CKR-93T (144x144mm)
Pcs / Carton
Product Code
CKR-93T 3 Phase + Earth (Adjustable Inverse and Fixed Times for Phase & Earth) 85-265 VAC / DC 4
CKR-92T 2 Phase + Earth (Adjustable Inverse and Fixed Times for Phase & Earth) 85-265 VAC / DC 4
SPECIFICATIONS
Correct protection for inverse time overcurrent
relays can be achieved under the following conditions: CKR-92T CKR-93T
1) Relays with same operation characteristics ENCLOSURE
Dimensions 144x144mm PR17
must be connected in series.
Weight 1,3kg/pcs
2) OFF-delay of the relays used in the system Three-phase protection
must be set as "Current/time steps". Earth fault protection
MEASUREMENTS
Current-based start-up delay of the relays must be
Operating Current 1A earth, 5A phase
set so that the “current/time steps” will decrease as Accuracy Current In or Iset 5%; Time 7,5% or ±40ms
they move away from the supply. By this manner, the Burden <3VA
Overcurrent pick-up 0.2 - 3.35 x In 0.25
relay at the end of the line (R4 in the following figure) Overcurrent instant 2-17xI,step 1
should have the shortest OFF-delay time. Definite Time 2.5,5,15 sec 0.1-1 step 0.1
This situation can be observed from diagrams According IEC255, ANSI (normal, very, extremely,
Inverse Time longtime, moderately)CKR-9XT series don't have
and current-time characteristics given below: moderately inverse time.
SUPPLY
Operating Voltage 24VDC,
85-265VAC/DC±10%
Operating Frequency 50/60 Hz
Current - Time Characteristics
Power Consumption <2VA
I1 = (t) I2 = (t) I3 = (t) I4 = (t) t (sn.) INPUT / OUTPUT
R1 R2 R3 R4
Output Contact 1NO for phase;
~ I1 (t)-R1
I2 (t)-R2
I3 (t)-R3
1NO for neutral;
10A/1400VA
Power I4 (t) < I3 (t) < I2 (t) < I1 (t)
Energy flow I4 (t)-R4
Source direction AMBIENT CONDITIONS
1 10 20 IA / I Ambient Temperature -5 / +550C
CONNECTIONS
Mounting Front mounting with rear terminals
A. CKR series have the following I/t characteristics. Connection Types 2 phase + netural ;
According to IEC-255, BS-142 these are: 3 phase + neutral (for current input)
a - Normal Inverse
b - Very Inverse
c - Extreme Inverse
d - Long Time Inverse (CKR-93T)
Protection & Control
96
Print Date: 03.2014
Overcurrent Protection Relays
CKR Series
Connection Diagram
L3 L2 L1 7 IE 1
8 L3
2
9
10 L2 IL 3
4
11
12 L1
K k K k K k 13
+ 5
ECU
14 +
15 E
L l L l L l 6
Ko
Auxiliary device
ER-3Y
Ao
L3 L2 L1 7 IE 1
8
2
9
10 L2 IL 3
11 4
12 L1
K k K k K k 13
+ 5
ECU
14 +
15 E
L l L l L l 6
Ko
Auxiliary device
ER-3Y
Ao
Dimensions
122
103
140
140
140 105
TYPE PR 17
Connection diagrams are given for reference. Please always check the latest user manual given with product or download from www.entes.com.tr
97