Abstract-An analytical model for the shielding of transmission and the data are shown to be consistent with the model. An index
lines against lightning is extended to the case of partially effective number is developed to aid in classifying line performance, and
shielding, including the effect of possible leader approach angle dis- suggestions are made regarding the study of the backflash problem.
tributions. Results of the Pathfinder projects are brought up to date,
INTRODUCTION
Paper 68 TP 616-PWR, recommended and approved by the OVER the past ten years the theory of shielding HV and
Transmission and Distribution Committee of the IEEE Power EHV electric power transmission lines has been signifi-
Group for presentation at the IEEE Summer Power Meeting,
Chicago, Ill., June 23-28, 1968. Manuscript submitted February 7, cantly advanced both in Europe and in the United States,
1968; made available for printing April 2, 1968. although some of the underlying ideas were advanced much
G. W. Brown is with the University of Pittsburgh, Pittsburgh, Pa. earlier. The work of Golde, and more recently that of Wagner
E. R. Whitehead is with Illinois Institute of Technology, Chicago,
Ill. on the relation between prospective stroke current and the
618 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, MAY 1969
strike distance from the leader tip provided the missing link
between the electrical parameters of the lightning stroke and
GROUND I\
the geometrical parameter of the transmission line leading to
the development of what may be termed the electrogeometric WIRE LEADER
theory of transmission line shielding [1]-[3].
In January, 1967, Armstrong and Whitehead reported on the
development of an analytical model based on the Wagner light-
°t|
PHASE CONDUCTORS
bsL
ning stroke mechanism and its application to the design of
effectively shielded lines. This model was tentatively calibrated EARTH
against the parameters of 50 effectively shielded lines for a
total experience of 52 000 mile years. The paper also reported on Fig. 1. Geometry of transmission line shielding.
the design and operating characteristics of the Pathfinder device
and the initial results of its installation on 433 tower line miles
to determine the effects of partially effective shielding and other
causes of insulator flashover from lightning. The extension of the
electrogeometric model to partially effective shielding was, how-
ever, indicated only briefly [41.
The present paper will extend the application of the analytical
model to the case of partially effective shielding, including the
effects of an assumed leader angle probability density function, (a) (b)
give typical samples from the 240 curves obtained in a computer Fig. 2. Common limitations on approach angle. (a) Region I-
study, and bring the Pathfinder field data up to date [5]. 0 < 0,. (b) Region II-0 > 0,.
ELECTROGEOMETRY OF TRANSMISSION LINE SHIELDING is the stroke density measured at the horizontal, while
The geometry of the transmission line model is given in Figs.
1 and 2. In Fig. 1, for the illustrated strike distance r8 to the con- Nos(f ) d
--= N41 (4)
ductors and r80 to earth, there will be an effective horizontal Cos V
swath X which will depend upon the leader angle probability is the stroke density as would be measured in the plane of the
density function. The exposed cylindrical surface is indicated above elemental area. Hence, the number of strokes striking
by the arc abc. If all leaders are vertical, the swath for one side this element is
of the line is the projection of the arc ab on the horizontal
axis. If a frequency distribution f(r8) of strike distances can be dn = °9 + ) 6 r8 sin (O-64)dOf (r8)dr8.
found, the number of shielding failure outages per unit length cos& (5)
and time in a region of known stroke density No is given as The limits of integration V12 and '1, depend on several factors,
as indicated in Fig. 2. It is assumed that no leaders approach
n = kNof Xf(r,) dr8. (1) from below the horizontal.
sx min
Here, r8 mi is the minimum strike distance for which an outage Effective Shielding
could possibly occur and r, max the maximum strike distance If in (1), r,mi is equal to r8 max, no shielding failures can
for which a stroke can hit the phase conductor. The coefficient occur. However, since most quantities used are averaged quan-
k is the proportion of shielding failure flashovers which cause tities, use of the term perfect should be avoided. The term
outages (i.e., which allow power follow current), and X the effective shielding is preferred.
effective swath at,r, for both sides of the line.
Effect of Leader Angular Distribution DETERMINATION OF VARIABLES
Since not all stroke leaders approach earth (or line) from a Distribution of Strike Distance
vertical direction, some angular distribution must be found for The frequency distribution f(r,) rests upon the relation be-
the approach angle of the leader. If 41 is defined as in Fig. 1, tween strike distance and current, and the frequency distribution
and a frequency function g(4&) is determined, it can be shown of current. The connection between the distribution of monoton-
that (1) applies if the swath X is reinterpreted as an effective
swath ically related functions is
j01 'PI'I0 sin (0 - 11') f (r8) h (I) dI
=
dT
(6)
X = r8 2 2(0) Cos g(1/./)) didO. (2) dr8
The function h (I) is the frequency distribution of currents,
The trigonometric coefficient results from the fact that the which can be determined from the cumulative or probability
number of strokes to an elementary arc r,dO from strokes at distribution, such as found in [6]. The connection between rS
angle with total variation d,6 is as follows: and I is found by the series of functional dependencies
r8dO sin (O-41) = dA v= v(I)
is the elemental area presented perpendicular to the oncoming
strokes at angle 11'. V-s =
V, U, v) (7)
Nog(VI)dil = Nh (3) rs =
r, (V.,) -
BROWN AND WHITEHEAD: TRANSMISSION LINE SHIELDING 619
Thus m=l
= r8(I).
g0f9)= Km1Om, /m=2
H=R125ft BIL=18O0
Here, v is the return stroke velocity and V8 the leader voltage
[4], [5].
E
B H 2sn L83 m- co
nio
Distribution of Approach Angle
The distribution of leader approach angle can at p)resent 2
only be estimated. However, a reasonably wide class of so]lutions
0
is represented by o 10 20 30 40
0, 1 < -7r/2 es -DEGREES
g (1) {mcosm1, -7r/2 <
K= . <.7r/2 (8) n, -TRIPOUTS PER 100 MILES
PER YEAR FOR No= 10
l0, 7r/2 < ,t.
Three of this class are of greatest interest; namely, imf= 1 Fig. 3. Influence of exponent m on shielding failures.
(K1 = 1/2), m = 2 (K2= 2/7r), and m = a which is th.e case
for all strokes vertical, and for which g (41) degenerates to the
Dirac function. Calibration of the end result and limited visual where
observation by one of the authors suggest that m is at)out 2 2 BIL
[4], [5]. Imiii z (lOh)
Real-Line Geometry and TD is thunderstorm days per year.
For a real line, factors such as terraini and conduct(or sag It is noted that (lOb) is an approximation which may be
determine the angular parameters and heights of Fig. 1. Under valid only for transmission lines. For applications where precision
these circumstances, (1) can be interpreted as outages pe r unit is necessary in calculating strike distances having currents out-
length at a given poilnt on the line, and the total outages fbor the side the range of about 5-80 kA, such as backflash and area
line will be protection, the current probability distribution and (6) must be
L utilized [4].
N= fLn(x) dx (9) It has been pointed out that g(41) cannot presently be accu-
rately estimated. Perhaps it will never be isolated. Nevertheless,
where x is the dimension along the line and L the tots31 line it is believed prudent to provide for a reasonable possibility of
length. It is felt, however, that there is insufficient justifi cation leader angle deviation from the vertical. Fig. 3 shows the in-
in going to this extreme, as long as the caution in the pr evious fluence of the exponent m on shielding failures under one set
section on effective shielding is observed. Calibration c)f the of line parameters. The exponent m= 2 has been selected
above formulas, based on averaged heights, sags, and shiielding tentatively as preferable to either m= o or m= 1 (as are
angles indicates that lines designed for effective shieldin;g and used in [3] and [4], respectively).
ground resistances of less than 25 ohms can be expected to have The estimate for No is quite close to that of other investigators,
fewer than 0.5 outage per hundred miles and year. yielding a value of 12 strokes per square mile per year for 30
thunderstorm days per year. It is clear that a significant im-
TENTATIVE CALIBRATION OF ANALYTICAL MODEL provement would be made if storm frequency could be expressed
in thunderstorm hours per year as is reported abroad [12].
Numerical representation has been left to one section, since
in large measure numerical values are interdependent For
K8g was originally intended to reflect a possible difference in
strike distance for a leader-to-earth and a leader-to-ground wire
example, the frequency distribution of strike distance de,pends for the same leader voltage. The use of this constant is such
on both the velocity-current relation and the probability (distri- that it actually subsumes uncertainties in r8, in the angle distri-
bution of current. In addition, many of the factors are rela6tively bution function, and in the smoothness of terrain such as the
poorly known, resulting in the necessity of calibrating thEe final averaged effect of trees, brush, or buildings along the right of
analytical model against actual field results. With this in mind, way. It serves as a calibration constant having values variously
the following formulas are given as a unit, based on the work estimated from 0.85 to 1.00 with the value 0.9 selected for the
indicated in [4] and [5]: estimates reported.
r, = 7.1 j314 meters (I in kA) (10a) It is important to note that all calculations for partially
effective shielding have been made using the so-called AIEE
O, I< 5kA current magnitude distribution curve as numerically adapted
f(r8) = (lOb) for computation. It follows that f(r3) is affected by any un-
7.4r.-5/3 I> 5 kA certainty in this curve. While the AIEE curve has the merit of
2 quantity, its quality is open to considerable question. Recent
gP4) = 7r-cos2'4 (lOc) oscillographic measurements by Berger tend to support the
higher current levels reported by Baatz and others. Since larger
No = 0.4 TD (lOd) values of current could increase r8 and affect f (r8), it is possible
that compensating adjustments in the exponent m of g (4') and
K,g = 0.9 (lOe) perhaps in the value of K80 might be required [7], [8].
k = 0.9 (lOf) Estimates of the height-angle relation for effective shielding
depend upon the more accurately known values of BIL and
r8 Iin. = rs for Imi (10g) conductor surge impedance, and any uncertainty in this relation
620 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, MAY 1969
H= 100 ft.
16 16BIL %0°_:7T\
kV
0106
2188°0-A _,
eS 4- -l
[BIL ~ o uz$
__
I0
2- 0° 2 0
H=150 ft. 0 --
16 3 0 50 100 150 200 0 50 100 150 200
FEET FEET
H MEAN GROUND WIRE HEIGHT
?, -2
-20 00 20 40
20 40 60 80 100 120 140 160
50 ) RECORDED 50
H = 175 ft. H =200 ft. 6AAA A SHIELDING
16 B I °- 6 40 A ~~~___ ___~FAILURES 4
IC0 20 0 60 8 005 _ 10
EFFECTIVELY 70
SHIELDED LINES
- 20 0 20 40
es -20 0 20 40
0TRIPOUT RATE sg0 -OA
-10J .75/I100 mi/ YEAR 0.9
n,O TRIPOUTS PER 100 MILES PER YEAR FOR No= 10 0 20 40 60 80 100 120 140 160
Kg=o.9
m=2 MEAN GROUND WIRE HEIGHT- H- FEET
Fig. 4. Estimated shielding failures for partially Fig. 6. Height-angle relations for effectively shielded
effective shielding. and partially shielded lines.
would derive from the mean strike distance-current formula. verified the integrity of the impulse circuitry, and the electro-
Moreover, the final calibration of the analytical model for explosive devices functioned properly. It is therefore assumed
effective shielding depends on a very satisfactory volume of that the failure to indicate resulted from volt-time signals
statistical data as discussed later in connection with Fig. 6 [4]. below the activation level of the electroexplosive elements. Such
cases are expected to be rare [9].
COMPUTER STUDY The Pathfinder devices have been in the field for only 1.7
Utilizing the above equations, shielding failure outages for
lightning seasons and the 1967 season was noteworthy for a
over 200 combinations of possible line heights, values of BIL,
low level of thunderstorm activity over most of the sample
and various assumptions regarding g (4') and K,0, were calculated. lines. Only one company reported above average activity. It is
For these, it was assumed that No = 10 strokes per square mile expected that a resumption of normal thunderstorm incidents
and year and Z = 400 ohms.
will accelerate the accumulation of operations. The data yield
Several typical sets of curves are shown in Fig. 4. In order to
is only slightly below projections for the actual instrumented
stress the effect of height, data derived from these curves is
time, but it is expected that the full five-year period will be
shown in another form in Fig. 5. In connection with these figures,
required to yield the variety and number of data needed.
it cannot be overemphasized that H is the mean height of the
ground wire above the earth surface which must take into Interpretation of Pathfinder Data
account the actual or estimated earth profile [5]. If higher The estimation of shielding failure tripouts is subject to much
accuracy is justified, (9) can be employed.
more variability than the estimation of a critical height-shielding
CURRENT PATHFINDER DATA FROM EDISON ELECTRIC INSTITUTE angle relation and it has long been recognized that the Path-
FIELD STUDY finder data taken alone could never yield sufficient data to
permit statistical curves of tripout rates versus height and
Table I shows the accumulated Pathfinder operation as re- shielding angle. The approach to the problem is threefold:
ported by the Edison Electric Institute. This table may be 1) a large-scale statistical study of the height-angle relations
summarized as reflecting a total of 40 Pathfinder operations for lines showing excellent performance, 2) verification of shield-
on 29 individual strokes. Nineteen of these strokes caused ing failure or backflash events for a variety of line geometry,
shielding failures, eight caused backfiash events, and two caused insulation, and grounding conditions, and 3) the use of an
implied backflash events. In the last two cases the instruments analytical model as an extrapolation mechanism consistent with
were returned from the field for checking. Laboratory tests the findings of 1) and 2). While it is yet too early to form firm
BROWN AND WHITEHEAD: TRANSMISSION LINE SHIELDING 621
TABLE I
conclusions, some interesting patterns are beginning to emerge to the maximum BIL of 1600 kV for the circle points and that
which suggest that sound conclusions can be reached with effective shielding for 125 feet and 1600 kV would be indicated
sufficient data. Fig. 6 shows height-angle relations for 50 ef- for a shielding angle slightly less than zero degrees. The data
fectively shielded lines as indicated by their mean tripout rate of Fig. 4 confirms this estimate. The circled cross of Fig. 5
of only 0.175 per 100 miles per year. Plotted on the same figure represents the performance of this same line plotted for the
are the estimated critical height-angle lines for K80 = 1.0 and mean height and angle where shielding failures occurred. These
K80 = 0.9. The mean BIL value for the circled points is 1300 kV. parameters may not conform exactly to the average for the
Numbers adjacent to points indicate the number of lines having entire line, but marked departure is not anticipated.
the same geometry. Also plotted on this figure are the height-
angle points for the confirmed shielding failures of Table I. Application of Shielding Theory to the Backf ash Problem
The group of triangles near H = 70 feet and As= 40 degrees Shielding theory affects the backflash problem through its
has an averaged BIL of 760 kV, the group near fI = 125 feet application to the estimation of the number of strokes to the
and 08 = 33 degrees has a BIL of 1600 kV, and the triangle at ground wire system. Although an extended study of this appli-
[H = 138 feet and 08 = 7 degrees has a BIL of 945 kY. It is cation is beyond the scope of the present paper, it is appropriate
interesting to note that the upper envelope line A corresponds to suggest the directions to be taken in such a study.
622 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, MAY 1969
TABLE IV
Commonwealth Edison
345-kV Line OVEC Ontario Hydro
Pathfinder'r-- -
Records Line 11601 Line 11602 345-kV Line 230-kV Line
Shielding failures 66% 58% 62% 82% 61.1%
Backflashovers 34% 37% 38% 13% 30.5%
Flashes to unknown
destination 0 5% 0 5% 8.3%
References Brown and White- Engimann and Engimann and Schlomann et al. [14] Lishchyna [15J
head Caswell [13] Caswell [13]
R. H. Golde (The Electrical Research Association, Cleeve Road, HINCHINBROOK E TS ST. LAWRENCE TS
Leatherhead, Surrey, England:) The authors are to be congratulated _ 44.38 Ml 55.87 Ml -
on having presented an outstanding contribution to the solution
of the question of the lightning performance of EHV transmission xL21H Xx
lines. In fact, as one of the early contributors to what the authors
call the electrogeometrical approach, I would suggest that the L20H - T
authors have perfected this method to such an extent that attention W -TOP 1471M \L R TOP
should now be concentrated on the main parameters on which this F' CENTRE
20 47 MK
W
-
- CENTRE
El - BOTTOM |_ B - BOTTOM
investigation is based. With this in view, the following comments
are offered as a constructive contribution to the discussion. T2 44
KV
KY
T.
Manuscript received June 24, 1968. Fig. 10. Tower type of line S.
1 In honor of Benjamin Franklin, who introduced the term
"striking distance," I prefer this term to the authors' "strike dis-
tance" and hope that it will find wider application. It was also noted that nine of these single-circuit tripouts (SCT)
were from one of the top phases to ground, eight were from one
of the center phases to ground, and in one case the phase involved
was not established (Table VI). Thus, if either one of the bottom
phases was involved in SCT at all it was not involved more than
once. However, out of nine double-circuit tripouts (DCT) that
L. Lishchyna (The Hydro-Electric Power Commission of Ontario, occurred on this line during the same period, three tripouts in-
Toronto, Canada): Over the past eight years we at Ontario Hydro volved both bottom phases.
have retained records of the lightning performance of a 230-kV The above findings suggested that the mechanisms initiating
double-circuit line as shown in Fig. 8. The relay operation records the single- and double-circuit tripouts on this line might not be the
show that during the years of 1960-1967 this line had a total of same. A reasonable explanation seemed to be that DCTs were
27 lightning tripouts of which 18 involved only one of its two circuits. initiated by backflashovers and SCT by shielding failures.
We were able to calculate the expected rate of shielding tripouts
on this line, the tower type of which is shown in Fig. 9, using the
Manuscript received July 24, 1968. methods which have been proposed in the literature. One of the
BROWN AND WHITEHEAD: TRANSMISSION LINE SHIELDING 625
TABLE VI
LIGHTNING FAULTS ON ST. LAWRENCE TS-HINCHINBROOKE TS
230-KV DOUBLE-CIRCUIT TRANSMISSION LINE 1960-1967
Line Total Number Phases Involved in
Length Number of of DC Phase Involved Single-Circuit
Year (miles) Faults Faults in DC Faults*t Faults*t
1960 100.25 2 0 W, W'
1961 100.25 1 1 R R,R',O't
R'-W'
1962 100.25 3 0
1963 100.25 7 1 B W, W, W, W, R', W'
B'
1964 100.25 1 0 R'
1965 114.96§ 5 4 W, B, B, R WI
WI, B', B', R'
1966 114.96 5 2 R-W 0 R, R, R
R'-W' e'
1967 114.96 3 1 R R, R'
R'-W'
1960-1967 27 9
* All faults are to ground.
t Primed phases are of circuit L21H and those not primed of circuit L20H.
t Phase involved not known.
§ Tap to Brockville TS added.
TABLE VII
CHARACTERISTICS OF LINES FOR WHICH SHIELDING TRIPOUT RATES HAVE BEEN CALCULATED
Mile-Years of
Number of Voltage Rating Line ft Vi Reported Service
Line Designation Circuits (kV) BIL (feet) (feet) (degrees) Experience
P 2 230 1275 112 82 25 845
Q 1 500 1800 87 48 17 1380
R 1 115 675 65 36 25 1100
S 1 115 675 44 34 34,67 500
methods tried was proposed in 1967 [4], and now has been expanded paper, qualifies this line as an effectively shielded line. The point
here. Its salient features are twofold; the length of the last step obtained by plotting RI, j. parameters of this line in Fig. 6 indicates
of lightning stroke is determined by the switching surge strength that the line is indeed effectively shielded. In fact, it would be ef-
of long air-gaps, and stroke leaders are assumed to have angle fectively shielded even if it had the BIL of 1600 kV instead of the
distribution. It is assumed that the probability density of stroke actual BIL of 1800 kV. The computer calculations indicated no
leader angles orthogonally projected on a vertical plane, perpendic- shielding tripouts for flat terrain.
ular to the direction of the transmission line, has a cosine distri- The shielding tripout rate for line R in Table VII was estimated
bution about a vertical line on such a plane. This latter parameter from the total lightning outages on this line and the flashover marks
of lightning stroke has not been included previously in calculations on the insulator strings observed during the helicopter patrol flights.
of shielding tripouts. Instead, it has been customary to assume that It was observed that each of the outside phases of this line had
all strokes proceed downward vertically. 4.9 times as many insulator strings with flashover marks as the
The long and tedious mathematical computations, required to center phase had. The estimated value was 0.95 tripout per 100
determine the exposure of line conductors to lightning strokes of miles per year which compares well with the calculated value of
various current magnitudes, were performed by a computer. The 0.90.
computer program provided the tripout rate on either single- or According to Fig. 6, the line with H, a, parameters corresponding
double-circuit lines. to those of line R would be effectively shielded if it had a BIL of
The calculated value of SCT was 1.3 per 100 miles per year. The not less than 1300 kV. The actual BIL of this line, as shown in
corresponding figure estimated from field data, assuming that all Table VI, is 675 kV.
18 single-circuit tripouts were because of shielding failures, was From the above given and other similar applications, it was found
1.6 and shows no conflict with the calculated value. Some SCT that on lines with either one or two symmetrically located sky-
actually may have been caused by backflashovers, in which case wires, shielding failure rates calculated by this method compare
there would be even better agreement between the above two figures. favorably with those estimated from field data.
Plotting H, U. parameters of this line (designated in Table VI by P), Next we tried this method on transmission lines with one skywire
in Fig. 6 a point is obtained that falls in the region of not effectively located asymmetrically (see Fig. 10 and Table VII). The calculated
shielded lines. shielding tripout rates for such lines were found to be too high;
Line Q in Table VII is a single-circuit 500-kV line with a hori- considerably higher than the estimated value. The author's comments
zontal phase configuration. Thus far it had two lightning tripouts clarifying this point would be appreciated.
(one of these involved the center phase) which constitutes 0.145 The field data obtained thus far from the Pathfinder project
tripout per 100 miles per year. This tripout rate, according to the and reported by the authors have already elucidated a number of
626 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, MIAY 1969
points concerning the shielding tripouits. It has demonstrated con- Dr. Golde suggests that the value for K.,, might perhaps be
vincingly that on some transmission lines such tripouts may play put at a value near unity, and a close examination of Fig. 6 will
an important role in determining the overall lightning performance. support this view. The value of K,,, = 0.9 was originally assigned
It is hoped that the authors will continuie to make their excellent to provide some protective margin against penetration of the mean
contribution in this field. striking distance surface by individual corona filaments when the
model was used to predict effective shielding. Obviously, this practice
should be reconsidered when the model is used to predict the results
for pcrttially effective shielding. Curves for K,, = 1.0 are available.
The authors agree that (lOh) is probably an oversimplification,
G. W. Brown and E. R. Whitehead: The authors wish to thank the but the alternatives do not yet appear justified in the presence of
discussers for their interesting and constructive commeints. other basic uncertainties.
Miss Chan presents a valtuable tabulation of data on a variety Dr. Golde directs ouir attention to the very intensive stuidies
of lines. We feel, however, that caution must be exercised in inter- of CIGRE Study Committee 33 in endeavoring to determine the
preting the apparent agreement with the Pathfinder results. The stroke density number from lightning-flash counter measurements.
Pathfinders are located on 12 different lines with voltage levels His pioneering work in this field has blossomed into most extensive
from 115 kV to 345 kV, and with wide variations in shielding angle studies throughout the world and extremely valuable data are
and terrain. Thus comparison of the overall results with specific becoming available. Proper interpretation, evaluation, and utiliza-
lines suggests that caution be used. Miss Chan raises two specific tion of these data are of utmost importance to future numerical
questions. The strike distance is related to the stroke current by analysis of the lightning performance of EHV lines. Finally, Dr.
the empirical relation Golde requests clarification of the fact that there are fewer than
r. = KrsIn. 27 points on the one-year average curve of Fig. 7. The explanation
is that several single years had identical tripout rates and it is this
The following values have been given in or derived from the literature: rate that is grouped as one point. Unfortunately, the dashed line
r8 7.1 J075 in Brown and Whitehead is still slightly in error, as the point at 10 specific tripouts was
r8 6.7 I085 Armstrong and Whitehead [4] inadvertently omitted. The objective of the figure is, however,
r, 3.3 IO-" derived from Golde's data as given by Chan not impaired by this error.
r8 10.6 IO.51 derived from Wagner [2]. The authors agree with Mr. Lishchyna that double-circuit trip-
outs are more likely to be associated with backflash events than
The values from Golde and Wagner yield critical height-shielding with shielding failures. This is corroborated by Table I where it is
angle lines much below those given in Fig. 6. A possible explanation seen that the double-circuit faults are invariably associated with
for this is that much lower current values, say 5-15 kA, are important high footing resistance or counterpoise. The authors are pleased
in deriving critical lines for effective shielding of transmission that the agreement of the theory with Mr. Lishchyna's estimates
lines, while the values cited by Miss Chan are much higher. Con- of actual line failures is as good as he indicates for the symmetrical
cerning Miss Chan's second question, the curves of Fig. 4 assume lines. Several comments are in order regarding the case which
the line to be symmetrical. In the event of asymmetry, each side apparently did not agree with the method of [4]; namely, the single
may be treated independently and the values of the curves divided circuit with one asymmetrical ground wire.
by two. Additional and poorly quantified influences become evident for
Dr. Golde raises the very important question of the validity very large shielding angles, say 50-90 degrees. Among these are:
of the current probability distribution as used by the authors. the shielding effects of the crossarm for steel construction or grounded
Our own reservations are pointed out in the paper along with our insulator hangers for wood construction, effect of variations in
tentative preference for a composite curve from the data of Baatz length of corona filaments from the assumed mean striking radius,
and Berger. The use of the so-called AIEE curve was dictated by a the poorly known current distribution curve between 0 and 10 kA,
desire to facilitate comparison with other studies based on the same and the effect of nonlinear stroke resistance at these low currents.
curve. Certainly improvement in our understanding of this relation Fortunately, these perturbing influences do not appear to affect
(as well as the other constants and functions which make up our the principal relations for modern line configurations, though they
tentative calibration of the model) is needed. Regarding the question may account in some measure for the scatter of points in data
of the basis for the strikinig distance versus voltage relation, it is presentations such as Fig. 6. Mr. Lishchyna has kindly furnished
noted that (10a) is based on long front switching surges which the authors with additional data in private communications and
Dr. Golde indicates as preferable. his cooperation is much appreciated.
In general, the authors believe that the estimating curves for
either K., = 0.9 or K, = 1.0 will yield results consistent with the
Manuscript received August 7, 1968. performance classifications in Table III.