Sunteți pe pagina 1din 24

NON-CYCLING REFRIGERATED DRYER

200-800 SCFM
MODELS D340IN, D420IN, D510IN, D680IN, D850IN,
D1020IN, D1190IN, D1360IN
OPERATORS MANUAL

Ensure that the operator reads and understands the decals


and consults the manuals before maintenance or operation.

Ensure that the Operation and Maintenance manual is not


removed permanently from the machine.

Ensure that maintenance personnel are adequately trained,


competent and have read the Maintenance Manuals.

C.C.N. : 80445471
DATE : APRIL 2009
REV. : A
1.0 contents
contents page contents page

1.0 contents 2 8.0 INSTALLATION AND INITIAL


2.0 INTRODUCTION 3 START-UP 11
3.0 WARRANTY 3 8.1 LOCATION AND MOUNTING 11
4.0 REFRIGERATED DRYER 8.2 PIPING AND VALVES 11
NOMENCLATURE 3 8.3 FILTRATION 11
5.0 RECEIVING AND INSPECTION 4 8.4 ELECTRICAL CONNECTION 12
5.1 INSPECTION 4 8.5 INITIAL START-UP 12
5.2 UNPACKING AND HANDLING 4 8.5.1 START- UP SEQUENCE 12
6.0 SAFETY AND OPERATION 8.5.2 START-UP OBSERVATIONS 12
PRECAUTIONS 4 9.0 SCHEDULED MAINTENANCE 12
OSHA Heading Descriptions 4 9.1 INTRODUCTION 12
6.0 SAFETY AND OPERATION 9.2 REFRIGERANT CONDENSER 12
PRECAUTIONS 5
9.3 CONDENSATE DISCHARGE SYSTEM 12
7.0 PRINCIPLES OF OPERATION 6
9.3.1 CLEANING INSTRUCTIONS -
7.1 INTRODUCTION 6 SOLENOID DRAIN 13
7.2 AIR SYSTEM 6 9.4 PANEL FILTER ELEMENT 13
7.3 MOISTURE REMOVAL SYSTEM 6 10.0 TROUBLESHOOTING 14
7.4 REFRIGERATION SYSTEM 6 10.1 INTRODUCTION 14
7.5 CONTROLS 8 10.2 PROBLEM / ACTION GUIDE 14
7.5.1 BASIC USER INTERFACE 8 11.0 WIRING DIAGRAM 16
BUTTONS 8 13.0 REPLACEMENT PARTS 22
LIGHTS 9 MISCELLANEOUS PARTS 22
7.5.2 HIGH TEMPERATURE ALARM 9 AIR COOLED PARTS 23
7.5.3 ADJUSTING SET POINTS 9 COMPRESSORS 23
7.5.4 ALARMS AND THEIR FUNCTIONS 10 14.0 ENGINEERING SPECIFICATIONS 23
7.5.5 ALERT MESSAGES 10 AIR COOLED CONDENSERS 23
7.5.6 START MODES 10
7.5.6.1 Manual Mode 10
7.5.6.2 Auto Restart 10

 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
2.0 INTRODUCTION
Ingersoll Rand refrigerated air dryer removes moisture, oil temperature the air is cooled to, normally between 34° and
vapor, and other contaminants from compressed air. These 38°F (1° and 3°C), is known as dew point. This dryer can be
contaminants are detrimental to pneumatically operated easily installed into various pneumatic systems in which
appliances, controls, instruments, machinery and tools. dry air is required or desired. Please refer to Principles of
This removal is accomplished by cooling the air with a Operation for complete operating details.
refrigeration unit to a temperature at which moisture in
the air is condensed and separated from the air stream. The

3.0 WARRANTY
The Company warrants that the equipment manufactured by THE COMPANY MAKES NO OTHER WARRANTY OR
it and delivered hereunder will be free of defects in material REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED
and workmanship for a period of twelve months from the OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED
date of placing the Equipment in operation or eighteen WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
months from the date of shipment from the factory, PARTICULAR PURPOSE, ARE HERBY DISCLAIMED.
whichever shall first occur. The Purchaser shall be obligated
Correction by the Company of nonconformities whether
to promptly report any failure to conform to this warranty,
patent or latent, in the manner and for the period of time
in writing to the Company in said period, whereupon the
provided above, shall constitute fulfillment of all liabilities of
Company shall, at its option, correct such nonconformity, by
the Company for such nonconformities whether based on
suitable repair to such equipment or, furnish a replacement
contract, warranty negligence, indemnity, strict liability or
part F.O.B. point of shipment, provided the Purchaser has
otherwise with respect to or arising out of such Equipment.
stored, installed, maintained and operated such Equipment
in accordance with good industry practices and has The Purchaser shall not operate Equipment which is
complied with specific recommendations of the Company. considered to be defective, without first notifying the
Accessories or equipment furnished by the Company, but Company in writing of its intention to do so. Any such use of
manufactured by others, shall carry whatever warranty the Equipment will be at Purchaser’s sole risk and liability.
manufacturers have conveyed to the Company and which Note that this is Ingersoll Rand standard warranty. Any war-
can be passed on to the Purchaser. The Company shall not ranty in force at the time of purchase of the equipment or
be liable for any repairs, replacements, or adjustments to the negotiated as part of the purchase order may take prec-
Equipment or any costs of labor performed by the Purchaser edence over this warranty.
or others without Company’s prior written approval.
The effects of corrosion, erosion and normal wear and tear
are specifically excluded. Performance warranties are limited
to those specifically stated within the Company’s proposal.
Unless responsibility for meeting such performance
warranties are limited to specified tests, the Company’s
obligation shall be to correct in the manner and for the
period of time provided above.

4.0 REFRIGERATED DRYER NOMENCLATURE


DRYER NOMINAL* INGERSOLL RAND CONDENSER POWER RATING CONVERSION CHART
FLOW (Nm³/hr) NON-CYCLING TYPE
D 340 IN A = AIR 2 = 230-1-60 0 = NEMA 1 340 Nm³/hr = 200 SCFM
420 4 = 460-3-60 420 Nm³/hr = 250 SCFM
510 5 = 230-3-60 510 Nm³/hr = 300 SCFM
680 6 = 575-3-60 680 Nm³/hr = 400 SCFM
850 D = 380-3-60 850 Nm³/hr = 500 SCFM
1020 1020 Nm³/hr = 600 SCFM
1190 1190 Nm³/hr = 700 SCFM
1360 1360 Nm³/hr = 800 SCFM
* Nominal Flows indicated are for 100°F inlet temperature, 100°F ambient temperature and 100 psig compressed air pressure

Non-cycling Refrigerated Dryer 


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
5.0 RECEIVING AND INSPECTION
5.1 INSPECTION To facilitate handling during shipment, all dryer packages
have been mounted on a base that provides for forklifting
Upon receiving your Ingersoll Rand air dryer, please inspect between two base channels. Forks should extend all the way
the unit closely. If rough handling has been detected, please through forklift channels to reduce unnecessary forces to
note it on your delivery receipt, especially if the dryer will not the dryer during moving. Slings can be used to lift the crates,
be immediately uncrated. Obtaining the delivery person’s but spreader bars must be used to prevent the slings from
signed agreement to any noted damages will facilitate any exerting a force against the sides of the crates or the dryer.
insurance claims.

5.2 UNPACKING AND HANDLING

WARNING
Under no circumstances should any person attempt
to lift heavy objects without proper lifting equipment
(i.e., crane, hoist, slings or fork truck). Lifting any unit
without proper lifting equipment, can cause serious
injury.

6.0 SAFETY AND OPERATION PRECAUTIONS


Because an air dryer is pressurized and contains rotating OSHA Heading Descriptions
parts, the same precautions should be observed as with
any piece of machinery of this type where carelessness in WARNING
operation or maintenance could be hazardous to personnel.
“Warning” is used to indicate a hazardous situation
In addition to obvious safety rules that should be followed
which has some probability of death or severe injury.
with this type of machinery, safety precautions as listed
Warning should not be considered for property
below must be observed:
damage accidents unless personal injury risk is
1. Only qualified personnel shall be permitted to adjust, present.
perform maintenance or repair this air dryer.
. Read all instructions completely before operating CAUTION
unit.
“Caution” is used to indicate a hazardous situation
3. Pull main electrical disconnect switch and disconnect
which may result in minor or moderate injury.
any separate control lines, if used, before attempting
to work or perform maintenance on the unit.
4. Do not attempt to service any part while machine is in NOTICE
an operational mode. “Notice” is used to indicate a statement of company
policy as the message relates directly or indirectly
5. Do not attempt to remove any parts without first
to the safety of personnel or protection of property.
relieving the entire air system of pressure.
Notice should not be associated directly with a hazard
6. Do not attempt to remove any part of the or hazardous situation and must not be used in place of
refrigeration system without removing and “Danger,” “Warning,” or “Caution.”
containing refrigerant in accordance with the EPA and
local regulations.
NOTICE
7. Do not operate the dryer at pressures in excess of its
rating. The user of any air dryer manufactured by Ingersoll
Rand, is hereby warned that failure to follow the
8. Do not operate the dryer without guards, shields and above Safety and Operation Precautions may result
screen in place. in personal injury or equipment damage. However,
9. Inspect unit daily to observe and correct any unsafe Ingersoll Rand does not state as fact, nor does it
operating conditions. mean to imply, that the preceding list of Safety and
Operating Precautions is all inclusive, and further, that
the observance of this list will prevent all personal
injury or equipment damage.

 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
6.0 SAFETY AND OPERATION PRECAUTIONS

ELECTRICAL CONNECTION BOX


CONTAINS HIGH VOLTAGE
• Turn Off Power And Lock Out At ALL Sources Before Opening
To Perform Service.
• Remote Alarm Contact Wiring Has Control Power From
Separate Source.

READ TECHNICAL MANUAL

ELECTRICAL CONNECTION BOX


Air Under Pressure Will Cause
Injury, Death Or Property Damage.
• All Customer Connections To Be Made At This Location.
• Do Not Exceed Pressure Rating.
• See Terminal Connection Diagrams, below.
• Relieve Press. Before Servicing.
• Be Certain To Follow All NEC, State, Local and Other Applicable
Codes During Installation.
• Do Not Modify/Repair/Rework
100-125VAC / 1 PH 200-240VAC / 1 PH 200-575VAC / 3 PH
ASME Coded Pressure Vessels 1 1 1
As Insurance Rating Affected. GRN G
2
INCOMING GRN G
2
INCOMING GRN G
2
INCOMING
FACTORY 3 LINE VOLTAGE FACTORY 3 LINE VOLTAGE FACTORY 3 LINE VOLTAGE
WIRING WHT N 100-125VAC WIRING 200-240VAC WIRING RED L1 200-575VAC
4 4 4
1PH/50-60HZ 1PH/50-60HZ 3PH/50-60HZ
BLK L1 (BY OTHERS) BLK L1 (BY OTHERS) WHT L2 (BY OTHERS)
5 5 5
READ TECHNICAL MANUAL 6
(REFER TO UNIT
NAMEPLATE FOR RED L2
6
(REFER TO UNIT
NAMEPLATE FOR BLK L3
6
(REFER TO UNIT
NAMEPLATE FOR
POWER POWER POWER
REQUIREMENTS) REQUIREMENTS) REQUIREMENTS)

Alternate three-phase wiring may be black / black / black.

Removing fuses will not disconnect


power from dryer. Always disconnect
power from ALL sources before
performing service.
READ TECHNICAL MANUAL
Air Under Pressure Will Cause
Injury, Death Or Property Damage.
• Relieve Press. Before Servicing.
• Condensate Drain Discharges
Under Pressure.
• Drain Requires Periodic
Cleaning (Service).

FAN MAY AUTOMATICALLY READ TECHNICAL MANUAL

START AT ANY TIME

This unit is charged with


refrigerant under high pressure. HIGH VOLTAGE

Non-cycling Refrigerated Dryer 


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
7.0 PRINCIPLES OF OPERATION
7.1 INTRODUCTION approximately 30 minutes, verify that when the
electric drain opens, all of the accumulated liquid is
Ingersoll Rand non-cycling dryers remove moisture, oil vapor discharged and then followed by a small burst of air.
and other contaminants from compressed air by cooling the
air temperature to 36 deg.F (2.2 deg.C). This cooling process • If a small amount of liquid and a large amount of air is
condenses the contaminants into liquid droplets which can discharged, decrease the on-time setting or increase
then be easily removed from the air. The major systems of the off-time setting. If there is all liquid and no air
the dryers that contribute to its operation are the following: has been discharged, increase the on-time setting or
Air System, Moisture Removal System, Refrigeration System decrease the off-time setting.
and the Controls System. The following paragraphs describe • The on/off-time settings will vary accordingly to
each of the systems in greater detail. seasonal conditions. During the summer when more
moisture is present in the air system, a shorter on-
7.2 AIR SYSTEM time that increases the valve opening frequency is
This system consists of the dryer components which are required. A longer off-time may be used during the
in contact with the compressed air. Referring to Figure winter months when moisture levels are lower.
1 and following the bold “AIR FLOW” path indication, hot
7.4 REFRIGERATION SYSTEM
saturated air from the air compressor enters the precooler/
reheater where the air temperature is reduced prior to The Refrigeration System consists of all the components
entering the chiller by the cool air exiting the air/moisture which handle refrigerant R-404A. This is a hermetically
separator. This precooling allows for the use of a smaller sealed closed-loop system. Referring to Figure 1 and
refrigeration system. The air then goes into the chiller following the dot-dash “REFRIGERANT FLOW” path
section where it is further cooled to the desired dew point indication, refrigerant is shown leaving the chiller evaporator
through direct heat transfer with evaporating refrigerant. section, which in the process of removing heat is changed
The air continues to the separator where the moisture is from a low pressure liquid to a low pressure gas. This
removed, thereby allowing the cool, dry air to return to the gas enters the suction side of the compressor where it is
precooler/reheater. As the air passes through the precooler/ compressed into a high pressure gas. The high pressure gas
reheater the air temperature is elevated by the warm, wet is cooled in the condenser section becoming a high pressure
inlet air. The air exiting the reheater portion of the dryer liquid. It then goes through a permanent filter-dryer that
should be approximately 15-20 deg.F lower than the inlet air ensures the refrigerant system is free of contaminants. A
temperature based on standard conditions at full rated flow. small diameter capillary tube or expansion valve meters
the refrigerant into the chiller’s evaporator. The pressure
7.3 MOISTURE REMOVAL SYSTEM is reduced upon entering the chiller evaporator where it
Liquid droplets are removed from the air stream in the removes heat from the air system. When there are low loads
separator. As the air and liquid mixture passes through the (low air flow rate or low inlet temperature), a hot gas valve
separator it spins, slows down and then changes direction. by-passes the condenser and throttling device. This valve
This causes condensate to fall out of the air stream and maintains a minimum evaporator pressure of 76 psig, which
collect in the bottom of the separator. The collected liquid is corresponds to a chiller temperature of 34 deg.F, to prevent
removed from the separator by a timed electric drain which freeze-up.
is controlled by the Controller.
The Drain Open time and Drain Closed time are accessed
by depressing the appropriate button and using the up and
down arrows to change the value. The Drain Open value is
seconds; the Drain Closed value is minutes.
• To obtain the optimum time values for operation of
the electric drain valve, set the drain closed time to
five minutes and the open time to ten seconds.
• After running the unit under full rated flow for

 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com



FAN MOTOR
AIR OUTLET AIR INLET

PRECOOLER/REHEATER

FILTER AIR COOLED


DRYER CONDENSER REFRIG
CAP
COMPRESSOR

figure 1
TUBE
SEPARATOR CHILLER

CONDENSATE
DRAIN LEGEND
AIR FL0W HOT GAS
PROCESS & INSTRUMENTATION DIAGRAM
REFRIG (R404A) FLOW BYPASS VALVE
D340IN - D680IN
CONDENSATE LINE 550140

FAN MOTOR

http://air.ingersollrand.com
AIR OUTLET AIR INLET

PRECOOLER/REHEATER
7.0 PRINCIPLES OF OPERATION

FILTER AIR COOLED


DRYER CONDENSER REFRIG
COMPRESSOR
EXPANSION

figure 1
SEPARATOR CHILLER VALVE
S

CONDENSATE
DRAIN
LEGEND
HOT GAS
AIR FL0W BYPASS VALVE
REFRIG (R404A) FLOW
PROCESS & INSTRUMENTATION DIAGRAM
D850IN - D1360IN
CONDENSATE LINE
550141

Non-cycling Refrigerated Dryer 


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
7.0 PRINCIPLES OF OPERATION
7.5 CONTROLS
Ingersoll Rand non-cycling dryers incorporate automatic
controls for proper operation. A refrigerant suction pressure
gauge is provided as standard equipment. This gauge
ADJUSTMENT
monitors the pressure of the refrigerant gas before it enters SCREW
the compressor. When the refrigeration system is running,
the suction pressure will be controlled between 76 and 85
psig.
Ingersoll Rand air-cooled models utilize a fan cycling switch
to control the condenser temperature. This switch controls
the condensing temperature by cycling the fan based on
refrigerant discharge pressure. When the unit reaches WATER REGULATING VALVE
275 psig, the fan cycling switch will run the fan until the
figure 2
discharge pressure is reduced to 195 psig.
Ingersoll Rand dryers include a Hot Gas By-Pass Valve to 7.5.1 BASIC USER INTERFACE
maintain suction pressure and temperature. This valve is The Microprocessor Control display provides the user with
necessary during low load applications to prevent freeze- the operating parameters and their corresponding values.
up in the chiller section. The normal suction pressure for The following illustration summarizes the keypad functions.
no load conditions should never drop below 72 psig. *This
setting may need adjustment to match the load/ambient
conditions encountered.
*This adjustment is not a procedure covered under warranty
as it is typically required for application-specific conditions.

CAUTION
Do not rotate Hot Gas By-Pass Valve adjustment
fully clockwise. Full clockwise rotation may result in
refrigerant compressor damage. Any suction pressure
setting above 90 psig is not recommended. BUTTONS

For Hot Gas By-Pass Valve adjustment, note the following: • ON / OFF
• Turning the adjustment screw clockwise raises suction Toggles the dryer operation between “On Line” and
“Off Line” status.
pressure and exchanger temperature.
• Turning the adjustment screw counter-clockwise • EXCH SET
When depressed, will display the current High
reduces suction pressure and exchanger temperature.
Temperature Alarm set point in the LCD window.
• All adjustments should be made without air flow While the High Temperature Alarm set point is
(load) on the dryer. displayed, the up and down arrows may be used to
For water-cooled models, a high pressure cut out switch is increase or decrease the set point temperature.
positioned near the water regulating valve. The switch is • ALARM RESET
designed to open at 320 psig and close at 270 psig. Pressing once clears the local alarm indication and
To compensate for water temperature variation, it may be de-energizes the remote alarm contact. Should the
necessary to adjust the water regulating valve to maintain alarm condition persist, the alarm will return after the
a 250 psig discharge pressure. Adjustment can be done alarm inhibit time has expired.
by rotating the adjusting screw counterclockwise for an • °F / °C
increase in discharge pressure. For conditions where low Toggles the LED temperature indicators between
water temperature and/or high water pressure are expected Fahrenheit and Celsius units of measure.
it is advisable to install a water pressure regulator ahead of
the condenser.

 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
7.0 PRINCIPLES OF OPERATION
• +/- 7.5.2 HIGH TEMPERATURE ALARM
Allows user to modify set point values. Set point
values cycle through a fixed range. The Controller allows the user to configure the dryer’s High
Temperature Alarm Setpoint.
• DRAIN OPEN
Press this button to set the length of time in seconds 7.5.3 ADJUSTING SET POINTS
that the condensate drain will be open. This is
adjustable from one (1) to sixty (60) seconds. Changing the High Temperature Alarm Setpoint is
accomplished as follows.
• DRAIN CLOSED
Press this button to set the amount of time in minutes
that the condensate drain will be closed. This is
adjustable from one (1) to sixty (60) minutes.
EXCH.
SET
46
• DRAIN TEST Pressing EXCHANGER SETPOINT button will change the
Press this button to open the drain to verify operation. display to show the current setpoint.

LIGHTS

• LCD Display 47
Displays exchanger temperature during normal
Pressing the UP or DOWN arrows modifies the EXCHANGER
operation. Also used to display high temperature set
SETPOINT in one degree increment.
point, alarm condition and timing functions.
• SYSTEM ENERGIZED
Indicates when power is applied to unit. 48
• DRYER ON
Illuminated when the On/Off switch has been pressed Pressing the UP or DOWN arrows modifies the EXCHANGER
to place the unit in operation. SETPOINT in one degree increment.

• REFRIGERATION COMPRESSOR ON
Indicates that the refrigeration system is operating.
• DEGREES F / DEGREES C
48
Indicates the temperature units of measure. The Controller accepts the last setpoint. After 5 seconds,
the readout will return to displaying the current Exchanger
• HIGH TEMP ALARM Temperature.
Indicates that the exchanger temperature has risen
above the High Temperature Alarm set point.
• LOW TEMP ALARM
When activated, indicates that the exchanger
temperature has dropped below 29°F or -2°C. This
condition stops the compressor. The compressor
will not restart until the temperature has risen two
degrees above exchanger set point.
• DRAIN OPEN
This light comes on when power is applied to open
the time solenoid drain.

Non-cycling Refrigerated Dryer 


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
7.0 PRINCIPLES OF OPERATION
7.5.4 ALARMS AND THEIR FUNCTIONS 7.5.5 ALERT MESSAGES

The Controller indicates critical alarms to alert the user of The Controller features the following readouts to
an out of tolerance condition. Once each alarm condition is communicate the status of the dryer’s operation.
detected, the appropriate LED indicator will illuminate and
Indicates a probe failure. This condi-
the remote alarm contact will close.
tion is usually caused by a probe be-
Alarm Display Alarm Set ing unplugged, damage to the probe
Point lead or a defective probe.
HIGH TEMPERATURE HI TEMP User Adjustable Indicates that the refrigerant com-
ALARM ALARM pressor will not start until the end of a
LOW TEMPERATURE LOW TEMP 28 °F three minute safety delay. The display
ALARM ALARM of “cd” is immediately followed by the
number of minutes left in the delay.
The alarm names and a brief description of each are This is a normal function of the con-
described in detail below. troller and not a fault indication.
HIGH TEMPERATURE ALARM (HITEMP ALARM)
7.5.6 START MODES
When the exchanger temperature reaches the alarm set
point, the alarm will be activated. This alarm condition may The noncycling dryers are capable of starting in one of the
not necessarily damage the dryer when subjected to long- following start modes:
term exposure. It may, however, have a significant impact
on downstream processes and thus should be investigated 7.5.6.1 Manual Mode
upon detection. Note that this alarm will not shut down the
dryer. This alarm will activate the remote alarm contact and After power is supplied to the dryer, the LCD display
reset automatically once the alarm condition is rectified. will indicate the exchanger temperature as well as the
time remaining for the safety delay. Once the delay has
LOW TEMPERATURE SAFETY ALARM (LOWTEMP ALARM) timed out, depressing the On/Off button will activate the
If the dryer temperature falls below the factory set point, refrigeration system.
the alarm routine will activate. This alarm condition may
cause damage to the dryer when subjected to continuous or 7.5.6.2 Auto Restart
long-term exposure. Note that this alarm will shut down the
Should the dryer lose power while in the “On” mode, the
dryer after a response time delay. This alarm will activate the
dryer will revert to the “On” mode once power is restored.
remote alarm contact and reset automatically once the alarm
Similarly, should power be removed from the dryer while
condition is rectified.
the dryer is in the “Off” mode, the dryer will remain in the
“Off” mode once power is restored until the On/Off switch is
depressed or the remote switch is closed.

10 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
8.0 INSTALLATION AND INITIAL START-UP
8.1 LOCATION AND MOUNTING 8.2 PIPING AND VALVES
The dryer should not be located in an area where ambient Install piping, fittings and accessories as required for specific
temperature is likely to exceed 113°F (45°C) or be less site conditions and requirements. Figure 3 indicates a typical
than 50°F (10°C). The dryer must be located in an area piping arrangement for a refrigerated dryer, including dryer
that provides sufficient clearance from walls and other and filter bypasses. This figure can be used as a guide for
adjoining equipment to allow easy access for servicing valve and accessory placement in the system.
and maintenance requirements. A minimum of 18 inches is
Ingersoll Rand dryers come factory installed with a drain
required to allow free flow of air to the condenser inlet.
isolation valve (D). The isolation valve permits maintenance
On installations with a relatively steady flow rate, the dryer of the automatic drain without isolating air flow to the dryer.
is normally connected after the air receiver. If loads fluctuate To operate dryer, all valves shown in Figure 3 are to be closed
widely, the dryer should be positioned ahead of the receiver except valves (B), (C) and (D). Valve (A) is used for bypass
and sufficient storage capacity downstream is necessary to purposes and valve (E) is for test and manual drain purposes.
prevent excessive air flow through the dryer.
8.3 FILTRATION
When installed after any compressor that causes significant
vibration or air pulsation, such as reciprocating compressors, To protect the air dryer from gross contamination associated
proper vibration isolation and pulsation dampening devices with compressor oil and debris and ensure maximum dryer
should be added to protect the dryer. performance, a pre-filter is recommended. Pre-filters and
post-filters sized to your drying application can be provided
NOTICE by Ingersoll Rand and are available factory installed. Call
Failure to comply to the above instructions may result your local distributor to select the filter that best suits
in equipment malfunction and will void warranty. your filtration requirements. In addition to air filtration,
condensate discharge oil/water separators are also available
NOTICE to address stringent EPA regulations.
Always use a backup wrench when making any
threaded connection to the dryer. Failure to use a
backup wrench may result in damaged tubing and
components internal to the cabinet.

AIR
DRYER
B C
AIR IN AIR OUT
PRE-FILTER
PREFILTER

E D

DRAIN DRAIN OIL


VALVE VALVE SEPARATOR

CHECK CHECK CHECK CHECK


VALVE VALVE VALVE VALVE

UNIT AS DELIVERED
OPTIONAL ACCESSORY ITEMS
NOTE: DRAIN TUBE MUST NOT RISE OR BE CONNECTED TO
EXCESSIVELY LONG PIPE WHICH MAY CREATE BACK PRESSURE
A CONNECTION TO OPEN FLOOR DRAIN IS REQUIRED

FIGURE 3 - TYPICAL PIPING ARRANGEMENT

Non-cycling Refrigerated Dryer 11


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
8.0 INSTALLATION AND INITIAL START-UP
8.4 ELECTRICAL CONNECTION • Start Dryer, using one of the following methods,
depending on Start Mode setting:
Equipment is available in various electrical configurations.
All customer connections can be made at the terminal Manual Mode - Press the ON pushbutton.
connections located in the customer electrical connection Auto Restart Mode - No additional action required
box on the rear of the dryer. (Refer to General Arrangement
and appropriate Wiring Diagrams.) 8.5.2 START-UP OBSERVATIONS
A suitable fused disconnect switch or circuit breaker, in The following conditions should be observed during start-
accordance with national and local code requirements, is up:
recommended for all Ingersoll Rand equipment. Refer to
Section 13 for voltage requirements and load. • The suction pressure gauge will typically pull down to
between 76 and 85 psig. The Hot Gas By-Pass Valve
CAUTION may require adjustment at start-up. Refer to Section
7.5 for details.
Never wire directly or connect any additional wires to
the compressor junction box. This will cause severe • The refrigerant discharge pressure will vary with
system malfunction. ambient temperature.
• The “Power On” light will illuminate.
8.5 INITIAL START-UP
• The “High Temp” alarm will illuminate. The thermostat
notice for this alarm samples the chilled compressed air.
Shortly after flow has been introduced, the “High
For water cooled models, the water valve must be Temp” light will go out.
manually opened to ensure that the condenser is full
of water prior to start-up. • After a sufficient amount of time, air flow may be
slowly introduced to the dryer.
8.5.1 START- UP SEQUENCE • Set and adjust timed drain operation as described in
• Apply power to dryer. LCD Panel will illuminate. The Section 7.5.1.
Anti-Short Cycle delay will commence counting down.

notice
After installation or a prolonged shutdown, start the
dryer with no air load (no air flow). This enables the
dryer to reach its proper operating temperature in the
shortest time possible (typically within 30 minutes).

9.0 SCHEDULED MAINTENANCE

9.1 INTRODUCTION this option, it is imperative that this filter be inspected and
cleaned on a regular basis. Annual replacement of the filter
Ingersoll Rand noncycling refrigerated air dryers require is recommended. For applications where excessive dirt, dust
little maintenance. These dryers utilize hermetically sealed or debris is encountered, more frequent inspection and
compressors which do not require any lubrication. Fan cleaning may be required.
motors require lubrication at both oil ports every six months.
The condensate drain requires annual replacement of 9.3 CONDENSATE DISCHARGE SYSTEM
the service unit. Ingersoll Rand recommends component
inspection and service at regular intervals to obtain On a minimum of a monthly basis, the operation of the
maximum performance from your dryer. drain should be checked. Periodically, the drain should be
removed and cleaned to ensure no debris from the system
9.2 REFRIGERANT CONDENSER is trapped inside. Ingersoll Rand non-cycling dryers are
equipped with a drain isolation valve, enabling the valves to
For standard dryers, regular inspection and cleaning of the be cleaned during dryer operation after the drain isolation
condenser is recommended. Ingersoll Rand dryers may valve has been manually closed. The drain valve is located
be equipped with an optional ambient air filter designed near the solenoid valve and requires a quarter turn to isolate
to protect the condenser from dirt and debris that can the drain from system pressure.
accumulate on the condenser. For proper operation with

12 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
9.0 SCHEDULED MAINTENANCE
9.3.1 CLEANING INSTRUCTIONS - SOLENOID DRAIN Be especially careful to clean the center brass orifice
and the rubber gasket orifice on the orifice cup with a
• Be sure dryer is depressurized or isolation valve is straight pin.
closed.
• Reassemble all drain components after the drain has
• Disconnect drain body from filter stop. been cleaned and inspected. Reposition the orifice
• Loosen connector screw to allow the electrical hole on the rubber gasket of the orifice cup in the line
connector assembly to be removed from the D.I.N. and closest to the arrow indicated on the valve body.
unit solenoid. • Reassemble valve and install in reverse order as
• Remove retainer nut and separate the valve body described above.
from the D.I.N. unit solenoid.
9.4 PANEL FILTER ELEMENT
• Unthread the plunger tube assembly in a counter-
clockwise direction until plunger separates from valve Annual replacement of the panel filter element is
body. recommended. To replace the panel filter element, remove
the panel filter by pulling up and out of its slots, then fit the
• Clean beveled washer, thread gasket, spring assembly new element in.
and strainer with soap and water. Do NOT use
solvents of any kind, as failure to the seals will occur.

RETAINER NUT PROFILE GASKET


SPRING WASHER
ELECTRICAL CONNECTOR
WASHER

SCREW

D.I.N UNIT SOLENOID

APPLIANCE SOCKET

SEAL

WASHER

PLUNGER TUBE ASSY.


CABLE GLAND

THREADED FLANGE
GASKET
PLUNGER W/ SPRING
ASSEMBLY

ORIFICE CUP
BEVELLED WASHER
STRAINER
BODY

Solenoid Valve Detail

Non-cycling Refrigerated Dryer 13


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
10.0 TROUBLESHOOTING

10.1 INTRODUCTION
Ingersoll Rand dryers are designed for reliable, trouble-free operation. In the event of any dryer malfunction, the guide below
has been developed to facilitate problem identification and corrective actions.

WARNING WARNING
An air dryer always operates under pressure. Any Prior to working on the unit, make sure that all circuit
maintenance procedure that involves disassembly of breakers or disconnected switches are tagged “Out of
pipe fittings, valves or any other components requires Service.”
the dryer be isolated from the compressed air stream
and fully depressurized.

10.2 PROBLEM / ACTION GUIDE

PROBLEM SYMPTOM(S) POSSIBLE CAUSE CORRECTIVE ACTION


Moisture down stream Dryer is properly cooling Condensate drain failure Replace Drain
air stream (Check Chiller. Excessive flow Check inlet and outlet pressure and
Temp on controller) system design capacity. Correct cause
of excessive flow.
Dryer by-pass valve not Close by-pass valve
closed
Inlet and outlet No power to the dryer Check power supply and fuses/circuit
temperatures are the breakers
same. High suction pressure Check and clean condenser.
Refrigerant leak Check suction pressure gauge if
reading is 0 psig, turn dryer off and
contact your distributor
Compressor not running and Check and clean condenser.
fan is running Check ambient temperature and
reduce below 113°F
Moisture down stream Inlet and outlet Compressor and fan not Check Exchanger Temperature
temperatures are the running. Check MAIN CONTROL fuse.
same.
Compressor and fan not Compressor relay may be bad, replace
running. Controller indicates relay
compressor is ON. Check for loose wire connections at
contactor or loss of power at control
board
Defective control board - replace as
necessary
Contact your local distributor for
further assistance.

14 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
10.0 TROUBLESHOOTING

PROBLEM SYMPTOM(S) POSSIBLE CAUSE CORRECTIVE ACTION


Apparent controller Display Blank Blown Fuse Check Fuses
display malfunction Board Failure Contact your local distributor for
further assistance.
Unrealistic temperature Probe loose, off connection Inspect probe cable and terminal
displayed or defective probe connection Replace probe
Erratic or inaccurate Probe not completely in Inspect probe and check readings
temperature readings thermal well against independent source (eg.
temperature analyzer/pyrometer/ice
bath) both in temperature well and to
ambient
Defective probe Replace probe
High pressure drop Outlet pressure Inlet and outlet valves not Open valves
across dryer substantially lower than completely open
inlet pressure System Inlet and outlet filters Change filter elements
operating temperature is blocked up
above 32°F
Outlet pressure Compressor relay / contactor Replace relay / contactor.
substantially lower than stuck.
inlet pressure System Microprocessor Control relay Replace relay
operating temperature is bad
below 32°F
Probe not completely in Inspect probe and check readings
thermal well against independent source (eg.
temperature analyzer/pyrometer/ice
bath) both in exchanger well and to
ambient
Problem persists Turn dryer off and consult your local
distributor for further assistance
Condensate drain does Inlet / outlet pipe internal Replace with larger diameter piping.
not fire diameter too small causing
air-lock or back pressure.
Excessive use of bends / Reduce the amount of bends and
elbows in inlet / outlet pipe elbows.
work causing air-lock/ back
pressure.
Outlet pipe too long / too Reconfigure condensate piping.
high causing back pressure.
More than one condensate Reroute condensate to eliminate
source connected providing secondary path. Install check valves as
alternative path for required.
condensate.

Non-cycling Refrigerated Dryer 15


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
11.0 WIRING DIAGRAM

16 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
11.0 WIRING DIAGRAM

D850IN-D1020IN W/COMPUSTAT
208, 230, 460 & 575V/3/60
WIRING DIAGRAM

550136

Non-cycling Refrigerated Dryer 17


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
11.0 WIRING DIAGRAM

D1190IN-D1360IN W/COMPUSTAT
208, 230, 460 & 575V/3/60
WIRING DIAGRAM

550137

18 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
11.0 WIRING DIAGRAM

D340INA AIRCOOLED
230/1/60, 220/1/50
WIRING DIAGRAM

550152

Non-cycling Refrigerated Dryer 19


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com


20
CONDENSER AIR
DISCHARGE

CONDENSER AIIR
CONDENSER AIR
DISCHARGE MICROPROCESSOR CONTROL SUCTION PRESSURE GAUGE
INLET (SEE TECHNICAL MANUAL FOR
OPERATION DETAILS)
32.62

30.375

25.00

CONTROL PANEL

23.38
TOP VIEW

AIR INLET CONNECTION AIR OUTLET CONNECTION


1) 1 1/2" MPT FOR D340IN & D420IN MODELS 1) 1 1/2" MPT FOR D340IN & D420IN MODELS
2) 2" FOR D510IN & D680IN MODELS 2) 2" FOR D510IN & D680IN MODELS

CUSTOMER ELECTRICAL 28.09


CONNECTIONS ACCESS ADJUDTABLE HOT GAS
2.38 BYPASS VALVE

http://air.ingersollrand.com
CONDENSER AIR
INLET
PANEL FILTER LOCATION
12.0 GENERAL ARRANGEMENT

40.25 (NOT SHOWN)

33.75
CONDENSATE DRAIN

LEFT SIDE VIEW FRONT VIEW STANDARD DRAIN OUTLET


1/4'' O.D. NYLON TUBE

MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN


RIGHT SIDE VIEW

GENERAL ARRANGEMENT
D340IN-D680IN
550131

Non-cycling Refrigerated Dryer





39.25
1.00
37.25

1.12

13.00

37.00
16.00 40.250

O .50 MTG HOLES


(4 PLCS) TOP VIEW

SUCTION PRESSURE GAUGE


MICROPROCESSOR CONTROL
3" MPT AIR OUTLET 3" MPT AIR INLET (SEE TECHNICAL MANUAL FOR
CONNECTION CONNECTION 5.00 35.63 OPERATION DETAILS)

HOT GAS BYPASS


VALVE
CONDENSER AIR CONDENSER AIR
CONDENSER AIR
DISCHARGE INLET
DISCHARGE

http://air.ingersollrand.com
CUSTOMER ELECTRICAL 61.50
CONNECTION BOX
12.0 GENERAL ARRANGEMENT

35.75

39.00
REAR VIEW 1/4" O.D. NYLON LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW
DRAIN TUBE

GENERAL ARRANGMENT
D850IN-D1360IN
550132

Non-cycling Refrigerated Dryer 21


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
13.0 REPLACEMENT PARTS
MISCELLANEOUS PARTS

Models D340IN - D680IN


QTY SPARES
CCN DESCRIPTION
/UNIT 1 2 3
38052197 BOARD, CONTROL 1 1 1 1
38052718 CONTACTOR, COMPRESSOR 1 1 1 1
23391071 DRAIN, SOLENOID VALVE 1
23141278 DRAIN, SERVICE UNIT 1
38052916 DRYER, REFRIGERANT FILTER 1
23141690 GAUGE, PRESSURE 1
38446753 PANEL FILTER ELEMENT 1
38052874 FUSE, TRANSFORMER PRIMARY 2 2 2 4
23391089 FUSE, TRANSFORMER SECONDARY (EXCEPT D340IN, 230/1/60) 1 1 1 2
23390842 OVERLAY, CONTROL BOARD 1
38052908 PROBE, EXCHANGER TEMPERATURE 1 1 1 1
38052221 SWITCH, FAN CYCLING 1
38052189 TRANSFORMER, CONTROL - 0.075 KVA (EXCEPT D340IN, 230/1/60) 1
23390925 VALVE, HOT GAS - D340IN, D420IN, D510IN 1
23390933 VALVE, HOT GAS - D680IN 1

Models D850IN - D1360IN


QTY SPARES
CCN DESCRIPTION
/UNIT 1 2 3
38052197 BOARD, CONTROL 1 1 1 1
38052718 CONTACTOR, COMPRESSOR 1 1 1 1
38052858 CONTACTOR, CONDENSER FAN (D1190IN; D1360IN) 1 1 1 1
23391071 DRAIN, SOLENOID VALVE 1
23141278 DRAIN, SERVICE UNIT 1
38052015 DRYER, REFRIGERANT FILTER 1
23391097 GAUGE, PRESSURE - 2 1/2 INCH 1
38052437 PANEL FILTER ELEMENT 1
38052874 FUSE, TRANSFORMER PRIMARY 2 2 2 4
23391089 FUSE, TRANSFORMER SECONDARY 1 1 1 2
23390842 OVERLAY, CONTROL BOARD 1
38052908 PROBE, EXCHANGER TEMPERATURE 1 1 1 1
38052221 SWITCH, FAN CYCLING 1
38052171 SWITCH, LOW REFRIGERANT PRESSURE 1
38052189 TRANSFORMER, CONTROL - 0.075 KVA 1
23391063 VALVE, HOT GAS - D850IN, D1020IN 1
23390941 VALVE, HOT GAS - D1190IN, D1360IN 1
38052452 VALVE, REFRIGERANT EXPANSION 1

22 Non-cycling Refrigerated Dryer


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
13.0 REPLACEMENT PARTS
AIR COOLED PARTS COMPRESSORS

FAN MOTORS IN
IN 230/1/60 230/3/60 460/3/60 575/3/60
CONDENSERS NEMA 1 NEMA 1 MODEL
MODEL
230V 460V D340IN 23141104 23390867 23390859 23390859
D340IN 38053104 38053229 38446498 D420IN - 23390867 23390859 23390859
D420IN 38053104 38053229 38446498 D510IN - 23340875 23390883 23390883
D510IN 38052700 38053229 38446498
D680IN - 23390909 38052288 38052288
D680IN 38052700 38053229 38446498
D850IN - - 38052288 38052288
D850IN 38052460 - 38052734
D1020IN - - 23390917 23390917
D1020IN 38052460 - 38052734
D1190IN 38052460 - 38052734 D1190IN - - 38446480 38446480
D1360IN 38052460 - 38052734 D1360IN - - 38052296 38052296

14.0 ENGINEERING SPECIFICATIONS

AIR COOLED CONDENSERS

MAX. MIN. COMPRESSOR


WEIGHT R-404A FAN RATINGS
MODEL VOLTS/ FUSE CIRCUIT RATINGS
NO. PH/HZ LB-
LBS. KG. KG. SIZE AMPACITY HP RLA LRA QTY HP RLA LRA
OZ
D340IN 230/1/60 325 147 3-0 1.36 20 11.8 1 8.4 34 1 1/6 1 3
D340IN 460/3/60 325 147 3-0 1.36 6 3.7 1 2.5 10 1 1/6 0.5 1.2
D340IN 230/3/60 325 147 3-0 1.36 12 7.3 1 4.8 25 1 1/6 1 3
D340IN 575/3/60 325 147 3-0 1.36 5 3 1 2.5 10 1 1/6 0.5 1.2
D420IN 460/3/60 340 154 3-8 1.59 6 3.7 11/2 2.5 10 1 1/6 0.5 1.2
D420IN 230/3/60 340 154 3-8 1.59 12 7.3 11/2 4.8 25 1 1/6 1 3
D420IN 575/3/60 340 154 3-8 1.59 5 3 11/2 2.5 10 1 1/6 0.5 1.2
D510IN 460/3/60 375 170 4-0 1.81 8 5.1 11/2 3.6 16 1 1/6 0.5 1.2
D510IN 230/3/60 375 170 4-0 1.81 12 8.8 11/2 6 38 1 1/6 1 3
D510IN 575/3/60 375 170 4-0 1.81 7 4.1 11/2 3.6 16 1 1/6 0.5 1.2
D680IN 460/3/60 375 170 4-0 1.81 12 7.4 21/2 5.4 23 1 1/6 0.5 1.2
D680IN 230/3/60 375 170 4-0 1.81 25 15.5 21/2 11.4 57 1 1/6 1 3
D680IN 575/3/60 375 170 4-0 1.81 10 5.9 21/2 5.4 23 1 1/6 0.5 1.2
D850IN 460/3/60 950 432 7-8 3.40 12 7.7 21/2 5.4 23 1 1/4 0.8 1.2
D850IN 230/3/60 950 432 7-8 3.40 25 16.4 21/2 11.4 57 1 1/4 1.9 3.9
D850IN 575/3/60 950 432 7-8 3.40 10 6.1 21/2 5.4 23 1 1/4 0.8 1.2
D1020IN 460/3/60 950 432 8-0 3.63 15 8.9 3 6.4 30 1 1/4 0.8 1.2
D1020IN 230/3/60 950 432 8-0 3.63 25 17.3 3 12.1 74 1 1/4 1.9 3.9
D1020IN 575/3/60 950 432 8-0 3.63 12 7.1 3 6.4 30 1 1/4 0.8 1.2
D1190IN 460/3/60 1050 477 6-8 2.95 15 10.6 31/2 7.1 38 2 1/4 0.8 1.2
D1190IN 230/3/60 1050 477 6-8 2.95 35 23.7 31/2 15.7 98 2 1/4 1.9 3.9
D1190IN 575/3/60 1050 477 6-8 2.95 12 8.5 31/2 7.1 38 2 1/4 0.8 1.2
D1360IN 460/3/60 1050 477 8-0 3.63 15 10.2 4 6.8 42 2 1/4 0.8 1.2
D1360IN 230/3/60 1050 477 8-0 3.63 35 23.7 4 15.7 100 2 1/4 1.9 3.9
D1360IN 575/3/60 1050 477 8-0 3.63 12 8.4 4 6.8 42 2 1/4 0.8 1.2
NOTE: Maximum allowable operating pressure 300 psig.

Non-cycling Refrigerated Dryer 23


MODELS D340IN, D420IN, D510IN, D680IN, D850IN, D1020IN, D1190IN, D1360IN
http://air.ingersollrand.com
LOOK WHAT INGERSOLL RAND CAN DO FOR YOU!

Efficient Field Service


We maintain a highly trained staff of technicians
to service your equipment for preventive
maintenance, or to assist you should emergencies
ever occur.
Complete Repair Service
Our trained technicians will repair or overhaul
your equipment to factory specifications,
using only genuine Ingersoll Rand parts.

Special Engineering Service


We can help you identify and solve your problems
by evaluating your needs and recommending
theproper equipment to give your maximum
efficiency.
Spare Parts
By stocking genuine Ingersoll Rand spare
parts, we can help you avoid costly delays
or substituting inferior parts. Using genuine
Ingersoll Rand parts on you Ingersoll
Rand equipment will help to keep even
older equipment running in good-as-new
Complete Stock of Equipment condition.
We carry a complete line of Ingersoll Rand
equipment and accessories designed to meet
any compressed air application. We are backed
by Ingersoll Rand’s prompt factory shipment to
ensure you on-time delivery.

A SUBSTITUTE IS NOT A REPLACEMENT!


Ensure you get peak performance and longevity out of your Ingersoll Rand product by insisting on genuine Ingersoll
Rand replacement parts and maintenance kits. Not only are the replacement parts made to precise dimensions and OEM-
specified metallurgy, but each part is backed by the Ingersoll Rand warranty. Your local Customer Center, Distributor, or
direct Ingersoll Rand salesperson will work with your to ensure you get the parts you need to do the job right. Equip your
machines with only the best Ingersoll Rand genuine parts.

NOTE: THE USE OF REPAIR PARTS OTHER THAN THOSE INCLUDED WITHIN THE INGERSOLL RAND COMPANY
APPROVED PARTS LIST MAY CREATE UNSAFE CONDITIONS OR MECHANICAL FAILURES OVER WHICH INGERSOLL
RAND COMPANY HAS NO CONTROL. INGERSOLL RAND COMPANY SHALL BEAR NO RESPONSIBILITY FOR
EQUIPMENT ON WHICH NON-APPROVED REPAIR PARTS ARE INSTALLED.

The manufacturer reserves the right to make changes or add improvements without notice and without incurring any
obligation to make such changes to products previously sold.

S-ar putea să vă placă și