Documente Academic
Documente Profesional
Documente Cultură
A. AZIZ
To cite this article: A. AZIZ (1997) The Critical Thickness of Insulation, Heat Transfer Engineering,
18:2, 61-91, DOI: 10.1080/01457639708939897
A. AZIZ
Department of Mechanical Engineering, Gonzaga University, Spokane, Washington, USA
The theory of critical thickness of insulation for cylindrical and spherical geometries is discussed in a
comprehensive and methodical manner. The article begins with the introduction of the classical
analysis, which assumes surface convection with a constant heat transfer coefficient, h. Next, various
modifications of the basic theory are discussed in detail. These modification allow for:
The last three sections of the article consider the optimum configurations for a circular pipe covered
with insulations of equilateral polygonal, rectangular, and eccentric circular shapes. For polygonal and
rectangular geometries, the two-dimensional conduction analysis reveals that the conduction for the
critical configuration is the same whether the outside surface boundary condition is that of convection
or constant temperature. This permits the use of conduction shape factors to determine the optimum
configuration for polygonal and rectangular insulations. The analysis leads to the concept of critical
perimeter, which is more general than the concept of critical radius. The optimum sizing of eccentric
circular insulation, however, requires a complete two-dimensional analysis. A total of 12 examples
have been included to illustrate the various theoretical models described in the article. The detail and
the number of examples makes the article pedagogically as well as practically appealing.
When a planar surface that is losing heat is the total resistance is always increased when a
covered with insulation, the effect is always to planar surface is insulated. However, with cylin-
reduce the heat dissipation. With the total tem- drical and spherical systems, the addition of insu-
perature drop fixed, the addition of insulation lation, while increasing the conduction resistance,
causes the conduction resistance of the system to lowers the surface resistance because of the in-
increase but, because there is no change in exter- creased surface area. The total resistance can
nal surface area, the surface resistance (convec- increase or decrease depending on which effect
tive, radiative, or both) remains unchanged. Thus prevails. The critical thickness of insulation corre-
sponds to the condition when the total resistance
Address correspondence to A. Aziz, Department of Mechanical is minimized. For a given overall temperature
Engineering, Gonzaga University, Spokane, WA 99258-0001. difference, this condition leads to maximum heat
heat transfer engineering vol. 18 no. 2 1997 61
dissipation. Alternatively, for a given heat transfer
rate, the critical thickness results in a minimum
overall temperature difference.
Because the critical radius is typically small, the
heat transfer enhancement due to insulation oc-
curs only when the radius of the bare cylinder or
sphere is smaller than the corresponding critical
radius. This situation arises only for small-diame-
ter wires or tubes or spheres and with a weak
surface heat transfer mechanism. For example,
~he heat ~issipation (and hence the current-carry-
mg capacity) of a small-diameter electrical con- «s.r;
ductor operating in a natural-convective environ-
Figure 1 System with cylindrical or spherical insulation.
m.ent ma~ be significantly improved by wrapping it
with a~ Insulation of critical thickness. Similarly,
the buildup of frost on a small-diameter refrigera-
Heat loss by simultaneous convection and radia-
tion tube can increase (not decrease) the heat
tion
transfer until the thickness attains the critical
The effect of surface heat generation due to
value.
change of phase of the ambient fluid at the
However, the concept of critical radius of insu-
external boundary
lation breaks down when the shape of the insula-
Effects of radiation, inclination, and insulation
tion is not that of a cylindrical or spherical shell.
opacity
For example, the tubes in a flat-plate solar collec-
tor are sometimes housed in square channels
This is followed by a discussion of the classical
(square insulation). Another example of noncircu-
theory and its refinements for the spherical geom-
Jar insulation is found in undercarpet flat cables
etry. The final section of the article focuses on the
which carry rectangular insulation around them:
theory of the critical perimeter and its application
R~ce~t research has shown that a more general
to insulations that take the shape of an equilateral
cntenon for maximum heat dissipation is that of a
polygon or a rectangle. Here the case of a tube
critical perimeter of insulation, which applies not
sitting eccentrically in circular insulation is also
only to the cylindrical and spherical geometries
discussed, to demonstrate the failure of the con-
but is also valid for equilateral polygonal and
cept of the critical perimeter.
rectangular-shaped insulations.
A total of 12 examples are included to illustrate
The purpose of this article is to provide a
the ~pplicability of the various analyses to engi-
methodical and comprehensive exposition of the
neering problems. This, together with the fact that
theo~ ~f critical insulation and its engineering
th~ discussion throughout the article is fairly de-
applications. The coverage begins with the presen-
tailed, makes the work not only pedagogically
tatio~ of t.he classical theory for a cylindrical sys-
use~ul, but also convenient for use by practicing
tem In which the surface heat dissipation mode is
engineers.
modeled as convection with a constant heat trans-
fer coefficient, h, Next, the refinements of the
basic theory are discussed. These refinements in-
1 BASIC THEORY FOR CYLINDRICAL
clude allowance for
INSULATION .
The variation of Iz with outside insulation radius
.
as In a forced-convection situation
' . Co~sider a cylinder of radius ri and length L
The variation of Iz with outside radius and the With Its surface maintained at temperature, T as
temperature difference between the outside shown in Figure 1.1 The cylinder is covered to a
surface and the surroundings, as in a natural- radius r0 with a layer of insulating material having
convection situation a thermal conductivity k. The outer surface of the
The t~mperature dependence of fluid properties insulation loses heat by convection to an environ-
The circumferential variation of Iz within a two-
1 The subscript i does not refer to the inside of the tube but to
dimensional conduction model the inside of the insulation that is wrapped around to the tube. The
Pure surface radiation heat loss temptation to call it the outer tube radius, '0' should be resisted.
ro
p=-
ri
Figure 2 Variation of heat dissipation with radius ratio for a cylindrical system.
critical thickness is 6 - 4 = 2 cm. The maximum The convective Biot number Bi, is
heat dissipation is given by Eq. (5).
hr 3(0.04)
Bi =_1 = _
27TkL(Tj - T,) e k 0.18
qrnllx = 1 + In ( 'o,c jr)
j = 0.667
27T(0.18)(l)(80 - 20) and using the values of qbllre and Bi, in Eq. (6)
=------,---,--- yields
1 + In(6j4)
1.50
= 48.28 Wjm In P + P = 1.50
The heat dissipation from the bare tube is which can be solved by trial and error to give
P = 2.396 or '0
= (2.396)(4) = 9.59 em. Thus it is
only after 9.59 - 4 = 5.59 em of insulation has
been added that q will be lowered below qbare'
= (27T )(0.04)(1)(3)(80 - 20) This might be considered a high value for the
insulation thickness, and its addition may not be
= 45.2Wjm economically feasible.
64 heat transfer engineering vol. 18 no. 2 1997
2 REFINED ANALYSES FOR CYLINDRICAL Setting dq rdr.;
INSULATION
2Vro,c 2k *
__ Pr- 1/ 3
)I/m
Reo , c (variable h)
This section discusses the various refinements
= ---
/I ( em
of the classical theory of Section 1. These refine- (10)
ments, which were briefly mentioned in the intro-
ductory paragraphs, will be considered in detail Equation (10) gives the dimensionless critical
here. Reynolds number, Reo co when the variation of h
with ro is taken into 'account. For the classical
case of constant h, ro,c = kjh, which makes the
2.1 Forced Convection with Constant Properties left-hand side of Eq. (8) unity. Thus, for the con-
stant-h case,
If the cylindrical system of Figure 1 is cooled by
forced convection in cross flow, the average con- 2Vro c 2k *
__ Pr- 1/ 3
)I/m
Reo , c = - -/I' - (constant h)
vective heat transfer coefficient, h, varies with the ( e
outside radius r o , and therefore cannot be re- (11)
garded as constant as stipulated in the analysis of
Section 1. This variation of h with ro is given by Because the values of e and m depend on Reo,
Incropera and Dewitt [2] as Eqs. (10) and (11) were solved iteratively by Mus-
sulman and Warrington [4] for Pr = 1 and for a
2hro range of values of k*. Their results, which are
-- =
k e Rem Pr 1/ 3
0
(7) displayed in Figure 3, show that the classical the-
r ory overestimates the critical radius by an order of
magnitude. For example, at k* = 3, the variable-h
where Reo = 2Vroj/l is the Reynolds number analysis predicts Reo,c = 11.2 while the constant-h
based on the outside radius ro ' Pr is the Prandtl theory gives Reo,c = 134.
number, V is the flow velocity, k r is the thermal
conductivity of the fluid, /I is the kinematic viscos-
ity of the fluid, and e and m are constants. The
values of e and m, which depend on the Reynolds
number, are given in Table 1.
After rewriting Eq. (7) in the form
hr; e
- = -- Rem Pr 1/ 3 (8)
k 2k* 0
(9)
4
(13) Pr = 0.707
(constant h)
The thermal conductivity ratio, k", is
where Rei:: 2Vr;/v is the Reynolds number
based on inside radius ri , The results for Rca c k 0.14
from Figure 3 can be used to compute Qrnax from k* = - = - - = 5
kf 0.028
Eqs, (12) and (13), The results for Q rnax are shown
in Figure 4 for Rei = 50 and 500, The classical
Assuming that m = 0.466, C = 0.983, and Pr =
analysis (constant h) underestimates the heat
0.707, it follows from Eq. (10) that Reo,c = 78.94.
transfer rate significantly.
Thus
Example 2. A O.5-cm-diameter electrical con-
ductor is to be insulated with polystyrene having a 2Vr
thermal conductivity of k = 0.14 W1m K. Air at Reo,c = --!!.:..:.. = 78.94
20°C flowing in cross flow at 20 cmy's cools the v
conductor. Calculate the thickness of the insula- Because Reo,c lies in the range 40-4,000, the
tion so that heat dissipated to air is maximized. assumed values of m and C arc correct. Using the
How does this compare with the value predicted definition of Reo,C'
406v
r =--
2 3 456 7 8 O,c 2V
k
k"=-
k, (406)(18.08 X 10- 6)
Figure 4 Maximum dimensionless heat dissipation from a (2)(20 X 10- 2 )
forced convection cooled cylindrical system. (Adapted from
[4].) = 0.01835 m or 1.835 ern
66 heat transfer engineering vol. 18 no. 2 1997
This gives the critical thickness for constant h as When Eqs. (14) and (15) are put into Eq. (7), the
1.80 - 0.25 = 1.55 ern. This shows that the classi- expression for the convective heat transfer be-
cal critical thickness is roughly 1.55/0.07 = 14.5 comes
times greater than the correct value predicted by
the variable-h theory.
For Reo,c = 78.94, Table 1 gives C = 0.683 and (16)
m = 0.466. Using Eq. (8), the convective heat
transfer coefficient h is calculated as where
and
(0.683)(0.028)(78.94) 0.466( O. 707) 1/3
(2)(0.0036) C [2V]m Pr l / 3
C = -k(T.) --
I 2 00v(Too)
= 18.1 W/m 2 K
Let dRT/dro = 0 in Eq. (2), while noting that h
The maximum heat transfer, qrnax can be evalu- is a function of roo The condition for maximum q
ated as then becomes
(17)
27T(0.14)(1.0)(80 - 20) which reduces to Eq. (3) for constant h. Using Eq.
(16) and noting that cPo is also a function of ro'
In(0.357/0.25) + [0.14/18.1(0.00357)] the derivative is obtained as
= 21.1 W/m
_ (cPo + 1 )(3-7ffl)/4]
2.2 Forced Convection with Variable Properties +mrm I
o 2
The use of the correlation of Eq. (7) requires
that the thermal properties of k f and v which =hr [( 3 - 7m )( 2 )-
1 - o
BcP+ - m] (18)
appear in Reo be evaluated at the mean film o 4 cPo + 1 2 Bro ro
temperature, Tf = (To + Too)/ 2. This is somewhat
complicated because To itself is a function of roo To find BcPo/ Bro' consider the temperature dis-
For gases, the dependence of kf and v may be tribution in the insulation,
assumed to be of the form
(19)
(14)
which gives
(15) BT I To -T;
(20)
Br '-'0 = ro In(ro/r)
heat transfer engineering vol. 18 no. 2 1997 67
Next consider the heat transfer q through the where Reo,e = 2Vro,c1vT~. After elimination of
insulation, hr; e between Eqs. (27) and (28), the critical Reo e
is obtained as '
(21)
2k*m 1/ 3
) 11m
Re o,e =
( -C- Pr- F( '1'0
-I. ) (29)
which gives
where
aqo 2rrk [ To - 1'; ]
aro In(r,,/r) ro In(rolr) - (aTol ar o)
(22)
(25)
In both Sections 2.1 and 2.2, the convective
heat transfer coefficient h was allowed to vary
and from Eqs. (24) and (25) it follows that with the outer radius of the insulation, roo How-
ever, experimental studies of convective heat
acPo h transfer from an isothermal cylinder in cross flow
- = - -(cP - 1) (26) [5] indicate that h also varies circumferentially as
ar o k 0
q'
- = -
21T a()
-
I Pd() (34)
where Ra , 0 = 8g f3(To - T",)r; / va is the
q fo aR R-P Rayleigh number and C and n are constants.
Table 2 gives the values of C and n. Rearrange-
The value of c/Jj corresponding to q' follows as ment of Eq. (36) allows h to be expressed as
q
(35) (37)
q'
heat transfer engineering vol. 18 no. 2 1997 69
1.04 r - - - - - - - - - - - - ,
1.00 0.80 \,
1le;=25 6.0%
, 1'-----
\ . 1 I
0.96 ,, ,,
" ',.
0.92 "'",,- L----·- ...... _--------- ...
~
'
\, ----- h"h(8)
0.64 - \ 0.50
',\ ZI%
0.60 -
"
'","
617°;'
j--~---- 0.48 ""',... J-------
, I I I
4 6 8 0.46 ---=---~------,!
L,
4
2
1'0/1',
Figure 5 Dimensionless temperature variation with radius ratio for the cylindrical system: comparison of results for constant h
and circumfercntially variable h. (Adapted from [6).)
(40)
With h given by Eq. (37), the convective heat and it follows from Eqs. (39) and (40) that
loss from the outer surface of the insulation be-
(l-m )k
comes
(41)
'o,c = 1+ n h
q=
This result was first reported by Sparrow [7].
Equations (38) and (41) must be solved itera-
(38) tively to obtain the critical value of '0 correspond-
ing to qrnax' and it is convenient to write the
equations in dimensionless form before attempt-
Setting aq / ii, 0 = 0 in Eq. (38) gives the ex-
ing the iterative solution.
tremum of q,
Introducing h", cPo, and P,
ot;
(39)
iJ,o (42a)
(0.850)(0.032)(322.6)
or, in dimensionless form, 2(0.0025)
= 16.1 W/m 2 K
1 - cPo = B'
-cjJ-o-n+"""1'--
>
len
n
I p (45) Now the Biot number, Bi., can be calculated:
h*r.
Bi =_'
k
where Bi, = h*rJk. The conduction heat flow q e
and
(49)
8g (3(~ - Too)r?
Ra, , = ----,---,---,--
If Eq. (49) is used to find the critical radius, the '.' v(Too) a (T,,)
result is
T, is the absolute temperature at the inner radius
r;, To is the absolute temperature at the outer
(50) radius ro , Too is the absolute environment temper-
ature, k is the thermal conductivity of the insulat-
where A is one of the real roots of the cubic ing material, and v(Too), k/Too}, and a(Too) are the
equation kinematic viscosity, thermal conductivity, and
thermal diffusivity of the fluid, respectively, at
temperature Too.
(51) The heat transfer corresponding to the critical
radius is given by
and a and bare qrnax
Qrnax = 27TkL(~ - Too)
a = 0.4243( k f f/2 (52)
- 1
2 3 7cPo + 13 1 Ra; 0
8g{3(T0 - Too)lav= ) - - + -In --'- (57)
b = 0 2737(k )1/2 5 [ toe, + 10 5 ( Ra;.; ) ]
. f ( [1 + (0.559/Pr)9/16f6/9
The results of an iterative numerical solution of
(53) Eqs. (54)-(56) are shown in Figure 6. The dimen-
sionless critical radius Ra, 0 is affected by all
In another analysis, Mussulman and Warring- three parameters, namely, k*, Raj.; and cP;. Fig-
ton [4] considered a correlation given by Eq. (36) ure 7 shows the corresponding results for Qrnax
72 heat transfer engineering vol. 1B no. 2 1997
700 .-------.--,-----,---.---,-,---,..-"";1
i
"" 0.3
0.1
2 3 4 7 10
5 7 p=!.
kJ
k
k" = k;
Figure 7 Maximum dimensionless heat dissipation from a
Figure 6 Dimensionless critical radius for natural convec- natural convection cooled cylindrical insulation. (Adapted
tion cooling of cylindrical insulation. (Adapted from [4]'> from [4).)
obtained from Eq. (57). The value of Qrnax is seen Equation (58) can be written as
to decrease with increase in k* and decrease in
Raj t: _l_-_cP.,-
o = Bi (A,. 4_ rA 4) (60)
Pin P r. '1"0 cc
Example 3, when solved with the aid of Figures
6 and 7, leads to approximately the same results as
and the conduction heat transfer may be ex-
the Maple-driven solution.
pressed in dimensionless form as
Q= q
1 - cPo
2.5 Pure Radiative Cooling (61)
27TkLT; In P
Once again, consider Figure 1. The outer sur- For a given radiative Biot number Bi, and cP"".
face of the insulation is assumed to lose heat by Eq. (60) can be solved for cPo by trial and error for
pure radiation to a large enclosure at temperature a range of values of P. This result can then be
Too- Let € be the emissivity of the outer surface of substituted into Eq. (61) to find Q. The value of P
the insulation. For steady state, the conduction at which Q exhibits a maximum identifies the
heat flow through the insulation must match the critical value P, = ro.clr;. Alternatively, one may
surface radiative heat loss. Thus use the method of Lagrange multipliers to seek
the extremum of objective function Q given by
Eq. (61) subject to the constraint of Eq. (60). The
(58) former strategy was illustrated in Example 3.
Therefore, in the example that follows, the latter
strategy is employed.
Using. the dimensionless quantities Example 4. An electrical cable 1.27 ern in
diameter is to be insulated with rubber (k =
T 0.159 W1m K). During operation, the surface of
cP =- the cable attains a temperature of 65.6°C. If the
T; outside surface of the sheathed cable loses heat by
(59)
€CTT/r; ro radiation to the surroundings at 21.2°C, calculate
Bi r = - - - P= - the critical radius of insulation, the heat dissipa-
k r. tion from the critically' insulated cable, the tem-
heat transfer engineering vol. 18 no. 2 1997 73
perature on the outside surface of the insulation, The definition of </>0 gives
and the percentage increase in heat loss obtained
with critical amount of insulation compared with To
that from the uninsulated cable. Assume the emis- </>0 = - = 0.9272
sivity of the surface of the insulation to be 0.90. t;
Solution: Calculate Bi, and </>00 using the given
data. or
P, = 3.92 </>0 = 0.9272 Qmax = 0.05328 where Too is taken to be approximately equal to To.
From these, the result for ro • e follows as Replacing h in Eq. (3) by he' the critical radius
r o • e for radiative cooling becomes
ro e = 3.92r;
k k
= (3.92)(0.00635) r =-=--"7 (64)
o,e h, 4€uT. 0
3
= 0.0249 m or 2.49 cm
Using Eq. (61), qrnax/L follows as or, in dimensionless form,
r 1
p = ~ = -----,,- (65)
e rj Hi, </>J
= (21T )(0.159)(338.6)(0.05328)
= 18.02 W/m where Bi, = 4eaT,Jr;/k and </>0 = To/Too.
74 heattransler engineering vol. 18 no. 2 1997
The balance of conductive and radiative heat Equation (68) and Figure 8 shew that as <Pi
flows gives increases, the limiting Biot number becomes
smaller and smaller. In space applications, the
27TkUT; - T) effective sink temperature Too is very low, making
q=
In e, cPi very large. Thus the usefulness of insulation to
augment heat transfer in space is severely limited.
= Ecr(27Tro,cL)(To - Too)(To + Too)(T; + T}) The maximum heat dissipation, qmax' corre-
(66) sponding to the critical insulation follows from
Eq. (66) as
and this can be expressed in dimensionless form
to give the relationship among <Po, <Pi' and Pc,
Qmax = 27TkUT; - Too)
(69)
where <Pi = T;/Too. In writing Eq. (67), Eq. (65)
was utilized to eliminate Bi.,
Musselman and Warrington [4] solved Eqs. (65) The numerical solution of Eqs. (65) and (67) yields
and (67) numerically to obtain P, as a function of P, and <Po as a function of Bi and <Pi' This
Bi, and <Pi' Their results are shown in Figure 8. information can be used to evaluate Qmax as a
For a given <Pi' the critical radius decreases as Bi r function of Bi, and <Pi' Figure 9 depicts the results
increases, that is, as the radiative cooling becomes for Qmax' For a given 0i' Qmax increases as Bi r
stronger. Each curve is seen to terminate tP; = 1) increases. Each curve terminates at the corre-
at a certain value of Bi., indicating that the criti- sponding limiting value of Bi, as dictated by Eq.
cal condition ceases to exist beyond that value. (68).
This limiting value of Bi, can be found by putting Example 5. Repeat Example 4 using the lin-
Pc = 1 (no insulation) in Eq. (65) and noting that earized radiation model.
in the absence of insulation, <Po = <Pi' giving Solution: First, obtain <Pi and Bi.
r
Pc = .-!!.:.:... = 4.3
r.
so
= (4.3)(0.00635)
Figure 8 Critical radius ratio for a radiatively cooled cylin-
drical system. (Adapted from [4],) = 0.027 m = 2.7 cm
heat transfer engineering vol. 18 no. 2 1997 75
duced by linearization, some error also occurs in
the interpolation and reading of Figures 8 and 9.
Bi,
qnlllx =
L Q max 2 7T ur,I - T.cc )
cPo = 1.0346
and (72)
Case T. _ T.1/ 4
'",c (rn) qrn.,/L (W /m) h=l.l09~
r.
(a) 0,0183 316 21.2
(b) 0,0116 326 19.2
(c) 0,0100 325 28.6
(d) • critical
No solution exists
0 .0\5 .020
r<')
r" - r, m
<t
N Table 6 Solution for Cases (a)-(d) of Example 8
-a
~
0'1..,
N
N
Case
(a)
(b)
r; (rn)
0.00686
0.00338
To (K)
312
325
qrn,,/L (W/m)
17.7
18.4
0 (c)
N (=0 0.00536 315 19.4
(d) 0.00280 327 21.0
0::>
T. - T.l/t
Kuehn wrote the energy balance as
U) h=1.109~-
r. • critical
27TkL(To - T)
q=
<t In(,o/')
-0 .020
r,,-rj (m)
= h(27T'oL)(Too - To)
Flgure 10 Heat dissipation from a cylindrical system of + (27T'oL)eaP(C - To4 )
inside radius = 0.3175 ern: comparison of results for natural-
convection and natural convection/radiation cooling. 27T'oLh(Xoo - X)I'
(Adapted from [12],) +----=----- (76)
Le Cpt
where the heat flow is assumed to be from the
TobIe 5 Solution for Cases (a)-(d) of Example 7 surroundings to the inside of the tube. The last
term in Eq. (76) accounts for the heat release due
Case '",c (rn) to the phase change. The symbols X, 1', Le, and
(a) 0.0183 307 12.6 Cpt denote the mole fraction of the moisture, the
(b) 0.0137 314 11.3 latent heat of sublimation, the Lewis number, and
(c) 0.0107 310 14.8 the specific heat of air, respectively. For saturated
(d) 0.0083 315 14.3 air, the concentration difference (Xoo - X) is pro-
78 heat transfer engineering vol. 18 no. 2 1997
~r----r----r----r-------, the equation that represents h for natural convec-
tion from a horizontal cylinder,
~h=3.246;r:.382 W/m'-K
2hr o [
h = 22.7 W/m'-K - = 2/ln 1 + 2/
kf
-5/12 15
{(0.518 Ra
l / 4[1 + (0.559/Pr)3/5j )
en
-e..,
~
+(0.1 Ra l / 3)15
}
1/15]
(79)
~
- r--
has been reported by Kuehn [13] for three sets of
values of R, B, and G. Figure 13 shows his results.
The curve marked R = B = G = 0 represents the
<.D case of pure natural-convective cooling (Section
2.4). The curve labeled R = B = 1, G = 0, repre-
• critical sents a case of combined radiation and natural
convection. Finally, the curve R = B = G = 1 is
representative of combined radiation, natural con-
.002 .004 .006 vection, and heat release due to phase change.
This last curve clearly shows that the presence of
phase change lowers the critical radius signifi-
Figure 12 Heat dissipation from a cylindrical system of cantly.
inside radius = 0.15875 em: comparison of results for For a typical frost-buildup situation in a hori-
forced-convection and forced convection/radiation cooling. zontal refrigeration tube, Kuehn [13] assumed the
(Adapted from [12].)
data
ri = 0.3175 cm
portional to the temperature difference, (Too - To),
that is, X; - X; = ur; - T), where b is a T, = -woe
constant.
Replacing (Xoo - X) by b(Too - To) and repeat-
ing the analysis of Section 2.6, the expression for
the critical radius is found to be
hr; c (1 - m)(1 + G) + R
--=
k [(1 + n)(1 + G) + b][l + G + R]
(77)
where
R=B=l,G=O
R=8=G=1
(78)
h
bl'
G=--
Le cpf
loglORa
For no surface heat release, G = 0 and Eq. (77)
Figure 13 Critical Biot number for a cylindrical system:
reduces to Eq. (73).
comparison of results for natural-convection, natural convec-
The solution for hr; elk obtained from the tion/radiation, and natural-convection/radiation/phase-
simultaneous solution of Eqs. (76) and (77) and change heat release conditions. (Adapted from Kuehn [13].)
heat transfer engineering vol. 18 no. 2 1997 79
where R T is the sum of conduction and convec-
tion thermal resistance. The expression for R T is
k* = 5 W/mK
F=l (81)
b = 2.S2 X 1O- 4C- 1
For q to be a maximum, R T must be a mini-
and for the frost layer, mum. Setting dRrld,o = 0 in Eq. (81), the critical
radius '0, e is obtained as
E = 0.95
2k
and found 'o.e to be 2.23 cm for pure natural
,
o;c
=-
h
(S2)
convection (Section 2.4), 1.17 cm for combined
radiation and natural convection (Section 2.6),
When r o = r o , <, the second derivative of R T is
0.S6 cm for radiation and natural convection with
h given by Eq. (79), and 0.43 em for combined
radiation, natural convection, and heat release 1
(this section). ----=- >0 (S3)
41Tk';,e
2k
3 BASIC THEORY FOR SPHERICAL
r:: = h
INSULATION
(2)(0.17)
Figure 1 may also be considered to represent a 3
spherical system. For constant heat transfer coef-
ficient h, heat flow through the system is [1, 2] = 0.1133 m or 11.33 cm.
O.""l:-----<--+-~-+------:I--~-+---+---_~__1
To
p=-
To
Figure 14 Variation of heat dissipation with radius ratio for a spherical system.
heat transfer engineering vol. 18 no. 2 1997 81
and showed that the critical radius ro e is given by Introduction of the dimensionless quantities cPo,
cPoo' Bi,; and P, defined as
r
o,e
= ( 1-
1+n
im )(2kh ) (85) _E_u _T.:....
/ .:....
r;
Bi, =
k
The derivation of Eq. (85) parallels that given in
(92)
Section 2.4. By solving Eqs. (37) and (85) and the
heat flow equation,
allows Eq. (91) to take the form
(86) (93)
simultaneously, one can obtain ro c s To' and q. The conduction heat transfer q is
Balmer [10], however, used the' correlation
h = - + C2 1/4 (87)
ro ro
or, in dimensionless form,
and derived for ro,e'
(95)
. hr.I
2k B1 =-
r
o.e
= ---=-
4EUT3
(90) e k
o
Find the critical radius of insulation, the maxi- Substitution of cPoo and Bi, into Eq, (92) leads
mum heat dissipation, and the outside surface to
temperature when the surface heat loss is by pure
convection with constant h, pure radiation, and by 1- cPo
a combined mode with convection with constant h cP: - 0.6274 = O.IP(P - 1) (98)
and radiation.
Solution: For convection with constant hand
no radiation, Eq. (82) gives and after reading the library extrema in Maple and
then using the command extrema, the extremum
2k of Eq. (95) subject to the constraint of Eq. (98)
ro ;c =-
h gives
+ [1/(15)(0.021)2]
= (0,1185)(41T )(0.16)(330)(0.01)
= 0,92 W
= 0.77W
The temperature To corresponding to qrnax can be
found from Eq. (94): By definition;
To
-
T = A,
'1'0
= 08987
•
,
(0.92)(0,021 - 0.01)
= 330 - ...,....---,--,--...,....,-------,-,----,- or
(41T )(0.10)(0.021)(0.01)
= 306K To = 0.89871'; = (0.0987)(330) = 296.6 K
For the case of pure radiative cooling, first For combined convection and radiation, first
compute cPoo and Bi: evaluate Bi c :
Too 295
~ = - = - = 0.89 hr (15)(0,01)
00 1; 330 Bi = - ' = = 0.94
c k 0.16
heat transfer engineering vol. 18 no. 2 1997 83
Substitution of cf>", = 0.89, Bi, = 0.1, and Bi, = 5 EQUILATERAL POLYGONAL INSULATION
0.94 in Eq. (97) gives
The focus of the previous sections has been on
1 - cf>o circular insulation in the form of either a cylindri-
-P---1 = 0.94P(cf>o - 0.89) cal annulus or a spherical annulus. The circular
shape permitted the use of a one-dimensional
+ O.lP( cf>: - 0.6274) (99) conduction model except when the circumferen-
tial variation of h was taken into account (Section
and after reading the library extrema in Maple and 2.3). In some applications, insulation shape other
then using the command extrema, the optimiza- than annular are encountered. For example,
tion of Q, that is, Eq. (95) subject to the con- heated pipes in a flat-plate solar collector are
straint of Eq. (99), gives sometimes housed in square channels forming a
square insulation around a circular pipe ..
Pe = 1.5694 cf>o = 0.9420 Q rnax = 0.1598 With equilateral polygonal insulation covering a
circular conductor or pipe, heat conduction be-
Thus comes two-dimensional even if the convection heat
r transfer coefficient is assumed to be uniform and
~ = 1.5694 constant. With two dimensional conduction, the
r, outside surface temperature To no longer remains
uniform.
or The problem of critical thickness of a square
insulation on a circular conductor or pipe was first
ro,e = 1.5694r; = 1.5694(1) = 1.5694 cm analyzed by Hsieh [15]. Considering two-dimen-
sional conduction in the insulation and using a
Equation (95) gives qrnax as finite-difference approach, he found that the criti-
cal half-width we of the square is given by
= (0.1598)(47T )(0.16)(330)(0.01) k
we = 079-
• h (101)
= 1.06 W
Using the definition of cf>o' In a commentary on Hsieh's paper, Aziz [16]
suggested the use of the conduction shape factor
T"
- = cf>o = 0.9420
for a circular cylinder in a square to obtain a
r, simple analytical. solution. He wrote the steady-
state heat flow through the system as
or
q T; - Too
T" = (0.9420)(330) = 310.9 K (102)
L (1/Sk) + (l/8hw)
4.4 Combined Radiation and Natural Convection where, S, the conduction shape factor for the
configuration is given by Krieth and Black [17],
The analysis for this case parallels that of Sec-
tion 2.6 for the cylindrical geometry. The final 27T
S =-,----...,.- (103)
result for ro,e is In(1.08w /r.)
0.4 - -
:<;
-
• (square)
0.2 - -
0
• h, Too
- 0
0
-
0
0 0
-~:==w_--""r~-l......
~~~.- 0=0 ... x 0'-
Circular
Limit
,
a ~ 3 5
I
7
I
9
I I
rI
ro I n
~
Figure 16 Parameter N as a function n for polygonal insu-
Figure 15 Polygonal insulation on a circular pipe. lation. (From [19].)
heat transfer engineering vol. 18. no. 2 1997 85
Setting dR-rldw = 0 in Eq. (106) gives For a square insulation, the critical half-width
we follows from Eq. (109):
wc = n'7T(~)
h
(107)
and
(108)
= ; (0~~6)
= 0.01257 m or 1.257 em
From Eq. (106), the critical perimeter P, fol-
lows as Each side of the square is 2 X 0.01257 = 0.025 m
or 2.5 em, and the conduction shape factor S is
given by Eq.(l05):
(109)
qmllx T; - To>
--=
L In((ro,clr)/2'7Tk) + [1/h(2'7Tro)]
= (80 - 20)j[Jn(1.6/0.5)j2'7T(0.16)]
+ [l 1(10) (2'7T )(0.016)]
= 27.88 W/m = 0.01676 m or 1.676 em
86 heat transfer engineering vol. 18 no. 2 1997
The critical a c (Figure"15) follows from Eq. (108): The maximum heat dissipation per cubic centime-
ter for each shape is
= 33.82 W/m
b 9 • h, Too
Squares: V = [2(1.257)f - 7T(0.50)2
= 5.535 cm'
/2
1 [ 2 (3.35 )2]1
Triangle: V = 2'(3.35) (3.35) - -2-
27T
S = .,........,.----,---- (1lD)
In(4aj7T') - X
27T
S = -----,---------
In(,,,j') - [X- In«4cos a)j7T)]
(112)
Figure 18 Parameter N and X versus b/ a for rectangular
insulation, (Adapted from [19].)
where
N ~ X - In (
4 cos
7T
a) tiated with respect to a and set equal to zero. This
gives the critical a as
7Tk
and a = -.,------ (115)
c 2h[1 + (bja)]
b
a = tan- 1 - The corresponding expression for 'o,c then be-
a comes
• h, Too
80 - 20
1.7416
{J
= 34.44 W/m
The volume of insulation per centimeter length
is