Sunteți pe pagina 1din 2

Calculation Table # 4

Solar Heat Gain for Glass


qsg = Asg x SCsg x SHGFsg x CLFsg - Eqn. 8

Window Size Window Shading


Room Window
Area Covered LxW Area Coefficient
Quantity Facing
(m²) (ft²) (SC)

20 1 1 215 SW 0.22
Assembly Area
20 1 1 215 NE 0.22
Rectifier Room 1 - - - - - -
Rectifier Room 2 - - - - - -
Formation Room 1 15 1 1 161 SW 0.22
Formation Room 2 15 1 1 161 SW 0.22
Green Group Area 25 1 1 269 SW 0.22

Total Solar Heat Gain due to Glass (qsg)


Eqn. 8

Cooling Load
SHGF qsg
Factor
(Btu/hr-ft²-°F) (Btu/hr)
(CLF)

162 0.58 4,444.31


156 0.26 1,918.49
- - -
- - -
162 0.58 3,328.06
162 0.58 3,328.06
162 0.58 5,560.55

18,579.48