Earth-Fault

Compensation Controller
EFC50 / EFC50i
Application Control Algorithm

In high impedance grounded Minimal Coil Movement values and calculates out of
power distribution networks the - EFC50 these the resonance curve.
neutral point of the network is Taking into consideration the
connected to earth by means of During a tuning operation the desired under- or overcompen-
a stepless adjustable inductor. ASC is adjusted by a small sation, it computes the neces-
If the resonance circuit formed amount. Measuring the coil- sary position and adjusts the
by the adjustable inductive coil position as well as the neutral- ASC to that value.
and the earth capacitance of the to-ground voltage during the
network is tuned to or close to adjustment operation, the con-
resonance, the fault current is troller computes the detuning Determination of the
greatly reduced in case of a - value v, the asymmetry value k Resonance point by cur-
line-to-earth fault (earth fault). and the damping value d, rent injection - EFC50
In most cases the arc caused by which determine the resonance
the fault current is extinguished curve of the neutral-to-ground The EFC50i calculates the
without the need to switch off voltage. Taking into considera- resonance curve by injecting a
the faulty part of the network. tion a customer settable under- current into the zero sequence
or overcompensation, the con- system of the network and mea-
As the Arc Suppression Coil troller calculates the necessary suring the vectors of both the
(ASC) and the earth capacitance position and directly adjusts the neutral-to-ground voltage and
form a resonance circuit, the ASC to the calculated value. the injected current. Where a
neutral-to-ground voltage of the network is essentially symmetri-
network depends on the value cal and the neutral-to-ground
of the inductance of the ASC Determining the voltage extremly low, and no
and reaches a maximum when Resonance Peak by reliable control signal is readily
the ASC is tuned to resonance. going beyond it - EFC50 available, it is possible to increase
This dependence of the neutral- the neutral-to-ground voltage
to-ground voltage is utilised by This method may be used if the by using the permanent current
the EFC50 and EFC50i Earth- asymmetry of the network is injection in a way that changes
Fault Compensation Controller small, which results in very low of the network configuration
for automatic tuning of on neutral-to-ground voltages. In provide a reliable signal for the
load adjustable ASCs. this case, network reactions controller (inverse operation
may cause fluctuations of the mode). In case of an outage of
neutral-to-ground voltage. the current injection, the EFC50i
Therefore it is not possible to automatically changes to a
compute reliably the parameters redundancy control mode
of the network by means of a whereby the resonance curve
small detuning of the ASC. is determined via a slight
So the controller adjusts the adjustment of the ASC.
ASC over a wider range, which
must include the resonance
2 peak. It stores the measured
Conception - EFC50 / EFC50i

Hardware • central acquisition and Hardware Options


display of arc suppression coil
• microprocessor based alarms via LEDs at the front • housing for wallmounting
controller 19‘‘-rack
mounted (3 HU), width 42 TE • serial interfaces and • alternative power supply
Ethernetport
• optimized operation by • EFC50: additional module
means of a graphic LCD • analogue output modules for digital inputs and outputs
display, keypad and scroll 0 ... 20 mA outputs for
wheel external indication of coil • optical serial port
position and neutral-to-
• extended operation via PC by ground voltage • IEC 61850 modul
means of a terminal program
• EFC50: prepared for easy
• indication of the digital out- upgrade to the Earth-Fault
puts via customer labeled Compensation Controller
and parameterized LED’s at EFC50i (see page 2)
the front

fig. 1 Earth-Fault Compensation Controller EFC50i with 19¨- rack mounted Current Injection Device ECI 3
Operating

• easy operation by means of


an integrated 20 line display
and the scroll wheel

• clear menu guide with


„help“ - text

• automatic, adaptive
menu according to activated
software options

• easy adaptation to individual fig. 2 operating panel


conditions via network
adjustable parameters

• Windows terminal program


EFCTerm for parameter set-
ting and on-site operation via
PC as well as for remote
control by means of modem

fig. 3 EFCTerm

4
Software Software Options

• easy parameter setting, • several controllers within


since pre-set factory values the same network (reliable
can be adjusted by the user control without mutual influ-
as required ences), no remote connection
necessary
• high flexibility through
software controlled inputs • adjusting the ASC to a
and outputs, free assignment predefined value when the
of digital outputs to different ASC is switched off
state functions as well as free
assignment of digital inputs • automatic resistor control
to different control functions
• control of an additional
• powerful PLC - the functions fixed coil (automatic
of a modern PLC are available switching on/off of the
fixed coil)
• indication of operating
status via text messages • control back to ideal
compensation (v=0) if an
• counting of various events earth fault occurs
(e.g. transient earth fault)
and controller conditions for • SCADA
statistical evaluations SPABus
IEC 60870-5-101/103/104
• remote parameter changes IEC 61850 (with optional
by means of a PC connected hardware modul)
via modem to the serial
interface • automatic switching of a
damping resistor during
• several parameter levels for search operation if
adaptive user settings U exceeds Umax

• software-update via serial


interface or Ethernet port

5
Technical Data – EFC50 / EFC50i

EFC50 EFC50i

hardware

operating
20 line display, 26 characters per line x x
scroll wheel, keypad

serial interface for SCADA, PC or modem x x


2 pieces RS-232, 9 pin, 1x front and 1x rear x x
1 piece RS-485 (alternative optical port) x (x)* x (x)*

Ethernet port
1 piece RJ-45 x x

analogue voltage inputs


3 mV ... 110 V AC 50 Hz 2 (+1)* 3
rated burden < 0,5 VA

analogue current inputs


0 ... 1 A AC 50 Hz (3)* 3

analogue outputs for Vo, coil position


0 ... 20 mA DC, software programmable 1 (+2)* 3

coil position
linear potentiometer 0 ... 200 ohms resp 0 ... 2 kOhm 1 1
or 0 ... 20 mA DC input signal

digital inputs
potential free contacts 48 ... 230 V AC/DC, 6 (+5/+10)* 11 (+10)*

digital outputs
potential free change over contacts, 230 V AC/DC, max 5 A continuous
max switching capacity AC1 - 1000 VA 2 2
max switching capacity AC15 (230 V AC) - 300 VA
max switching capacity DC1 (30/110 V DC) - 5 A / 0,2 A

digital outputs
potential free make contacts, 230 V AC/DC, max 5 A continuous
max switching capacity AC1 - 1000 VA 5 (+5/+9)* 10 (+9)*
max switching capacity AC15 (230 V AC) - 300 VA
max switching capacity DC1 (30/110 V DC) - 5 A / 0,2 A

auxiliary voltage
100 ... 240 V AC/DC x x
(other voltages on request)

6
*(…) Option
EFC50 EFC50i Option
(EFC50 / EFC50i)

software

automatic earth fault compensation control of stepless x


adjustable plunger core coils
automatic earth fault compensation control of stepless
adjustable plunger core coils by means of the current x
injection into the zero-sequence system
terminal program EFCTerm for Windows x x
automatic, adaptive menu x x
measurement memory x x
3 menu access levels for users x x
software-update via serial interface or Ethernet port x x
several controllers within the same network system x
predefined coil position x
automatic resistor control x
fixed coil control x
control back to ideal compensation (v=0) at earth fault condition x
SCADA x
automatic switching if U exceeds Umax x

mechanical data
dimensions EFC50/50i module 19’’ Rack
width 213,3 mm (42 TE) width 483 mm
height 132,5 mm (3 HE) height 132,5 mm
depth 270 mm depth 320 mm

weight approx 3 kg approx 2 kg

temperature operating 0°C ... +40°C


storage -25°C ... +55°C
transport -25°C ... +70°C

max installation altidude ≤ 2000 m. a. m. s. l.

protection class IP20

7
ECI Current Injection Device

The Current Injection Device reliable control signal is readily winding of the Arc Suppression
ECI is used to produce differen- available, it is possible to Coil.
tial measurement values by increase the neutral-to-ground
means of the current injection voltage by using the perma- The Current Injection Device
into the zero-phase sequence nent current injection in a way ECI essentially consists of a
system. This approach is used that changes of the network transformer, capacitors for
by both the Earth-Fault Com- configuration ensuring a current limiting, relays,
pensation Controller EFC50i reliable signal for the controller control- and signal contacts.
(see page 2) and the Earth- (inverse operating mode
Fault Detection Device EFD implemented in the EFC50i The following designes are
(see brochure E667). Where a control algorithm). The current available: indoor design, out-
network is essentially symmetri- injection into the zero-phase door design, mounting plate
cal and the neutral-to-ground sequence system is usually for installation in an existing
voltage extremely low, and no done via a power auxiliary cubicle, 19˝-rack mounting.

fig. 4 Increase of the zero-sequence voltage by means of conti- fig. 5 ECI in conventional design (indoor design, outdoor
nuous current injection design and design on mounting plate available)

8 fig. 6 ECI 19˝-rack mounted


fig. 7 EFC50/50i wiring diagram - standard 9
10 fig. 8 EFC 50i wiring diagram - control with current injection
fig. 9 EFC 50/50i wiring diagram - with option board 11
Trench Austria GmbH
Paschinger Straße 49
AT-4060 Linz-Leonding/Austria
Phone +43.732.6793-0
Fax +43.732.67 13 41
email sales.at@trench-group.com
Trench Brasil LTDA
Via Expressa de Contagem, 2685
CEP 32370-485
Contagem, Minas Gerais/Brasil
Phone +55.31.391-5959
Fax +55.31.391-1828
email sales@trench.com.br
Trench China Limited
3658 Jiang Cheng Road
Minhang, Shanghai 200245
P.R. China
Phone +86.21.64630088
Fax +86.21.64637828
email sales.cn@trench-group.com
Trench France S.A.
16, rue du Général Cassagnou
B.P. 70
FR-68302 St-Louis/France
Phone +33.3.89 70 23 23
Fax +33.3.89 67 26 63
email sales.fr@trench-group.com
Trench Germany GmbH
Nürnberger Straße 199
DE-96050 Bamberg/Germany
Phone +49.951.1803-0
Fax +49.951.1803-224
email sales.de@trench-group.com
Trench Italia S.r.l.
Strada Curagnata 37
IT-17014 Cairo-Montenotte/Italy
Phone +39.019.5161.111
Fax +39.019.5161.401
email sales.it@trench-group.com
Trench Limited
Coil Product Division
71 Maybrook Drive, Scarborough
Ontario, Canada M1V 4B6
Phone +1.416.298-8108
Fax +1.416.298-2209
www.trenchgroup.com email sales.ca@trench-group.com
Trench Limited
Instrument Transformer Division
390 Midwest Road, Scarborough
Ontario, Canada M1P 3B5
Phone +1.416.751-8570
Fax +1.416.751-6952
email sales.ca@trench-group.com
Trench Switzerland AG
Lehenmattstraße 353
CH-4052 Basel/Switzerland
Phone +41.61.315 51 11
Fax +41.61.315 59 00
email sales.ch@trench-group.com
Trench (UK) Limited
South Drive
Hebburn
Tyne & Wear
NE31 1UW, Great Britain
Subject to change without notice
03.10
Phone +44.191.483.4711
Fax +44.191.430.0633
E 656
email sales.uk@trench-group.com