100 500 100

300
R.C. COVER W/ 15 MM0
LIFTING COVER

100 MM DIA. BARS @ 200MM


O.C. BOTH WAYS
CB
100

DP DP 500
300

1800 750 750 WATER PROOFING MEMBRANE


COUNTER SUNK
FLOOR CLEAN OUT 100
(VERIFY SPECIFICATION)
150 150 150 Ø10 mm PVC EFFLUENT
PIPE TAPPED TO NEAREST CONCRETE TOPPINGS
CONCRETE TOPPINGS
PLAN
CATCH BASIN COUNTER SUNK
FLOOR CLEAN OUT
B WATER PROOFING MEMBRANE
(VERIFY SPECIFICATION)

Ø10mm PVC INFLUENT PIPE FIN. FLR. LEVEL FIN. FLR. LEVEL
Ø50mm PVC VENT
100

CO SLAB SOFFIT
HANGER ROD
100 MM CHB
200mm
LATERAL/BRANCH
CO CO SOIL/WASTE PIPE

CO
SLAB SOFFIT 500
DP DP
1500 600 A
MH MH MH
SECTION 200mm
150
SECTION
500
Ø10mm @ 300mm B.W

CLEAN OUT DETAILS


PLAN SCALE NTS
CATCH BASIN DETAILS
SCALE NTS

Ø10mm @ 300mm B.W


UNION PATENTE 50Ø WATER METER
PLUMBING NOTES:
Ø.50 mm PVC VENT 50Ø GATE VALVE UNION PATENTE
1. ALL SANITARY ORS SHALL CONFORM ITH THE PREVAILING REQUIREMENTS
CO MH CO CO CO
90Ø ELBOW OF LOCAL ORDINANCES AND NATIONAL LAS
2.READ THE DRAING IN CONETION WITH OTHER RELATED DRAWINGS AND
150 NATURAL GRADE LINE SPECIFICATION, THE ARCHITECT AND THE ENGINEER SHALL BE NOTIFIED
AIR SPACE
WRAPPED WITH BURLAP & IMMEDIATELY OF ANY DISCREPANCIES FOUND THEREIN.
COATED WITH COAL TAR IF
BURIED UNDERGROUND 10Ø REBARS FOR 50Ø CHECK
3. THE CONTRACTOR SHALL DETERMINE THE ACTUAL LOCATION, DEPTH AND
WATER LEVEL FOR CORROSION
PROTECTION 300 150x150 R.C.
PEDESTAL
VALVE 50Ø CWL INVERT ELEVATION OF EXISTING PIPE AND STRUCTURE TO CONFORM WITH THE
COARSE
50Ø GATE VALVE PROPOSED SANITARY UTILITIES.
650
SAND 300600 50Ø CWL
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REQUIRED FLOOR AND
1500 WALL OPENING
150 mm THICK
CHB WALL
5. ALL PIPES SHALL BBE INSTALLED AS INDICATED, ANY RELOCATION REQUIRED
50Ø CWL FROM 50Ø CWL TO
MAIN WATER LINE MOTOR PUMP FOR PROPER EXECUTION OF THE OTHER TRADE SHALL BE PRIOR TO THE
Ø10mm @ 300 O.C TEMP. BARS
CEMENT PLASTER FINISH GRAVEL FILL APPROVAL OF THE ARCHITECT AND THE ENGINEER.
INSIDE AND OUTSIDE
6. ALL SLOPE FOR HORIZONTAL PIPE SHALL MAINTAIN 1% AS MINIMUM
UNLESS OTHERWISE NOTED.
150 7. ALL FIXTURE SHALL BE VENTED UNLESS OTHERWISE NOTED.
8. ALL PIPES SIZES INDICATED ARE IN MILLIMETER (MM) DIAMETER UNLESS
Ø10mm BARS 0.20 m.
400 500 500 3 - Ø12 mm MAIN BAR OTHERWISE NOTED
SPACING BOTHWAYS
MAIN WATER METER DETAIL 9. ALL UNDERGROUND G.I PIPES SHALL BE COATED WITH 2 LAYERS OF TAR OR
CARBOLINE
SCALE NTS

SECTION 10. ALL WATER PIPES SHALL BE PROVIDED WITH 0.30m PIPE EXTENSION
CAPPED AT THE END
11. ALL EXPOSED HOT WATER PIPES SHALL BE ISULATED.
PIPE RISER U-BOLT

HEX NUT WITH LOCK WASHER 3.2 X 50 X 50


ANGLE BAR PLUMBING SYMBOLS:
DETAILS OF SEPTIC TANK WELDED FD FLOOR DRAIN
SCALE NTS ST SEPTIC TANK
CB CATH BASIN
EXPANSION SHIELD
CO CLEAN OUT
KS KITCHEN SINK
WS WATER CLOSET
CHB WALL LAV LAVATORY
OR BEAM F FAUCET
SH SHOWER HEAD
CV CHECK VALVE
GV GATE VALVE
MH MAN HOLE
RISER SWAY BRACE DETAIL
SCALE NTS

CLIENT'S GOVERNMENT
CONSTRUCTION
APPROVAL APPROVAL

P-4