Vector Groups
Transformer nameplates carry a vector group reference such at Yy0, Yd1, Dyn11 etc. This
relatively simple nomenclature provides important information about the way in which three
phase windings are connected and any phase displacement that occurs.
Winding Connections
HV windings are designated: Y, D or Z (upper case)
LV windings are designated: y, d or z (lower case)
Where:
Y or y indicates a star connection
D or d indicates a delta connection
Z or z indicates a zigzag connection
N or n indicates that the neutral point is brought out
Phase Displacement
The digits ( 0, 1, 11 etc) relate to the phase displacement between the HV and LV windings
using a clock face notation. The phasor representing the HV winding is taken as reference
and set at 12 o'clock. It then follows that:
All references are taken from phase-to-neutral and assume a counter-clockwise phase
rotation. The neutral point may be real (as in a star connection) or imaginary (as in a delta
connection)
When transformers are operated in parallel it is important that any phase shift is the same
through each. Paralleling typically occurs when transformers are located at one site and
connected to a common busbar (banked) or located at different sites with the secondary
terminals connected via distribution or transmission circuits consisting of cables and
overhead lines
Basic Theory
An ac voltage applied to a coil will induce a voltage in a second coil where the two are linked
by a magnetic path. The phase relationship of the two voltages depends upon which way
round the coils are connected. The voltages will either be in-phase or displaced by 180 deg
as below:
1 of 3 12/26/2010 9:16 PM
Tutorial T6 http://www.transformerworld.co.uk/vector.htm
When 3 coils are used in a 3 phase transformer winding a number of options exist. The coil
voltages can be in phase or displaced as above with the coils connected in star or delta and,
in the case of a star winding, have the star point (neutral) brought out to an external terminal
or not.
Example - Dyn11
We now know that this transformer has a delta connected primary winding (D) a star
connected secondary (y) with the star point brought out (n) and a phase shift of 30 deg
leading (11). Connections and vector diagrams are as follows::
HV
LV
Other Configurations
By connecting the ends of the windings in other ways a wide range of options becomes
available as set out below.
End
2 of 3 12/26/2010 9:16 PM
Tutorial T6 http://www.transformerworld.co.uk/vector.htm
We hope you found this tutorial useful, your comments are welcome. Contact Us