Calculation Table # 13

Latent Heat Gain due to Ventilation


qlv = 0.70 x Airflow x ΔWv - Eqn. 19

Area of Height Volume of Air Change


Area Covered Room of Room Room per Hour
(m²) (m) (ft³) (ACH)

Assembly Area 1280 6.70 302,902.92 2.83


Rectifier Room 1 125 5.70 25,165.38 8
Rectifier Room 2 120 7.00 29,668.66 8
Formation Room 1 578 5.70 116,364.74 12
Formation Room 2 578 7.00 142,904.06 12
Green Group Area 900 5.50 174,833.19 1.5

Total Latent Heat Gain due to Ventilation (qlv)


n Table # 13
due to Ventilation
w x ΔWv - Eqn. 19

Factor Airflow ΔWv qlv


(Btu-min/hr-ft³-°F) (ft³/min) (grains/lb) (Btu/hr)

0.70 14,287 84.50 845,071.39


0.70 3,355 84.50 198,470.99
0.70 3,956 84.50 233,986.86
0.70 23,273 84.50 1,376,594.82
0.70 28,581 84.50 1,690,555.04
0.70 4,371 84.50 258,534.58

lation (q lv) 4,603,213.68