SPEC.NO.

BHABHA ATOMIC RESEARCH CENTRE SECTION: A


IP1/132/05007802/ PACKAGE SUBSTATION SHEET 1 OF 40
DOC/002/R0
FOR INRP PROJECT AT TARAPUR
Government of India
Bhabha Atomic Research Centre
Nuclear Recycle Board

TENDER DOCUMENT

2 MVA, 6.6 kV OUTDOOR TYPE PACKAGE SUBSTATION

Section – A: Tendering and Contract conditions.

Section – B: General conditions of contract.

Section – C: Technical Specifications.

Section – D: Format for submission of Tender.

Part –I: Technical & Vendor Evaluation Proforma

Part –II: Price

Section – E: Tender drawings.


SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: A
IP1/132/0500780 PACKAGE SUBSTATION SHEET 2 OF 40
2/DOC/002/R0
TENDERING AND CONTRACT CONDITIONS
SECTION - A

TENDERING AND CONTRACT CONDITIONS

1. Introduction
This tender covers manufacturing, testing at manufacturer’s works, supply at site of 2
MVA, 6.6 kV Outdoor type Package Substation for construction power supply for
INRP Project, Tarapur. Detailed technical specifications with complete scope of
tender are given in Section-C of this tender.

2. Location
The site of INRP, Tarapur herein after referred to as ‘site’ is located in the state of
Maharashtra. The project site is located at sea coast & the atmosphere is laden with
salt spray. The climate is tropical with high humidity and heavy rainfall conducive to
rust and fungus growth. The maximum temperature and relative humidity likely to
occur simultaneously are 40°C and 80% respectively. The derating of the equipment
shall be done by taking 45C as an ambient temperature if it is designed at a lower
ambient temperature.

3. Copies of Bids and Specifications


Quotation with copies of supporting signed documents shall be uploaded at website
online.

4. Time for Completion


The material shall be delivered within 8 months from date of release of purchase
order.

5. Information to be included with the Proposal


The Bidder shall submit all supporting information and technical data as requested for
in Section-D: Part-I - Format for submission of Tender with vendor evaluation
proforma to permit the purchaser to make a detailed comparison and evaluation of the
offers.
The tenderer may in addition, furnish any other supporting information, technical
data, drawings or booklets which, in his view, are necessary to assist the purchaser to
make a detailed technical evaluation of his offer.

6. Price
6.1. Tenderers are hereby advised to quote against the offer in compliance with the
specification and then to quote alternative offers with their suggested equipment &
system, if there is any.
6.2. Break–up of prices, as asked for in Part – II of section D (Price format) of this
tender document, shall be furnished.
6.3. A list of recommended spare parts and prices of all items, which in Tenderer’s
opinion are required to ensure trouble free operation of the electrical equipment for
a period of two years, shall be submitted.
6.4. Bidders are informed that no Foreign Exchange will be provided by the purchaser.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: A
IP1/132/0500780 PACKAGE SUBSTATION SHEET 3 OF 40
2/DOC/002/R0
TENDERING AND CONTRACT CONDITIONS
7. Deviation from Tender Specification
Deviations, if any, shall be brought out clause wise clearly in the offer along with the
quotation. In case there are no deviations with the technical specifications, a note of
compliance shall be submitted with the offer.

8. Validity of Offers
The offer shall be kept valid for a period of 120 days from the date of opening of the
tender.

9. Inspection, Quality Surveillance and Progress Reports


All works covered by this document shall be subject to quality surveillance by the
purchaser or his authorized representative, for which purpose, the contractor shall allow
access at all reasonable times during manufacture and assembly to:
(a) The premises in which the work is being carried out.
(b) The drawings and/or tooling involved.
(c) Gauges, instruments etc. required for inspecting the work.
Prints of drawings shall be made available for inspection and retention, if so desired.
The tenderer shall give at least 15 days advance notice prior to the commencement of
testing, so that the purchaser’s representative can plan to witness the test. Inspection and
testing shall be carried out as per Section-C of this tender document. One hard copy and
three soft copies of documents including approved drawings, datasheets, catalogues,
QAP, test reports etc. shall be submitted after completion of the work.
Parts found unsatisfactory as to workmanship or materials, shall be removed by the
contractor and replaced by parts, which are satisfactory, at no extra cost.
Waiving of quality surveillance or acceptance of materials or equipment by the quality
surveyor shall not relieve the contractor from the responsibility of furnishing material and
workmanship in accordance with this tender document.
The bidder shall submit, monthly detailed progress report on the manufacture or
assembly of all equipment covered by this tender document. It shall contain the
following information:
Scheduled dates for completing: -
 Engineering work.
 Different important phases of material procurement, manufacture and fabrication.
 Assembly and testing.
 Packing and shipping.
Actual progress in percentage and rates of completion of each of the above items.

10. Training
The scope of tender shall include training of purchaser’s engineers and technicians for
operation and maintenance of all the electrical equipment included in the tender.

11. Packing & Marking


The tenderer shall note that packing for shipment shall be in accordance with the
following instructions:
11.1. All the materials shall be suitably packed and protected, so as not to suffer
deterioration, damage or breakage during transit from supplier’s works to site and
storage in a tropical climate.
11.2. Each package shall be stenciled in bold character with indelible paint, protected
with shellac to indicate shipping marks, package numbers, kind of packages,
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: A
IP1/132/0500780 PACKAGE SUBSTATION SHEET 4 OF 40
2/DOC/002/R0
TENDERING AND CONTRACT CONDITIONS
other necessary dates to identify the particular components shall be given.
11.3. All the spare parts shall be packed in separate cases and clearly marked for easy
identification.
11.4. If different items are in a package, the net weight for each item and all necessary
information to identify the particular components shall be given.

12. Transport
The suppliers should, at his responsibility check and ascertain the existing rail/ road
limitation for transport of the equipment to the site and indicate the route along which the
equipment will be transported. Packaging of the equipment shall be properly done. Each
package shall be limited to size and weight that are permissible under the existing rail and
road limitations. All lifting points shall be clearly marked. The supplier shall not ship the
equipment without the prior approval of the purchaser’s inspector and subsequent written
instructions to do so.

13. Sub-Contracts
The contractor shall not sub- contract any or all of the work without a written consent
from the purchaser. The contractor shall be responsible to the purchaser for all work of
the sub-contractor, if allowed by the purchaser.

14. Guarantee
14.1. All the equipment supplied under this contract shall be guaranteed for
satisfactory performance and against manufacturing and material defects for a
period of 18 months from the date of delivery.
14.2. Material damaged in transit or during guarantee period shall be replaced
immediately and such replacement shall also be governed by similar guarantee.

15. Pre-Qualification Criteria


15.1. Tenderer should have satisfactorily executed contracts for any department of Govt.
of India or public/ private sector units for supply of outdoor type package sub-
station equipment and shall have minimum experience of 5 years.
15.2. Tenderer should have executed one job of Package Substation worth minimum Rs.
40 lacs or 2 jobs of minimum 30 lacs or 3 jobs of minimum 20 lacs in the last five
years.
15.3. Tenderer shall have an average annual turnover of at least 1.87 Crores in last three
financial years ending March 2017.
15.4. Tenderer shall furnish test reports duly certified from reputed institutions/
laboratories such as CPRI/ERDA for equipment/ materials similar to that
offered for the tender for type and routine tests.
15.5 In case tenderer is a dealer/ contractor, the authorization certificate from original
equipment manufacturer (OEM) shall be submitted.

16.0 Confidentiality Clause


16.1. No party shall disclose any information to any third party concerning the matters
under this contract generally. In particular, any information identified as proprietary
in nature by the disclosing party shall be kept strictly confidential by the receiving
party and shall not be disclosed to any third party without the proper written consent
of the original disclosing party.
16.2. Any contravention of the above mentioned provisions by any contractor, sub-
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: A
IP1/132/0500780 PACKAGE SUBSTATION SHEET 5 OF 40
2/DOC/002/R0
TENDERING AND CONTRACT CONDITIONS
contractor, consultant, advisor of the employees of the contractor will invite penal
consequences under the aforesaid legislation.
16.3. The contractor or sub-contractor, consultant, advisor or the employees engaged by
the contractor shall not use BARC’s name for any publicity purpose through any
public media like press, Radio, T.V. or Internet without the prior written approval of
BARC.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: B
IP1/132/0500780 PACKAGE SUBSTATION SHEET 6 OF 40
2/DOC/002/R0
GENERAL CONDITIONS OF CONTRACT

SECTION – B

GENERAL CONDITONS OF CONTRACT

2 MVA, 6.6 kV Outdoor Type Package Substation

The general conditions of the contract can be obtained from the online portal of NRB
Purchase & Stores Unit (NRB PSU), Regional Purchase Unit, Mumbai.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 7 OF 40
2/DOC/002/R0
TECHNICAL SPECIFICATIONS
SECTION - C

TECHNICAL SPECIFICATIONS FOR 2 MVA, 6.6 kV OUTDOOR TYPE


PACKAGE SUBSTATION

1. Scope of Work
Scope of work includes design, manufacturing, testing & supply at site of Package
Substation suitable for outdoor installation. The prefabricated package substation shall
be designed for compactness, fast installation, maintenance free operation and
maximum safety for operating personnel. The following equipment shall be housed
inside a single enclosure of the Package substation:
 One no. 6.6 kV Vacuum Interrupted SF6 gas Insulated Breaker.
 One no. 2 MVA, 6.6/ 0.433 kV Natural Ester Oil Cooled Transformer.
 One no. LT Switchboard.
The substation equipment shall be manufactured as per relevant & latest IEC/IS
standard and the design and operational features will comply with the provision of
latest version of Indian Electricity Act, Indian Electricity Rules, Factory Act and Fire
Insurance Regulation.
2. Applicable Codes & Standards
For Vacuum Circuit Breaker
IEC 60529 Classification of degrees of protection provided by enclosures of
electrical equipment.
IEC 60298 A.C metal-enclosed switchgear and control gear for rated voltages
above 1kV and up to and including 52 kV.
IEC High voltage/Low voltage prefabricated substations.
62271/61330
IS 13118 High Voltage Alternating Current Circuit Breakers.
IEC 60694 Common specification for HV switchgear standards.
IEC 60265 High-voltage switches-Part 1: Switches for rated voltages above
1kV and less than 52 kV.
IEC 60185 Current Transformers.
BS 159 Bus Bar.
IEC 60137 Bushings.
IEC 60255 Specification for Static Protective Relays.
BS 6231 Wires and wiring.
IEC 61000 Electromagnetic compatibility.
IEC 60129 Alternating current Disconnectors (isolators) and earthing
switches.
IEC 62271-200 Metal enclosed BS 5311 switchgear.
IEC 62271-100 MV AC circuit breaker.
IEC 60060-1 BS High Voltage test technique
923
IEC 60947-4-1 Control Gears
IEC 60376 Specification of SF6 gas in RMU
For Oil Cooled Transformer
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 8 OF 40
2/DOC/002/R0
TECHNICAL SPECIFICATIONS
IS: 1180 Outdoor type Oil immersed Distribution Transformers up to and
including 2500 kVA, 33kV.
IEC 62770 Natural Ester Oil filled transformer.
IS: 2026, IEC: Power Transformers.
76
BS: 171, IEC:
354, IS: 6600
IS: 3639 Fittings & accessories for power transformer.
IS: 335, IEC: Specification for new insulation oil.
296, BS: 148
IS: 2099, IEC: Bushing for alternating voltage above 1000 Volts.
137, BS: 223
IS: 3347 Dimension for porcelain transformer bushings.
IS: 2705, IEC: Current transformers.
185, BS: 3938
IS: 3637 Gas operated relays.
IS:1271, IEC: Classification of insulating material for electrical machinery &
216 apparatus in relation to their thermal stability in service.
IS: 12063, IEC: Classification of degrees of protection provided by enclosures of
529, IS: 13947 electrical equipment.
IS: 2071, IEC: Method of high voltage testing.
60
IS: 5 Colors for ready mixed paints & enamels.
CBIP Specifications for power & distribution Transformers.
Publication
No. 275 (latest
edition)
IS: 6600 Guide for loading of oil immersed transformers.
NEMA, Noise level.
STANDARD-
TR1
For LT Switchboard
IEC 61439- Metal enclosure for switchgear & control gear.
2009
IS 4237 General requirements for switchgear and control gear for voltages
not exceeding 1000 volts.
IS 13947 (Part 1 Low Voltage Switchgear and control gear.
to 5)
IS-375-1963 Specification for switchgear, bus bars, main connections and
auxiliary wiring, marking and arrangement.
IS-2705 Specification for current transformers.
IS 3156 Specification for voltage transformers.
IS 3231-1965 Specification for electrical relays for power system protection.

IS 1248 -1968 Specification for direct acting electrical indicating instruments.

IS 1554 PVC insulated heavy-duty cables.


IS 513 Cold rolled carbon sheet steel.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 9 OF 40
2/DOC/002/R0
TECHNICAL SPECIFICATIONS
IS 6005 Code of practice for phosphating of iron and steel.
IS 5 Color for ready mixed paints.
IS 159 Busbar & Bus bar connection
IS 162 Electric power switchgear & associated apparatus
IS 5082 Wrought Aluminium & Aluminium alloys, bars, rods, tubes &
sections for electrical apparatus.
3. General Technical Requirements
The specification covers technical and constructional details of Outdoor type Package
Substation Unit which shall be capable of performing satisfactorily in open
atmosphere/heavy dust atmosphere with high relative humidity. The Package
Substation Unit shall be compact in size, transportable, light weight rugged and of
robust construction and capable to withstand rough use in highly humid. The complete
unit shall be installed on a substation plinth (base) as Outdoor substation. Its overall
dimension shall be kept to minimum as far as practicable.
3.1. SF6 Gas insulated Vacuum Circuit Breaker
The SF6 gas insulated VCB shall be suitable for indoor installation within the
Compact Substation (IP 54 compatible). The circuit breaker shall be used to control
and isolate the 6.6/0.433 kV, 2 MVA Oil cooled Distribution transformer in the
Package Substation.
3.1.1. Constructional Features
The Circuit breaker shall be triple pole fixed type with motorized spring charging
mechanism. The outer enclosure shall be made of Galvanized sheet of 2 mm thickness
having a degree of protection of IP: 54. The inner enclosure shall be made of stainless
steel (minimum thickness 2.5 mm), gas tight metal enclosure (IP: 67), sealed for life,
which shall group together the live parts, earthing switch and circuit breaker. All live
parts, high voltage components, excluding the HV cable termination of the switchgear
shall be insulated in SF6 gas to provide complete proofing against dangers of flashover
between phase and earth and between phases. It shall be designed to operate at the
rated voltage of 6.6 kV and shall be internally arc fault tested for atleast 21 kA for 1
second. The breaker shall have three vacuum interrupters (one interrupter per phase)
mounted on same carriage. Vacuum Circuit Breaker and control gear (CTs, PTs, relays
etc.) shall be mounted on the same panel. Busbar shall be SF6 gas insulated. The Busbar
shall be of electrolytic grade tinned copper. The Busbar shall be rated for 630 A, short
circuit rating of 25 kA for 1 sec.
3.1.2. Method of operation
The circuit breaker shall have motorized spring charging mechanism. The breaker
shall also be provided with hand-operated spring charging handle. Mechanical
position indicator for ON, OFF & EARTH status of breaker shall be provided. A
visual mechanical indicating device shall be provided to indicate the status of the
spring, i.e. SPRING CHARGED. The rated operating sequence shall be O – 3 min –
CO – 3 min – CO. Manual close & open push buttons shall also be provided. The
breaker shall be provided with closing coil suitable for 230V AC, supply of which
shall be tapped directly from the LT bus section by the supplier.
3.1.3. Voltage Transformers
The burden per transformer shall be not more than 50 VA and the voltage ratio shall
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 10 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
be 6600/110 V. The accuracy class shall be 1.0. The PT shall be of cast epoxy-resin
construction and they shall conform to IS 3156.
3.1.4. Current Transformers
The breaker shall be provided with necessary Current Transformers (CTs)
(conforming to IS 2705) for metering and protection purposes. For metering CTs, the
accuracy class shall be normally 1.0. The Protection CTs shall have class of accuracy
of 5P10. The burden requirement of the CTs shall be 2.5 VA. The CT secondary for
protection shall be 1 A & for metering it shall be 5 A.
3.1.5. Relays
The circuit breaker shall be fitted with static type self-powered microprocessor based
relay for over current & earth fault protection.
The numerical relays shall have following features: -
 Self-Diagnosis
 Minimum last five abnormal events recording (over current & earth fault)
including fault level and phase along with date & time.
 On-line display of current.
3.1.6. Metering Compartment
Metering compartment shall be air insulated and shall include the following:
 Multifunction meter with RS-485, Cl-1.0.
 Ammeter with ASS, Cl-1.0.
 Voltmeter with VSS, Cl-1.0.
3.1.7. Indications
Indications viz. ON, OFF, EARTH, TRIP & PIL shall be provided on the front of the
panel.
3.1.8. SF6 Gas Pressure Gauge
Pressure gauge with a safety level bar marking shall be provided for monitoring SF 6
gas pressure.
3.1.9. Fault Passage Indicator
Fault passage indicator shall be provided for detecting and indicating earth faults &
phase to phase faults.
3.1.10. Live Cable Indicator
The panel shall be equipped with a voltage indicator box on the front of the device to
indicate whether there is voltage in the cables.
3.1.11. Safety of Equipment
With respect to panel’s SF6 gas filled equipment, any accidental over pressure inside the
sealed chamber shall be limited by the opening of a pressure-limiting device in the
enclosure so that the gas will be released away from the operator without endangering the
operator or anyone else in the vicinity of the panel.
3.1.12. Padlocks
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 11 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
Padlocking facility shall be provided for circuit breaker and earthing switch.
3.1.13. Cable Compartment with cover
The Cable compartment of the circuit breaker shall be provided with suitable bushings
for termination of incoming/ outgoing 6.6 kV, 3 core cables. The cable termination
shall be done by Heat shrinkable termination method so that adequate clearances shall
be maintained between phases for termination. Cable termination boots shall be
supplied by the switchgear manufacturer. The cable compartment cover shall be
interlocked with the earth switch.
3.1.14. Painting & Finishing
All interiors and exteriors of breaker enclosure, breaker mechanism etc. shall be
finished and painted to produce a neat, fire resistant and durable surface which would
prevent rusting and corrosion. The powder coating shall be with Polyurethane based
paint with Siemens gray shade (RAL 7032) with thickness of 70 microns.
3.1.15. Tests and Test Certificates
3.1.15.1. Type Tests
The equipment offered in the tender should have been successfully type tested at NABL
laboratories in India or equivalent international laboratories in line with the relevant
standards and technical specifications within the last 5 (five) years from the date of offer.
The bidder shall be required to submit complete set of the type test reports/ certificates
along with the offer.
The type test reports/ certificates to be submitted by the tenderer are listed in the
datasheet.
3.1.15.2. Routine Tests
All acceptance and routine tests as stipulated in the respective applicable standards
amended up-to-date for all the equipment shall be carried out by the supplier in the
presence of purchaser’s representative without any extra cost to the purchaser before
despatch.
The supplier in the presence of purchaser’s representative shall carry out the following
acceptance and routine tests. The supplier shall give at least 15 days advance intimation
to the purchaser to enable them to depute their representative for witnessing the tests.
The routine tests are as follows:
 Conformity with drawings and diagrams.
 Measurement of closing and opening speeds.
 Checking of filling pressure (for SF6).
 Checking of gas tightness (for SF6).
 Functional test.
 I.R. test.
 Dielectric testing and main circuit resistance measurement.
 Power frequency voltage test.
 Mechanical operations test.
 Checking of partial discharge on complete unit.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 12 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
Technical Particulars for Vacuum Circuit Breaker Panel

S. NO. DESCRIPTION SPECIFICATIONS


Vacuum Circuit Breaker
1. Type & Rating
1.1 Type SF6 gas insulated VCB
1.2 Pole 3
1.3 Rated voltage (Nominal/ Maximum) 6.6/7.2 kV
1.4 Rated frequency 50 Hz
1.5 System Neutral Earthing Resistance grounded
2. Insulation Level
2.1 Impulse withstand 60 kV (peak)
2.2 One minute power frequency withstand 20 kV (rms)
voltage for Type tests & Routine Tests
3. Rated Current
3.1 Continuous at 50 oC 630 A
3.2 Short time current for 1 sec. 25 kA
4. Rated Breaking Capacity
4.1 Symmetrical 25 kA
4.2 Asymmetrical As per IS: 13118 (2002) or
IEC‐62271(2007-10)
4.3 Internal Arc Fault withstand capacity of the 21 kA for 1 sec.
breaker panel
5. Rated making capacity 62.5 kA (peak)
6. Rated short time withstand current for 1 sec. 25 kA
7. Total Break time 4 cycles (max.)

8. Total Make time 5 cycles (Max.)


9. Degree of protection IP-54 for Outer enclosure
and IP 67 for inner steel tank
10. Operating duty O–3 min- CO -3 min – CO
11. Operating mechanism Motorized
12. No. of openings at current 100% of 30 Nos.
breaking capacity

13. No. of openings at 50% & 100% of rated 20000 Nos.


current
14. Minimum no. of Auxiliary contacts 4 NO + 4 NC
15. Breaker Application For Transformer control
16. Mechanical emergency trip push button on Shall be provided.
VCB compartment door.
17. Spring charging motor (if provided) 240 V AC
18. LED Indications for ON, OFF, TRIP, Shall be provided.
EARTH & PIL.
20. SF6 gas pressure indicator (Pressure gauge/ Shall be provided.
Manometer)
Voltage Transformer
21. Highest equipment voltage 7.2 kV
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 13 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
22. No. of phases. 3 nos. single phase VTs
23. Rated Output 50 VA/ phase
24. Insulation level
24.1 Impulse Withstand Voltage 60 kV (peak)
24.2 One minute power frequency withstand voltage on
24.2.1 Primary Winding 20 kV (rms)
24.2.2 Secondary Winding 3 kV (rms)
25. Frequency 50 Hz
26. Transformation Ratio 6600/ 110 V
27. Accuracy Class 1.0
28. Class of Insulation F
29. Type of insulation Cast resin
30. Applicable Standard IS: 3156 (1997)
Current Transformers
31. Rated voltage 6.6 kV
32. Type Cast resin
33. Class of insulation F
34. Insulation level
34.1 Impulse withstand voltage 60 kV (peak)
34.2 One minute power frequency voltage on
34.2.1 Primary winding 20 kV (rms)
34.2.2 Secondary winding 3 kV (rms)
35. Frequency 50 Hz
36. Rated continuous thermal current 120 % of rated primary
current
37. Short time thermal rating and its duration. 25 kA for 1 sec
38. Transformation ratio of CTs 630/5 A Core-I Core-II
38.1 Rated output 2.5 VA 2.5 VA
38.2 Class of accuracy 5P10 1
38.3 Purpose Relaying Metering
39. Applicable Standard IS-2705
Bus bars
40. Material Electrolytic grade Tinned
Copper
41. Rated Current 630 A
42. Type SF6 insulated
Tests & Test Certificates
43. Routine Tests to be  Conformity with drawings and diagrams.
witnessed by the  Measurement of closing and opening
Purchaser’s representative speeds.
 Checking of filling pressure (for SF6).
 Checking of gas tightness (for SF6).
 Functional test.
 I.R. test.
 Dielectric testing and main circuit
resistance measurement.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 14 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
 Power frequency voltage test.
 Mechanical operations test.
 Checking of partial discharge on complete
unit.

44. Test Certificates required  Impulse withstand test.


 Temperature-rise test.
 Short-time withstand current test.
 Mechanical operation test.
 Checking of degree of protection.
 Circuit breaker & earthing switch making
capacity.
 Circuit breaker breaking capacity.
 Internal arc withstand test.
 Checking of partial discharge on complete
unit.
 For earthing switches, test reports on
making capacity, short time withstand
current and peak short-circuit current shall
be supplied.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 15 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
3.2. Transformer
2 MVA 6.6/0.433 kV Natural Ester Oil Cooled Distribution transformer shall be a part
of the Package Substation which shall be housed inside the enclosure. The transformer
shall be 3-phase core type double wound with Copper conductor along with Natural
Ester Oil cooled KNAN and a hermetically sealed corrugated tank arrangement.
3.2.1. Electrical Performance Particulars
 The transformer shall be operable at its rated capacity at any tap with voltage
variation of ± 10% of corresponding voltage of the particular tap.
 The transformer shall be designed to withstand the thermal and dynamic stresses
due to short circuit at its terminals or symmetrical/ asymmetrical faults on any
winding.
 The overload capacity of the transformer shall be as per IS 6600.
3.2.2. Construction Particulars
3.2.2.1. Core
The core of the transformer shall be made of PRIME GRADE, CRGO with M4 grade or
better perfectly insulated and clamped to minimize noise and vibrations. The
transformer shall be of BOLTLESS core design. The core shall be procured from one of
the approved manufacturers as given in the List of Approved Makes annexure.
3.2.2.2. Windings
The winding of the transformer shall be made with 99.9% pure electrolytic grade
copper, insulated with thermally upgraded paper (Insulation Class A/ Conductor Inter-
turn insulation Class E). The HV & LV winding should be able to withstand thermal and
mechanical stress in the event of short circuit. Neutral point of the Low Voltage
windings shall be brought to the tank cover.
3.2.2.3. Insulating Oil
Transformer oil shall be Natural Ester vegetable oil complying with IEC 62770. Oil
should be Environment friendly, Green & Biodegradable. It should also exhibit safety
against fire hazards.
3.2.2.4. Temperature Rise
 Temperature rise in winding shall be 45 oC above the ambient temperature of
50oC.
 Temperature rise in oil shall be 40 oC above ambient temperature of 50oC.
3.2.2.5. Off-circuit tap changer
The tappings (-10% to +5% in steps of 2.5%) of the HV winding shall be connected to
the off-circuit tap changer located horizontally between the yoke and the tank cover.
The handle shall be located on the cover and shall be operated when the transformer is
deactivated. The design shall prevent setting the off-circuit tap changer to intermediate
positions. The mechanism shall also be padlocked during normal transformer operation.
3.2.2.6. Tank and cover
The sides of the tank shall be made of corrugated cooling surfaces. The bottom plate,
side and frames shall be of a welded construction. The welds shall be tested for oil
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 16 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
tightness. The cover shall be bolted to the tank frame. The undercarriage shall be welded
to the bottom plate and the rollers shall be suitable for either longitudinal or transverse
movements.
3.2.2.7. Current Transformers
CTs for REF protection and back up earth fault shall be provided on the neutral end.
3.2.2.8. Temperature Indicator
One set of winding temperature indicators with necessary current transformer, heating
coil and a detector element and one set of oil temperature indicator with maximum
reading pointer shall be mounted locally so as to be readable at a standing height from
ground level. Each of the above indicators shall be provided with necessary contacts for
alarm and trip.
3.2.2.9. Painting and Finishing
The transformer shall be either hot-dip galvanized or painted. The metal parts shall be
carefully sandblasted. The painting system shall be a single coat one-pack epoxy. The
top coat shall be Siemens Grey (RAL 7032). The hot-dip galvanizing shall be 70 μm.
minimum.
3.2.2.10. List of Fittings & Accessories
 OTI with alarm & trip contact.
 WTI with alarm & trip contact.
 Pressure relief valves with or without contacts.
3.2.2.11. Transformer Losses
Losses shall be as per IS 1180 for Star-2/ efficiency level 3. Respective Current density
& Flux Density of the transformer shall be so as to suit the above required No load &
loss levels.
3.2.3. Tests and Test Certificates
3.2.3.1. Type Tests
The bidder shall submit Type Test reports/ certificates of the transformer having
identical technical parameters as that of the transformer offered in the tender from
NABL/ Govt. approved laboratories, conducted within 5 years, along with their offer
failing which their offer may not be technically accepted. The type tests should
comprise of the tests specified in IS: 2026 up to the latest amendment as well as the
short circuit test.
The type tests reports/ certificates required are as follows:
 Temperature rise test.
 Lightning impulse test.
 Partial discharge test.
 Chopped wave test.
 Short circuit test.
 Mill’s test certificate.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 17 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
3.2.3.2. Routine tests
The transformer shall be subject to routine tests at the manufacturer’s works in presence
of purchaser’s representative. The supplier shall give at least 15 days advance intimation
to the purchaser to enable them to depute their representative for witnessing the tests.
The routine tests are as follows:
 Measurement of winding resistances.
 Measurement of voltage ratio and testing of voltage vector relationship.
 Measurement of impedance voltage, short circuit impedance and load loss.
 Measurement of no-load loss and current.
 Dielectric tests:
o Separate source voltage withstand test.
o Induced overvoltage withstand test.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 18 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
Technical Particulars for 2 MVA 6.6/0.433 kV Natural Ester Oil Cooled
Transformer

S. NO. DESCRIPTION SPECIFICATIONS


1. Quantity 1 No.
2. Installation Inside the Package substation
3. Type of insulating oil Natural Ester Oil
4. No. of phases 3
5. Frequency 50 Hz
6. Type of cooling KNAN
7. Rated output under site 2000 kVA
conditions
8. Rated voltage
8.1 HV Winding 6.6 kV
8.2 LV Winding 0.433 kV
9. No-load transformation ratio 6.6/ 0.433
10. Vector group Dyn11
11. % impedance As per IS 1180
12. Total range of tappings and -10% to +5% in steps of 2.5%
tapping steps
13. Type of tap changing equipment Off-circuit Rotary type
14. System Highest Voltage
14.1 HV Winding 7.2 kV
14.2 LV Winding 415V + 10%
15. Phase Connection
15.1 HV Winding Delta
15.2 LV Winding Star
16. Insulation Levels
16.1 One minute power frequency withstand voltage
16.1.1 HV Winding 20 kV (rms)
16.1.2 LV Winding 3 kV (rms)
16.2 Impulse Withstand Voltage
16.2.1 HV Winding 60 kV (peak)
16.2.2 LV Winding -
17. Terminal details
17.1 HV Line Cable Box (XLPE Cables)
17.2 LV Line Copper Flexibles/ busbars
17.3 LV Neutral One neutral as part of LV Copper flexibles/
busbars and second neutral with copper
earthing bar for system earthing brought
near the base of the transformer.
18. System fault level
18.1 HV Winding 25 kA (rms) for 1 sec.
18.2 LV Winding 50 kA (rms) for 1 sec.
19. Method of System Earthing
19.1 LV System Solidly grounded
20. Provision/ accommodation of CT Ratio 3200/1 A, Dual Core
CTs in LV Neutral Class 5P10 (for protection), Class PS (for
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 19 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
REF).
21. Max. no-load Losses at rated As per IS 1180
frequency and rated voltage
22. Maximum Load losses at As per IS 1180
normal ratio, rated current
and 75 oC
23. Temperature Rise
23.1 Winding 45 oC over ambient temperature of 50 oC
23.2 Oil 40 oC over ambient temperature of 50 oC
Tests & Test Certificates
24. Routine Tests to be witnessed by
 Measurement of winding resistances.
the Purchaser’s representative
 Measurement of voltage ratio and testing
of voltage vector relationship.
 Measurement of impedance voltage,
short circuit impedance and load loss.
 Measurement of no-load loss and
current.
 Dielectric tests:
 Separate source voltage withstand test.
 Induced overvoltage withstand test.
25. Test Certificates Required
 Temperature rise test.
 Lightning impulse test.
 Partial discharge test.
 Chopped wave test.
 Short circuit test.
 Mill’s test certificate.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 20 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS

3.3. LT Switchboard
The LT Panel shall be a part of the Package Substation housing the following equipment:
i. Air circuit breaker 3200 A, 4 Pole with Microprocessor based releases – 1 no. as
incomer.
ii. Following breakers with 3 Pole & Thermal magnetic based releases as outgoings
 250 A, MCCB – 2 nos.
 400 A, MCCB– 1 no.
 630 A, MCCB – 1 no.
 800 A, ACB – 1 no.
 1000 A, ACB – 1 no.
iii. Cable glands for outgoing feeders.
iv. CT for metering & protection.
3.3.1. General finish
The LT panel shall be in a cubicle made of Galvanized sheets of thickness not less than 2
mm, treated against corrosion protected with phosphate coating and powder coated for
long life. The cubicle shall be of dust and vermin proof construction. The design and
arrangement of the equipment shall be such that an adequate space and access is provided
in cubicle for inspection and maintenance of MCCBs and breakers etc. The panel shall be
tropical, totally enclosed, metal clad, weatherproof, vermin and dust proof.
3.3.2. Construction Particulars
3.3.2.1. Enclosure
The LT Panel, shall be metal clad enclosed and be fabricated out of high quality CRCA
sheet of thickness not less than 2 mm, suitable for installation in Package substation.
The LT Panel shall be provided with sufficient no. of removable gland plates at bottom to
drill holes for cable entry at site.
The LT Panel shall be designed to facilitate easy inspection, maintenance and repair. The
LT Panel shall be sufficiently rugged in design and shall support the equipment without
distortion under normal and short circuit condition; they shall be suitably braced for short
circuit duty. The complete structure shall rigid, self-supporting and free from vibrations,
twists and bends.
3.3.2.2. Earthing
Earthing arrangement shall be provided for earthing each cable, cable glands, neutral
Busbar, chassis and framework of the cubicle with separate earthing terminals at two
ends. The earthing conductor size should be suitable for 50kA for 1 sec. The main
earthing terminals shall be suitable marked. The earthing terminals shall be of adequate
size, protected against corrosion, and readily accessible. These shall be identified by
means of sign marked in a legible manner on or adjacent to terminals.
Neutral Busbar strip shall be connected to Earthing terminal with the help of copper strip
of suitable capacity and nut-bolt arrangement.
3.3.2.3. Cleaning and Painting
a) All steel surfaces shall be thoroughly cleaned by sand blasting or chemical agents, as
required to produce a smooth surface free of scales, grease and rust.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 21 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
b) All the internal-external surfaces, after cleaning, shall be given two coats of high
quality epoxy based rust resisting primer as per IS: 2074 followed by filler coats.
c) Both sides shall be given Epoxy based electrostatic powder coating with Siemens
grey (RAL 7032) shade.
d) Special care shall be taken by the manufacturer to ensure against rusting of nuts, bolts
and fittings during operation. All bushings and current carrying parts shall be cleaned
properly after final painting.
3.3.3. Equipment Specification
3.3.3.1. Air Circuit Breaker (ACB)
The incomer ACB shall be fixed type with motorized spring charging mechanism. The
breaker shall have microprocessor-based releases for O/C, S/C & E/F protection. The
outgoing ACBs shall be manually fixed type with thermal and magnetic based releases
with O/L, S/C & E/F Protection. In addition to the above, the following shall be provided
for the operation of the breaker from the switchgear.
 Mechanical trip knob for actuation in emergency.
 Mechanical indication for ON/OFF/ SPRING CHARGED position.
 Safety shutters automatically operated with necessary interlock and padlocking
facility.
 ON, OFF, TRIP indicating lamps.
 Phase barriers between the poles.
 Trip reset facility.
 The tripping shall be achieved by energizing a shunt trip coil.
In the incomer, separate electromagnetic relays shall be provided for the following
protections:
 Overcurrent & Earth fault.
 Restricted Earth fault protection.
The breaker mechanism shall be 230V AC motor spring charged operated type. Tripping
shall be achieved by means of a shunt trip coil. The operating mechanism shall be trip-
free. Failure of spring, vibrations or shocks shall not cause unintended operation of
breaker or prevent intended tripping operation. Closing of breakers shall be prevented
unless the spring is fully charged.
3.3.3.2. Moulded Case Circuit Breaker (MCCB)
MCCB conforming to latest IS specifications with adjustable over load thermal magnetic
releases and having short circuit breaking capacity 50 kA at 415 Volt, 50Hz with Rotary
Handle.
3.3.3.3. Interconnecting Busbar
A set of electrolytic grade copper bus bars of rating 3200A shall run along the entire
length of the switchgear. The bus bars shall be supported on insulators. Heat shrinkable
HRPVC sleeved buses shall be supported on insulators which should be flame-retardant,
track resistant, non-hygroscopic, and high impact strength. They shall be designed to
withstand the electrical and mechanical stresses due to a fault having a prospective
current of 50 kA rms for a minimum period of 1 second. Bus bars shall be brazed to
impart high impact strength. All the bus bar joints shall be suitably shrouded.
The temperature rise test shall be carried out at full rating of the rated current for all
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 22 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
Busbar. The type test certificate for temperature rise test shall be furnished for
acceptance.
3.3.3.4. Meters
Following meters shall be provided on incomer:
 Analog Ammeter with ASS, Cl-1.0.
 Analog Voltmeter with VSS, Cl-1.0.
 Multifunction meter with RS-485, Cl-1.0.
3.3.3.5. Panel Indication Lamps
Indicating Lamps shall be cluster LED type suitable to operate on 240 V AC.
On Incomer ACB: Breaker ON, OFF, Trip & PIL indication.
On Outgoing MCCB feeders: ON, OFF, Trip & PIL indication.
3.3.3.6. Current Transformers & Terminal Block
CT’s of rating as specified below are to be provided, mounted on the Transformer LT
Busbar.
S. No. Particulars Requirement
1. Current Ratio 3200/5 A
2. Class of Accuracy 1/5P10
3. Burden 5VA/5VA
4. Type Cast resin
The secondary terminals of the CTs shall be individually wired, using 2.5 sq.mm flexible
copper wires (with color coding and ferrules at both ends) up to a terminal block. The
Terminal block shall be located, at a suitable height. The three phase voltages also are to
be tapped from the LT Busbar and wired up to the terminal block. The CT secondary
shall be covered with sealable covers.
3.3.4. Tests & Test Certificates
3.3.4.1. Type Tests
Type test certificates shall be furnished on the circuit breakers, switches and other major
components provided the equipment furnished under the scope of this specification is
essentially the same. Type test certificate shall be furnished for:
 Short circuit test.
 Temperature rise test.
 Degree of protection.
3.3.4.2. Routine Tests
Routine tests shall be performed in presence of Purchaser’s representative at the
manufacturer’s works. The supplier shall give at least 15 days advance notice of the date
when the tests are to be carried out.
The routine tests are as follows:
 Mechanical & electrical operations of components and devices.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 23 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
 Insulation resistance measurement of power and control circuits.
 High voltage test for one minute at 2.5 kV.
 Continuity & polarity tests on all coils and circuits.
 Functional tests on relays.
 Physical verification of bill of materials.
 Verification of dimensions and visual inspection.
 Inspection of painting and thickness thereof. It should not be less than 70
microns.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 24 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
Technical particulars for LT switchboard
S.NO. DESCRIPTION SPECIFICATONS
1. Service/ system voltage 415V10%, 3 phase & Neutral
2. Insulation voltage 1100V
3. Insulation level 2.5 kV for 1 min.
4. Maximum voltage at which all 415V + 10%
equipment shall operate satisfactorily.
5. Frequency 50 Hz ± 5%
6. One-minute power frequency test
voltages withstand strength (between
phases and between phase and ground).
a) Power circuits 2500V (rms)
b) Control circuits 1500V (rms)
c) Aux. circuits 2000V (rms)
connected to
Secondary of CTs
7. Rated continuous current 3200 A

8. Rated short time current (thermal) 50 kA


capacity for one second of complete
assembly without incurring any damage.
9. No. of poles for incomer & outgoing 4 Pole, for incomer ACB and 3 Pole with
feeders. neutral link for outgoing MCCB & ACB
feeders.
10. Shunt trip coil voltage 230 V AC
11. ACB with microprocessor based releases Shall be provided only for incomer.

12. MCCB & ACB with thermal-magnetic Shall be provided only for outgoing feeders.
based releases
13. Protections in I/C ACB Microprocessor based releases with O/C, S/C
& E/F protections. In addition, separate
protection shall be provided with
electromagnetic relays for O/C, E/F & REF.
14. Make (model) and protections available O/L, S/C (delayed & instantaneous) & E/F
in MCCB
15. For ACB & MCCB, Icu=Ics= Icw= 50 kA Shall be provided.

16. Busbar
16.1 Rated short time current (thermal) 50kA
capacity for one second without
incurring any damage.
16.2 Standard IS: 8130 for Copper
16.3 Material 99.9% pure Copper electrolytic grade
16.4 Busbar insulation Black heat shrinkable PVC sleeves with color
codes
16.5 Degree of protection IP: 54
16.6 Temperature rise 40oC over ambient temperature of 45 oC
17. Earth bus 50mm x 6mm Cu
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 25 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
18. Sheet steel CRCA
19. Paint finish
19.1 Both interior and exterior Epoxy based electrostatic powder coating
Siemens grey (RAL 7032) shade for
enclosures.
19.2 Thickness (total) 70 microns min.
20. Current Transformer
20.1 Insulation Resin cast
20.2 Rating As per SLD
20.3 Accuracy Metering Cl. – 1, Protection 5P10, Class PS
for REF CTs.
21. Panel indoor illumination with switch Shall be provided
22. Degree of protection for Panel IP 54
23. Mimic Shall be provided
24. Meters Multifunction meter, Voltmeter, Ammeter,
(for incomer);
25. The size of analog meters 96 x 96 sq. mm.

26. Indicating Lamps LED type indicating lamps for Breaker


ON, OFF, Trip & PIL
27. Switches/Pushbuttons T-N-C switch, Ammeter and Voltmeter
Selector Switches shall be provided
along with push buttons for Start, Stop,
Trip.
28. Tests & Test Certificates
28.1 Routine Tests to be witnessed by 1. Mechanical & electrical operations of
Purchaser’s representative components and devices.
2. Insulation resistance measurement of
power and control circuits.
3. High voltage test for one minute at 2.5
kV.
4. Continuity & polarity tests on all coils
and circuits.
5. Functional tests on relays.
6. Physical verification of bill of materials.
7. Verification of dimensions and visual
inspection.
8. Inspection of painting and thickness
thereof. It should not be less than 70
microns.
28.2 Type test certificates Type test certificates shall be furnished on
the circuit breakers, switches and other
major components, provided the
equipment furnished under the scope of
this specification is essentially the same.
Type test certificate shall be furnished for
Short circuit test, Temperature rise test and
Degree of protection.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: C
IP1/132/0500780 PACKAGE SUBSTATION SHEET 26 OF
2/DOC/002/R0 40
TECHNICAL SPECIFICATIONS
4. General points regarding Package Substation
The package substation shall have the following features:
 The outer enclosure shall be made of 2.0 mm thickness Galvanized Sheet Steel
tropicalized to meet Indian weather conditions including all the partition sheets &
doors.
 The complete design shall be compartmentalized inside a single enclosure.
 The enclosure of package substation shall be K10 class as per IEC 60694
standard.
 The entire Package Substation shall be Factory Assembled & Factory Fitted.
 The Package Substation shall be tested for Internal Arc fault test of atleast 20 kA
for 1 second.
 Louvers shall be provided in the outside enclosure for efficient cooling.
 The Enclosure shall have IP 54 degree of protection for HT & LT switchgear
compartment & IP 23/34 degree of protection for Transformer compartment.
 The enclosure exterior shall be powder coated with Polyurethane based paint with
Siemens grey shade (RAL 7032).
 Each compartment shall be provided with the door and padlocking arrangement.
 The Compartment illumination lamp with door-operated switch shall be provided
for each compartment.
 The connection between VCB panel and transformer shall be through Aluminium
conductor and between transformer and LT panel through Copper flexibles or
busbars.
 Lifting arrangement shall be provided for the Package substation. In case of
relocation of the Package Substation, the entire substation should be capable of
getting lifted and placed as a single unit without dismantling of any of the major
equipment inside.
4.1. Tests & Test Certificates for the Package Substation completely assembled
The Package Substation offered must be type tested as per IEC 61330. The copy of type
test summary should be submitted along with the tender.
4.1.1. Routine Tests: The routine tests shall be made on the complete pre-fabricated
substation.
 Voltage tests on auxiliary circuit.
 Functional tests.
 Verification of complete wiring.

4.1.2. Test Witness: Routine test shall be performed in presence of Purchaser’s


representative if so desired by the purchaser. The Contractor shall give at least fifteen
(15) days advance notice of the date when the tests are to be carried out.

4.1.3. Test Certificates: Certificate reports of all the tests carried out at the works shall
be furnished in quadruplet copies (one hard copy + 3 soft copies) for approval of the
Purchaser.
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION SHEET 27 OF
2/DOC/002/R0 FORMAT FOR THE SUBMISSION OF THE TENDER 40
(PART – 1 : TECHNICAL)

SECTION D

FORMAT FOR SUBMISSION OF TENDER

PART-1: TECHNICAL
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 DATASHEET (TO BE FILLED BY THE BIDDER) SHEET 28 OF
40

GUARANTEED TECHNICAL PARTICULARS FOR 2 MVA, 6.6 kV OUTDOOR


TYPE PACKAGE SUBSTATION

The tenderer shall furnish the technical particulars below for the equipment quoted,
without which the tender shall be considered as incomplete.
SF6 Gas insulated Vacuum Circuit Breaker Panel
S. NO. DESCRIPTION SPECIFICATIONS
Vacuum Circuit Breaker
1. Type & Rating
1.1 Type
1.2 Pole
1.3 Rated voltage (Nominal/ Maximum)
1.4 Rated frequency
1.5 System Neutral Earthing
2. Insulation Level
2.1 Impulse withstand
2.2 One minute power frequency withstand
voltage for Type tests & Routine Tests
3. Rated Current
3.1 Continuous at 50 oC
3.2 Short time current for 1 sec.
4. Rated Breaking Capacity
4.1 Symmetrical
4.2 Asymmetrical
4.3 Internal Arc Fault withstand capacity of the
breaker panel
5. Rated making capacity
6. Rated short time withstand current for 1 sec.
7. Total Break time
8. Total Make time
9. Degree of protection
10. Operating duty
11. Operating mechanism
12. No. of openings at current 100% of
breaking capacity
13. No. of openings at 50% & 100% of rated
current
14. Minimum no. of Auxiliary contacts
15. Breaker Application
16. Mechanical emergency trip push button on
VCB compartment door.
17. Spring charging motor (if provided)
18. LED Indications for ON, OFF, TRIP,
EARTH & PIL.
20. SF6 gas pressure indicator (Pressure gauge/
Manometer)
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 DATASHEET (TO BE FILLED BY THE BIDDER) SHEET 29 OF
40

Voltage Transformer
21. Highest equipment voltage
22. No. of phases.
23. Rated Output
24. Insulation level
24.1 Impulse Withstand Voltage
24.2 One minute power frequency withstand voltage on
24.2.1 Primary Winding
24.2.2 Secondary Winding
25. Frequency
26. Transformation Ratio
27. Accuracy Class
28. Class of Insulation
29. Type of insulation
30. Applicable Standard
Current Transformers
31. Rated voltage
32. Type
33. Class of insulation
34. Insulation level
34.1 Impulse withstand voltage
34.2 One minute power frequency voltage on
34.2.1 Primary winding
34.2.2 Secondary winding
35. Frequency
36. Rated continuous thermal current
37. Short time thermal rating and its duration.
38. Transformation ratio of CTs 630/5 A
38.1 Rated output
38.2 Class of accuracy
38.3 Purpose
39. Applicable Standard
Bus bars
40. Material
41. Rated Current
42. Type
Tests & Test Certificates
43. Routine Tests to be witnessed by the
Purchaser’s representative
44. Test Certificates required
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 DATASHEET (TO BE FILLED BY THE BIDDER) SHEET 30 OF
40

2 MVA 6.6/0.433 kV Natural Ester Oil Cooled Transformer

S. NO. DESCRIPTION SPECIFICATIONS


1. Quantity
2. Installation
3. Type of insulating oil
4. No. of phases
5. Frequency
6. Type of cooling
7. Rated output under site
conditions
8. Rated voltage
8.1 HV Winding
8.2 LV Winding
9. No-load transformation ratio
10. Vector group
11. % impedance
12. Total range of tappings and
tapping steps
13. Type of tap changing equipment
14. System Highest Voltage
14.1 HV Winding
14.2 LV Winding
15. Phase Connection
15.1 HV Winding
15.2 LV Winding
16. Insulation Levels
16.1 One minute power frequency withstand voltage
16.1.1 HV Winding
16.1.2 LV Winding
16.2 Impulse Withstand Voltage
16.2.1 HV Winding
16.2.2 LV Winding
17. Terminal details
17.1 HV Line
17.2 LV Line
17.3 LV Neutral
18. System fault level
18.1 HV Winding
18.2 LV Winding
19. Method of System Earthing
19.1 LV System
20. Provision/ accommodation of
CTs in LV Neutral
21. Max. no-load Losses at rated
frequency and rated voltage
22. Maximum Load losses at
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 DATASHEET (TO BE FILLED BY THE BIDDER) SHEET 31 OF
40

normal ratio, rated current


and 75 deg. C
23. Temperature Rise
23.1 Winding
23.2 Oil
Tests & Test Certificates
24. Routine Tests to be witnessed by
the Purchaser’s representative
25. Test Certificates Required
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 DATASHEET (TO BE FILLED BY THE BIDDER) SHEET 32 OF
40

LT Switchboard

S.NO. DESCRIPTION SPECIFICATONS


1. Service/ system voltage
2. Insulation voltage
3. Insulation level
4. Maximum voltage at which all
equipment shall operate satisfactorily.
5. Frequency
6. One-minute power frequency test
voltages withstand strength (between
phases and between phase and ground).
a) Power circuits
b) Control circuits
c) Aux. circuits
connected to
Secondary of CTs
7. Rated continuous current
8. Rated short time current (thermal)
capacity for one second of complete
assembly without incurring any damage.
9. No. of poles for incomer & outgoing
feeders.
10. Shunt trip coil voltage
11. ACB with microprocessor based releases
12. MCCB & ACB with thermal-magnetic
based releases
13. Protections in I/C ACB
14. Make (model) and protections available
in MCCB
15. For ACB & MCCB, Icu=Ics= Icw= 50 kA
16. Busbar
16.1 Rated short time current (thermal)
capacity for one second without
incurring any damage.
16.2 Standard
16.3 Material
16.4 Busbar insulation
16.5 Degree of protection
16.6 Temperature rise
17. Earth bus
18. Sheet steel
19. Paint finish
19.1 Both interior and exterior
19.2 Thickness (total)
20. Current Transformer
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 DATASHEET (TO BE FILLED BY THE BIDDER) SHEET 33 OF
40

20.1 Insulation
20.2 Rating
20.3 Accuracy
21. Panel indoor illumination with switch
22. Degree of protection for Panel
23. Mimic
24. Meters
25. The size of analog meters
26. Indicating Lamps
27. Switches/Pushbuttons
28. Tests & Test Certificates
28.1 Routine Tests to be witnessed by
Purchaser’s representative
28.2 Type test certificates
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 VENDOR EVALUATION PROFORMA (TO BE FILLED AND SHEET 34 OF
SUBMITTED WITH THE TENDER) 40

1. General:

a) Reference: Tender Enquiry No.:

Material :

Quotation No. & Date :

b) Vendor Details:

i) Name :

ii) Address : Office

: Works

iii) Telephone Nos. :

iv) Telex Nos. :

v) E-mail :

vi) Contact person :

vii) Ownership of premises :

viii) Registration details with


Registration No. :

c) Organization :

i) Nature :

ii) State/Central undertaking :

iii) Public/ Pvt. Ltd. :

iv) Partnership :

v) Proprietary :

vi) Top Management. :


(Name, qualification &
position).
vii) Date of inception. :

viii) Commercial performance :


SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 VENDOR EVALUATION PROFORMA (TO BE FILLED AND SHEET 35 OF
SUBMITTED WITH THE TENDER) 40

over the past two years.

ix) Anticipated performance :


for the present year.

x) Details of facilities :

Floor space :

Key departments :

xi) ISO certification available :

2. Activity details:

a) Trader or manufacturer :

b) Products handled or manufac- :


tured.

c) Development (List of major :


Clients)

3. Manpower & Facilities

a) Skilled :

b) Semi and unskilled :

c) Welder :

d) Supervisor. :

e) Office Staff. :

f) Design Engineers. :

g) Production engineers. :

h) Draftsman. :

4. Proof of ability

4.1 Salient features of facilities available

4.2 Quality control procedures and practices

4.3 Documentation:
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART – 1)
2/DOC/002/R0 VENDOR EVALUATION PROFORMA (TO BE FILLED AND SHEET 36 OF
SUBMITTED WITH THE TENDER) 40

a) General reference standards. :

b) Standard specific to tender. :

4.4 List of Testing facilities :


available at Works.

4.5 Test certificates from CPRI/ERDA/ :


ITI or equivalent laboratory/
institution for offered items

4.6 i) List of major clients :

ii) List of major supplies made :


in last 3 years

4.7 Catalogues/leaflets for the :


offered items ,

5. TENDER DRAWINGS
The tenderer shall submit drawings showing plan, front and side elevation of
transformers, foundation details etc., and as requested in clause of section ‘C’ along with
the quotation itself.

6. DEVIATIONS
All deviation from the specification including the General conditions of contact shall be
set out by the tenderer clause by clause in this schedule. Compliance with specification
will be taken as granted in absence of mention of any departure from any of the clause of
this specification in this schedule.

Clause Deviations, if any


no.

7. LIST OF APPENDICES TO TENDER

The lists of appendices are as follows:

The appendices list forms an integral part of the document.

Dated at ………………………………………..

The ………………………………Day of ……………….2014

Witness …………………………………Signature (s) of Tenderer.


SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART-2)
2/DOC/002/R0 SHEET 37 OF
FORMAT FOR SUBMISSION OF TENDER (PART – 2 )
40
FORMAT FOR SUBMISSION OF TENDER
PART-2: COMMERCIAL

MANUFACTURING, TESTING & SUPPLY OF 6.6 kV, 2 MVA OUTDOOR TYPE


PACKAGE SUBSTATION FOR CONSTRUCTION POWER SUPPLY FOR INRP
PROJECT, TARAPUR

The scope covers manufacturing, testing at manufacturer’s works and supply of 6.6 kV, 2
MVA Outdoor Type Package Substation with all accessories & spares for construction
power supply for INRP Project, Tarapur.

Sr. Description/Reference Qty. Unit Basic Packing GST (in Freight Any Total
No. cost & % only) Charges Other Cost
(in Forwardi (in % Charges (in
Rs.) ng only) (inclusive Rs.)
charges Inclusive of all
(in % of GST taxes)
only)

1. 2 MVA, 6.6 kV Outdoor Type Package Substation

Manufacturing, testing and supply 01 No.


of Outdoor type 6.6 kV, 2 MVA
Package Substation comprising of:
i) 1 No. 6.6 kV, 630 A, 25 kA/ 1
sec. Vacuum interrupted SF6 gas
insulated circuit breaker suitable for
termination of incoming XLPE
Aluminium cables of size 3C x 300
Sq.mm complete with standard
accessories.
ii) 1 No. 2 MVA, 6.6 / 0.433 kV
Natural Ester Oil cooled
transformer (hermetically sealed
with corrugated tank), Dyn11, Off-
circuit tap changer on HV side with
tap changing range of -10% to +5%
in steps of 2.5% complete with
standard accessories.
iii) 1 No. 3 Phase, 4 Wire, 415 V
fixed type LT Switchboard with
Copper Busbar of rating 3200A and
a short circuit capacity of 50 kA for
1 sec. and consisting of following
incoming & outgoing feeders:
Incoming:
a) 3200A, 4P Microprocessor based
ACB - 1no.
Outgoings:
a) 250 A, 3P, MCCB with Thermal
Magnetic based releases - 2 nos.
b) 400 A, 3P, MCCB with Thermal
Magnetic based releases - 1 no.
c) 630 A, 3P, MCCB with Thermal
Magnetic based releases - 1 no.
d) 800 A, 3P, ACB with Thermal
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION: D
IP1/132/0500780 PACKAGE SUBSTATION (PART-2)
2/DOC/002/R0 SHEET 38 OF
FORMAT FOR SUBMISSION OF TENDER (PART – 2 )
40
Magnetic based releases - 1 no.
e) 1000 A, 3P, ACB with Thermal
Magnetic based releases - 1no.

Grand Total Charges


SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE SECTION - E
IP1/132/0500780 PACKAGE SUBSTATION SHEET 39 OF
2/DOC/002/R0 40
TENDER DRAWINGS

SECTION – E

TENDER DRAWINGS

Sl. No. Name of Drawing Drawing No.

Single –line diagram for 6.6 kV, 2MVA IP1/132/05027339/DWG/001/R0


1.
Outdoor type Package Substation
R
SPEC.NO. BHABHA ATOMIC RESEARCH CENTRE ANNEXURE
IP1/132/0500780 PACKAGE SUBSTATION SHEET 40 OF
2/DOC/002/R0 40
LIST OF APPROVED MAKES
ANNEXURE

Sl. No. DESCRIPTION OF EQUIPMENT PREFERRED MAKES


1. Natural Ester Oil Cooled Transformer Schneider /ABB/ Crompton Greaves/
equivalent
2. Transformer core Posco / Nippon/ Novex/ Ak Steels/
equivalent
3. HV Vacuum Switchgear BHEL/Jyoti Ltd./ Siemens/ ABB/
Schneider/L&T/ equivalent
4. LT Switchboard Schneider /GE/ ABB/ L&T/ Siemens/
equivalent
5. Numerical Relays Schneider/ Siemens/ Alstom/ ARGUS(ER)/
Micro Electrica Scientifica (Marketed by
L&T)/ equivalent
6. Electromagnetic Relays Alstom / Easun Reyrolle/ Omron/
Schneider/ equivalent
7. Current Transformer Pragati/Kappa/Automatic Electric /
Silkaans/Precise/Recco/ ECS/NPT/
equivalent
8. Potential Transformer Automatic Electric / Indcoil / Kappa /
Precise/ equivalent
9. ACB & MCCB Schneider / ABB/ GE/ L&T / Siemens/
equivalent