STEEL AUTHORITY OF INDIA LIMITED

BHILAI STEEL PLANT


BHILAI

7.0 MT EXPANSION OF BSP

TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS


OF ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III
(PACKAGE 77-01A-1)

MECON LIMITED
BHILAI – 490 001

TS No. MEC/S/9101/02/40/10/24/077-01A-1 Page 1 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

CONTENTS
*****************

SI Description Page No.


No.
01. Content 2
02. Section 01 : Introduction 3
03. Section 02 : Scope of civil works 4
04. Section 03 : Specification of civil works 6
05. Section 04 : General 6
06. ANNEXURE- I to specification 15
07. Schedule of Quantities 17

Prepared By Checked By Approved By

S.K.Pandey S.K.Mondal KR Pal Chaudhuri


DE DGM GM

Copyright © 2016. MECON Limited. All Rights Reserved Page 2 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

01.00 Introduction

Steel Authority of India Limited (SAIL), a Govt. of India undertaking, has


planned major modernisation and capacity expansion programme to become
more competitive and maintaining its share in the growing domestic steel
market.

Bhilai Steel Plant (BSP), SAIL is located at Bhilai in Durg district of the state
of Chhatisgarh in the central region of India. The site lies between 21.15°
North latitude and 81.22° East longitude. The nearest convenient rail head is
Durg which is about 12km west of Bhilai. Bhilai/Durg stations are on the
Howrah-Mumbai rail line of SEC Railway of the Indian Railways

The location of Bhilai is as follows:


From New Delhi, the national capital - 1359 kms
From Kolkata - 868 kms
From Chennai - 1269 kms
From Mumbai - 1100 kms

The distance from State Capital Raipur to Bhilai Steel Plant is around 40KM. It
is well connected by rail and road network. National Highways NH 6 & NH 43
cross through Raipur. The city Durg is situated about 13km from Bhilai Steel
Plant site.

The climatic condition of Bhilai is as follows


Average Ambient temperature - 35°C
Maximum temperature - 50°C
Minimum temperature - 5°C
Average Annual Rail fall - 1000 mm

Present TS covers the balance civil engineering works for buildings,


technological structures, new equipment and facilities described elsewhere in
this specification on a non-turnkey basis for units under “External Water
Supply System for SMS-III” (Earlier in Package: 77-01) as defined in
Section 02.02.

Copyright © 2016. MECON Limited. All Rights Reserved Page 3 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

02.00 CIVIL

02.01 SCOPE OF CIVIL WORKS

The scope of work relating to this package is to execute out the balance civil
engineering works pertaining to essential units under “External Water Supply
System for SMS-III”,(Earlier in Package: 77-01) as defined in Section
02.02 on item rate contract basis.

Major Units and Facilities

The major civil works involved for the proposed Package shall pertain to the
following areas:

A) Water System for the proposed Basic Oxygen Furnace (3x180 t converters)
B) Water System for the proposed Continuous Casting Plant:
2x6 Strand Billet Casters,
1x3 Strand Beam Blank Caster,
1x6 Strand Billet cum Bloom Caster,
C) Water System for the proposed Steel Refining Unit (SRU):
3x160 t off-line LFs,
3x160 t on-line ARS,
1x160 t RH Degasser.

Following major units are in the scope of this package.

 W TP-1: Scale Pit & Pump House


 Th i ck ner S RU 7701 -THK-3001B
 Th i ck ner BO F 7701 -THK-3001C
 S S T Pu m p Hou s e
 Mak e-u p W ater Pu m p Hou s e
 Co m mo n W ater Pu m p Hou s e
 ECR: Electrical control room
 EOHT: Emergency overhead tank

Copyright © 2016. MECON Limited. All Rights Reserved Page 4 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

02.02 Units Covered under the Scope of work

The broad scope of civil works has been identified and has been listed as :

1. W TP-1 (Scale Pit & Pump House)


2. Th i ck en er S RU 770 1 -THK-3001B
3. Th i ck en er BO F 7701 -THK-3001C
4. S S T Pu mp Hou s e
5. Ma k e-u p Wa te r Pu mp Hou s e
6. Co mmo n W ater Pu mp Hou s e
7. ECR (Electrical control room) : upto 2 nd floor (i.e. upto +8.5 m)
8. EOHT(Emergency overhead tank) Foundation

The civil work shall not be limited to these but shall be guided by
technical/technological aspects for the total scope of work. Overall layout of Various
Buildings with different units shall be as per relevant technological drawings.

Construction Work

Construction works consist of foundation, plinth beam, brick work, slab, flooring,
doors, trenches, equipment foundation and all other civil engineering works (RCC
and PCC).

The materials and services shall include but not be limited to the following:

i. Earthwork for foundations, pits, trenches, basements, tunnels, drains, sumps,


sewers, etc including final grading of area covering units up to +/-500mm and
disposal of surplus earth up to 5kM distance in side plant.
ii. Reinforced concrete for well structure, tunnel trench etc as required.
iii. Soling and sub-grade work for all foundations, flooring, trenches, pits and
other underground structures.
iv. All doors, windows, gates, etc.
v. Reinforced concrete work in columns, beams, floors, slabs, frames and other
superstructures.
vi. Reinforced concrete work in supporting structures of pipe line/equipments.
vii. All masonry work in superstructure and partition. Fly ash cement bricks shall
be used in construction
viii. All finishing work in flooring, wall-cladding and ceiling.

Copyright © 2016. MECON Limited. All Rights Reserved Page 5 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

ix. All necessary waterproofing, heat resisting, fireproofing and anti-corrosive


treatment to building structures and foundations.
x. All plumbing, rainwater drainage, sanitary sewerage works for all buildings,
roadway, parking, paved areas and open spaces within the battery limits of this
specification.
xi. All temporary buildings, offices, roads, tracks and services for construction of
the proposed Package.
xii. Removal of all materials, cleaning, and handing over of site in a workable
manner.

It shall include all works required for completeness of the project. All the materials and
workmanship shall conform to relevant Bureau of Indian Standard norms and
specifications.

03.00 Specification for Civil Works

This specification shall be read in conjunction with the general conditions of contract and
other project requirement provided in the other volume containing special conditions of
contract, instruction to bidders, special instructions to bidders etc.

Specification for civil works comprises, besides this section, one volume of general
specification for civil engineering works titled 11-CIVIL-GS-07. This volume shall also
form part of this section and therefore shall be read in conjunction with this section.

04.00 GENERAL

04.01 Price

The Contract is an item rate/unit rate Contract.

The provisions of GCC for item rate contract of SAIL along with amendments shall be
made applicable without any deviation or omission.

The unit rate/item rate shall remain firm, fixed and binding on the Contractor irrespective
of any variation of quantities stated under schedule of items.

The payment to the Contractor will be made as per actual quantities done against each
item and as per agreed unit rate of the item.

Copyright © 2016. MECON Limited. All Rights Reserved Page 6 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

04.01.1 Rate for Extra Item

It is compulsory on the part of the contractor to execute any number of Items which are not
mentioned in the schedule of items but are necessary to execute in connection with the
above packages.

In case it is found necessary to execute any item of work which is not included in the
schedule of items, the rates for such extra item shall be fixed as per the following
procedure.

a) Where the extra works are of similar character and/or executed under
similar conditions as any of work appearing in the schedule of quantities,
then the rates for such extra item shall be derived from the contract rates
of similar/ closest item of work provided.

b) Where the nature of extra item is such that the rate for the same cannot
be derived as per procedure (a) above, then the rate shall be mutually
agreed in line with CPWD norms or by following CPWD guide lines.

04.02 Measurement of Work


Measurement of work shall be carried out from the working drawing/sketches issued
by Purchaser and mode of measurement shall be as specified in this document or as
per IS: 1200 (latest revision).
Measurement at site shall be taken only in case of site deviation from
drawings/sketches issued to the Contractor or in cases where measurement from
drawings is not possible.

04.03 Time Schedule


The time of completion for the whole civil work shall be 4 (Four) months from the
effective date.( Effective date shall be date signing of the contract or 30 days from the
date of Letter of Award whichever is earlier).

04.04 Site Visit / Local Conditions

The contractor, before submitting his tender, shall visit the site and ascertain the local
conditions, labour rules, availability of area, traffic restrictions, all obstructions in
the area and also ascertain all site conditions including the subsoil conditions and
shall allow for any extras likely to be incurred due to all such conditions in his quoted

Copyright © 2016. MECON Limited. All Rights Reserved Page 7 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

price. Further, contractor is advised to accustom himself of status of balance civil


works for various units mentioned in Section-02 of this specification. After award of
the work, no additional claims will be entertained on these accounts under any
circumstances, whatsoever, from the successful contractor.
04.05 Completeness
Any item of work which has not been specifically mentioned but is required for
completing the dismantling or the new construction work shall be under the scope
of the tenderer. The tenderer shall clearly indicate such additional requirements, if
any, with adequate justification.

04.06 Purchaser's Obligations

Bhilai Steel Plant shall provide all reinforcement steel and structural steel required
for the construction work free of cost. Purchaser shall also arrange supply of
construction power. However, construction water is in the scope of the contractor.

04.07 Tools & Tackles

The contractor shall be equipped with all the modern tools like batching plants,
concrete pumps, weigh batchers, transit mixers and other construction
equipments required to execute the work. A list of equipment to be deployed for
executing the work shall be submitted by the contractor along with the tender.

04.08 Deviations

The Tenderer shall NOT indicate any deviations and/or exclusions from technical
specifications in respect of the scope of work, specification and any other details
mentioned in the tender documents.

After placement of order, the successful tenderer shall strictly follow the
technical specification, material specification and any other parameters indicated
in the tender specification or its amendments, if any.

04.09 In case of any difference/discrepancies, in the provisions of


a) Bill of Quantities
b) Special Conditions of Contract

Copyright © 2016. MECON Limited. All Rights Reserved Page 8 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

c) Scope of work
d) General Conditions of Contract
the stipulations under special conditions of contract & scope of work shall prevail.

04.10 In the event of any discrepancies between drawings and specifications, it may be
noted that drawings shall supersede the specifications. Similarly in case of
any discrepancies between description in
a) Drawings
b) Schedule of items(BOQ)
c) Specifications
The provisions in the schedule of items shall prevail.

04.11 Working Drawings


Three copies of working drawings shall be issued to the successful tenderer for
construction purposes. Drawings shall be issued in phased manner conforming to
detail project schedule and review of site progress from time to time.

Contractor shall submit monthly programme for execution of works for various units
in advance to facilitate smooth flow of drawings.

04.12 Bench Mark

Standard bench mark reference pillar indicating the absolute level and reference axes
shall be indicated to the contractor. Contractor shall construct all other survey
pillars required by them for survey work with reference to the bench mark pillar.
Contractor shall take all precautions to protect the survey pillars from being
damaged / dislocated during progress of work, by providing suitable barbed wire
fencing around the survey pillars.

04.13 Site Instruction Book

For issuing site instructions to contractor by purchaser/consultant, the contractor shall


maintain triplicate order books with pages numbered. All written site instruction
shall be given on this book which shall be signed by the contractor as token of his
acceptance of the same. One carbon copy of the instruction shall be left in the book
for contractor for his taking necessary action and record. Any instruction given to the

Copyright © 2016. MECON Limited. All Rights Reserved Page 9 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

contractor in the order book shall have the same force as that of any instruction
conveyed to the contractor through a registered letter.

04.14 Dimensions

Figured dimensions shall prevail in preference to scaled dimension. Large scale


details will supersede small scale details shown in drawings. In case of
discrepancy between the two, the contractor shall obtain clearance of
purchaser/consultant before proceeding with work.

04.15 Works not to be misused

All works under or in course of execution or executed shall not be used by the
Contractor for any of his purpose e.g. storage of materials, residence, office etc.
under any circumstances.

04.16 Sequence of work

Contractor shall plan the sequence of all works so as to achieve the desired progress
keeping in mind overall safety and stability at all points of time. If due to a
particular design or specification or availability of machines or any other reason,
a particular sequence of operation is demanded by the engineer due to which some
interruptions are inherent to any one or more types of work or items of execution,
then no claim for such interruption shall be entertained and contractor shall have
to follow the sequence as instructed by the engineer.

04.17 Specialized agency

Works like water proofing of underground premises and roof slabs, false
flooring, false ceiling, wall panelling, pressure grouting etc. shall be carried out by
employing such agencies as are specialized in the respective field. Before
employing specialized agency contractor shall obtain prior written approval for
engaging the same from purchaser/consultant.

Any guarantee obtained by the contractor from such specialized agency, shall be
passed on to the purchaser at the end of the Contract.

04.18 Damages

Any existing services or other properties if damaged or demolished during the


course of execution either willingly or negligently, shall be repaired and re-
erected to its original shape & size by the Contractor at his own cost.

Copyright © 2016. MECON Limited. All Rights Reserved Page 10 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

The Contractor will take all precautions against damages due to rain and storm and
no liability shall rest with the purchaser for any loss for redoing of any work on this
account.

Existing underground services coming in the way of trench or foundation


excavation etc. have to be adequately supported by the Contractor at his own cost
so as to avoid any damage to those services. In case of any accidental damage, the
Contractor shall arrange to rectify and reinstall those services immediately at his
own cost.

04.19 Testing

All sewer, manholes, drainage lines shall be tested for smooth flow without any
stagnation as per specification. Smoke test shall be conducted on sewer lines.
Pressure test shall be carried out in all water supply lines as per specifications by
dividing the whole system, if required, into suitable number of sub-systems by using
stop cocks etc. for isolation of system. Before, putting the bib-cocks etc. entire
water supply plumbing lines shall be pressure tested for ensuring no leakage
condition. All such tests shall be carried out by the Contractor at his own cost.

04.20 Quality Assurance

a) To ensure quality of construction, the contractor shall ensure inspection


and testing of all materials and works at his own cost conforming to
specifications.

b) All certificates and guarantees obtained by the contractor from different


suppliers of materials, subcontractors doing part job, manufacturers of
doors, windows etc. shall be passed on to the purchaser.

c) All defective materials / works which do not conform to the specifications


shall be rejected / dismantled and removed from site by the Contractor at
his own cost.

d) The Contractor shall provide a site laboratory with equipment and shall
maintain and engage qualified technical personnel at site to run the
laboratory at his own cost. All routine tests of cement, aggregates, sand,
bricks, concrete cubes, etc. shall be conducted at site, and equipment
required for accelerated concrete cube test should also be provided in
the laboratory for predicting the strength of concrete early.

e) For those tests which are not possible to be carried out at site laboratory,
Contractor shall arrange to send requisite samples to BSP approved
laboratory outside the site and get those tested as required entirely at his
cost.

f) Before starting any concreting or erection work at site, the stage passing
certificates have to be obtained from the engineer in the formats
prepared after mutual discussion and agreement.

g) As-built survey details marking location of all bolts and inserts shall be
submitted by the Contractor so as to enable further structural/equipment
erection without any loss of time.

Copyright © 2016. MECON Limited. All Rights Reserved Page 11 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

h) Before covering up any work within excavated pits, clearance has to


be taken from engineer in respect of completion of said works as per
drawing and specification.

04.21 Explosives

Use of any kind of explosives either for rock blasting excavation or for any other
works is not envisaged. However controlled blasting can be taken up for hard
rock excavation with written permission of client on case to case basis.

04.22 Construction Materials

a) All construction materials needed for civil works including cement shall
have to be arranged and procured by the Contractor. The reinforcement
steel, rails and raw material for fabricating inserts like plate, angles,
channels except structural bolts, pipes for making inserts required for the
work shall be issued by BSP free of cost. However, the contractor has to
make his own arrangements for collecting and transporting the same
from the BSP store to site at his own cost.

b) Responsibility for ensuring the quality and custody of cement shall rest
with the Contractor. If the contractor uses the cement without any check
on quality which may result in poor quality concrete, then dismantling and
redoing such defective structures shall be at contractor's cost. No claim
whatsoever due to poor quality of cement shall be entertained later.

c) Tools, tackles & labour : The contractor shall make his own
arrangements for all tools, tackles and labour including hutment etc.

04.23 Safety

The Contractor shall ensure that the safety requirements are met in respect of
men, materials, adjoining structures, equipment etc. and shall be totally
responsible in case any mishap occurs due to negligence or otherwise. In this
connection the contractor shall strictly adhere to the rules, norms and
regulations as applicable. The successful bidder shall collect the BSP Steel Plant
safety rules from the client. The successful tenderer shall strictly adhere to the
safety regulations mentioned therein. The penalties for violation of safety norms
as per purchaser stipulations are applicable. The safety precautions shall
conform to the safety regulations prescribed by the safety code for constructions
and relevant Indian standard codes, some of which are started below:
IS376 4:1992 : Safety code for excavation work.
IS 4014 : 1967 : Safety regulations for scaffolding work
IS 4081 : 1986 : Safety code for drilling and blasting operations.
IS 4138 : 1977 : Safety code for working with compressed air.
IS 7923 : 1985 : Safety code for working with
construction machinery.

Copyright © 2016. MECON Limited. All Rights Reserved Page 12 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

04.24 Preliminary Acceptance

After completing the construction or dismantling of a unit(as the case may be) or
agreed upon thereof, the Contractor shall give a notice in writing stating that the
job is completed in all respects and ready for preliminary acceptance. The job
shall jointly be inspected by the Owner, Consultant and Contractor to ascertain
whether the job is completed as per requirements and technical specifications.
All observed defects, deficiencies and omissions shall be noted. If the defects,
deficiencies and omissions are not major in the opinion of Purchaser /
Consultant, the contractor will be issued a preliminary acceptance certificate
mentioning observed defects, deficiencies and omissions. The noted
defects,deficiencies and omissions shall be made good by the contractor within
a period of 2 to 3 weeks time.

04.25 Completion Certificate

Completion certificate will be issued to the contract only after the defects,
deficiencies and omissions noted during preliminary acceptance have been
completely rectified by the contractor.

04.26 Defect liability period

Defect liability period of one year shall start after issuance of Completion
certificate . The contractor shall maintain and attend to all defects arising in the
structures constructed by them during the maintenance period .If any major
defects arises during such period ,the contractor shall reconstruct/rectify the
same in stipulated period mutually discussed with Purchaser/Consultant.
Maintenance period of such area of work shall be extended for a period of one
year after rectification of major defects.

04.27 Final Acceptance

The contractor shall attend to all defects deficiencies and omissions during the
defect liability period and after rectifying or making good the above in all
respects, shall inform 10 days in advance to Purchaser/ Consultant for
conducting final acceptance. Before issue of final acceptance all defects
deficiencies and omissions noted during defect liability period will be checked.
Any defects / deficiencies /omissions not notified during issuance of Completion
Certificate, if pointed out during defect liability period shall be rectified by the
contractor. Final acceptance certificate shall be issued by Purchaser /
Consultant only after all the defects / deficiencies / omissions noted during
Detect liability period have been rectified.

04.28 Conditions applicable for free material issued by Purchaser

Contractor will be issued reinforcement steel, rails and raw material for
making inserts like plate, angle, flat channel as free issue material for use in
permanent works

a) All the steel will be issued on weighment basis without any rolling
margin
b) For the purpose of payment and accounting ,the weight of steel shall

Copyright © 2016. MECON Limited. All Rights Reserved Page 13 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

be calculated as per bar bending schedules considering running


meter weight as per IS
c) Wastage to an extent of 3%(2.5% accountable to be returned as
scrap and 0.5% unaccountable) shall be allowed for reinforcement
steel. For structural -5% accountable & 2% unaccountable.
d) Contractor shall account for all steel drawn by him and shall return
all surplus steel including all cut pieces after separating the usable
bars having minimum length of 3 meters and scrap to Employer go
down /stockyard at his own cost
e) Contractor shall make all his efforts to use the cut pieces/scrap to a
maximum.

f) For any misuse/unaccountable quantity of free issue material (


reinforcement, insert steel and rails) steel recovery @200% of
prevailing market rate shall be made by the Employer
g) Surplus stock of reinforcement steel/rails ,if any in full length or
having minimum length of 3 meters will be taken back as raw steel
by Employer. Contractor to return the above raw steel in diameter
wise at Employer store

Copyright © 2016. MECON Limited. All Rights Reserved Page 14 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

ANNEXURE- I : SPECIFICATION FOR FLY ASH -CEMENT BRICKS

1.1 Unless specifically mentioned otherwise, all applicable codes and standards
published by the Bureau of Indian Standards shall govern design, workmanship,
quality and properties of materials, method of field and laboratory testing,
method of measurement for different items of work etc.

1.2 Materials

1.2.1 Cement : 33 grade ordinary Portland cement conforming to IS:269 or Higher


Grade above 33 Grade.

1.2.2 Sand : Sand shall be free from deleterious materials like clay and silt in sand
and shall be less than 5%. Sand shall conform to IS: 383.

1.2.3 Fly Ash : Fly ash used for manufacturing fly ash cement bricks shall conform to
Grade-I or Grade-2 of IS:3812.

1.3 Proportion

1.3.1 The proportion of Fly ash, sand and cement shall be as given below:

Cement : 8-10%
Sand (fine aggregate) : 35-40%
Fly ash : 50 -6 0%

1.3.2 The fly ash bricks manufactured shall meet the testing and acceptance criteria
specified in Clause 1.6

1.4 Marking

All pre-cast bricks shall be marked in a manner approved by the Engineer-in-charge in


a conspicuous place with date of manufacture and marking number. The upper part of
the bricks shall be marked distinctly to ensure proper handling.

1.5 Curing

The contractor shall keep all the bricks wet for not less than 28 days.

1.6 Testing & Acceptance criteria

1.7 Sampling and criteria for conformity

Sampling and criteria for conformity of the bricks shall be as given in IS: 5454.

1.8 Compressive strength

Minimum compressive strength of fly ash bricks shall be as specified in IS:12894 when
tested as per IS:3495 (Part-1) of class 10, as specified in sub clause No. 6.1 page 02.

1.9 Drying shrinkage

Copyright © 2016. MECON Limited. All Rights Reserved Page 15 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

The average drying shrinkage of three units shall not exceed 0.15% when tested by the
method described in IS:4139.

1.10 Efflorescence

The bricks shall be tested as per IS:3495 (Part-3) and shall have the rating of
efflorescence not more than moderate.

1.11 Water absorption

The bricks, when tested in accordance with the procedure laid down in IS:3495 (Part-2)
after immersion in cold water for 24 hours, shall have average water absorption not
more than 20% by mass.

1.12 Laboratory

The quality of raw materials and quality of bricks shall be tested in the presence of
Engineer-in-charge in the approved laboratory with proper testing facilities.

Copyright © 2016. MECON Limited. All Rights Reserved Page 16 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

CIVIL
SCHEDULE
OF
QUANTITIES

Copyright © 2016. MECON Limited. All Rights Reserved Page 17 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

04.00 CIVIL SCHEDULE OF QUANTITIES

Rate
(inclusive of
all duties &
taxes, freight,
etc. but
Item excluding
No Description Of Item Unit Quantity service tax) Amount

SECTION- EW [ EARTHWORK ]
Earthwork in excavation of foundations for
buildings, equipments, structures, channels,
tunnels, trenches, drains, pits, wells, manholes,
chambers, pavements, basements, tanks, culverts
etc. in all kinds of soil upto 2.0 M depth
(excluding rock requiring excavation by
mechanical means )and including all lifts, in both
wet and dry conditions, dewatering of surface and
EW-1 subsurface water, shoring, planking and strutting
(if required) including backfilling with approved
earth and compacting in layers of 15 cm within
500 M lead as directed with watering, ramming
and compacting thoroughly each layer around
foundations, structures, plinth including floor etc.,
disposal/stacking of surplus excavated soil etc.
within a lead of 500 M and as per specifications &
direction of the engineer. Cu.m 1000
(The measurement for payment shall be for the
theoretical excavation volume only as per drawing
i.e. for the volume of the block of the excavation
having the depth and maximum bottom
dimensions of the foundation/structures as per
drawing after deducting corresponding quantity of
hard rock if any paid separately under respective
items. The contractor shall take into account in his
rate the provision for any excess excavation for
necessary working space, steps, sloping etc
required for excavation safety and other allied
works and refilling the side slopes/working space
etc.).
Same as per Item EW-1 above, but for depth
EW-2 greater than 2.0 M upto 4.00 M Cu.m 1000
Same as per Item EW-1 above, but for depth
EW-3 greater than 4.00 M upto 6.00 M Cu.m 900
Same as per Item EW-1 above, but for depth
EW-4 greater than 6.00 M upto 8.00 M Cu.m 250

Copyright © 2016. MECON Limited. All Rights Reserved Page 18 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

Transportation & filling approved earth in all


position in layers of 15 cm including watering,
ramming and compacting thoroughly each layer, at
all heights and depth, in foundation pits, trenches,
under floor and any other locations with clean river
EW-5
sand including transporting, loading, unloading,
depositing, dressing, levelling, watering and
compacting etc. complete with all bye-works as
per drawing, specification and as directed by the
Engineer. From borrow pits within a lead of 5 Km. Cum 36200
Transportation, carriage and disposal of excavated
earth, into low lying areas etc. including loading,
unloading, stacking, levelling by mechanical
EW-6 means, dressing etc. with all bye works complete
as per specification and instruction of the
engineer. .(Disposal location shall be indicated by
the purchaser)
Up to a lead of 5 Km beyond initial lead of 500m Cu.m 3250
SUB TOTAL : EW:

SECTION - CC [ CEMENT CONCRETE ]


Supplying and laying plain cement concrete
(machine mixed) of Grade M-10 with stone
aggregate of 40 mm and down size (including
formwork if required), in all levelling courses, in
foundations, footings, pipelines, pits, sumps,
CC-1 manholes, basements, tunnels, floors, platforms,
steps, walls, drains, culverts, chambers, channels,
retaining walls, kerbs including mass concrete etc
at all heights & depths with all bye-works complete
as per drawing, specification and instruction of the
engineer. Cu.m 800
Same as Item No.CC-1, but with concrete of grade
M-15 with stone aggregate 20mm and down size
CC-2 in screed concrete for roofs and in underground
tunnels, basements etc at all heights and depths. Cu.m 900
Supplying and laying of reinforced cement
concrete (machine mixed) of following grade with
stone aggregate (excluding formwork and
reinforcement) at all levels and shapes in
foundations, footings, retaining walls, equipment
foundations, raft, walls, basements, tunnels, floors,
columns, buttresses, ducts, lintels, trenches,
tanks, cantilevers, beams, brackets, slabs,
staircases, coffered / grid slabs, chajjas, sills, fins,
CC-3
facia, bands, railings kerbs, balustrades, parapets,
louvers, spouts, shelves, brackets, work table,
cover slab, mentle piece, bed block, copings,
cornices, mouldings, string, over sailing courses,
anchor blocks, posts, struts, newels, pillars and
similar members with all bye-works including
supply and mixing of plasticiser, retarder etc
complete as per drawing, specification and
instruction of the engineer.
i) Using stone aggregate 20 mm down graded.

Copyright © 2016. MECON Limited. All Rights Reserved Page 19 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

(a) Grade M-30 Cu.m 6508


Supplying and laying reinforced cement concrete
grade M-30 (machine mixed) with stone aggregate
of 20 mm and downgraded (excluding formwork
and reinforcement) at all heights for super
CC-4
structures of chimneys, silos bunkers, hoppers
and elevated tanks of all shapes with all bye-works
complete as per drawings, specification &
instruction of the engineer. Cu.m 100
Supplying and laying plain cement concrete/
reinforced cement concrete flooring of following
grade with stone aggregate 20mm downgraded
laid directly over earth / sub-base (including
CC-4 shuttering wherever required but excluding
reinforcement) with all bye-works including supply
and mixing of plasticizers, retarders etc complete
as per drawings, specifications and instruction of
the engineer.
a) Concrete Grade M-20 850
Cu.m
Fabricating and fixing in position TOR/TMT steel
reinforcement at all levels and positions excluding
the cost of steel but including cost of taking
delivery from BSP store, transportation,
straightening, cutting, bending, cranking, binding,
welding etc. as per drawings and specifications,
including cost of binding wire, welding electrodes,
labour, preparation of bar bending schedule etc.,
CC-5 all complete, for reinforced concrete and
reinforced brick work and any other place as
specified and directed by the engineer. The
reinforcement steel shall be supplied by BSP as
free issue item at their stores / place of delivery.
(Payment will be made on the basis of standard
weight per metre length of the bar).
(a) Plain mild steel bars Tonne 1
(b) High strength deformed steel bars Tonne 895
Providing and fixing all types and shapes of
cantering, shuttering, strutting and propping firmly
with screws, bolts, separators, tension devices,
true to line and level including stripping off the
same from positions for PCC and RCC works at all
depths and heights with all bye-works complete as
per drawing, specification and instruction of the
engineer.
(a) In all types of foundations, footings, retaining
CC-6
walls, equipment foundations, rafts, walls,
basements, tunnels, floors, columns, buttresses,
ducts, lintels, trenches, tanks, cantilevers, beams,
brackets, slabs, stair cases, coffered /Grid slabs
and any other similar type of works both
underground and in super structure. Sq.m 39048

(b) In chimneys, shafts, silos, bunkers, hoppers,


elevated tanks and any other similar type of works. Sq.m 800

Copyright © 2016. MECON Limited. All Rights Reserved Page 20 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

(a) Fabricating and fixing in concrete and mason-


ry, at all levels and positions, Mild Steel inserts like
plates, angle iron, flats, channels, including
painting the exposed surface with 2 coats of
approved quality paint over and including a coat of
primer, providing grease to the exposed area of
CC-7 the bolts, welding wherever necessary, complete
as per drawing and specification and as per
instruction of the engineer (PCC blocks, jigs and
fixtures will not be paid separately) and protecting
the same till final erection.The steel shall be
supplied by BSP as free issue item at their stores /
place of delivery Kg. 165200
b) Same as above but with supply of items like
structural bolts pipe inserts, pipe specials using
material confirming to IS 2062 grade A with nuts
and washers including applying grease wherever
required. Kg. 12000
Supply, Fabricating and fixing in already
constructed concrete and masonry, at all levels
and positions, Mild Steel inserts like plates, angle
iron, flats, channels with anchor fasteners like
HILTI bolts(including the cost of anchor fastener),
CC-8
painting the exposed surface with 2 coats of
approved quality paint over and including a coat of
primer, welding wherever necessary, complete as
per drawing and specification and as per
instruction of the engineer. Kg. 3000
Fabricating and fixing in position steel inserts
made from rails in concrete walls, floors etc. at all
levels and positions excluding the cost of rails but
including cost of taking delivery from BSP store,
transportation, straightening, cutting, painting the
exposed surface with 2 coats of approved quality
CC-9 paint over and including a coat of primer, welding
wherever necessary, complete as per drawing and
specification and as per instruction of the engineer
(PCC blocks, jigs and fixtures will not be paid
separately) and protecting the same till final
erection. The rails shall be supplied by BSP as
free issue item at their stores / place of delivery. Kg. 109500
Supplying and grouting foundation pockets under
base plates etc. with ready mixed non-shrink grout
(Shrinkkomp, ARALDITE/ SIKA/ FOSROC or
equivalent) of approved manufacturer) at all
CC-10
locations including shuttering (wherever
necessary) with all bye works complete as per
drawings, manufacturer’s specification and as
directed by the engineer. Cu.m 2
Construction of anchor holes or anchor pockets of
following sizes at all positions including necessary
shuttering and its removal, cleaning and keeping
CC-11
the holes/pockets covered till erection of anchor
bolts with all bye-works complete as per drawings,
specification and instruction of the engineer.
(a) Cross section upto 120 Sq.cm. RM 20

Copyright © 2016. MECON Limited. All Rights Reserved Page 21 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

(b) Cross section more than 120 Sq.Cm. but not


exceeding 300 Sq.Cm 20
RM
Manufacturing, supplying and erecting pre-cast
RCC Members/Structures of different types
including in-situ concreting/grouting/fixing in
position by welding or other means to lines and
levels and accuracy’s complete as shown in the
CC-12 drawings and as directed by the engineer, at all
depths and heights using stone aggregate of
20mm and down graded including smooth
finishing requiring no further rendering, and
including cost of shuttering but excluding cost of
inserts and reinforcements.
i) Using Concrete of grade M-25
(a) Weight of individual element upto 0.5 tonne Cu.m 25
Providing water-proofing system to reinforced
concrete structures to make water tight (using
compounds of reputed manufactures like
ARALDITE, SIKA ,FOSROC) at all locations,
depths and heights as indicated in drawings
consisting of 2 coats of approved acrylic polymer
modified cementitious material over 10 mm thick
1:5 CM plastered (including water proofing
CC-13
additive in mortar) surface over mud mat below
base raft and over rendered wall and roof
surfaces in contact with soil any other locations as
directed, placing of 15mm dia MS/PVC nozzles of
suitable length all over the inside surfaces of
raft/wall/roof slab and all construction joints at
regular intervals not exceeding 1.5m centre to
centre, mixing approved super
Plasticizer. cum cement water proofer during
concreting and finally pressure injecting non-shrink
polymeric water proof grouting compound admixed
with cement milk through the nozzles and sealing
the nozzles with approved sealant after grouting
all complete with all bye-works as required so as
to make the structure water tight. (Manufacturer's
specification shall be followed depending on
approved materials used and payment shall be
made based on measurements on inside surface
dimensions only and no separate payment will be
made for rendering).
a) For over plastered surface below base raft Sq.m 4000
b) For walls and roof surfaces Sq.m 8650

Copyright © 2016. MECON Limited. All Rights Reserved Page 22 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

CC-14 Providing water-proofing system to reinforced


concrete structures to make water tight (using
compounds of reputed manufactures like
ARALDITE, SIKA ,FOSRAC ) at all locations,
depths and heights as indicated in drawings
consisting of placing of 15mm dia. GI nozzles of
suitable length(125mm max) all over the inside
surfaces of raft/wall/roof slab and all construction
joints at regular intervals not exceeding 1.5m
centre to centre, mixing approved super plasticiser
cum cement water proofer and finally pressure
injecting non-shrink polymeric water proof grouting
compound admixed with cement milk through the
nozzles and sealing the nozzles with approved
sealant after grouting all complete with all bye-
works as required so as to make the structure
water tight. (Manufacturer's specification shall be
followed depending on approved materials to be
used Payment will be based on number of grout
points). Each 5100
SUB TOTAL CC:

SECTION - MN [ BRICK MASONRY ]


Providing flyash cement brickwork in cement
mortar of following proportions in superstructure in
all types of facing, coping, bands, projections,
parapets, ornamental cornices, string course and
reinforced brickwork (excluding the cost of the
reinforcement which shall be paid separately
MN-1 under reinforcement items) and at any other
location, of circular, curved or any shape including
moulding and cutwork at all lead and heights,
curing, scaffolding complete with all bye-works as
per drawing, specification and instructions of the
engineer, with bricks of approved quality.
(a) 1: 6 mortar (1 cement : 6 sand) Cu.m 2200
Providing flyash cement brickwork of half brick
thickness in cement mortar with continuous wire
netting or 2 Nos. 6 mm dia MS bars at every 4th
course of following proportions in all type of walls,
pillars, abutments, ducts, manholes, drains
(vertical and inclined sides), projections, railings,
parapets, fins, bands, copings, over sailing course,
facia, ornamental cornices, sling course etc. and
MN-2 at any other location of circular, curved or any
shape, at all depths, heights, including mouldings,
cutworks and reinforced brickwork (excluding the
cost of the reinforcement which shall be paid
separately under reinforcement item), at all lead,
curing, scaffolding complete with all bye-works as
per drawing, specification and instructions of the
engineer, with bricks of approved quality .
(a) 1:4 mortar(1cement:4sand) Sq.m 1000
SUB TOTAL : MN :

Copyright © 2016. MECON Limited. All Rights Reserved Page 23 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

SECTION - FN : PLASTERING & FINISHING


15 mm thick cement plaster in one layer on faces
of walls, pillars, projection, bands, cornices, fins,
sills etc. including raking out joints, if any left out,
necessary dabbing, curing, scaffolding complete
FN-1 with all material & labour at all heights and depths
as per specification and drawings and as per
direction of Engineer.
(a) with 1:6 cement mortar (1 cement : 6 sand) Sq.m 27000
20 mm thick cement plaster all details same as per
item No.FN-1 above, but in two layers in place of
FN-2 one.
(a) with 1:6 cement mortar (1 cement:6 sand) Sq.m 11000
6 mm thick cement plaster to ceiling of slab,
chajja, bands, sills, beams, columns, channels, loft
slabs, staircases, fins, parapets and any other
location with drip course wherever required with all
FN-3 bye-works, dabbing, curing, scaffolding complete
with all material & labour at all heights and depths
as per specification and drawings and as per
direction of Engineer.
(a) with 1:4 cement mortar (1 cement : 4 sand) Sq.m 3300
Providing and applying water proof cement paint
Acrylic exterior grade paint of "Super Snowcem" or
approved equivalent make of approved shade,
FN-4 three coats over surfaces, at all heights and
locations with all bye works complete as per
manufacturer's specification and application
procedure and as per instructions of the engineer. Sq.m 11000
White washing three coats with approved quality
lime at all heights and locations with all bye-works
FN-5 including provision of scaffolding complete as per
specifications and instruction of the engineer.
(Single then subsequent) Sq.m 3300
Providing and applying two coats of synthetic
washable distemper of approved manufacturer like
ASIAN PAINT/ BERGER/NEROLAC or equivalent
make with approved shade at all locations over
FN-6 and including a coat of approved cement primer
over wall surface, ceiling etc. including preparation
of base complete with all bye works as per
manufacturers specification and application
procedure and as the instructions of the engineer. Sq.m 27000
SUB TOTAL : FN :

SECTION - FL [ FLOORING, PAVING & FACING


]

Copyright © 2016. MECON Limited. All Rights Reserved Page 24 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

Providing hard core with hard stone boulders of


minimum size 200 mm including laying, packing,
filling interstices, with good quality spoils, dry and
wet consolidation with mechanical means, blinding
FL-1
with good quality earth (cost inclusive) with all bye-
works complete for hard core upto 250 mm thick,
below floor as per specification and instruction of
the engineer (consolidated thickness will be paid). Cu.m 750
Providing and laying cement concrete of specified
thickness, of concrete grade M-20 with stone
aggregate of 12 mm and down graded, laid in
panels if required, with smooth integral finish at
floors resting on ground, steps, floors, pavements
FL-2
etc., at all levels and locations, including base
preparation with all bye works complete as per
drawing, specification and direction of the
engineer (The chequered finish if required is
inclusive) Cu.m 50
Providing and laying 40 mm thick grey artificial
stone flooring laid in panels at all location and
heights including steps, nosing, landing slab etc.
consisting of plain cement concrete 1:2:4 base
(under bed) 30 mm thick (1 cement, 2 coarse
sand, 4 stone chips, 12 mm and down) and
topping 10 mm thick (net) of mix 1:1:1 (1 cement :
FL-3
1 medium sand : 1 fine stone dust upto 6 mm size)
and finished with a floating coat of neat cement (at
2 Kg of cement per sq.m of flooring) supplying and
fixing glass strips 3mm thick upto 40 mm deep,
complete with all bye works as per specification,
drawing (chequering in floor finish inclusive if
required) and as directed by the engineer. Sq.m 500
Providing and laying 40 mm thick cement concrete
flooring with concrete hardener, like “NITOFLOOR
HARD TOP” or equivalent of approved make with
on topping of floors, steps nosing and other places
as shown in the drawing, at all levels and
locations, the flooring consists of 30 mm thick
concrete base (under bed) of 1:2:4 mix (1 cement,
2 coarse sand, 4 stone chips 12 mm downgraded),
and topping of 10 mm thick (net after cutting), the
topping consisting of 1:2 mix (1 part cement
FL-4 hardener mix and 2 parts stone grit 6 mm down
graded by volume) the cement metallic hardener
mix shall be by mixing 4 parts of cement and 1
part of metallic floor hardener (Pidilite Fosrock,
Sahara or approved equivalent) by weight, or as
per manufacturers specifications inclusive of
surface preparation, laying in panels, supplying
and fixing of glass strips 3mm thick upto 40 mm
deep, roundings, curing, finishing etc. with all
byeworks complete as per specification and
direction of the engineer. Sq.m 6700

Copyright © 2016. MECON Limited. All Rights Reserved Page 25 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

Providing and laying 21 mm thick gray cement


skirting or dado on walls, risers or steps or any
other vertical surfaces at any levels and locations
consisting of 15 mm thick back coat of cement
mortar 1:3 (1 cement : 3 sand) and 6 mm topping
FL-5 (net) with 1:1 cement stone chips mix (1 cement to
1 fine stone chips 3 mm down graded), finishing
with a floating coat of neat cement, sup-plying and
fixing glass strips 3mm thick upto 21 mm deep in
dado, complete with all bye-works as per
specification and direction of the engineer. Sq.m 1000
SUB TOTAL :FL:

SECTION - MS [ MISCELLANEOUS ]
Providing damp proof course over plinth with
cement concrete Grade M-20 using aggregate of
10 mm and down graded and mixing approved
waterproof admixture with cement as per
manufacturer's specification and application
procedure including necessary formwork/ shutter-
MS-1
ing, one coat of hot bitumen of Grade S-35/A-35
over the top surface of damp proof coarse and all
necessary bye-works complete as per
specification, drawing manufacturer’s specification
& application procedure and as directed by the
engineer.
40 mm thick Sq.m 300
Providing and laying water proofing treatment over
roof and other places as shown in the drawing
using approved material consisting of 2 coats of
Acrylic polymer based cementitious slurry coating
with one layer of fibre glass cloth in between
coatings including protecting the coated surface
with cement concrete screed of M-15 grade, laid in
the slope of 1:100 including all necessary bye-
MS-2
works like necessary base surface preparation,
rounding the corners/ ends/sides of dissimilar
materials, sealing the joints/ends etc. complete all
as per specification , drawing or manufacturer’s
specification & application procedure and as
directed by the engineer at all levels and locations
(undertaking for service guarantee for 10 years by
the contractor). Sq.m 3500
Supplying and laying G.I. (Medium Class) conduit
pipes of the following diameters in required length
and bending to required shape at all heights and
locations to be embedded in concrete or masonry,
and protruding out from the face, with threaded
ends (if required) as shown in the drawings, with
MS-3
all bye-works complete as per specification and
direction of the Engineer.
a)50mm dia RM 25
b) 65mm dia RM 25
c) 80mm dia RM 25

Copyright © 2016. MECON Limited. All Rights Reserved Page 26 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

d) 100mm dia RM 150


e) 150mm dia RM 100
Chipping of the concrete up to about 50 mm using
mechanical means such as HILTI gun etc. or any
other method with least disturbance to structure to
MS-4 expose the reinforcement bars necessary as
indicated in drawings with all labour, tools, tackles,
machinery etc., all complete as per specification
and direction of Engineer-In-Charge Sqm 200
Welding of reinforcement bars to existing
reinforcement after exposing the bars including
cleaning of the existing reinforcements bars so
exposed on chipping with approved quality
MS-5
electrodes including all bye works as per
specifications and instructions of engineer in
charge (reinforcement bars will be paid separately
under respective item) RM 100
Fixing of bolts during concrete in position the
bolts suppiled by equipment supplier complete as
per drawing and specification and as per
MS-6 instruction of the engineer and protecting the
same till final erection. ( Material used for jigs and
fixtures will be considered for reconcilation and no
payment for placing the same will be made) Kg 3000
Fixing of inserts during concrete in position the
inserts supplied by equipment supplier complete
as per drawing and specification and as per
MS-7 instruction of the engineer and protecting the
same till final erection. ( Material used for jigs and
fixtures will be considered for reconcilation and no
payment for placing the same will be made) Kg 1000
Fixing of conduit pipes supplied by equipment
supplier / client complete as per drawing and
specification and as per instruction of the
MS-8 engineerand protecting the same till final erection.
( Material used for jigs and fixtures will be
considered for reconcilation and no payment for
placing the same will be made)
a)50mm dia RM 20
b) 65mm dia RM 20
c) 80mm dia RM 20
d) 100mm dia RM 100
e) 150mm dia RM 100
Providing and fixing with Standard PVC water bars
of following width at all locations in construction
joints as per drawings including vulcanization of
MS-9
joints wherever required, with all bye-works
complete as per specification and drawings etc.
a) Width 230 mm (PVC) (8mm thick) RM 1500

Copyright © 2016. MECON Limited. All Rights Reserved Page 27 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

Providing and laying expansion joint treatment of


the following thickness with approved bitumen
impregnated fibre board including provision of
bituminous paint of approved quality make and
type on the sides, sealing the open joint with
approved quality sealing compound like poly
MS-10 sulphide of reputed manufacturers like FOSRAC,
SAHARA,SIKA at all heights and locations with all
bye-works complete as per drawing,
manufacturers specification and application
procedure and as per the instructions of the
engineer/ standard practice
50 mm thickness Sq.m 100
Supplying, fitting, joining and fixing in position PVC
rainwater down pipes, soil pipes of
Supreme/Finolex/Prince or equivalent make of
approved quality including all necessary specials
MS-11 like bends, shoe,tees etc. Joining with adhesive
solution of approved brand flat iron straps for fixing
to wall at all heights and locations with all bye-
works complete as per drawing, specification and
direction of the engineer
a) 100 mm dia RM 150
Supplying and applying bonding materials on
existing concrete surface for joining old and new
concrete, with ARALDITE HARDENERS or any
other approved epoxy material, at all locations and
MS-12 levels including preparation of concrete surface
and bonding material mix as per manufacturer's
specifications including all bye works, all complete
as per drawing, specifications and direction of
engineer. Sqm 250
SUB TOTAL :MS:

SECTION –DD (Dismantling works)


Breaking of PCC, removing debris and disposing
DD-1 of within a lead of 6 Km as directed by the
Engineer. Cu.M 10
Breaking of RCC structures , beams, columns,
posts, slabs foundation (including machine
foundations), lintels, chajjas, pits, walls & RCC
flooring above 250mm thick in ground floor or
DD-2 upper floors (upto 25M from GL),hume pipes
including cutting of reinforcement and
embedments, removing all debris and steel and
disposing off the same within a lead of 6 Km as
directed by Engineer Cu.M 10
SUB TOTAL : DD

SECTION - ST [IRON & STEELWORKS]

Copyright © 2016. MECON Limited. All Rights Reserved Page 28 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

Supplying, fitting and fixing fully glazed steel


windows, and ventilators of approved
manufacturer in single or composite units, both
openable and fixed type as per IS:1038 - 1983 and
IS:1361 - 1978 with all joints flash butt welded
including coupling bars, providing mullions,
transoms, friction hinges, mastic cement, glass
panes of plain/frosted sheet glass, fixing with
metal beads as per IS:1038-1983 with 2 coats of
ST-1 synthetic enamel paint of approved colour and
quality over and including a primer coat to steel
frames complete including all other standard C.P.
Iron fixture like handles, peg stays, locking
arrangements etc complete with all byeworks as
per specification, drawing & direction of the
engineer.
Fixed glazed windows of standard/ non- standard
size using M.S. sections and details as per IS :
1038 - 1983. Sq.m 200
Providing and fixing in position close fitting
coloured anodized(minimum 16 m) glazed
aluminium door with frame "INDAL" or any other
approved make extruded sections of size
101.6mmX44.75mmX3.18mm and standard
shutters with 5.5mm thick of approved quality fixed
ST-2
with standard glazing beads outside and inside,
and providing and fixing all standard fittings such
as handles, locks, bolts, push plates, rubber
gaskets etc as per drawings and manufacturer's
specification and instructions of engineer(Payment
will be for the overall size including frame)
a) Single shutter with single action spring. Sq.m 15
b) Double shutters with double action springs on
both shutters. Sq.m 30
Providing and fixing in position including grouting /
welding, steel doors consisting of steel plate single
walled, hinged type, fully plated door on frames
with or without service door, necessary bolting
device, locking arrangements, handles, threshold
ST-3
etc including painting with two coats of approved
co lour and quality of synthetic enamel paint over
and including a primer coat complete with all bye
works as per drawings, specification and direction
of the engineer Kg. 1000

Copyright © 2016. MECON Limited. All Rights Reserved Page 29 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

Supplying and fixing of rolling shutters of approved


make made of M.S. laths interlocked together at
the end by the locks, mounted on specially
designed pipe shaft with brackets, side guides and
arrangements for inside and outside locking, with
push and pull operation including cost of top cover
(1.25mm thick), spring and other necessary
fixtures complete, with two coats of synthetic
enamel paint over and including a primer coat,
ST-4 making chases in wall/floor and grouting the
clamps in PCC 1:2:4 or welded to inserts complete
with all bye-works as per specifications and
instruction of the engineer (Partial grills and
special stiffening members shall be provided
wherever necessary).
(a) Hand operated with ball bearing
arrangements.
Using 80x1.25 mm thick M.S. Laths. Sq.m 192
Supplying, fabricating and fixing in position (M.S.)
chequred plate covering with stiffners, frames, as
required, to the line and level over cable or any
ST-5 other trench including two coats of approved
synthetic enamel paint on both sides over and
including a coat of primer all complete as per
drawings and specifications. Kg 60000
Supplying and fixing at all levels and positions
structural steel works ( bolted or welded) in built
up sections, staircases, ladders, brackets, gratings
etc, using mild steel angles, channels, joists,
plates, flats, pipes, tubes, wall ties, stiffners,
ST-6
chequered plates, gratings, manhole covers etc
including two coats of approved synthetic enamel
painting over and including a coat of primer, with
all bye-works complete, as per drawings,
specification and instruction of the engineer. Kg. 5000
SUB TOTAL : ST :

SECTION - SW (SANITARY & WATER SUPPLY)


Supply, fitting and fixing white glazed vitreous
china wash basin of superior quality, size 55cm x
40cm of HSW/Parry ware of nearest size, with
provision of having single or double holes, 32 mm
CP brass waste fittings, 15 mm CP brass pillar tap,
SW-1 CP brass chain and plug, 32 mm CP brass bottle
trap, 15 mm PVC connection pipe with CP brass
coupling, painted metallic brackets and 15 mm
brass stop cock all of approved quality complete
with all bye-works as per specification and in-
struction of the engineer. Each 2

Copyright © 2016. MECON Limited. All Rights Reserved Page 30 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

Providing and fixing white vitreous china pedestal


type water closet (European type W.C. pan) with
seat and lid, 10 litre low level white P.V.C. flushing
cistern with manually controlled device (handle
SW-2 lever), conforming to IS : 7231, Parryware
/Hindware/ Seabrid / Orient (Coral) with all fittings
and fixture complete including cutting and making
good the walls and floors wherever required : W.C.
pan with ISI marked white solid plastic seat and lid Each 2
Providing and fixing white glazed vitreous China flat
back, front lipped standing urinal size 61 x 40 x
38cm of superior quality of HSW or of approved
equivalent make of nearest size in range as
indicated below with automatic cistern HSW/Parry
ware with accessories with concealed CI wall
hangers and bracket for automatic cistern, etc.,
SW-3 15mm dia CP brass stop cock as per Jaquer or of
equivalent approved make, standard size CP brass
flush pipe, spreaders with unions and clamp (all CP
brass) with 15 mm dia PVC connection pipe with
CP brass coupling joint at both ends, with 32 mm
dia PVC waste pipe with CP brass coupling upto
floor, with all bye-works as per specification and
direction of the engineer. (Partition excluded).
(a) In range of one with 10 Ltrs capacity cistern Per
2
Set
Providing and fixing 5.5mm thick polished glass
(with bevelled edge) mirror "Atul/Golden Fish"or
approved equivalent with 5 mm thick glass shelf
with CP brass bracket's and hinged guard
approved equivalent make, with 6 mm thick
SW-4
asbestos sheet backing for mirror including fixing to
wall by means of wooden plug with CP brass
screws, washers over rubber washers complete
with all bye-works as per specification and direction
of the engineer
600 x 450 mm size Each 2
Providing and fixing 600 x 16 mm anodised
aluminum solid type towel rail with brackets of
SW-5 approved quality fixed on wooden plugs with CP
brass screws with all bye-works complete as per
specifications and direction of the Engineer. Each 2
Providing and fixing vitreous China white glazed
soap tray, size 15 x 7.5 cm recessed pattern of
SW-6 superior quality of HSW/Parry ware of nearest size, 2
with all bye-works complete as per specification
and direction of the engineer. Each
Supplying, fitting and fixing and/or laying GI pipes
of medium quality (B Class) conforming to IS :
1239 - 1990 (Part-I) of approved make bearing IS
mark with all necessary fittings such as bends,
tees, elbows, reducers, unions, nipples, plug,
SW-7
clamps and other fixtures conforming to IS : 1239 -
1992 (Part-II) including necessary earth work and
back filling, painting, etc. complete with all bye-
works as per specification and direction of the
engineer (including concealing in walls/floors, as

Copyright © 2016. MECON Limited. All Rights Reserved Page 31 of 32


STEEL AUTHORITY OF INDIA LIMITED
BHILAI STEEL PLANT, BHILAI
TECHNICAL SPECIFICATION FOR BALANCE CIVIL WORKS OF
ESSENTIAL FACILITIES UNDER
EXTERNAL WATER SUPPLY SYSTEM FOR SMS-III (PACKAGE 77-01A-1)

necessary).

(a) 32 mm dia nominal bore RM. 20


(b) 25 mm dia nominal bore RM. 20
(c) 20 mm dia nominal bore RM. 30
(d) 15 mm dia nominal bore RM. 30
Supplying, fitting & fixing superior quality bearing
ISI mark brass gun metal wheel valve(full way)with
SW-8
all bye-works complete as per specification and
direction of the engineer.
(a) 40 mm dia nominal bore Each 1
(b) 32 mm dia nominal bore Each 1
(c) 25 mm dia nominal bore Each 1
Construction of septic tank of internal size as per
standard drawings in cement mortar 1:4 using fly
ash bricks including 2 no of 560 mmdia circular CI
manhole covers of approved make, fitted and fixed
in the top slab with necessary fittings,19mm thick
cement plaster (1:4)with neat cement finish to
internal surfaces and 12mm cement plaster to
SW-9
outside surfaces up to 200 mm belowground level,
floor finished with 25 mm thick grey artificial stone
including supplying, fitting and fixing all necessary
specials ,fittings ,SW Tees, CI foot rests etc
including excavating earth in all types of soil,
shoring batting and pumping out water as
necessary, ramming, dressing the
bed and refilling the sides of the tank with
necessary earth, removing the spoils filling up the
chamber with clear water, removing foreign
materials from the chamber and including
constructing attached inspection pit as per
approved drawing and connecting all necessary
pipes, joints etc with internal plaster work and
artificial stone flooring is to be done with admixture
of approved water proofing compound @5% by
weight of cement, complete in all respects as per
the directions of engineer –in-charge
a) Of size2300x1100x1800mm No. 2
SUB TOTAL : SW :
Total Amount

NOTE : The quantities indicated in BOQ may vary to any extent subject to (+/-) 15 %.

Copyright © 2016. MECON Limited. All Rights Reserved Page 32 of 32