Heron Tower
London
Multi-stage Multi-outlet Firepumps
Heron Tower, London
Zone 1
Multi-stage Multi-outlet Firepumps
Heron Tower, London
So using EN12845, the pump duty for Zone 1 is:-
Zone 4
• Zone 3 Nom 3100 l/min @ 11.3 Bar
NLT 1350 l/min @ 14.7 Bar
NLT 1100 l/min @ 15.0 Bar
Zone 3
• Zone 4 Nom 3100 l/min @ 15.5 Bar
NLT
NLT
1350 l/min @ 18.9 Bar
1100 l/min @ 19.2 Bar
Zone 2
Zone 5
Zone 4
Zone 1
Flow
1000 l/min 2000 l/min 3000 l/min
Multi-stage Multi-outlet Firepumps
Why use SPP’s multi-stage multi-outlet firepumps:-
• Pumps performance verified by independent approval authorities
• Pumps manufactured in accordance with strict engineering standards
• Pumps as standard can be use on buildings of up to 300 m tall
• Reduced pump room space requirement
• Reduced overall power supply requirement
• Avoids over pressurisation of sprinkler heads
• No need to use pressure reducing valves through out the system
• Pumps fully factory performance tested before despatch
• Reduces overall cost for fire protection system