INTERNAL COMMANDS
The controller writes to the object's priority array (always at priority 10) upon any internal command to
update the object's status (non-BACnet operations). This includes the events listed in the "Internal
Command Events" table.
Table 2: Internal Commands Events
Input Control Zone Control Zone Control Breaker Control
Internal Controller Event
Manual Auto Manual Auto (Override) Manual Auto
Dry-contact switch transition X X
Sync from any source X X
Expiration of input timer X
Command via C-Bus™communications X
Expiration of override timer X
Command via LCD screen X X X X
®
Command via Modbus communications X X X X X X X
Command via DMX communications X
Command via Web Page X X X
Any zone source event X X
PRESENT VALUE
All internal commands are written to the priority array and are arbitrated along with external commands
from BACnet clients to determine the object's present value.
RELINQUISH DEFAULT
The controller takes the following action if all 16 levels of the priority array contain the NULL value.
Table 4: Priority Array Relinquish Defaults
Object Relinquish Default Action
Input Control 3 Turn input Off, allow optional blink notice
Zone Control 3 Turn zone Off, allow optional blink notice
Zone Control (Override) 3 Release zone override
Breaker Control 3 Turn breaker Off, allow optional blink notice
OBJECTS
Table 5: Powerlink G4 Supported BACnet Status and Control Objects
Description Type Functionality
Device (1)
Status Device (DV) Supported object list, operational status
Input (256 each)
Status Binary Value (BV) On/Off
Status Analog Value (AV) 0 - 255
Control Analog Output (AO) 0 - 255
Control Multi-state Value (MV) Manual On/Off
Auto On/Off (allows blink notice)
Zone (256 each)
Status Binary Value (BV) On/Off
Non-Responding (NR) breaker in zone
Control Multi-state Value (MV) Override On/Off
Override Release
Control Multi-state Value (MV) Manual On/Off
Auto On/Off (allows blink notice)
Breaker (336 each)
1. BACnet-specific parameter directly configurable via the device’s local LCD screen.
2. Increments by value of ‘1’ if:
a. Name of Device object is changed (due to change in Device ID), OR
b. Names of Breaker objects are changed for any control bus (due to change in First Breaker Number or Numbering Sequence).
3. Resets to value of ‘1’ if a Clear Memory function is performed on the device.
Schneider Electric Schneider Electric is either a trademark or registered trademark of Schneider Electric in
35 rue Joseph Monier France, the USA and other countries. Other trademarks used are the property of their
respective owners.
92500 Rueil Malmaison – France
Electrical equipment should be installed, operated, serviced, and maintained only by
Phone: +33 (0) 1 41 29 70 00
qualified personnel. No responsibility is assumed by Schneider Electric for any
www.schneider-electric.com consequences arising out of the use of this manual.
1210DB1401R08/15 08/2015