MCR-...CLP-I/I-00
I
I
1. Description
UB ≥ UE = 2.5 V + 20 mA * RB UE /V
25
UB
UV = 2.5 V 20
I
I
UE RB 15
I I
10
MCR-1CLP
5
UV = 2,5 V
RB /Ω
0 200 400 600 800 1000
Headquarters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone +49 - 52 35 - 3 00 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
Multi-Channel Passive Isolator – MCR-...CLP-I/I-00
2. Technical Data
IN OUT
(4.508 in.)
114.5
(+) 0-20mA 1 5 (+) 0-20mA
(–) GND 2 6 (–) GND
99
(3.898 in.)
MCR-1CLP-I/I-00
with signal conversion: 0(4)...20 mA / 0(4)...20 mA
8 1-channel
M3
solid flexible Aa
[mm2] AWG
Output Module
Pcs.
Description Signal Width Type Order No. Pkt.
MCR passive isolator,
for electrical isolation of current 1-channel 12.5 mm MCR-1CLP-I/I-00 28 14 01 6 1
signals without power supply (0.492 in.)
Input
Input signal 0(4)…20 mA
Power loss 2.5 V at I = 20 mA
Maximum input current/overload 50 mA / 100 mA
Maximum input voltage/overload 30 V / 30 V
Voltage limitation with zener diode 33 V ± 5%
Output
Output signal 0(4)…20 mA
Maximum output signal < 50 mA
Maximum load 1375 Ω at I = 20 mA output signal
Ripple < 5 mVrms
General Data
Transmission error 0.1% of the final value
Additional error every 100 Ω load 0.02% of the measured value
Temperature coefficient ≤ 0.002%/K of the measured value / 100 Ω load
Cut-off frequency (3 dB) < 75 Hz at I = 20 mA and maximum load
Response time (10-90%) 5 ms at 500 Ω load
Test voltage Input/output 510 V, 50 Hz, 1 minute
Channel/channel –
Ambient temperature range – 10°C to +70°C (14˚F to 158˚F)
Housing material Polyamide PA, unarmored
IN OUT
(4.508 in.)
114.5
(+) 0-20mA 1 5 (+) 0-20mA
(–) GND 2 6 (–) GND
99
(3.898 in.)
MCR-2CLP-I/I-00
with signal conversion: 0(4)...20 mA / 0(4)...20 mA
8 2-channel
M3
solid flexible Aa
[mm2] AWG
Output Module
Pcs.
Description Signal Width Type Order No. Pkt.
MCR passive isolator,
for electrical isolation of 2-channel 12.5 mm MCR-2CLP-I/I-00 28 14 02 9 1
current signals without power supply (0.492 in.)
Input
Input signal 0(4)…20 mA
Power loss 2.5 V at I = 20 mA
Maximum input current/overload 50 mA / 100 mA
Maximum input voltage/overload 30 V / 30 V
Voltage limitation with zener diode 33 V ± 5%
Output
Output signal 0(4)…20 mA
Maximum output signal < 50 mA
Maximum load 1375 Ω at I = 20 mA output signal
Ripple < 5 mVrms
General Data
Transmission error 0.1% of the final value
Additional error every 100 Ω load 0.02% of the measured value
Temperature coefficient ≤ 0.002%/K of the measured value / 100 Ω load
Cut-off frequency (3 dB) < 75 Hz at I = 20 mA and maximum load
Response time (10-90%) 5 ms at 500 Ω load
Test voltage Input/output 510 V, 50 Hz, 1 minute
Channel/channel 2 kV, 50 Hz, 1 minute
Ambient temperature range – 10°C to +70°C (14˚F to 158˚F)
Housing material Polyamide PA, unarmored
IN OUT
(4.508 in.)
(–) GND 2 0 (–) GND
114.5
(+) 0-20mA 3 ! (+) 0-20mA
(–) GND 4 " (–) GND
(+) 0-20mA 5 § (+) 0-20mA
(–) GND 6 $ (–) GND
(+) 0-20mA 7 % (+) 0-20mA
(–) GND 8 & (–) GND
99
(3.898 in.)
MCR-4CLP-I/I-00
with signal conversion: 0(4)...20 mA / 0(4)...20 mA
8 4-channel
M3
solid flexible Aa
[mm2] AWG
Output Module
Pcs.
Description Signal Width Type Order No. Pkt.
MCR passive isolator,
for electrical isolation of current 4-channel 22.5 mm MCR-4CLP-I/I-00 28 14 04 5 1
signals without power supply (0.886 in.)
Input
Input signal 0(4)…20 mA
Power loss 2.5 V at I = 20 mA
Maximum input current/overload 50 mA / 100 mA
Maximum input voltage/overload 30 V / 30 V
Voltage limitation with zener diode 33 V ± 5%
Output
Output signal 0(4)…20 mA
Maximum output signal < 50 mA
Maximum load 1375 Ω at I = 20 mA output signal
Ripple < 5 mVrms
General Data
Transmission error 0.1% of the final value
Additional error every 100 Ω load 0.02% of the measured value
Temperature coefficient ≤ 0.002%/K of the measured value / 100 Ω load
Cut-off frequency (3 dB) < 75 Hz at I = 20 mA and maximum load
Response time (10-90%) 5 ms at 500 Ω load
Test voltage Input/output 510 V, 50 Hz, 1 minute
Channel/channel 2 kV, 50 Hz, 1 minute
Ambient temperature range – 10°C to +70°C (14˚F to 158˚F)
Housing material Polyamide PA, unarmored
c
Conforms to the EMC Directive 89/336/EEC and the
Low Voltage Directive 73/23/EEC
3. Connection Notes
25
UE = Input voltage at passive isolator
20
UT = Voltage drop at passive isolator
15
UB = Voltage drop at output load
10
URL = Voltage drop via both incoming cables
5
A = Conductor cross-section in mm2 UV = 2,5 V
RB = Load impedance
Magnetic inductive
flow meter
24V 0...20mA
0...20mA M CR- 1CLP- I/I- 00
1I I 5
IN OUT
2 GND 1 GND 2 6
Control system
http://www.phoenixcontact.com
TNR: 5105625-00
15.06.00
PHOENIX CONTACT