The purpose of this document is to outline the Design Basis for the engineering of the 6 X 5.8 MW CO-
GEN POWER PLANT. This document covers the specifications for firefighting system suitable for
covering the facilities completely for various areas. Equipment and materials covered in the
specifications are subject to the referenced codes and standards.
Page | 3
S. No Description Units Data
M/s DANGOTE INDUSTRIES LTD.,
A Purchaser
NIGERIA
B Consultant ---
C Project 6 x 5.8 MW Co-Gen Power Plant
Kano, Sokoto, Zamfara, Jigawa,
D Site Location
Adamawa, Niger
Elevation above mean sea
E m +40
Level
F Nearest Airport Lagos, 120 kms away
G Nearest Harbour Lagos
Nearest road (National/State
H
Highway)
I Ambient Temperature
i Design (for Performance) °C 35
ii Maximum °C 45
iii Minimum °C 15
J Relative Humidity
i Design (for Performance) % 70
ii Minimum % 60
iii Maximum % 80
k Design Wet Bulb Temperature °C +30.0
L Wind Data
i Wind speed Km/hr 140
M Seismic data
i Zone (as per UBC) Zone 2A
N Rainfall
i Maximum in a single day mm 150
Average Annual rainfall
ii mm 1600
(Maximum)
Average Annual rainfall
iii mm 1100
(Minimum)
N Soil bearing capacity & depth As received from Customer
O Electrical system
i Variation in voltage % ±10%
ii Variation in frequency % ±5%
iii Combined variation % ±10%
iv Design Ambient for Electricals °C 50
P ELECTRICAL PARAMETERS
Page | 4
1 Voltage (V) V 415
1.1.0 2. CODES AND STANDARDS
The system designed primarily as per NFPA and as per project specifications.
3. DESIGN BASIS
3.1 GENERAL:
The proposed power plant is qualified as Ordinary Hazard Occupancy, according it following fire-
fighting systems envisaged:
Fire Hydrant system.
Smoke & Fire detection and alarm system (Addressable type).
Portable Fire extinguishers.
Medium Velocity water spray
Page | 5
Fire Hydrant, Addressable type fire alarm and
19 FHS MCC room
detection system and Fire extinguisher
20 Dump Hopper (Rice Husk) Fire Hydrant
21 Bucket Elevator (Rice Husk) Fire Hydrant
Genral:
Fire Fighting system:
The designed fire hydrant system consist of two numbers of pumps (one working and one
standby). The main pump is an electrical motor driven and standby pump is of diesel engine driven. In
addition to the above, there is two electrical motor driven jockey pumps considered.
The fire hydrants, water monitor, hoses and nozzles shall be located throughout the power plant as per
the approved fire hydrant GA drawing..
The hydrant network sized and analyzed to ensure that about 3.5 kg/cm² pressure is available at the
hydraulically remotest point in the system. The velocity in the hydrant main shall not exceed 3m/sec.
Water for Fire fighting purposes will be taken from the raw water cum fire water storage tank.
The fire alarm system consist of Multi sensor(Heat & Smoke) detectors, Heat detectors, fire alarm
panel, hooter, manual call point & Response Indicator etc. The detectors & manual call point shall be
install in all the electrical panel rooms, control room and battery room as per approved Fire Alarm
Schematic drawing.
The portable fire extinguishers shall consists of dry chemical powder type, carbon-di-oxide type,
and foam type fire extinguishers.
The medium velocity water spray system cosist the auto actuated deluge valve and water spray
arrangement for the cable cellar and fuel handling conveyors.
Hydrants shall be provided internally and externally as shown on the approved drawings. Internal
hydrants shall be provided at each landing of and escape staircase Landing valve shall be single headed
SS valve with one-63 mm dia outlets and 80 mm inlet conforming to IS 5290-1998. Landing valve shall
have flanged inlet and instantaneous type outlets and mounted at 1.2 m above the floor level.
Instantaneous outlets for fire hydrants shall be of standard pattern approved and suitable for 63 mm dia
fire brigade hoses.
Fire protection water supply distribution systems for all new installations shall be looped to provide
two-way flow, with sectional valves arranged to provide alternate water flow paths to any point in the
system
Page | 6
3.2.2 FIRE PUMP HOUSE
The System is designed such that the Water supply header and main pipe up to hydrant valve/landing
valves shall be kept pressurized by the jockey pump which shall start automatically on receiving the
impulse from the pressure switch in case of any pressure drop in the header. It shall stop at a preset
pressure as soon as pressure builds up in the header. For smaller fires, first aid hose reel would be used;
while hydrant valve would be used for bigger fires. In the event of fire out break, opening of hydrant
valve/hose reel will result in fall of pressure in the header and electric motor driven fire pump shall
come into operation automatically through the impulse from the pressure switch. The fire pump shall be
stopped manually only. In case the electric driven main fire pump fails to start; the diesel engine driven
pump shall come into action automatically on further fall of pressure and receiving impulse from
pressure switch. The setting of the pressure switches shall be done keeping the above sequence in
consideration
Fire pump house is part of hydrant system following are the main components of the Fire pump house.
a. JOCKEY PUMP
End suction type, horizontally mounted centrifugal pump, capable to deliver 10.8 m3/hr of clear water
at minimum 120 MWC, coupled to a suitably electric motor mounted on a common base frame and
coupling guard and fixing bolts etc.
PUMP DETAILS
MAIN ELECTRICAL ELECTRICAL DRIVEN
DIESEL ENGINE
S.N DESCRIPTION
DRIVEN PUMP
DRIVEN PUMP JOCKEY PUMP
1 MAKE KIRLOSKAR KIRLOSKAR KIRLOSKAR
HORIZONTAL SPLIT
END SUCTION TOP END SUCTION TOP
2 PUMP TYPE
DISCHARGE DISCHARGE
CASE PUMP
3 CAPACITY 284 m3/hr 284 m3/hr 10.8 m3/hr
TOTAL HEAD
4 @ 120 m @ 120 m @ 120 m
(m)
5 PUMP MODEL CPHM 125/32 UP 150/56 CPHM 40/32
Page | 7
6 QUANTITY 01 NO. 01 NO. 01 NO.
7 SUC. x DEL. 150 x 125 200 x 150 65 x 40
The Addressable Fire Alarm System designed as per technical specifications and project requirements.
Smoke, heat detectors are provided in the building. Manual Call Point is also provided at appropriate
locations.Hooters are also provided for notifications in plant at appropriate location.
The detection circuit is wired as a loop and up to 99 devices may be connected to each loop. The
detectors are essentially Conventional Detectors, with an address built in. The address in each detector,
is set by dial switches and the Control Panel is programmed to display the information required when
that particular detector is operated. Additional Field Devices are available which may be wired to the
loop for detection only ie: it is possible to detect a normally open contact closing such as DVP O/P, or a
normally closed contact opening. Sounders are wired in a minimum of two sounder circuits.
Following are the major components of the proposed addressable fire alarm system,
a.1 ADDRESSABLE MULTI SENSOR DETECTOR
The multi sensor (MSD) combines optical smoke detection, heat detection and microprocessor control
with analogue addressable communications. For smoke detection the MSD incorporates an improved
sensing chamber design, linked to sophisticated processing circuitry with smoothing filters. This helps
to eliminate the transient environmental noise conditions which can be the cause of false alarms. The
sensor’s performance is further enhanced by the integration of special algorithms which automatically
compensate for contamination of the sensing chamber. This enables the sensor to provide a consistent
level of sensitivity and increased immunity to unwanted alarms. In combined modes of operation both
the inputs from the optical and thermal sensors are processed using special algorithms before an alarm
decision is made. If the presence of smoke is detected above a threshold value for a period of time, or if
Page | 8
the heat sensor detects temperatures above 58 º C then an alarm condition will be generated. In “ heat
only ” mode only temperatures above 58 º C will generate an alarm condition.
a-7 SIREN
This siren is a loud noise-making device shall be use mass emergency evacuations, its selected effective
distance range is 1km in ideal flat windless conditions.
Fire alarm system shall be provided for the following areas as mentioned in the approved drawing.
Page | 9
7 FIRE PUMP HOUSE 0 8 0 1 1 0 0 0 9 0 0 0 1
CRUSHER CUM SCREEN
8 0 0 0 0 0 3 3 0 6 4 1 0 0
HOUSE
WTP EQUIPMENTS
9 0 4 0 1 1 0 0 0 0 0 0 0 1
BUILDING
COAL & LIME STONE
10 0 0 0 0 0 2 2 0 0 1 1 0 0
STORAGE YARD
TG BUILDING
11 0 2 0 0 0 0 0 0 0 0 0 1 2
DEAERATOR AREA
MASTER DELUGE VALVE
12 0 0 0 0 0 0 0 0 5 0 0 0 0
CONTROL PANEL
TOTAL 1 71 2 9 9 9 9 19 24 9 4 1 8
Fire extinguishers considered for the following areas as mentioned in the approved drawing.
10 COMPRESSOR ROOM 0 0 1 0 0 0 0
Page | 10
Total 19 7 9 4 1 6 6
Once the polymer melts, the conductors initiate contact with one another and communicate with the
control panel to sound alarms or activate suppressing systems.
Operation:
Medium Velocity Water Spray System For cable cellar/conveyors’:
The system is auto actuated wet pilot based medium velocity (MV) water spray system. Heat will be
sensed by Linear heat detection cables and will give fire signal to deluge valve panel. This signal will
start automatic sprayers through Deluge Valve. The system can also be started by Push Lever
(Emergency valve) on the Deluge Valve Trim.
The bypass line is provided on this spray system, so that the spray system can be manually operated
without any automation, in case need arises.
Page | 11