, and for storing both required in industrial applications for one or more of the
raw and finished goods. These conditions are only following reasons:
typical of what has been used, and my vary with
applications. They may also vary as changes occur in 1. A constant temperature level is required for close
processes, products, and knowledge of the effect of tolerance measuring, gaging, machining, or
temperature and humidity. In all cases, the grinding operations, to prevent expansion and
temperature and humidity conditions and the contraction of the machine parts, machined
permissible limits of variations on these conditions products and measuring devices. Normally, a
should be established by common agreement with the constant temperature is more important than the
customer. temperature level. A constant relative humidity is
Some of the conditions listed have no effect on the secondary in nature but should not go over 45% to
product or process other than to increase the efficiency minimize formation of heavier surface moisture film.
of the employee by maintaining comfort conditions. Non-hygroscopic materials such as metals, glass,
This normally improves workmanship and uniformity, plastics, etc., have a property of capturing water
thus reducing rejects and production cost. In some molecules within the microscopic surface crevices,
cases, it may be advisable to compromise between the forming an invisible, non-continuous surface film.
The density of this film increases when relative
Part 1. Load Estimating | Chapter 2. Design Conditions

humidity increases. Hence, this film must, in many


instances, be held below a critical point at which 4. The temperature and relative humidity control are
metals may etch, or the electric resistance of required to regulate the rate of chemical or
insulating materials is significantly decreased. biochemical reactions, such as drying of
2. Where highly polished surfaces are manufactured Varnishes or sugar coatings, preparation of
or stored, a constant relative humidity and synthetic fibers or chemical compounds,
temperature is maintained, to minimize increase is fermentation of yeast, etc. Generally, high
maintained, to minimize increase in surface temperatures with low humidities increase drying
moisture film. The temperature and humidity rates; high temperatures increase the rate of
should be at, or a little below, the comfort chemical reaction, and high temperatures and
conditions to minimize perspiration of the operator. relative humidities increase such processes as
Constant temperature and humidity may also be yeast fermentations.
required in machine rooms to prevent etching or 5. Laboratories require precise control of both
corrosion of the parts of the machines. With temperature and relative humidity or either. Both
applications of this type, if the conditions are not testing and quality control laboratories are
maintained 24 hours a day, the starting of air frequently designed to maintain the ASTM
conditioning after any prolonged shutdown should Standard Conditions* of 73.4 F db and 50% rh.
be done carefully: (1) During the summer, the 6. With some industrial applications where the load is
moisture accumulation in the space should be excessive and the machines or materials do not
reduced before the temperature is reduced; (2) benefit from controlled conditions, it may be
During the winter, the moisture should not be advisable to apply spot cooling for the relief of the
introduced before the materials have a chance to workers. Generally, the conditions to be
warm up if they are cooled during shutdown maintained by this means will be above normal
periods. comfort.
3. Control of relative humidity is required to maintain
the strength, pliability, and regain of hydroscopic *Published in ASTN pamphlet dated 9-29-48. These conditions
materials, such as textiles and paper. The humidity have also been approved by the Technical Committee on
must also be controlled in some applications to Standard Temperature and Relative Humidity Conditions of the
reduce the effect of static electricity. Development FSB (Federal Specifications Board) with one variation: FSB
of static electric charges is minimized of 55% or permits ±4%, whereas ASTM requires ±2% permissable
higher. humidity tolerance.
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification

CHAPTER 3. HEAT STORAGE, DIVERSITY


AND STRATIFICATION

The normal load estimating procedure has been to This degree should be determined by the engineer from
evaluate the instantaneous heat gain to a space and to project requirements and customer desires. A system
assume that the equipment will remove the heat at this so designed, full reduction on refrigeration load and
rate. Generally, it was found that the equipment less than full reduction on air side or room load, meets
selected on this basis was oversized and therefore all of the flexibility requirements, except at time of peak
capable of maintaining much lower room conditions load. In addition, such a system has a low owning and
than the original design. Extensive analysis, research operating cost.
and testing have shown that the reasons for this are:
1. Storage of heat in the building structure. STORAGE OF HEAT IN BUILDING
2. Non-simultaneous occurrence of the peak of STRUCTURES
the individual loads (diversity). The instantaneous heat gain in a typical comfort
3. Stratification of heat, in some cases. application consists of sun, lights, people, transmission
This chapter contains the data and procedures for thru walls, roof and glass, infiltration and ventilation air
determining the load the equipment is actually picking and, in some cases, machinery, appliances, electric
into account the above factors. Application of these calculating machines, etc. A large portion of this
data to the appropriate individual heat gains results in instantaneous heat gain is radiant heat which does not
the actual cooling load. become an instantaneous load on the equipment,
The actual cooling load is generally considerable because it must strike a solid surface and be absorbed
below the peak total instantaneous heat gain, thus by this surface before becoming a load on the
requiring smaller equipment to perform a specific job. equipment. The breakdown on the various
In addition, the air quantities and/or water quantities are instantaneous heat gains into radiant heat and
reduced, resulting in a smaller overall system. Also, as convected heat is approximately as follows:
brought out in the tables, if the equipment is operated
somewhat longer during the peak load periods, and/of RADIANT CONVECTIVE
the temperature in the space is allowed to rise a few HEAT GAIN SOURCE HEAT HEAT
degrees at the peak periods during cooling operation, a Solar, without inside 100% -
further reduction in required capacity results. The blinds
smaller system operating for longer periods at times of Solar, with inside blinds 58% 42%
Fluorescent Lights 50% 50%
peak load will produce a lower first cost to the customer Incandescent Lights 80% 20%
with commensurate lower demand charges and lower People* 40% 20%
operating costs. It is a well-known fact that equipment Transmission† 60% 40%
Infiltration and Ventilation - 100%
sized to more nearly meet the requirements results in a Machinery or 20-80% 80-20%
more efficient, better operating system. Also, if a Appliances‡
smaller system is selected, and is based on extended *The remaining 40% is dissipated as latent load.
periods of operation at the peak load, it results in a †Transmission load is considered to be 100% convective load.
more economical and efficient system at a partially This load is normally a relatively small part of the total load, and
loaded condition. for simplicity is considered to be the instantaneous load on the
Since, in most cases, the equipment installed to equipment.
perform a specific function is smaller, there is less ‡The load from machinery or appliances varies, depending upon
margin for error. This requires more exacting the temperature of the surface. The higher the surface
engineering including air distribution design and temperature, the greater the radiant heat load.
system balancing.
With multi-story, multi-room application, it is usually CONSTANT SPACE TEMPERATURE AND
desirable to provide some flexibility in the air side or EQUIPMENT OPERATING PERIODS
room load to allow for individual room control, load As the radiant heat from sources shown in the
pickup, etc. Generally, it is recommended that the full above table strikes a solid surface (walls, floor, ceiling,
reduction from storage and diversity be taken on the etc.), it is absorbed, raising the temperature at the
overall refrigeration or building load, with some degree surface of the material above that inside the material
of conservatism on the air side or room loads. and the air adjacent to the surface. This temperature

S-ar putea să vă placă și