Documente Academic
Documente Profesional
Documente Cultură
Bottom of
I. INTRODUCTION the Bottom
oil
winding
H
temperat Temperature
otspot temperature is one of the most important ure rises(C)
parameters when defining thermal condition and
Figure 1: Basic thermal model
overloading capability of a transformer. Thermal ageing and
The basic calculation method, given as an example in (1)
degradation of the insulation affects the transformer lifetime,
for an ON transformer, relies on the measured top oil
since cellulose degradation caused by overheating is
temperature and the approximation of the temperature
irreversible. It is widely accepted that the insulation
difference between the hotspot temperature and the top oil
degradation approximately doubles with every 6°C increase of
temperature.
temperature [1]. Therefore an accurate prediction of hotspot 2m
§ I · (1)
temperature is important for both manufacturers and utilities. 4 HS 4 TO ' 4 HR ¨ ¸
There are a few methods to measure the hotspot temperature, © IR ¹
one of which is using fibre optical temperature sensors where HS is the hotspot temperature (°C), TO is the
positioned at the predicted hotspot of the windings. The measured top-oil temperature (°C) and HR is the rated
thermal sensors, attached to the end optical fibre, are usually hotspot temperature rise over top-oil temperature rise (°C)
placed between the insulated conductor and spacer, and their obtained during the heat-run test, and m is the winding
signals via optical fibre transmitted out of the tank. Significant exponent – an empirical parameter recommended by the
improvement over the years overcomes the fibre optic being loading guides.
too fragile and needing delicate handling. By using this However, this traditional hotspot temperature calculation
method, accurate measurement of hotspot temperature can be method has been shown inadequacy when compared to the
done. actual data measured by fibre optic sensors[4, 5]. It has been
IEEE and IEC Loading Guides [2, 3] have been used to noticed by [6, 7] that during overload conditions there is a
calculate hotspot temperature, by using data obtained through time lag between the top-oil temperature rise and the duct oil
heat-run test and empirical parameters. temperature rise. This phenomenon results in winding hotspot
temperature greater than predicted by the IEEE Loading
Mr. Ishak appreciates the sponsorship given by University Tun Hussein Guide Clause 7 method [3]. In [6] equations were proposed to
Onn, Malaysia to allow him studying at the University of Manchester for the account for the duct oil temperature, the change of winding
PhD degree in Electrical Power Engineering. resistance with temperature, the change of oil viscosity with
the temperature of the oil exiting the winding ducts is the 180 180
160 160
140 140
100 100
be calculated as: 80 80
TH T A ' T TO ' T H
60 60
(2) 40
20
40
20
temperature (°C), LJTO is the top-oil temperature rise over the OFAF Example, Steady state, Tamb=30 deg C ODAF Example, Steady state, Tamb=30 deg C
180 180
ambient (°C) and LJH is the winding hotspot temperature rise 160 160
140 140
120 120
100 100
60
80
60
20
40
20
130 130
110 110
1.5
100 100
90 90
40
80 80
70 70
AmbientTemperature
130
110 120
20 0.5
0 5 10 15 20 25
100
Time (h)
100
90
110 60 60
110 500 1000 1500 2000 2500 3000 500 1000 1500 2000 2500
Time (minutes) Time ( minutes)
100 100
Clause 7 Annex G
Ho t Sp o t te mp e ra tu re , C
Ho t Sp o t te m pe ra ture , C
90 90
60
70
60
condition
50 50
40 40
25 30 35
Tim e( h o u rs)
OFAF Co o li n g
40 45 50 25 30 35
Ti m e(h o u rs)
40 45 50
V. CALCULATED LOSS- OF -LIFE FOR TRANSFORMERS
ODAF Co o li n g
120 140
110
130
120
Experimental evidence indicates that the relationship
100
110
between insulation degradation to time and temperature
t m p era tu re, C
H ot Sp o t te mp e ra tu re , C
90 100
80
80
Clause 7 Annex G
Figure 4: Hotspot temperatures under daily load condition Normal life for most transmission transformers is
considered to be around 40 to 50 years, due to the
For typical daily load and ambient temperature profiles, conservative way of operating transformers by the utilities.
there results obtained show that the Annex G method predicts The hotspot temperature for thermally upgraded cellulose to
higher hotspot temperature than the clause 7 for all the cases attain a one per unit life is 110°C based on an assumed
except for OFAF cooled transformer. The hotspot ambient temperature of 30°C plus 65°C average winding
temperatures calculated by both methods show very close to gradient over ambient plus a 15°C allowance for the hot spot
each others. gradient over average winding temperature. Using hotspot
temperature of 110°C yields a per unit life=1, and lower than
C. Case 3: four hours overload condition 110°C yields a more than 1 per unit life, indicating an
In this case study, it is assumed that four hours overload of extended lifetime.
1.4 pu occurs on a transformer, with a constant loading Instead of using the per unit life, the IEEE Loading
condition of 0.7 pu before and after this overload period. The Guide[3] introduced the idea of relative aging rate. The
ambient temperature is assumed constant at 30°C. The hotspot accelerating aging factor in (5) can be derived and is defined
temperatures for the four transformers were calculated using as:
the two methods and the results are shown in figure 5. ª B B º
« »
As shown in figure 5, the Clause 7 method produces lower ¬« ( 4 273) (4 2 7 3 ) ¼»
FA A = e H ,R H
(5)
hotspot temperature than the Annex G method, except for the
where FAA is insulation aging acceleration factor, B is an
OFAF cooled transformer. The test data for this OFAF
ageing rate constant, typically 15000, and H,R is winding
transformer reported in [7], indicated that the hotspot
hotspot temperature at rated load (95°C if W/A,R=55°C and
temperature was 9.1 to 13.5°C lower than what was calculated
110°C if W/A,R=65° C )
by the Clause 7 method. It seems that for this case that the
If the value of FAA is greater than 1, the hotspot temperature
Annex G method agrees with the test result. Once again, for
is greater than 110°C, suggesting accelerated loss of life.
the ODAF transformer, the Clause 7 method underestimates
Since insulation ageing is a cumulative process, an
the hotspot temperature with a big difference as compared to
equivalent ageing acceleration factor can be expressed as a
the Annex G method. This comparison indicates the
summation of (5) over discrete time intervals, averaged over
limitation of the Clause 7 approach in its use to estimate the
the total time elapsed [3]:
hotspot temperature under overload conditions. The
N
VII. REFERENCES
¦F
n 1
AAn 'tn (6) [1] McNutt, W.J., Insulation Thermal Life Considerations for
FEQA N
Trasnformer Loading Guides. IEEE Transactions on Power
¦ 't
n 1
n Delivery, 1992. vol.7(no.1): p. 392-401.
[2] IEC 354:1991, Guide To Loading of Oil-Immersed Power
where FEQA is the equivalent aging factor for the total time Transformers. 1991.
period,t, 'tn is the time interval in hour, N is the total [3] C57.92-1995, I., IEEE Guide for Loading Mineral-Oil-Immersed
Transformers. IEEE Standard C57.92-1995, 1995. Institute of
number of time intervals, FAA,n is the ageing acceleration Electrical and Electronic Engineers (New York).
factor for the temperature which exist during the time interval [4] CIGRE WG 12-09, Direct Measurements of the Hot Spot
Temperature of Transformer. Electra 1990, 1990. Vol.129: p.
'tn . pp47-51.
The calculation of loss-of-life for case study 2 and case [5] Nordman H., Hironnimi E., Pesonen A.J., Determination of Hot
Spot Temperature Rise at Rated Load and at Overload. CIGRE
study 3 are shown as in table 1 and table 2. In table 1, the Paper, 1990. 12-103.
estimated loss-of-life over a daily load and ambient [6] Pierce, L.W., Predicting Liquid Filled Trasnformer Loading
temperature profile for all the four transformers are not greater Capability. IEEE Transactions on Industry Applications, 1994.
than 1 pu. Vol.30 (1): p. 170-178.
[7] . Pierce, L.W., An Investigation of The Thermal Performance of An
Table 1: Calculated loss-of-life under daily load Oil Filled Transformer Winding. IEEE Transactions on Power
Delivery, 1992. Vol.7 (3): p. 1347-1358.
Loss of ONAN
life, (hours) ONAF OFAF ODAF
Clause 7 0.20 1.00 0.16 0.38 APPENDIX: TRANSFORMER DATA
Annex G 0.15 0.84 0.18 0.21
The two methods show a reasonable agreement since the Unit ONAN ONAF OFAF ODAF
MVA Base for
loss-of-life is cumulative over a typical daily load and ambient Loss data MVA 80 250 605 200
temperature where the overloading condition does not occur Temperature
base for loss data °C 75 75 85 75
frequently. Winding I2R
Table 2 shows the loss-of-life for the four transformers Losses W 166434 411780 929800 525072
under a four hours overloading condition. The two methods Winding Eddy
Losses W 17340 29469 285000 0
yield quite different results since the ageing rate is sensitive to
Stray Losses W 24796 43391 71000 0
the hotspot temperature and the largest difference occur for
Core Losses W 0 0 0 54560
the ODAF transformer since the Clause 7 method produces
lower hotspot temperature than the Annex G method. Cooling mode
type 1 2 3 4
Nameplate MVA 80 500 605 200
Table 2: Calculated loss-of-life during 4 hours overload Rated Average
winding rise °C 65 65 65 65
ONAN ONAF OFAF ODAF Test average
Clause 7 2.25 16.76 5.42 24.84 winding rise °C 42.66 41.7 44.7 50.6
Annex G 3.34 55.53 2.48 121.87 Rated hotspot rise °C 55.2 58.6 56.9 62.2
Rated top oil rise °C 34.2 38.3 33.4 32.2
VI. CONCLUSIONS Rated bottom oil
rise °C 19.7 16 24.6 29.2
The winding hotspot temperatures obtained from the Clause Rated ambient
temperature °C 30 30 30 30
7 method has been compared to Annex G method. It shown
that the Annex G method yields higher hotspot temperatures Winding
compared to the Clause 7 method, and these higher hotspot conductor 2 2 2 2
temperature agreed with the test data reported. This shows that Per unit eddy loss
at winding hotspot 0.5 0.4 0.71 0
inadequate estimation methodology and underestimation of Winding time
hotspot temperature in the Clause 7 method. However, the constant min 8 6 10 5
Per unit winding
Annex G method is more complicated as it requires a height to hotspot 1 1 1 1
measured top oil temperature rise and bottom oil temperature
rise, which are normally not supplied by the manufacturer Weight of core
during the heat-run test. To accurate estimate hotspot and coil kg 66690 153606 195152 225500
Weight of tank
temperature and the related loss-of-life, an improved and fittings kg 19833 44096 50153 102600
specification on thermal aspects of a power transformer is Fluid type 1 1 1 1
needed. Weight of oil kg 34800 73887 79746 21696