Sunteți pe pagina 1din 8

Switchboard Case option

Socket Mount model

Intelligent Applications Summary Features Summary


Revenue Meters Revenue Metering Measurements
Monitor compliance with energy supply contracts. ! Advanced, high accuracy revenue metering
Used to monitor electric power networks, service Energy suppliers can offer customized rates, flexible ! True RMS 3-phase voltage, current and power
entrances and substations, the ION 8000™ series billing, transformer/line loss compensation, and ! Harmonics, K-Factor, symmetrical
are the world’s most advanced socket-based web-based reporting. Energy consumers can audit components, sag/swell
energy meters, providing high accuracy metering their power requirements and confirm their bills.
with a wide range of capabilities. Internet-Enabled Communications
Co-generation and IPP Monitoring ! Supports ION, Modbus, DNP 3.0 protocols
The ION 8000 series meters give you the tools to Use the Extended Current Range option to ! Compatible with Itron MV-90® software
manage complex energy supply contracts that monitor bidirectional flow for both generation and ! Two RS-485 ports, one switchable to RS-232
include commitments to power quality. Integrate stand-by modes. ! One front panel optical port
them with our ION Enterprise™ software or other
Compliance Monitoring ! Optional built-in modem with ModemGate,™
energy management and SCADA systems
through multiple communication channels and Monitor compliance with international flicker allows modem access to RS-485 devices
protocols including MV90. and harmonics standards, IEC 61000-4-7 / 4-15. ! Optional Ethernet port with EtherGate,™ allows
network access to RS-485 device networks
ION 8000 series meters with the Extended Current Power Quality Analysis
Use the meters to measure percentage of system ! Access meter data through web browser, with
Range option are ideal for independent power user-configurable web pages
producers and co-generation applications that up-time in nines (i.e. 99.9% up-time). Find the
cause of transients, harmonics and sags. Analyze ! GPS synchronization of meter clock
need to accurately measure energy bi-directionally
problems and avoid repeat interruptions. ! Remote alarm notification and log receipt
in both generation and stand-by modes.
Demand and Power Factor Control On-Board Data Logging
Patented ION® technology lets you customize
Avoid penalties with automated load shedding, ! Waveform and fault recording, plus transient
metering or analysis functions at your workstation,
detection up to 65 µs at 60 Hz*
without any hard-wiring. Just graphically link a scheduling, peak shaving or capacitor bank control.
few drag-and-drop icons, or select default ! Sequence-of-events and min/max logging
Load Curtailment ! Scheduled or event-driven logging of up
setups, and you're ready to go.
Implement load curtailment and distributed to 800 parameters concurrently*
generation strategies.
Setpoints for Control and Alarms
Equipment Monitoring and Control ! Setpoint on any parameter or condition
Base your maintenance schedule on actual ! 1 second and half-cycle† operation
operating history. Meter all your utilities including ! Outage dial-back capability
Not all features listed are available with every gas, steam, water and more.
Optional Digital Inputs/Outputs
model. Please refer to the detailed descriptions Energy Pulsing and Totalization ! 4 KYZ digital outputs and 3 Form A digital
within, for a complete list of feature availability. Use digital I/O for KYZ pulsing, end-of-interval inputs, under glass
and totalization. ! 8 digital inputs for status/counter functions,
Instrument Transformer Correction 8 solid state relay outputs for control/pulse
Use the meter’s ITC feature to correct for less functions and 4 analog outputs through
accurate transformers, saving money and external I/O expander
improving accuracy. ! Pluggable connection for
serial RS232 communications
† Available only on ION 8400 and ION 8500 *Available only on ION 8500
8000 Series www.pwrm.com

Energy Display Front Panel Display ! Calendar supports division into 4 seasons
ION 8000 series meters have a bright, easy-to- ! Supports 5 daily profiles per season
read, backlit LCD display screen with adjustable ! Supports 4 rate periods per daily profile
contrast that provide a user-friendly interface to
! Automatic mid-season rate change support
configure meter settings or view power system
data. The front panel displays all metered values Instantaneous
or any of 31 pre-configured data display screens, ION 8000 series meters provide a choice of
including phasor diagrams and harmonics high-accuracy 1 second or high-speed 1/2 cycle†
histogram, or you can customize the display. measurements, including true RMS, per phase
and total for:
Revenue Metering ! Voltage and current
Energy ! Active power (kW) and
ION 8000 series meters offer revenue approved, Reactive power (kVAR)
Peak demand with date and time-stamp
fully bi-directional measurements, and monitor
! Apparent power (kVA)
energy in all four quadrants. The meters provide
all traditional active, reactive and apparent energy ! Power factor and frequency
parameters and can also be configured to ! Neutral current on form 39S, 76S meters†
integrate any instantaneous power parameter ! Voltage and current unbalance
to provide measurements like Volt-Hours, ! Phase reversal
Amp-Hours, etc. Energy registers can be logged
automatically or on a programmed schedule. Transformer and Line
! kWh (delivered and received) Loss Compensation
! kWh, kVARh and kVAh net ! Flexible compensation methods
(delivered - received) ! Easy configuration
! kWh, kVARh and kVAh total ! Updated every second
(delivered + received) ! Available through all supported protocols
View Time-Of-Use data via the front panel
! kVARh, kVAh delivered and received Instrument Transformer Correction
! Volt-hours, Amp-hours and KQ-hours The meters provide high-accuracy instrument
! Integration of any instantaneous measurement transformer correction, allowing users to use
lower-accuracy, lower-cost transformers while
Demand retaining high-accuracy transformer function.
ION 8000 series meters support all standard
demand calculation methods, including block, Accuracy and Approvals
rolling block, thermal (exponential), and predicted ! Independent certification to C12.20-1998,
demand. The meters can measure demand on any class 0.2 by MET Labs
instantaneous value and record peak (maximum)
! Independent certification to
and minimum demand with date and time stamps
IEC 60687 - Class 0.2S by KEMA
to the second. Peak demand registers can be reset
manually (password protected) or logged and reset ! Industry Canada Approval (AE-0924)
The meters display system reliability in nines, automatically on a programmed schedule. ! US approvals include California ISO, New
(i.e. 99.9% up-time). Measurements include: England ISO, ERCOT and New York State
! kW, kVAR and kVA demand, min/max ! Certified by Comision Federal de Electricidad
! Volts and Amps demand, min/max and LAPEM in Mexico, and INTI in Argentina
! KQ and Cumulative Demand
! Demand on any instantaneous measurement Power Quality Metering
Time-Of-Use Compliance Monitoring*
ION 8000 series meters provide comprehensive ! IEC 61000-4-7 harmonics and
time-of-use (TOU) metering, configurable in inter-harmonics
accordance with virtually any utility tariff structure. ! IEC 61000-4-15 flicker
Built-in Web server provides browser access to TOU register values can be recorded automatically, ! CBEMA/ITIC
extensive real-time meter data† at user-specified time intervals, at pre-scheduled
The meters can also be configured to monitor:
dates and times, or when internal or external
events occur. Registers can be reset manually ! EN50160
(password protected) or on a pre-programmed ! IEEE 519 and IEEE 1159
schedule. Measurements include:
Waveform Recording*
! Active, reactive and apparent energy TOU The ION 8500 can simultaneously capture all
! Active, reactive and apparent demand TOU voltage and current channels.
! Automatic recording of maximum (peak) ! Sub-cycle disturbance capture
demand during each tariff period ! The maximum number of cycles for
! 20 year calendar with automatic leap-year contiguous waveform capture is 86,176
and daylight savings time adjustment (based on 16 samples/cycle x 72 cycles)

2 * Available only on ION 8500 † Available only on ION 8400 and ION 8500
www.pwrm.com 8000 Series

! Up to 256 samples/cycle Data and Event Recording 3-phase and average voltage
! Dynamic range: Voltage inputs - 14 bits The ION 8500 is equipped with 4 MB of meter-based
effective; Current inputs - 18 bits effective nonvolatile memory for historical data storage, the
ION 8400 has 2 MB and the ION 8300 has 1 MB.
Measure Up-time Using Nines
The current electricity supply infrastructure can Traditional Load Profiling
typically provide electricity with 99.9% reliability The ION 8500 incorporates 800 channels via
(3 nines or 8.8 hours downtime a year). However, 50 data recorders, the ION 8400 is equipped with
any disruption is unacceptable for businesses in 320 channels via 20 recorders and the ION 8300
the digital economy that can require up to offers 32 channels via 2 data recorders. Channel
99.9999999%, (9 nines or 2 cycles downtime) to assignments are user-configurable for historical
effectively run their business model. Measure the trend recording of energy, demand, voltage, current,
number of nines of reliability with the 8000 series. power quality, or any other measured parameter.
3-phase and neutral current
Recorders can be triggered on a time interval
Out-of-Limit Detection
basis, on a calendar schedule, by an alarm/event
Detect, record, and report the specifics of voltage
condition, or manually.
or current imbalances and loss, frequency/power
factor variations, over and undervoltages, etc. High-Speed Data Recording†
The ION 8400 and ION 8500 feature high-speed
Harmonic Distortion Metering
“burst” recording (as fast as 1/2-cycle intervals) to
The ION 8300 meters present harmonic distortion store detailed disturbance or outage characteristics.
to the 31st, the ION 8400 to the 63rd and the Recording can be triggered by a user-defined
ION 8500 to the 127th (via ION Enterprise software), setpoint, or from external equipment. Gated
for voltage, current and neutral inputs. recording logs data only during the critical event
! Individual to the 40th (including magnitude, so that memory is conserved.
phase and inter-harmonics for the ION 8500)
Coincident Min/Max Recording
! Total even or total odd harmonics Displays a complete range of power parameters
Configure the meters to record the values of key
! Total harmonics (even + odd) parameters or equipment conditions coincident
! K-factor, Crest factor with an extreme condition, complete with
date/time stamping to the millisecond. For
Sag/Swell Detection example, record all feeder voltages and currents
The meters offer a sag/swell capture capability at the moment a peak demand condition occurs.
that can be used to analyze the severity and
potential impact of sags and swells. Event Recording
Events, sequence-of-events, and alarm conditions
! Magnitude and duration data suitable for are recorded and date/time-stamped to millisecond
plotting on voltage tolerance curves resolution. Record the details of power quality
! Excess or deficient energy during the event† events, including magnitudes, durations, and
! Per phase triggers for waveform recording* equipment status. Use information from multiple
or control operations GPS equipped meters to correlate system wide Unique vector diagram with magnitude and phase angle
! Analyze sags and swells with our events and equipment operation. can help reduce installation time
ION Enterprise® software Time Synchronization and GPS
Transient Capture* The meters have real-time clocks that allow
! Detect and record sub-cycle transients as data records and internal events to be date and
short as 65 µs at 60 Hz (78 µs at 50 Hz) time-stamped within milliseconds. Synchronize
them to:
Symmetrical Components Metering ! The meter's internal crystal (+/- 12ppm)
The meters measure zero, positive, and negative ! The line frequency of the electrical network
sequence components for voltage and current. being metered (+/- 10ppm), default setup
Calculation of phase unbalances using symmetrical ! External GPS receiver with +/- 1 ms accuracy
components can also be performed. When in use, the pre-selected COM port is used
Outage Dial-back exclusively for GPS synchronization input. View THD and individual harmonics through the front
When equipped with the outage dial-back option, panel display screen
the 8000 series can notify a pager or MV-90
when control power is disrupted.

† Available only on ION 8400 and ION 8500 * Available only on ION 8500 3
8000 Series www.pwrm.com

Logic, Math and Control Modbus master read capability lets you perform XML Compatibility
The meters can perform on-board calculations detailed sub-metering using low-cost instruments The meters can also exchange information using
for any measured value. Calculate true quantities (like our ION 6200 or other Modbus slave devices). industry-standard XML format. Its simple machine
from pulse inputs (e.g. BTU calculations). You The meters can use the data from the Modbus readable-format supports easy integration with
can also implement real-time billing schemes. network for recording, trending, alarming and will custom reporting, spreadsheet, database and
also display parameters like energy, reactive energy, other applications.
Mathematical Functions power factor, frequency, voltage unbalance etc.
Customize formulas using the following Modbus master write capability allows control Communications
operators: commands or data to be sent directly to Modbus Multi-Port, Multi-Protocol Access
! Arithmetic (+, x, -, ÷) slave devices (e.g. control I/O points, reset The meters offer multi-port access that provides secure,
! Comparison (>, <, =, ≥, ≤, ≠) parameters, etc.). simultaneous data sharing with utility systems and
Modbus mastering allows for detailed facility customers directly at the hardware level using a
! Logical (AND, OR, NOT, TRUE, FALSE, IF)
monitoring so customers can now achieve a better choice of communication standards and protocols.
! Trigonometric (SIN, COS, TAN, ASIN, ACOS, ATAN) understanding of where inefficiencies are located
! Math (PI, SQRT, POWER, SUM, SUMSQ, AVG, RMS, and develop strategic load shedding applications. Serial Ports
LOG10, LN, MAX, MIN) 1 RS-232/485 and 1 additional RS-485 port

Programmable Logic and Setpoints


Internet Connectivity depending on the ordering options selected.*
MeterM@il® ! Protocols: ION, DNP 3.0,
The meters offer 65 setpoints configurable for Modbus RTU, GPS
An Ethernet port enables automatic e-mail alarm
1-second or 1/2-cycle† operation. Use them to trigger: ! Baud rate: (RS-232) 300bps to 115,200bps
notifications or scheduled system-status updates.
! Audible and visible alarms MeterM@il messages can be received like any (RS-485) 300bps to 57,600bps
! Modem/pager dial-back e-mail message, at a workstation, cell phone, Infrared Data Port
! Data logging pager or PDA. Data logs can also be sent on an Front panel ANSI C12.13 Type 2
! Waveform recording* event-driven or scheduled basis via e-mail, while
conveniently accommodating firewall restrictions. ! Protocols: ION, Modbus RTU, DNP 3.0
! Relays
! Baud rate: Up to 19,200bps.
! Clearing and reset functions WebMeter™
! Relative setpoints An on-board Web server offers quick and easy Internal Modem
access to real-time values and basic power Available internal telephone modem features fast
Modbus Master quality information without special software. connect and ModemGate™, a gateway letting up
The ION 8400 and ION 8500 meters can both Built-in, user-configurable web pages display a to 31 additional devices share a meter’s internal
read and write data to Modbus slave devices. range of energy and basic power quality modem through a serial port.
This powerful feature lets ION meters collect information through web-enabled devices and ! Protocols: ION, Modbus RTU, DNP 3.0
data from a Modbus network, process it, then even supports basic meter configuration. ! Baud rate: Up to 33.6kbps
deliver the information through any of the
meter’s communication channels. Ethernet Port
Optional 10Base-T port offers direct access
through an Ethernet LAN/WAN and features
EtherGate™, which permits the direct transfer of
Multiport Communications
data between an Ethernet network and up to 31
devices via the meter’s serial ports.
! Protocols: TCP/IP, ION, Modbus TCP
! Speed: 10Mbps
Itron Software Support
The meters are fully compatible with Itron
software platforms including MV-90®, MVP,
MVLT and MVCOMM. Our 8000 series are the
only socket meters with a direct Ethernet
connection to MV-90.
Flash Memory-Based Firmware
! Perform upgrades via communications
without removing the meter from the site.
! Easily add new ION modules and features
as they become available.**

4 * On the ION 8300 meter, if Ethernet and modem options are chosen, no serial port is available. ** In hardware locked meters, the seal must be broken to accommodate these functions
Meter Security Installation\Connections Mounting & Dimensions
In addition to traditional meter anti-tamper Installation 8000 Series Switchboard Case
mechanisms, the meters offer a number of ! 4-Wire Wye, 3-Wire Delta
advanced security functions for automatic Front view
! 3 voltage and 3 current inputs
detection, recording and annunciation of:
! Optional fourth current input†
! Loss of PT or CT phase due to transformer
wiring tampering or transformer failure ! All inputs pass ANSI/IEEE C37.90-1989
surge withstand and fast transient tests
! PT or CT phase reversal tampering or
installation error Voltage and Current Inputs
! Resets of peak demand registers ! Directly connect 9S, 39S, 36S, and 76S
! Meter power up/down systems up to 277VAC line-to neutral,
or 35S system up to 480VAC line-to-line
Multi-level Security ! 3 voltage inputs: auto ranging from 57-277 V (9S)
The ION 8000 series meters offer multi-user,
and from 120-480 V (35S)
multi-level security. Access to meter information
can be controlled and customized for up to ! Standard current inputs auto-ranging from
16 designated users with security levels ranging 0.005 - 20A, 50A overrange
from read access up to Administrative rights. ! Low Current option inputs autoranging
from 0.001 - 10A
Diagnostics ! Extended Current Range option inputs
The ION 8000 series performs advanced self autoranging from 0.001 - 24A.
diagnostic checks of hardware, firmware, and Socket mount only. Side view
logged data at startup and on a continual basis.
Monitoring is continuous and irregularities are Forms
logged for retrieval via communications. Critical ! ION 8400/ION 8500: 9S, 39S, 35S, 36S, 76S
warnings or errors are indicated immediately on ! ION 8300: 9S, 35S, 36S
the front panel.
Power Supply
The Power of ION ION 8000 series meters can be powered by the
Thanks to patented ION® technology, you voltage source being monitored, from an auxiliary
can quickly add or rearrange functions with power pigtail, an AC or DC supply, low-voltage
drag-and-drop icons and a few clicks of a mouse. supply or through standard voltage operating ranges.
Imagine any new feature and build it with ION. Pick the power supply option that meets your needs.
Auxiliary Power Input
An optional external power supply input lets the
meters be powered by a separate AC or DC supply,
Mounting & Dimensions allowing the units to continue functioning before,
8000 Series Socket Mount during and after an outage. Avoid damage to meter’s
power supply from spikes when monitoring high
Front view voltage networks.
Rear View
Switchboard Draw-out Case
The Switchboard Case option gives you all the
benefits of the socket meters in a compact,
switchboard mount, draw-out configuration.
Quick disconnect system lets you “rack out” the
meter electronics in one easy action, without having
to manually disconnect wires, including I/O wiring.

I/O Box
Top view

Side view
237.00 mm (9.33 In)

204.50 mm (8.05 In)

End View

† Available only on ION 8400 and ION 8500 5


8000 Series www.pwrm.com

Inputs/Outputs Measurement Specifications


ION 8000 series meters can be ordered with
optional built-in I/O comprising 4 KYZ digital Parameter Accuracy Extended Current Range Option
± %Reading Accuracy#
outputs and 3 form A digital inputs.
± (%Reading+ %FS##)
An optional external I/O Expander provides
additional I/O capabilities and standard serial Voltage (l-l) (l-n) 0.1% 0.1%
port connections for the meters. The I/O Expander Frequency (47 - 63 Hz) 0.02 Hz 0.02 Hz
offers an easy connection to external equipment Current (I1, I2, I3)† 0.1% 0.1% + 0.0001%
and a physical interface for energy management
Current (I4)† 0.4% 0.4%
systems. Meter operation remains unaffected during
installation and configuration of I/O. The I/O Expander kW, kVAR, kVA (Unity PF) 0.2% 0.2% + 0.00005%
can be equipped with: kW, kVAR, kVA (-0.5, 0.8 PF) 0.3% 0.3% + 0.00001%
! 8 digital inputs and 8 digital outputs kWh, kVARh, kVAh Class 0.2* class 0.2*
(4 Form A and 4 Form C solid state outputs) Power Factor at Unity PF 0.5% 0.5%
! Pluggable connections for Harmonics (to 63rd)** 1% 1%
serial RS-232 communications
Harmonics (to 40th) IEC 61000-4-7 IEC 61000-4-7
! 4 analog outputs can replace the 4 Form A
digital outputs. 2 analog output options are K Factor 5% 5%
available, 0 to 20mA (scalable 4 to 20mA) Crest Factor 1% Full Scale 1% Full Scale
and -1 to +1mA (scalable 0 to 1mA). † Accurate ranges: Standard = 0.05-20A (overrange to 50A);
# At a nominal voltage of 120V +/- 30% (I-I or I-n)
## Percent of Full Scale Current (20A) Extended Current Range option = 0.01-20A (accurate overrange
Software Integration *
**
Refer to Compliance section on page 7
On ION 8400 and ION 8500 meters only; ION 8300 to 31st
to 24A); Low Current option = 0.01 - 10A

With their extensive communication capabilities,


Display resolution meets or exceeds accuracy.
the meters can be integrated into energy
management or automation control systems.
ION Enterprise Software User Programmable Log Capacity
ION 8000 series meters are compatible with Example Log Configurations:
Power Measurement’s ION Enterprise software. ION 8300 ION 8400 ION 8500
ION Enterprise is a comprehensive PC based
Event 500 Events 500 Events 500 Events
power monitoring, analysis and control system
that lets you take advantage of all the advanced Data 85 daysA 340 days B 0.5 yearsA 2 years B 1 yearA 4 years B 280 daysA 3 years B
features of the ION 8000 Series. Waveform - - 6C 6C 24 D 24 D
A16 parameters recorded every 15 minutes B16 parameters recorded hourly
ION Setup™ Software
Con each of 6 channels at 128 samples per cycle for 14 cycles Don each of 6 channels at 16 samples per cycle for 96 cycles
The meters are further enhanced by ION Setup
for Windows, a software solution that displays
real-time data from your power monitoring devices
and provides device configuration capabilities. ! Dielectric withstand: 2500Vrms, 60Hz for 1 min. Power Supply
(ANSI C12.1-1995/C12.16-1991/C12.20-1998) Standard Power Supply, 120-2277 VAC
ION Setup lets you create a network of sites and
! Surge withstand: 6kV peak (1.2/50 uS) voltage surge ! Type: 3-Phase powered from voltage sensing inputs
devices, so that the meters are easy to find and
L-L and L-GND (IEC 255-4) ! Burden: Max, 4W, 6.6VA / phase
the communication links are ready whenever you
ANSI/IEEE C37.90.1-1989 SWC and Fast Transient ! Form 9S/39S, 36S/76S: 120-277
want to upgrade the firmware or make any Common and transverse modes. ANSI C62.41
configuration changes to your meters or network. -15%/+20% VLN rms, 47-63Hz
! Impedance: 5 MΩ/phase ! Form 35S: 120-480 (-15%/+20%) VLL rms, 47-63Hz
As well, the Setup Assistant within ION Setup
guides you through the common setup Current Inputs ! Ride-through: Min:100ms 6 cycles at 60Hz at 96 VAC
requirements for ION meters, simplifying and ! Low Current option: Start at 0.001A, accurate from ! Surge withstand: 6kV/0.5kA peak (100kHz Ring Wave)
accelerating the setup process. 0.01 - 10A RMS. Meets ANSI Class 10 and IEC 687 — ANSI C62.41 6kV/3kA peak (1.2/50-8/20 uS)
ION Setup is available to all ION 8000 series In = 1A or 2A, Imax=10A. Overload 50A RMS for 1 voltage surge L-L and L-GND ANSI C62.41
owners at no additional charge. second, non-recurring Standard (Low Voltage) Power Supply, 57-770 VAC
! Standard: Start at 0.005A, accurate from 0.05 - 20A, ! Type: 3-Phase supply, drawing off voltage inputs
Specifications overrange to 50A RMS. Meets ANSI Class 10 or 20 ! Burden: Typical: 3W, 5VA/phase, 3-Phase operation
and IEC 687 In=5A, Imax=20A. Overload: 500A RMS Max: 4W, 6.6VA/phase,3-Phase operation
Voltage Inputs for 1 second, non-recurring ! Form 9S/36S/39S/76S: 57-70
! Inputs: Va, Vb, Vc, Vref (9S/39S); ! Extended Current Range option: Start at 0.001A, (-15%/+20%) VLN rms, 47-63 Hz
Vab, Vcb, Vref (35S); Va, Vc, Vref (36S/76S) accurate from 0.01 - 24A RMS. Meets ANSI Class 10 ! Form 35S: Unavailable
! Form 9S/36S/39S/76S steady state: or 20 and IEC 687 In=1A, 2A or 5A, Imax=20A. ! Ride-through: Min 100ms or 6 cycles 60Hz at 46 VAC
Standard 57-277 (±15%) VLN rms† Overload: 500 RMS for 1 second, non-recurring
! Surge withstand: 6kV/0.5kA peak (100 kHz Ring
! Form 9S/36S/39S/76S overload: Standard power ! Surge withstand: 6kV peak (1.2/50 uS) voltage surge Wave) — ANSI C62.41, 6kV/3kA peak (1.2/50-8/20
supply: 120-277 (+/- 20%) VLN rms† L-L & L-GND Common and Transverse modes uS) voltage surge L-L and L-GND ANSI C62.41
Low Voltage power supply: 57.7-69.3 (+/- 20%) ! Burden: Low current switchboard - 0.05VA per phase
VLN rms† at 1A; Standard switchboard - 0.20VA per phase at
! Form 35S steady state: 120-480 (+/-15%) VLL rms† 5A; All socket mounts - 0.05VA per phase at 5A
! Form 35S overload: 120-480 (+/-20%) VLL rms
for 6 hrs max†

6 * Available only on ION 8500 †Specifications are limited by the operating range of the power supply if a non-aux power supply is used.
www.pwrm.com 8000 Series

Auxiliary Power Pigtail, 65-1120 VAC Packaging Standards Compliance


! Type: 1-Phase supply, powered through external ! Socket meters: Forms 9S, 35S, 36S, 39S, 76S
cable with Grounded U-Plug
Accuracy and Approvals
(ANSI C12.10-1997)
! AC: 65-120 (+/- 15%) VLN rms, 47-63Hz
! Independent certification to C12.20-1998,
! Switchboard case: (FT-21 style) Forms 9, 35, 36
DC: 80-160 (+/- 20%) VDC class 0.2 by MET Labs.
! Sealing/Cover: ANSI C12.1-1995/ANSI
! Burden: Typical: 10VA, Max: 20VA C12.10-1997/ANSI C12.16-1991 ! US approvals include California ISO, New
! Ride-through: Min: 100ms 6 cycles 60Hz at 46 VAC ! Weatherproof: Dustproof, raintight (as per UL50-1987 England ISO, ERCOT, and New York State
! Surge withstand: 6kV/0.5kA peak (100kHz Ring Wave) raintightness test) ! Industry Canada approved (AE-0924)
ANSI C62.41 6kV/3kA peak (1.2/50-8/20 uS) ! Base finish: Reinforced plastic UV and Corrosion ! Independent certification to IEC 60687 -
voltage surge L-L and L-GND ANSI C62.41 resistant (Class II) Class 0.2S by KEMA
Auxiliary Power Pigtail, 160-2277 VAC ! Cover finish: Polycarbonate, UV and Corrosion ! Certified by Comision Federal de Electricidad
! Type: 1-Phase supply, powered through external cable resistant (Class II) and LAPEM in Mexico, and INTI in Argentina
with Grounded U-Plug ! All inputs pass ANSI/IEEE C37.90-1989 surge
Shipping
! AC: 160-277 (+/- 20%) VLN rms, 47-63Hz withstand and fast transient tests
! Switchboard format: 15lbs / 6.8 kg; 12 x 12 x 15.5
DC: 200-350 (+/- 20%) VDC
inches; 30.48 x 30.48 x 33.97 cm
! Burden: Typical: 10VA, Max: 20VA Safety/Construction
! Socket format: 8 lbs / 3.7 kg; 10.5 x 10.5 x 17 inches; ! ANSI C12.20-1998 American National
! Ride-through: Min: 100ms 6 cycles, 60Hz at 96 VAC
26.67 x 26.67 x 43.18 cm
! Surge withstand: 6kV/0.5kA peak (100kHz Ring Wave) Standard for Electricity Meters 0.2 and 0.5
ANSI C62.41 6kV/3kA peak (1.2/50-8/20 uS) Communications Accuracy Classes
voltage surge L-L and L-GND ANSI C62.41 Serial ports (Via breakout cable or I/O box)
Electromagnetic Immunity
! RS-232E (DTE) and/or RS-485 (shielded twisted pair)
Environmental Conditions ! IEEE C.37-90.1-1989: IEEE Standard Surge
! Duplex: Full (RS232E), Half (RS485)
! Operating temp: -40°C to 85°C (-40°F to 185°F) Withstand Capability (SWC) Tests for
! Display operating temp: -20°C to 60°C (-4°F to 140°F) ! Isolation: Optical Protective Relays and Relay Systems (ANSI)
Internal Modem
! Storage temp: -40°C to 85°C (-40°F to 185°F) ! ANSI C12.20-1998: American National
! Humidity: 5%-95% non-condensing ! Interface: 33.6Kbps internal modem Standard for Electricity Meters 0.2 and 0.5
! Duplex: Half Accuracy Classes
Digital Inputs ! Data rate: 300bps-33.6kbps ! IEC1000-4-2 (EN61000-4-2/IEC801-2):
! 8 inputs: S1-S8, SCOM (through I/O Expander). (automatic data rate detection is supported)
Self-excited, dry contact sensing, no external voltage
Electrostatic Discharge (B)
! Interface: RJ11 (Tip and Ring), or RJ31
required. +30 VDC differential between SCOM and S1 ! IEC1000-4-3 (EN61000-4-3/IEC801-3):
! Governmental approvals: FCC Part 68 (USA),
through S8 inputs. Or 24-130 VDC externally excited. Radiated EM Field Immunity (A)
Industry Canada CS-03 (CAN)
! Minimum pulse width: 20 ms Infrared Data Port:
! IEC1000-4-4 (EN61000-4-4/IEC801-4):
! Maximum input transition rate: 50 transitions/second Electric Fast Transient (B)
! Interface: ANSI C12.13 Type 2 Optical Port
! Scan time: 20ms ! Baud rates: 300-19200bps
! IEC1000-4-5 (EN61000-4-5/IEC801-5):
! Timing resolution: 1ms, with 2ms accuracy ! Duplex: Half
Surge Immunity (B)
! Isolation: 1000Vrms, 60Hz for 1 minute to meter ! Protocols: ION 2.0, Modbus RTU, DNP 3.0 ! IEC1000-4-6(EN61000-4-6/IEC801-6)
! 3 additional internal inputs available through ! Location: Front of Meter
Conducted Immunity
optional on-board I/O
Ethernet ! ANSI C62.41: Surge Immunity
Solid State Outputs ! Interface: IEEE 802.3-1993, Electromagnetic Emission
! 8 solid state outputs: C-1, C-2, C-3, C-4 ISO/IEC 8802-3:1993 (Ethernet) 10BASE-T ! FCC Part 15 Subpart B, Class A:
(Form C) - through I/O Expander A-1, A-2, A-3, A-4 ! Cabling: Unshielded twisted-pair cable,0.5mm Class A Digital Device, Radiated Emissions
(Form A) - supported through I/O Expander (24AWG). Max. segment length: 100m
! Max. load voltage: 200 VAC/DC* ! Connectors: RJ45 Modem
! Max. load current: 100mA ! Data rates: 10Mbps, half duplex ! FCC Part 68
! On resistance: 30Ω (typical), 50Ω (max) Display ! Industry Canada CS-03
! Off resistance: 400MΩ (minimum) ! Type: FSTN Liquid Crystal Display (LCD)
Miscellaneous
! Isolation: 3750Vrms, 60Hz for 1 minute to meter ! Resolution: 240 x 67 pixels
! Optical Communications Port:
1000Vrms, 60Hz for 1 minute (between outputs) ! Size: 72 (H) x 32 (W) mm
ANSI C12.13-1991 Type 2
! Update rate: 20ms ! Temperature: Operational from -20°C to +60°C
! Maximum output transition rate: 50 transitions/s ! Backlight: LED (Green)
! 4 additional internal outputs available through ! Backlight timeout: 0 (always on) - 120 min
optional on-board I/O ! Standards compliance:
Exceeds ANSI C12.16-1991, IEC 687
Analog Outputs
! 4 analog outputs: Supported through I/O Expander
Output range: 0 - 20mA (scaleable to 4 - 20mA)
or -1 to +1mA (scaleable to 0 - 1mA)
! Max. load: 500Ω (0-20mA), 10KΩ (-1 to +1mA)
! Isolation: 3750Vrms, 60Hz for 1 minute to meter
2000Vrms, 60Hz for 1 minute
! Accuracy: +/- 0.3% (% of Reading) at 23° C
! Accuracy drift: 100ppm/° K ISO 9002-94
! Resolution: 12 bits Registration Cert# 002188
! Update rate: 1 second Quality Assurance: ISO 9002-1994

* 120V AC/DC for internal digital outputs 7


8000 Series

Some features are optional. Meet the World Leader


To identify standard and optional features, please see the ‘Product Order Forms’ at www.pwrm.com.
Power Measurement is the leading provider of
Features and Options List ION 8300 ION 8400 ION 8500 enterprise energy management systems for energy
Power, Energy, and Demand suppliers and consumers worldwide. Our ION®
Voltage/current per phase, average, unbalance " " " web-ready software and intelligent electronic devices
Power: real, reactive, apparent, power factor, frequency " " " comprise a complete, real-time information and
Energy: bi-directional, total, import, export, net " " " control network that supports billing for complex
Demand: block, rolling block, thermal, predicted " " " energy contracts and helps improve power quality,
Power Quality reduce energy costs and keep operations running
Sag/Swell monitoring " " " enterprise-wide, 24 hours a day. Our reputation for
Symmetrical components: zero, positive, negative " " " unparalleled value, quality and service is based on
Transient detection, microseconds 65 nearly two decades of innovation and experience.
Harmonics: individual, even, odd, total up to 31st 63rd 63rd
Harmonics: magnitude, phase and inter-harmonics 40th Worldwide Headquarters
Sampling rate, maximum samples per cycle 128 128 256 2195 Keating Cross Rd.
Flicker, (harmonics to EN50160, IEC 6100-4-7/4-15) " Saanichton, BC, Canada V8M 2A5
Configurable for IEEE 519 - 1992, IEEE159, SEMI " Tel: 1-250-652-7100 Fax: 1-250-652-0411
Uptime in number of nines " " " email: sales@pwrm.com
Logging and Recording
Europe
Standard memory capacity 1MB 2MB 4MB
Schulstrasse 6
Min/max logging for any parameter " " "
91320 Ebermannstadt, Germany
Historical logs, maximum # of channels 32 320 800
Tel. +49 (0) 9194-724 765
Waveform logs, maximum # of cycles 96
Fax +49 (0) 9194-724 766
Timestamp resolution in seconds 0.001 0.001 0.001
email: pme@pwrm.com
GPS time synchronization " " "
Communications and I/O
RS-232/485 ports 1 1 1
RS-485 ports 1 1 1
Ethernet ports 1 1 1
Infrared optical port 1 1 1
Internal modem 1 1 1
DNP 3.0 through serial, modem and I/R ports " " "
Modbus RTU slave on serial, modem and I/R ports " " "
Modbus RTU Master on serial ports " "
Modbus TCP through Ethernet " " "
EtherGate, data transfer between Ethernet & RS-485 " " "
ModemGate, data transfer between internal modem & RS-485 " " "
MeterM@il, logged data and alarms via e-mail " " "
WebMeter, on board web server " " "
Internal KYZ outputs 4 4 4
For the most up to date information, go to
Internal Form A inputs 3 3 3
External analog outputs 4 4 4 www.pwrm.com
External digital status inputs/counter 8 8 8
External solid state outputs 8 8 8 Toll free 1-866-466-7627
Setpoints, Alarming, and Control 866-ION-SMART
Setpoints, minimum response time 1 second 1/2 cycle 1/2 cycle USA And Canada only
Setpoints, number of 65 65 65
Math, logic, trig, log, linearization formulas " " " Revision Date: May 2003
Single & multi-condition alarms " " " © 2003 Power Measurement. Printed in Canada 70100-0120
Call-out on alarms " " " ION, ION Enterprise, ION 8300, ION 8400, ION 8500,
Dial-out on outage " " " MeterM@il, WebMeter, EtherGate, ModemGate are trademarks
of Power Measurement. MV-90 is a registered trademark of
Revenue Metering and Standards Itron Inc. Any reproduction or re-transmission in whole or in
ANSI C12.16 accuracy compliant " " " part of this work is expressly prohibited without the prior
ANSI C12.20 0.2 compliant " " " consent of Power Measurement. Information contained herein
IEC 60687 0.2S compliant " " " is subject to change without notice. Any technical assistance
provided by this Power Measurement document for system
IEC 60687 accuracy class 0.5S compliant " " " design or configuration shall be deemed to be a proposal and
ANSI class 10; IEC 1A, 2A nominal, 10A max. " " " not a recommendation. The responsibility for determining the
ANSI class 10, 20; IEC 5A nominal, 20A max. " " " feasibility of such proposals rests with the original purchaser
ANSI class 10, 20; IEC 1A, 2A, 5A nominal, 20A max. " " " and should be tested by the original purchaser.
MV-90 on serial, modem & Ethernet ports (if present) " " "
Multi-year scheduling: hourly activity profiles " " "
Transformer/line loss compensation " " "
YOUR LOCAL