Calculation Table # 1

Sensible Heat Gain for Exposed Roof


qsr = Ur x Ar x CLTDrc - Eqn. 1

Area of Area of U-Factor CLTDrc qsr


Area Covered
Roof (m²) Roof (ft²) (Btu/hr-ft²-°F) (°F) (Btu/hr)

Assembly Area 1280 13,779.15 0.13 96 171,963.79


Rectifier Room 1 125 1,345.62 0.13 96 16,793.34
Rectifier Room 2 120 1,291.80 0.13 96 16,121.61
Formation Area 1 578 6,222.15 0.13 96 77,652.40
Formation Area 2 578 6,222.15 0.13 96 77,652.40
Green Group Area 900 9,688.46 0.13 96 120,912.04

Total Sensible Heat Gain due to Roof (qsr) 481,095.58