Documente Academic
Documente Profesional
Documente Cultură
LIMITED
MUMBAI REFINERY
TECHNICAL DEPARTMENT
DESIGN PHILOSOPHY
FOR
HEAT EXCHANGERS
TABLE OF CONTENTS
Nozzles
Economic Pressure drop consideration
Means of increasing heat transfer
Means of decreasing pressure drop
Allocation of shell and tube side fluid
7. Attachments
8. References
DESIGN PHILOSOPHY
FOR
HEAT EXCHANGERS
Baffle Plate: Higher Heat Transfer Coefficients are obtained when the
liquid is in turbulent condition. To introduce turbulence outside the tubes,
baffles are used. Also called support plate. A plate in which the tubes pass
through for support. Also provides a blocked path for the shellside medium.
This blocked path forces the shellside medium across the tubes providing
better heat exchanger performance.
End Plate:
End plates are covers, which have been welded to the heat exchanger. Most
end plates are used on bonnet assemblies.
End Zone:
The first baffle space on a tube bundle. It is the space between the tubesheet
and the first baffle plate. The end zone is adjusted to keep the baffle plates
within the two shell side nozzles.
Ferrule:
A small piece of tubing approximately 1 inch long made of copper or
stainless steel. The ferrule is crimped or squeezed onto the tie tube, up
against the last baffle, thus locking all the baffles into position.
In and Out End: The end of the heat exchanger which contains the
tubeside inlet and outlet connections in a multi-pass unit.
Outer Tube Limit: The O.T.L. is the diameter created by encircling the
outer most tubes in a tube layout. The design O.T.L. is used by engineers to
calculate clearances between bundle parts. The actual O.T.L. is usually a
few thousandths less than the design O.T.L.
Reversing End: The end of a heat exchanger where the tubeside fluid
reverses its flow in a multi-pass unit. It usually contains only small vent and
drain connections.
Seal strips: This are flat strip of metal that extend the length of the shell in
order to prevent shell side fluid from flowing through the clearance
between tube bundle and inner wall of shell.
Shell Assembly: The name of the assembly into which the tube bundle fits.
The shell also contains the shellside connections.
Shell Head: A shell head is a formed plate which is welded to the shell (or
bonnet) pipe. The shell head can be many styles or shapes, including
flanged and dished, elliptical, ellipsoidal, and hemispherical. Generally, as
a head gets flatter it gets weaker, therefore designers can use a flat end plate
or a thinner formed head to do the same job.
Shell Side: The side of a heat exchanger where the fluid circulates around
the outside of the tubes.
Spacer: A piece of tubing that slides over the tie rod or tie tube between the
baffle plates. The spacer holds the baffle plate in a permanent position.
Stacking: Two or more heat exchangers which have been stacked together
either side by side or one on top of the other. These units have
interconnecting piping hooking them together.
Temperature cross : If hot stream outlet temperature < cold stream outlet
temperature is called temperature cross.
Test Pressure: Generally 1.5 times the design pressure. The pressure used
during a hydrostatic test. The test is made to detect leaks at any joint on the
heat exchanger.
Tie Rod: A small diameter rod which threads into the stationary end
tubesheet. This rod ties the baffles and spacers together.
Tie Tube: A tie tube takes the place of the tie rod in a small diameter heat
exchanger. It serves the same purpose as a tie rod.
Tube Layout: The tube layout drawing shows the positioning of the tubes
inside the heat exchanger. It also shows the locations of the tierods.
Tube counts : Number of tubes in the layout is the tube count. For a given
shell ID with specified tube OD for particular type of pitch, number of
tubes (tube count) is given in heat exchanger standards
Tubesheet: The tubesheet is a plate that secures both ends of the tube in a
heat exchanger. Both the shellside and tubeside mediums come in contact
with it.
Tube Side: The side of a heat exchanger where the fluid circulates through
the inside of the tubes..
1,2,4 Pass : The number of times the fluid passed through the tube bundle.
In a one pass unit the tube side medium passes through all the tubes once.
In a two pass unit it passes through one half of the tubes and returns
through the other half. A four pass unit goes through approximately one
quarter of the tubes, down and back four times. Greater than 1 Pass is
referred to as a multi-pass unit.
3.0 HEAT EXCHANGE EQUIPMENT:
Cooler : To cool process fluid, water is the main cooling medium. Cooling
media can be air also called air cooler or by other process fluid.
Horizontal thermosiphon
This reboilers work on natural circulation due to difference in
density of the liquid column from the tower to the reboiler and the
vapor/liquid column back to the tower. Density difference is the
driving force for process flow through the reboiler. Material being
boiled is normally on the shell side.
Size process lines carefully or else friction will restrict boil-up rate.
Vertical thermosiphon
Characteristics
SHELL:
REAR HEAD:
All exchangers shall have two design temperature for each side, a
maximum design temperature and minimum design metal temperature
(MDMT).
Consider worst case conditions for hot and cold fluids. This may not be the
highest temperature, but a combination of high temperature and higher
pressure.
For external bolting and components exposed to both shell side and tube
side fluids, the design temperature shall be the same as the shell side or
tube side design temperature, whichever is more severe.
For cooling water services normally used design pressure is 100 psig and
design temperature is 150 deg F
The maximum area per shell is usually limited to a unit having a shell
inside diameter of 48 inches or tube bundle weight of 15 tons.
If a temperature cross occurs, the F factor for correcting the LMTD will be
0.8 or less. When this occurs, it is necessary to use two shells in series it
two or more tube passes are present.
In special cases, such as reboilers and fixed tube sheet exchangers, larger
areas per shell are occasionally used. Areas up to 25,000 sq. ft. have been
used in fixed tube sheet exchangers.
Heat Exchanger tube metals viz. Carbon Steel, SS, Copper, Admiralty,
Brass, 70-30 copper-nickel, etc. are available. Specific metal is used for
specific service.
Smaller tube diameter provides better heat transfer but higher pressure drop
and harder to clean.
FCC flue gas coolers (firetube often uses 1.75 “ OD x 0.2” thick
The wall thickness of tubes is defined by Birmingham Wire Gauge (BWG).
Wall thickness specified as minimum or average
The mean radius of U bends shall not be less than 1 and ½ times the
nominal outside diameter of the tube.
The number of tubes in any pass shall not be greater than 10 % above or
below the average number of tubes per pass.
Tube length: TEMA suggest 8, 10, 12, 16 & 20 feet tubes are common.
UOP’s upper limit is 65 feet
16 feet and 20 foot are probably the most common for horizontal unit and
longer for vertical units. Mumbai Refinery uses normally16 foot. A U-tube
exchanger uses many different tube length.
The cost of exchanger surface depends upon the tube length, in that the
longer the tube, the smaller the bundle diameter for the same area. The
savings result from a decrease in the cost of shell flanges with only an
annual increase in the cost of the longer shell. In the practical range of
tube lengths, there is no cost penalty for the longer length extras are added
for steel only over 24 feet and for copper alloys over 30 feet.
Tube layout:
There are four types of tube layouts with respect to the shell side cross flow
direction between baffle tips; square (90°), rotated square (45°), triangular
(30°), and rotated triangular (60°). The four types are illustrated in fig 3,
Appendix. The 60° triangular layout is seldom used, since its heat transfer
characteristics are poor compared to the pressure drop expenditure.
However, some vendors still use this layout occasionally.
Square or rotated square tube layout should be for all shell and tube
exchangers when the shell aide fouling factor is over 0.0020, whenever
mechanical cleaning of the outside of the tubes is required, or when
requested by the refinery and for reboilers with a heat flux exceeding 6000
Btu/hr sq ft. Rotated square layouts are preferable for laminar flow,
because of higher heat transfer coefficient caused by induced turbulance.
In turbulent flow, especially for pressure drop limited cases, square layout
is preferred since the heat transfer coefficient is equivalent to that for
rotated square layout while the pressure drop is somewhat less.
Tube layout for removable bundles may be either square (90°), rotated
square (45°), or triangular (30°). Non removable bundles (fixed tube sheet
exchangers) are always triangular (30°) layout.
Tube pitch:
Tube Pitch/ Tube Pattern may be square pitch or triangular pitch. Square pitch is
much easier to clean but triangular tube layouts are cheaper. The tube holes can
not be drilled very close together, since it will weaken the tube sheet. The
shortest center-to-center distance between two tubes is called Tube Pitch
(PT). Square or triangular pitch can be used.
Square pitch: Shell side fluid has straight lanes between tube layers.
Unlike triangular where alternate tube layers are offset. This pattern
makes for easy cleaning since a lance can be run completely
through the bundle with out interference. This pattern has less
pressure drop than triangular but shell requirements are larger and
there is a lower heat transfer coefficient for a given velocity at many
velocity levels. Joining the centers of a 4 adjacent tubes forms a
square. Any side of this square is the tube pitch.
The Baffle Spacing is usually not greater than the Shell ID or closer than
one fifth of Shell ID. Segmental baffles having 20 -30 % cut are common.
The thickness of transverse baffles and support plates shall not be less than
the specified shell side corrosion allowance.
Select baffle cut so that Delta P all windows = 20- to 25 % Delta P total
Seal strips shall be used for non isothermal services when bypass clearance
exceed 5/8”.
Impingement baffles are required on shell side inlet nozzles to protect the
bundle against impingement by the incoming fluid when the fluid is : a) is
condensing b) is a liquid vapor mixture, c) contains abrasive material, or is
entering at high velocity. In addition, TEMA requires bundle impingement
protection when nozzle values of ρv2 (fluid density, lb/cuft, times velocity
squared sqft/sec) exceeds:
1. 1500 lb/ft sq sec for non corrosive, non abrasive, single phase liquids
2. 500 lb/ft sq sec for all other liquids
Also, the min. bundle entrance area should equal or exceed the inlet nozzle
area and should not produce a value of ρv2 greater than 4000 lb/ft sq sec,
as per TEMA.
The nominal thickness of the impingement plate baffle shall not be less
than ¼ inch(6 mm).
Nozzles for exchangers are normally made the same line as the
corresponding line because of pressure drop and velocity considerations
size of lines and nozzles in vapor service is more critical than liquid
service.
Maximum nozzle size should not exceed half the diameter of shell dia due
to mechanical considerations.
When chemical cleaning connections are specified, the size shall not be less
than NPS 2.
For pressure streams, the pressure drop should be maximized. When there
are no material or process restrictions on maximum velocity, a reasonable
limitation for liquids is about 10 to 15 ft./sec. For gases and vapors,
velocities up to 100 ft/sec are common.
Tube side (Number of Passes) – For coolers and condensers using water,
specify enough tube passes to maximize the utilization of the available
pressure drop as limited by materials. The permissible maximum and
minimum water velocities vary with the tube material and water type as
shown in attachment.
Ordinarily, no fewer than 2 nor more than 8 tube passes are used. With
more than 8 or less than 2 passes, the construction becomes complicated
and fabrication costs tend to become excessive. Note that 2, 4, or 8 tube
pass arrangements are easily interchanged.
Shell side
Number of Shell Passes - Exchangers may have more than one shell pass
(one pass is the most common.) Multiple shell passes per shell require the
use of a longitudinal baffle of either welded or removable design.
Cross Baffles – Segmental baffles are normally specified, unless shell side
pressure drop is excessive, even at maximum baffle spacing. In such
cases, double segmental baffles should be used because tray result in lower
pressure drop with only a slight decrease in the shell side heat transfer
coefficient.
Nozzles - Use two shell outlet nozzles (one at each end of the shell) and a
center inlet nozzle or vice versa, if other means of reducing pressure drop
are ineffective. This is termed a “divided flow” (TEMA J) shell.
If a design requires more surface than is necessary for heat transfer simply to
provide sufficient low area to prevent exceeding the allowable pressure drop,
two courses of correction are possible.
If none of the above give the desired results, consider the use of units in parallel.
4.13 ALLOCATION OF SHELLSIDE AND TUBESIDE:
b. Pressure drop
Pressure drop higher on tubeside for the same HTC, especially for viscous
liquids. Thus viscous liquids are better handled on the shellside.
Gas pr. drop often lower on tubeside if a single tube pass can be used, e.g.,
FTS exch’s. However, if tube diameter has to be increased, not worthwhile.
c. Viscosity
1. Viscous liquids far better handled on shellside: much higher HTC for
same pr. drop
2. The greater the viscosity, the greater the difference between the HTC’s.
On the shellside, shell, shell cover, tubes, floating-head cover and shellside
tubesheet face have to be of costlier metallurgy.
f. Flow rate
Low flow rate streams better handled on tubeside: number of tube passes
can be increased
On the shellside, baffle spacing and cut can be reduced only to a certain
extent. Thereafter, multiple shells in series are required: costly.
Guideline for allocating fluid on tube side – whichever fluid appears higher
on following list will normally be passed thru tubes.
1) Finalise process fluid conditions for cold as well as hot fluid: Stream
composition, Flow rates, Temperatures, pressure etc.
2) Establish the required properties of the fluids such as following:-
Specific heat (c), Specific gravity (s) or density, viscosity (µ), thermal
conductivity (k).
3) Establish the heat duty of the exchanger from heat balance.
4) Determine the LMTD.
5) Determine LMTD correction factor from fig.2. If temp. correction factor
is less than 0.8, increase no of shells required
6) Specify the type of the exchanger including TEMA type.
7) Determine corrected mean temp diff.ce MTD
8) Determine which fluid will pass thru shell & which thru tube side as per
criteria outlined in design considerations
9) Establish allowable pressure drops
10) Specify fouling factors for both shell & tube side fluids (refer enclosed
table).
11) Determine design temp. & press. required for both shell & tube side
12) Determine nozzle sizes based on velocity criteria
13) Assume the overall duty coefficient based on fluids handled
14) Calculate assumed area from the above overall duty coefficient
28) Calculate overall HTC Uo from above determined tube, shell side htc’s,
assumed fouling factors & wall resistance
29) Calculate effective mean temp. diff.ce MTDe from temp. diffce.
correction factor
30) Calculate required surface area from calculated overall HTC Uo &
MTDe. Compare area calculated with area assumed and repeat calculation
until they are equal.
31) Final design should meet process requirement without resulting in future
penalties.
6.0 REFERENCES: