Compensation Controller
EFC50 / EFC50i
Application Control Algorithm
In high impedance grounded Minimal Coil Movement values and calculates out of
power distribution networks the - EFC50 these the resonance curve.
neutral point of the network is Taking into consideration the
connected to earth by means of During a tuning operation the desired under- or overcompen-
a stepless adjustable inductor. ASC is adjusted by a small sation, it computes the neces-
If the resonance circuit formed amount. Measuring the coil- sary position and adjusts the
by the adjustable inductive coil position as well as the neutral- ASC to that value.
and the earth capacitance of the to-ground voltage during the
network is tuned to or close to adjustment operation, the con-
resonance, the fault current is troller computes the detuning Determination of the
greatly reduced in case of a - value v, the asymmetry value k Resonance point by cur-
line-to-earth fault (earth fault). and the damping value d, rent injection - EFC50
In most cases the arc caused by which determine the resonance
the fault current is extinguished curve of the neutral-to-ground The EFC50i calculates the
without the need to switch off voltage. Taking into considera- resonance curve by injecting a
the faulty part of the network. tion a customer settable under- current into the zero sequence
or overcompensation, the con- system of the network and mea-
As the Arc Suppression Coil troller calculates the necessary suring the vectors of both the
(ASC) and the earth capacitance position and directly adjusts the neutral-to-ground voltage and
form a resonance circuit, the ASC to the calculated value. the injected current. Where a
neutral-to-ground voltage of the network is essentially symmetri-
network depends on the value cal and the neutral-to-ground
of the inductance of the ASC Determining the voltage extremly low, and no
and reaches a maximum when Resonance Peak by reliable control signal is readily
the ASC is tuned to resonance. going beyond it - EFC50 available, it is possible to increase
This dependence of the neutral- the neutral-to-ground voltage
to-ground voltage is utilised by This method may be used if the by using the permanent current
the EFC50 and EFC50i Earth- asymmetry of the network is injection in a way that changes
Fault Compensation Controller small, which results in very low of the network configuration
for automatic tuning of on neutral-to-ground voltages. In provide a reliable signal for the
load adjustable ASCs. this case, network reactions controller (inverse operation
may cause fluctuations of the mode). In case of an outage of
neutral-to-ground voltage. the current injection, the EFC50i
Therefore it is not possible to automatically changes to a
compute reliably the parameters redundancy control mode
of the network by means of a whereby the resonance curve
small detuning of the ASC. is determined via a slight
So the controller adjusts the adjustment of the ASC.
ASC over a wider range, which
must include the resonance
2 peak. It stores the measured
Conception - EFC50 / EFC50i
fig. 1 Earth-Fault Compensation Controller EFC50i with 19¨- rack mounted Current Injection Device ECI 3
Operating
• automatic, adaptive
menu according to activated
software options
fig. 3 EFCTerm
4
Software Software Options
5
Technical Data – EFC50 / EFC50i
EFC50 EFC50i
hardware
operating
20 line display, 26 characters per line x x
scroll wheel, keypad
Ethernet port
1 piece RJ-45 x x
coil position
linear potentiometer 0 ... 200 ohms resp 0 ... 2 kOhm 1 1
or 0 ... 20 mA DC input signal
digital inputs
potential free contacts 48 ... 230 V AC/DC, 6 (+5/+10)* 11 (+10)*
digital outputs
potential free change over contacts, 230 V AC/DC, max 5 A continuous
max switching capacity AC1 - 1000 VA 2 2
max switching capacity AC15 (230 V AC) - 300 VA
max switching capacity DC1 (30/110 V DC) - 5 A / 0,2 A
digital outputs
potential free make contacts, 230 V AC/DC, max 5 A continuous
max switching capacity AC1 - 1000 VA 5 (+5/+9)* 10 (+9)*
max switching capacity AC15 (230 V AC) - 300 VA
max switching capacity DC1 (30/110 V DC) - 5 A / 0,2 A
auxiliary voltage
100 ... 240 V AC/DC x x
(other voltages on request)
6
*(…) Option
EFC50 EFC50i Option
(EFC50 / EFC50i)
software
mechanical data
dimensions EFC50/50i module 19’’ Rack
width 213,3 mm (42 TE) width 483 mm
height 132,5 mm (3 HE) height 132,5 mm
depth 270 mm depth 320 mm
7
ECI Current Injection Device
The Current Injection Device reliable control signal is readily winding of the Arc Suppression
ECI is used to produce differen- available, it is possible to Coil.
tial measurement values by increase the neutral-to-ground
means of the current injection voltage by using the perma- The Current Injection Device
into the zero-phase sequence nent current injection in a way ECI essentially consists of a
system. This approach is used that changes of the network transformer, capacitors for
by both the Earth-Fault Com- configuration ensuring a current limiting, relays,
pensation Controller EFC50i reliable signal for the controller control- and signal contacts.
(see page 2) and the Earth- (inverse operating mode
Fault Detection Device EFD implemented in the EFC50i The following designes are
(see brochure E667). Where a control algorithm). The current available: indoor design, out-
network is essentially symmetri- injection into the zero-phase door design, mounting plate
cal and the neutral-to-ground sequence system is usually for installation in an existing
voltage extremely low, and no done via a power auxiliary cubicle, 19˝-rack mounting.
fig. 4 Increase of the zero-sequence voltage by means of conti- fig. 5 ECI in conventional design (indoor design, outdoor
nuous current injection design and design on mounting plate available)