Documente Academic
Documente Profesional
Documente Cultură
Distributed generation (DG) may improve the electric To minimize the impact on the system voltage, utilities prefer
distribution system reliability when properly integrated with DG to operate using the unity power factor control mode.
the existing grid. However, the addition of DG may However, even if DG operates in unity power factor mode, it
complicate protection coordination and voltage control. If not can impact the system voltage. Traditionally, voltage
properly handled, lower reliability and even a reduction in regulation practice has been based on radial power flow from
power quality may result. the substation to the load. Most SVRs are equipped with a
line drop compensation (LDC) feature to estimate line
Criteria for DG integration into existing distribution grids has voltage drop and regulate its output voltage to maintain
been defined by Standards [1] which provide requirements proper voltage at the load location. If DG is located
relevant to the performance, operation, testing, safety immediately downstream of a SVR, it may interfere with the
considerations, and maintenance of DG interconnections. proper operation of the SVR. This occurs when the feeder is
However, Standards do not provide methods for determining heavily loaded and DG generates a significant fraction of the
practicality, or whether the distribution system has load current. The SVR will sense relatively low load current,
appropriate current and voltage ratings, and other relevant causing the SVR to adjust its output voltage to lower
characteristics to allow interconnection. Standards do not magnitude than needed to maintain adequate voltages at the
prescribe methodologies for determining system limitations end of the feeder. The line voltage drop from the DG location
or DG unit protection and operating requirements. To to the load center still reflects heavy loading, but the SVR
optimize DG integration into a distribution system adequate output voltage has not been increased because of the low load
computer modeling techniques are needed. current sensed by the SVR. As a result, low voltage
conditions may occur at the load center. DG can cause high
This paper presents methodology to study DG and step voltages in situations such as when connected at the feeder
voltage regulator (SVR) operations for improved distribution end under light load conditions, or when connected to a
system voltage regulation. Section II discuses general distribution transformer that serves several other residences
requirements for voltage regulation specified by IEEE and introduces reverse power flow, counteracting the normal
Standards. Section III describes modeling techniques for SVR voltage drop.
and different types of DG. Section IV presents the impact on
voltage profile depending on DG location in the distribution DG voltage regulation is referenced to the system voltage.
system. Finally, Section V presents DG–SVR operation Since SVRs regulate the system voltage, adequate DG–SVR
coordination. operation coordination is important to maintain proper
voltages at the feeder and its load.
∗
Ljubomir A. Kojovic is with Cooper Power Systems, 11131 Adams Rd., Franksville, WI 53126 USA, e-mail: Ljubomir.Kojovic@CooperIndustries.com
III. MODELING TECHNIQUES neutral are required. SVRs regulate voltages independently in
each phase. Most distribution systems in the USA are of this
type.
A. Step Voltage Regulators
Three-wire ungrounded or uni-grounded systems are common
Distribution step-type voltage regulators (SVR) are used to outside of the USA. In these systems, loads are connected
maintain constant voltage for individual customers. SVRs phase-to-phase requiring SVRs to be connected in open or
hold line voltage within predetermined limits and ensure closed delta arrangement. SVRs cannot regulate voltages
consumer voltage magnitudes specified by Standards [2]. The independently from each other like in four-wire, multi-
SVR is an auto-transformer with many taps, usually designed grounded systems. This means by regulating voltages in one
to regulate voltages in the range ±10%, in 32 steps, with 5/8 phase, voltages on one of the other phases will also change.
percent voltage change per step. Two types of SVR By regulating two phases ±10% with two open delta-
constructions are defined by the C57.15 standard from the connected regulators, the third phase is also regulated ±10%.
Institute of Electrical and Electronic Engineers (IEEE): Type By regulating all three phases ±10% with three closed delta
"A" has the series winding located on the load-side, while connected regulators, the voltage on all phases will change
the Type "B" has the series winding located on the source- ±15% .
side. The SVR short circuit impedance is small (less than 1%) SVR
output
and in many short-circuit studies may be neglected. Vsource voltage
Vload
Series Feeder
CT R, X
winding
Load
SW SVR Control
Step PT R, X LDC
Shunt
Voltage Algorithm
Source winding Load Regulator
Side Side
During reverse power flow, the LDC must have adequate Figure 3 Matlab SVR Model
control algorithms to properly perform voltage corrections.
The reverse power flow may result from loop feed setups, Another method to model the SVR is to use a multi-winding
switching operations that reconfigure the feeder, or it may be power transformer model element. Circuit breaker model
due to DG supplying power back to the substation. There are elements perform switching of the SVR series winding taps.
several Reverse Power Flow modes of operation presently This modeling technique is effective to simulate real time
available in modern SVR controls. The impact of DG varies SVR operation by implementing the SVR control model as
with each of them. well as the LDC algorithms. The SVR’s bandwidth (low and
high voltage magnitudes) can be set to desired range and this
The SVR connection and number of units depends on the model will automatically run until the SVR tap is selected to
distribution system design. In four-wire, multi-grounded satisfy the set parameters.
systems, three wye-connected regulators with a grounded
3
Test Case: Figure 4 shows a single-phase circuit diagram of a previous case. Figure 7 shows a snapshot of the model
distribution system consisting of a power system source display for 1.0 p.u. source voltage. This time the SVR raised
equivalent model, feeder, SVR located at the beginning of the the voltage and stopped at the highest tap (Tap 16) increasing
feeder, and load. Figure 5 shows Matlab model that also the voltage at the load to 0.98 p.u. Even though the set
includes the SVR tap position indicator and metering voltage/bandwidth was not reached, the load voltage is within
displays. The system voltage is 7200 V, bandwidth ±1.2 V the specifed standard limits. When the source voltage
based on 120 V (0.99 p.u. low and 1.01 p.u. high voltage increased to 1.04 p.u., the SVR tapped down to bring the load
magnitudes). voltage within the bandwidth. Figure 8 shows that the load
voltage is within the voltage limits most of the time. LDC
Power System SVR Feeder Load setting for VR and VX:
0.2 Ω j2 Ω
CTprimary 400
VR = R = 0.2 = 1.33
PTratio 7200
120
CTprimary 400
7200 V
VX = X =2 = 13.3
Figure 4 Voltage Regulation using SVR PTratio 7200
120
1833.23 1808.00 1.1
P [kW ] P [kW]
1576.27 Q [kvar ] 1348.88 Q [kvar]
p.f. p.f.
1.08
0.76 0.80
V [p.u.] V [p.u.]
1.00 0.93 1.06
I [A] I [A] Upper Voltage
336.00 336.00
1.04 Limit
Source
1.00 V_out Load
Voltage
1.02
Voltage [p.u.]
Feeder
v2
V 1 Bandwidth
0.98 SVR
Conn1 Output
0.96 Voltage Lower Voltage
Raise Lower Limit
Power System Tap 16 0.94
0 0 Load
Bandwidth 0 0 0.92 Voltage
High 1.01 0 0
Low 0 0 0.9
0.99 TAP_1 TAP_2 0
0 0 Time
TAP_4 Vn = 7.2 [ kV]
0 0 Figure 6 Computer Simulation of SVR Operation without LDC
0 0
Tap 2 0 0 1 TAP_0 2018.62 1989.94
P [kW] P [kW]
Neutral Tap 1736.91 Q [kvar ] 1484.62 Q [kvar]
p.f. p.f.
Figure 5 Computer Model from Figure 4 (LDC not Engaged) 0.76
V [p.u.]
0.80
V [p.u.]
1.00 0.98
I [A] I [A]
371.00 353.00
Without LDC (Disabled). In this case, the LDC feature was 1.05 V_out Load
then the source voltage has a step change to 1.04 p.u., and Bandwidth 0
0
0
0
then returns back to 1.0 p.u. High
Low
1.01
0.99 TAP_1
0 0
TAP_2
0 0
0 0
At 1.0 p.u. source voltage, the voltage at the load is 0.93 p.u. TAP_4 Vn = 7.2 [k V]
0 0
because of the voltage drop on the feeder. Without LDC the Tap 2 0 0 0 TAP_0
Neutral Tap
SVR will not increase its secondary voltage since the SVR Figure 7 Computer Model from Figure 4 (LDC Engaged)
load side voltage is within the bandwidth. When the source 1.1
SVR
voltage increased to 1.04 p.u., the SVR tapped down to bring 1.08 Output
its secondary voltage back within the bandwidth. When the 1.06
Voltage
Upper Voltage
source voltage decreased to 1.0 p.u., the SVR raised the 1.04 Limit
Source
voltage back within the bandwidth. Without LDC, the load Voltage
Voltage [p.u.]
1.02
voltage was below the lower voltage limit for most of the 1 Bandwidth
time. This demonstrates that the SVR without LDC cannot 0.98 Load
provide satisfactory voltage regulation. Figure 5 shows a 0.96
Voltage
Lower Voltage
snapshot of the model display for 1.0 p.u. source voltage. Limit
0.94
0.92
LDC Enabled. In this case, the LDC feature was enabled so
0.9
the SVR can estimate the voltage drop on the feeder and 0
Time
accordingly regulate its output voltage. The power system Figure 8 Computer Simulation of SVR Operation with LDC Engaged
conditions and setting parameters are the same as in the
4
These generators can provide sustained fault current for faults Figure 9 Radial Feeder with DG
on the utility system.
Table 1 Feeder Power Consumption
The synchronous machine model represents the dynamics of P [MW] Q [Mvar] S [MVA] I [A]
a three-phase round rotor or salient-pole synchronous 3.6 2.9 4.6 462
machine. The model simulates both generating and motoring
modes. The electrical part of the machine is represented by a Figure 10 shows the Matlab model of the power system from
sixth-order state-space model. The model takes into account Figure 9. To visualize real and reactive power flow and to
the dynamics of the stator, field and damper windings. The monitor voltage magnitudes at Locations 1, 2, and 3, the Altia
equivalent circuit of the model is represented in the rotor q-d Design model was developed as shown in Figure 11 and
axis reference frame. The rotor is simulated as a salient-pole interfaced with Matlab.
or round (cylindrical) type.
Meters at three corners of Figure 11 monitor real and reactive
Voltage-Sourced Converters. To simulate operation of power coming from the system and/or DG, and real and
voltage-sourced converters (VSC) the Universal Bridge block reactive power consumed by the load. Three meters in the
from the model library may be used. This block implements a middle of Figure 11 show voltage magnitudes at Locations 1,
universal three-phase power converter that consists of up to 2, and 3. Two horizontal lines represent the lower and upper
six power switches connected in a bridge configuration. The voltage limits.
types of power switch and converter configuration are
selectable from the dialog box. The Universal Bridge block
Test Case #1: Figure 10 and Figure 11 show a test case when
allows simulation of converters using both naturally
DG is spinning but does not deliver any power. Both real and
5
due to voltage drop on the feeder is 0.94 p.u., which is below 1.08
1.04
Voltage [p.u.]
1.02
DG at Location 3
1
DG
at Loc
0.98 atio
n 2
0.96 Low Voltage Limit
0.94 DG a
t Lo
catio
n1
0.92
0.9
1 2 3
Feeder Location
Figure 12 Voltage Profile on the Feeder for Different DG Locations (DG
providing total real and reactive power)
Figure 13 Model from Figure 10 Visualizing Real and Reactive Power Flow
(DG provides total power for the load)
Figure 11 Model from Figure 10 Visualizing Real and Reactive Power Flow
(DG spinning, does not deliver any power)
DG – SVR operation coordination was simulated using the When DG is interconnected to the distribution system, it can
same test case from Section IV, a radial feeder with DG impact the system voltage profiles and interact with step-type
connected as shown in Figure 15. The SVR was located at the voltage regulator (SVR) operation. The computer modeling
beginning of the feeder. Initial assumption is that no DG is technique presented in this paper can effectively simulate the
connected to the feeder. To provide proper voltage at the SVR real time operation, representing in detail the SVR
load, the LDC must be enabled so the SVR can estimate the control and line drop compensation algorithms. All types of
voltage drop on the feeder and additionally increase the DG generators and controls methods can be modeled. DG–
output voltage above the set voltage. Figure 16 shows the SVR interactions and operation coordination can be studied
SVR increased the system voltage to 1.04 p.u. to satisfy the for different system conditions. Simulations can be enhanced
voltage requirements at the load. DG control of real power by visualizing operation and control of SVR and DG
delivery did not change. However, to deliver reactive power, components.
DG excitation voltage must be increased since the system
voltage regulated by the SVR is higher than in the previous
VII. REFERENCES
case. When DG operates at unity power factor the impact on
[1] “1547™ IEEE Standard for Interconnecting Distributed
the voltage profile along the feeder is small as shown in
Resources with Electric Power Systems”.
Figure 17. [2] ANSI C84.1-1995 “American National Standard for Electric
P, Q 1 2 3
Power Systems and Equipment – Voltage Ratings (60 Hz)”.
R
Load
[3] Lj. A. Kojovic, “Modern Techniques for Distribution System
X R X
Analysis using Electromagnetic Transient Programs”, The 7th
International conference of Power Systems Transients, IPST
SVR 2007, Lyon, France, June 4-7, 2007.
[4] Lj. A. Kojovic, “The Impact of Dispersed Generation and
DG DG DG
Voltage Regulator Operations on Power Quality”, CIGRE
Figure 15 Model to Study DG – SVR Operation Coordination Symposium – Power Systems with dispersed generation, Athens,
1.1
Greece, April 13-16, 2005.
1.08 [5] Lj. A. Kojovic, “Modeling Techniques for Studying DG
1.06
High Voltage Limit Interconnections to Distribution Systems”, CIRED, Turin, Italy,
June 6-9, 2005.
1.04 DG at Location 3
[6] Lj. K Lj. A. Kojovic, “The Impact of Dispersed Generation and
1.02
DG
at Loc Voltage Regulator Operations on Power Quality”, CIGRE
Voltage [p.u.]
atio
1
DG a
t Loca
n2
Symposium – Power Systems with dispersed generation, Athens,
SVR Regulated Voltage tion
to 1.04 p.u. No D
G
1
Greece, April 13-16, 2005.
0.98
DG at
Locati
1 SVR Regulated Voltage
on 3 Wisconsin. He has earned eight U.S. patents and authored more than
to 1.04 p.u. No D
G 150 technical publications.
0.98
0.94
0.92
0.9
1 2 3
Feeder Location
Figure 17 DG – SVR Operation Coordination (DG providing total real and
NO reactive power, operates at unity power factor)