Documente Academic
Documente Profesional
Documente Cultură
Earthfault
Compensation Controller
EFC50
TRENCH AUSTRIA GMBH
Paschinger Straße 49
A 4060 Leonding
Austria
Software
Manual
EFC50-V1.00 Page 1
December 2010 Revision sheet
Page 2 EFC50-V1.00
Revision sheet December 2010
Overview
1. General
2. Technical Data
3. Operation
4. Start-up
5. Service
6. Messages / Malfunctions
7. Parameter
8. EFC50Term
9. Software Options
EFC50-V1.00 Page 3
December 2010 Overview
Page 4 EFC50-V1.00
Overview December 2010
Table of Contents
1 General.................................................................................................................................... 9
1.1 Safety ............................................................................................................................... 9
1.1.1 Hints & warnings........................................................................................................ 9
1.1.2 Operating instructions................................................................................................ 9
1.1.3 Qualified personnel.................................................................................................. 10
1.1.4 Additional hints ........................................................................................................ 10
1.2 Range of delivery ........................................................................................................... 10
1.2.1 Standard .................................................................................................................. 10
1.2.2 Hardware options .................................................................................................... 11
1.2.3 Software options...................................................................................................... 11
1.3 Control basics................................................................................................................. 12
1.3.1 Earthfault compensation.......................................................................................... 12
1.3.2 Control by coil movement ........................................................................................ 13
1.3.3 Control by current injection...................................................................................... 16
3 Operation............................................................................................................................... 27
3.1 Operation elements ........................................................................................................ 27
3.2 Operation concept ..........................................................................................................27
3.3 Standard control panel ................................................................................................... 28
3.3.1 Display..................................................................................................................... 28
3.3.2 Scroll wheel .............................................................................................................29
3.3.3 Local key – remote control ...................................................................................... 29
3.3.4 CONTR – key .......................................................................................................... 29
3.3.5 ESC – key................................................................................................................29
3.3.6 Motor <> keys.......................................................................................................... 29
3.4 Installed controller software............................................................................................ 29
3.5 PLC programming .......................................................................................................... 30
3.5.1 H - Editor ................................................................................................................. 30
3.5.2 Line editor................................................................................................................ 33
3.6 EFC50Term .................................................................................................................... 33
EFC50-V1.00 Page 5
December 2010 Table of Contents
4 Start-up..................................................................................................................................35
4.1 Necessary preparations..................................................................................................35
4.1.1 Safety.......................................................................................................................35
4.1.2 Mechanical mounting...............................................................................................35
4.1.3 Electrical connection................................................................................................35
4.2 Start-up instruction .........................................................................................................36
4.2.1 Menu System configuration .....................................................................................36
4.2.1.1 Time and Date ..................................................................................................36
4.2.1.2 Language..........................................................................................................36
4.2.1.3 EFC50Term Parameter ....................................................................................37
4.2.2 Menu Basic preselection..........................................................................................37
4.2.2.1 analog Inputs ....................................................................................................37
4.2.2.2 Controller works with ........................................................................................40
4.2.2.3 trafo impedance (only for control with ECI).......................................................40
4.2.2.4 Coil....................................................................................................................40
4.2.3 Analogue output configuration .................................................................................44
4.2.3.1 Coil position Ipos .............................................................................................45
4.2.3.2 Neutral to ground voltage ................................................................................45
4.3 Current injection .............................................................................................................46
4.4 First check of control ......................................................................................................47
4.5 Enable software options .................................................................................................48
4.6 Final activities .................................................................................................................48
4.7 Commissioning report.....................................................................................................48
5 Service...................................................................................................................................51
5.1 Main parameter ..............................................................................................................51
5.1.1 Controller configuration............................................................................................51
5.1.1.1 Control behavior ...............................................................................................51
5.2 Evaluations .....................................................................................................................53
5.2.1 Measurement buffer.................................................................................................53
5.2.2 Show statistics .........................................................................................................53
5.3 Show important informations ..........................................................................................54
7 Parameters ............................................................................................................................67
7.1 Enable options................................................................................................................72
7.2 Basic preselection ..........................................................................................................72
7.2.1 coil ...........................................................................................................................73
7.2.1.3 current injection devices (only with ECI) ...........................................................74
Page 6 EFC50-V1.00
Table of Contents December 2010
7.3 Controller configuration .................................................................................................. 74
7.3.1 Fixed coil ................................................................................................................. 74
7.3.2 Controller behaviour ................................................................................................ 74
7.3.2.1 Fine tuning controller ........................................................................................ 75
7.3.2.1.1 Vo < Vmin .................................................................................................. 76
7.3.2.1.2 Vo<Vlimit ................................................................................................... 76
7.3.2.1.3 Vo>Vlimit ................................................................................................... 76
7.3.2.1.4 Vo>Vmax ................................................................................................... 76
7.3.3 Options .................................................................................................................... 77
7.3.3.1 Fix coil control................................................................................................... 77
7.3.3.2 Resistor control................................................................................................. 77
7.3.3.3 External power switch....................................................................................... 78
7.3.3.4 Additional controller .......................................................................................... 78
7.3.3.5 Control at earthfault .......................................................................................... 78
7.3.3.6 Automatic switch for V > Vmax......................................................................... 78
7.4 In/Outputs ....................................................................................................................... 79
7.4.1 programming PLC ................................................................................................... 79
7.4.2 text definitions.......................................................................................................... 79
7.4.3 Analogue output AO characteristics ........................................................................ 79
7.4.4 Check in/outputs...................................................................................................... 79
7.5 System configuration ...................................................................................................... 79
7.5.1 Data recorder........................................................................................................... 79
7.5.2 Password assignment ............................................................................................. 79
7.5.3 LAN settings ............................................................................................................ 80
7.5.4 EFC50Term ............................................................................................................. 80
7.5.5 Scada ...................................................................................................................... 80
7.5.5.1 Configuration SPABus...................................................................................... 81
7.5.5.2 configuration IEC101 (unbalanced balanced) .................................................. 81
7.5.5.2.1 Command configuration............................................................................. 81
7.5.5.2.2 Measurands configuration ......................................................................... 82
7.5.5.2.3 Counter configuration ................................................................................ 82
7.5.5.3 Configuration IEC103 ....................................................................................... 82
7.5.5.3.1 Command configuration............................................................................. 82
7.5.5.3.2 Protocol fine tuning .................................................................................... 82
7.5.5.4 Configuration IEC61850 ................................................................................... 83
7.5.5.5 LAN Parameter................................................................................................. 83
7.5.6 Reset counters ........................................................................................................ 83
7.5.7 Reset event list ........................................................................................................ 83
8 EFC50Term........................................................................................................................... 85
8.1 Basics............................................................................................................................. 85
8.2 Minimum requirements to the PC ................................................................................... 85
8.3 Installation ...................................................................................................................... 86
8.4 EFC50Term .................................................................................................................... 86
8.4.1 Menu File................................................................................................................. 86
8.4.2 Menu Functions ....................................................................................................... 86
8.4.3 Menu Settings.......................................................................................................... 88
8.4.4 Menu View............................................................................................................... 90
8.4.5 Menu About EFC50Term......................................................................................... 91
8.4.6 Menu Help EFC50Term........................................................................................... 91
EFC50-V1.00 Page 7
December 2010 Table of Contents
8.5 EFC50Analyse................................................................................................................91
8.5.1 Menu File .................................................................................................................91
8.5.2 Menu Edit.................................................................................................................92
8.5.3 Menu Zoom..............................................................................................................95
8.5.4.Menu Settings..........................................................................................................96
8.5.5 Menu View ...............................................................................................................96
8.5.6 Menu About EFC50Analyse ....................................................................................98
8.5.7 Menu Help EFC50Analyse ......................................................................................98
8.6 EFC50Param..................................................................................................................98
8.6.1 Menu File .................................................................................................................98
8.6.2 Menu Edit parameters .............................................................................................99
8.6.3 Menu Settings..........................................................................................................99
8.6.4 Menu View ...............................................................................................................99
8.6.5 Menu About EFC50Param.....................................................................................100
8.6.6 Menu Help EFC50Param.......................................................................................100
8.7 SPS - Editor (EFC50Param).........................................................................................101
9 Options ................................................................................................................................103
9.1 Scada - SPABus...........................................................................................................103
9.1.1 Realisation in EFC50.................................................................................................103
9.1.1.1 Checksum and parity ......................................................................................103
9.1.1.2 Internal processing of messages ....................................................................103
9.1.1.3 Dialog between EFC50 and SPABus-Master .................................................103
9.2 Scada IEC 870-5-101 (balaced/unbalanced) ...............................................................107
9.2.1 Events IEC 101 Protocol........................................................................................107
9.2.2 Commands IEC 101 Protocol ................................................................................108
9.2.3 Measureands IEC 101 Protocol.............................................................................108
9.2.4 Counters IEC 101 Protocol ....................................................................................109
9.3 Scada IEC 870-5-104 ...................................................................................................110
9.4 Scada IEC 870-5-103 ...................................................................................................110
9.4.1 Data units in supervision direction .........................................................................110
9.4.2 Data units in command direction ...........................................................................112
9.4.3 Events....................................................................................................................114
9.4.4 Commands ............................................................................................................114
9.5 Scada IEC 61850 - protocol .........................................................................................115
9.6 Resistor control.............................................................................................................116
9.6.1 Temperature model ...............................................................................................116
9.6.2 Home position OFF................................................................................................116
9.6.3 Home position ON .................................................................................................117
9.7 Control at earthfault ......................................................................................................117
9.8 Automatic switch Vo>Vmax ..........................................................................................117
9.9 More controllers............................................................................................................118
9.10 External circuit breaker...............................................................................................119
9.11 Fix coil control.............................................................................................................119
9.12 Vectorial trigger ..........................................................................................................120
Page 8 EFC50-V1.00
Table of Contents December 2010
1 General
1.1 Safety
1.1.1 Hints & warnings
Please note the following signs that are placed on the device or in the manual!
Attention
Hint
An operation instruction, a practical application and so forth which must be respected to avoid damage of the
device.
Warning
An operation instruction, a practical application and so forth which must be respected to avoid destruction of the
device or personal injury.
The earthfault compensation controller EFC50 should be operated resp. used only by qualified personnel and only
according to the technical data in compliance with the below mentioned security instructions and standards.
Additionally, all laws and safety regulations applicable have to respected.
WARNING
During operation of electrical devices some parts of the devices are inevitably live. Disregarding the hints may lead
to severe injuries or damages.
Proper transport, storage, installation and mounting and furthermore careful control and maintenance are
mandatory for faultless and safe operation of the device. If it is assumed that safe operation is not possible any
more the device has to be switched off immediately and furthermore it has to be protected against unintentional
reuse.
It has to be assumed that safe operation is not possible any more if the device:
- is visibly damaged,
- has been exposed to unfavorable conditions i.e. for a period of time outside the rated climatic limits (e.g.
storage outside allowed climatic limits without adaptation to the indoor environment, moisture condensation and
so forth) or
- has been exposed to heavy transport stress (e.g. drop from great height without visible external damage and so
forth).
EFC50-V1.00 Page 9
December 2010 1 General
1.1.3 Qualified personnel
…are persons, acquainted to installing, mounting, put-ting into service and operating the product and who have the
respective qualifications, e.g.
- Education resp. training and furthermore authorization according to safety standards to switch on, switch off, to
isolate, to earth and to mark circuits and devices.
- Education resp. training and furthermore authorization according to safety standards for maintenance and use
of suitable safety equipment.
- Training in first-aid.
- The product leaves the factory in a condition fulfilling all safety requirements. To maintain this condition and to
allow safe operation the user has to follow the hints and warnings in this manual.
- Prior to switching on the device must check that the rated voltage of the device corresponds to the used power
supply.
- The operator must check that the protective earth terminals of the device (shown in the connection diagram) are
connected with earth. Any internal or external disconnection of the protective conductor or unintentional
disconnection of the protective earth terminals may lead to dangerous condition and is therefore not allowed.
- Live parts may be exposed when opening cover parts or removing parts. Also terminals may be live. If opening
of the device is necessary for adjustment, maintenance, repair or exchange of parts the device has to be
disconnected from all power supplies prior. If then adjustment, maintenance, repair or exchange of parts in live
condition is in-evitable this has to be performed by skilled personnel, acquainted to involved risks, only.
Capacitors inside the device may still be charged even though the device is disconnected from all power
supplies.
- The operator must check that only fuses according to the stated type and rated current are used for spare. Use
of repaired fuses or shorting the fuse holder is not allowed.
- Earthfault compensation controller EFC50 (Minimum configuration, CPU-board X1 – X4, AIO1 board X7 – X11)
- Board for additional 10 digital inputs and 9 digital outputs (DIO – board – extension, X5, X6)
- Board for additional 4 analogue inputs (1xU, 3xI), 5 digital inputs and 5 digital outputs,
2 analogue outputs 20mA (AIO2-Board - ECI-expansion, X12 - X14 )
- cassette or 19” rack mounting unit (3 HE)
- 2 pcs. serial interface RS232 (1x front-, 1x backside)
- 1 pcs. serial interface RS485 (1x backside)
- LAN interface ((1x backside for EFC50Term, IEC870-104 or PLC-communication)
- Terminal program EFC50Term
- interface cable
- Manual
German or English version
- Mounting material
Screws, mating connectors
Page 10 EFC50-V1.00
1 General December 2010
1.2.2 Hardware options
SCADA
SPABus V2.4 dated 21.2.1992 (via RS232)
IEC 60870-5-103 (via RS232)
IEC 60870-5-101 (via RS232)
IEC 60870-5-104 (via RJ45)
IEC 61850 (via RJ45)
EFC50-V1.00 Page 11
December 2010 1 General
1.3 Control basics
1.3.1 Earthfault compensation
Earthfault compensation (arc suppression) is based on the principle, that the capacitive part of the fault current at
fault location can be equalized (compensated) by the inductive current of the ASC. Hence, with ideal compensation
only a very small resistive residual current flows over the fault location.
E1
N E2
E3
C V1
C C V2
V3
Vp L
2 3
N
V21 V31
Ic capacitive discharge current of the system. At exact tuning (Ipos = Ic) the
neutral-to-ground voltage measured on the ASC (sound network condition)
reaches its maximum ("resonance - point"). Inside the controller this value
is named Ires.
Page 12 EFC50-V1.00
1 General December 2010
Detuning v
Variation of the adjustment of the ASC from the resonance point. Detuning at the resonance point is zero (v = 0).
v = (Ipos - Ic) / Ic
Asymmetry k
Due to the geometrical arrangement of the conductors the phase-to-ground capacitances are not equal. For the
equivalent diagram a mean capacitance C and a capacitance dC of one phase (causing the asymmetry) are
assumed.
k = dC/3C.
Asymmetry Zu
The asymmetry can also be described by an asymmetry impedance between phase and earth. In the case of a
capacitive asymmetry „Zu“ equals the impedance of dC, in the case of a high resistive fault it equals the fault
resistance. The EFC50 calculates the amount of this impedance during an automatic tuning operation. If
required a signal can be created, when Zu falls below an adjustable threshold.
Damping d
Leakage resistances and losses of the ASC dampen the resonance circuit formed by the ASC and the line
capacitances.
Resonance curve
In systems with natural asymmetries (k > 0) the necessary inductive compensation current for the single-phase
fault condition can be pre- determined in the healthy network condition. By variation of the ASC’s inductivity the
following characteristic shape of the neutral-to-ground voltage is received
Vp
E1
detuning v
EFC50-V1.00 Page 13
December 2010 1 General
System perturbations
are variations of the network that have an effect on the neutral-to-ground voltage. Switching operations or damping
variations (e.g. due to weather) are not considered to be system perturbations.
By adjusting the inductivity of the ASC and measuring the neutral-to-ground voltage the system’s resonance curve
(resp. locus diagram) can be determined. This way, the calculation of the resonance curve is possible with a few
measurement points only. By knowing the resonance curve the determination of the resonance point is possible.
Furthermore it is possible to consider a certain over- or under-compensation for the final tuning point of the ASC.
For describing the control procedures the following definitions are necessary.
Compensation v
If the capacitive leakage current is not fully compensated by the inductive current of the ASC, this is called under-
compensation (v < 0). If the inductive current is greater than the capacitive leakage current, this is called over-
compensation (v > 0).
At the end of the pre-set delay time the controller starts the search operation from its actual position towards middle
position of the coil. After approx. 2% of coil adjustment the control procedure is continued towards direction of rising
neutral-to-ground voltage (thus, eventually meaning reverse coil adjustment). After a minimum necessary coil
movement (factory setting: 5%) a first estimation of the network parameters (resonance point Ires, asymmetry k,
damping d) is available.
Since the available measurement data are not exact (measurement tolerances of coil position and neutral-to-
ground voltage), this first result does not exactly represent the final values.
By estimation of the resonance point the tuning point is determined also. Hence, the ASC is adjusted to this point.
The estimation of the resonance point (and hence also of the tuning point) is continuously corrected and improved
during the coil movement.
In order to reach the highest possible tuning accuracy the resonance peak is passed at least once, before the
tuning point is finally reached. (Exception: Depending on the settings at “Vo>Vmax“ the controller can stop the coil
at Vmax without passing the resonance peak. Then the coil position however is not at the final calculated tuning
point.)
If during the coil movement a sudden rise of the neutral-to-ground voltage happens, a new control procedure is
started.
Page 14 EFC50-V1.00
1 General December 2010
Control with non-negligible system perturbations (Vo < Vlimit)
Owing to system perturbations slow variations (in the range of 20 ... 40s) of the neutral-to-ground voltage may
happen. During adjustment of the coil virtual side-resonances may occur.
A voltage maximum is however only accepted as resonance point, if during control procedure one measurement
point before and another measurement after the voltage maximum can be found, both of which have to be in a pre-
set ratio related to the maximum value.
In the following example this ratio is set to 80% (adjustable in the menu).
If the neutral-to-ground voltage is lower than Vlimit at the beginning of a search operation, the procedure
“Control with non-negligible system perturbations" is used. Hence, disturbing influences caused by system
perturbations are minimized.
If the neutral-to-ground voltage exceeds Vlimit during control procedure, the controller internally changes the used
procedure without interrupting the process.
If the neutral-to-ground voltage is higher than Vlimit at the beginning of a search operation, the procedure "Control
with negligible system perturbations" is used.
In order to have a successful tuning operation the neutral to ground voltage in the resonance point should at least
exceed approximately 0,1% - 0,3% (depending on the net conditions).
EFC50-V1.00 Page 15
December 2010 1 General
1.3.3 Control by current injection
dI
ECI 3 Zu (>>)
dUo 3L 3R C E1
ECI
In the sound network the neutral to ground voltage is caused by the asymmetry 3Zu. An additional injected current
dIECI, flows into the resonance circuit formed by 3L, 3R and C and leads to a change of the neutral to ground
voltage dVo.
Because of the vectorial measurement of voltage and current by the EFC50, the complex zero sequence
impedance Zo of the resonance circuit can be calculated.
Hint
The vectorial measurement requires the availability of the so called reference voltage U12, which serves as a
phase reference fort he measurement of the phases of all other signals.
From this data the active and the reactive part of the fault current (during solid fault) can be calculated.
If the coil position is known (potentiometer), the resonance point of the network can be derived.
If necessary, the controller adjusts the coil to the calculated tuning point. Switching operations during the coil
adjustment are recognized by supervision of the course of neutral to ground voltage.
The control by means of the current injection offers the following advantages:
Attention
If the current injection is not available any more, or the calculation delivers an invalid result, the device will
automatically change to a control procedure with coil movement, similar as described under item (1.3.2).
Page 16 EFC50-V1.00
1 General December 2010
2 Technical Data
Dimensions cassette :
EFC50-V1.00 Page 17
December 2010 2 Technical Data
2.2 Operation Elements
Front:
Rear:
Page 18 EFC50-V1.00
2 Technical Data December 2010
2.3 Type tests
Following tests were passed :
EFC50-V1.00 Page 19
December 2010 2 Technical Data
2.4 Mechanical data
Page 20 EFC50-V1.00
2 Technical Data December 2010
2.6 Electrical data, outfit
standard operating
1
20 line display, 21 characters per line, scroll wheel, buttons
serial interfaces
RS 232 for Scada, PC or modem, 2 pcs. 9 pole Sub-D male, 2
1x front and 1x rear
serial interface
1
RS 485 for Scada, 3 pole connector, 1x rear
ethernet interface
1
RJ45 for Scada or PC
analog voltage input
3
3 mV ... 110 V AC 50 Hz, rated burden < 0,5 VA
analog outputs
for e.g. Vo, coil position 0 ... 20 mA/DC, freely programmable 3
maximum burden at 20 mA/DC: 800 Ohm
coil position
Linear potentiometer, 0 ... 200 Ohm or 0 ... 2 kOhm 1
or 0 ... 20 mA/DC - input signal
digital inputs
21
potentialp free input 48 ... 230 V AC/DC,
g
potential free changeover contact (normal open, normal closed) 230 V AC/DC
max 5 A continuous, max making capacity 1000 VA, max breaking capacity 30 2
VAg p
potential free contact (normal open) 230 V AC/DC
max 5 A continuous, max making capacity 1000 VA, max breaking capacity 30 19
VA
Power supply
Standard: 110 - 230V AC/DC (+/-10%) / Option: 20 - 70V DC 1
(other voltages on request) power consumption max. 20W
Maximum permissible overvoltage at the voltage inputs 130V AC continuous, 2 x Un for 1s
Maximum permissible over current at the current inputs 1,2 x In continuous, 100 x In for 1s
EFC50-V1.00 Page 21
December 2010 2 Technical Data
2.7 Interface cables
PC => Controller
(Zero-modem cable)
PC EFC50
9pins female 9pins female
Pin Pin
TXD 3 ----------------- 2 RXD
RXD 2 ----------------- 3 TXD
GND 5 ----------------- 5 GND
CTS 8 ----------------- 7 RTS
RTS 7 ----------------- 8 CTS
DTR 4 ----------------- 1 DCD
DSR 6 6 DSR
DCD 1 ----------------- 4 DTR
Hint
Commercial cables for the RS232 interface may be used.
Corresponding burden:
1 mA___5,6 kOhm
5 mA___ 1 kOhm
10 mA___560 Ohm
20 mA___270 Ohm
Page 22 EFC50-V1.00
2 Technical Data December 2010
2.9 Connection diagram
Attached connection diagram shows the wire connection of the device as proposed by Trench Austria. This
proposal corresponds with the factory setting of the parameters.
Since the use of in- and outputs can be configured in a wide range within the PLC file, the configuration of wiring
can be changed if needed.
ENOAG01-0_EFC50 Rev. 0
EFC50-V1.00 Page 23
December 2010 2 Technical Data
4 3 2 1
R e fe r e n z s p a n n u n g ( o p tio n a l) X 1 0 /1 U 1
A I
r e fe r e n c e v o lta g e ( o p tio n a l)
X 1 0 /2 V 1
V e r la g e r u n g s s p a n n u n g V e r la g e r u n g s s p a n n u n g
F X 1 0 /3 U X 6 /3 F
E r d s c h lu s s L ö s c h s p u le / T A - S ta n d a r d
n e u tr a l to e a r th v o lta g e A I 0 -1 1 0 V A C
n e u tr a l to e a r th v o lta g e
A r c s u p p r e s s io n c o il / T A - S ta n d a r d
X 1 0 /4 V X 6 /4
S t e llu n g s p o t.
m a x S tro m
p o s it io n p o t.
X 7 /1 + P o t. X 5 /2
P o te n tio m e te r m a x c u rre n t
A I
p o te n tio m e te r X 7 /3 s P o t,m A X 5 /1
m in S t r o m
X 5 /3 m in c u r r e n t
X 7 /2 -P o t.
0 - 2 0 m A V e r la g e r u n g s s p a n n u n g X 8 /2 -
A O -U H -S V
0 - 2 0 m A n e u tr a l to e a r th v o lta g e X 1 /2
X 8 /1 +
X 1 /6 + U H + S V
X 9 /3 E C O M .1 X 1 /2 2 m in S t r o m
E n d s c h a lte r
E E n d s c h a lte r m a x . S tr o m + U H + S V E
D I X 9 /1 X 1 /7
fin a l p o s . s w itc h m a x .c u r r e n t E 1 .1
X 1 /1 9 m a x . S tro m
m a x c u rre n t
X 1 /2 1
X 4 /3 K C O M .1 X 1 /1 5 + U H
+ S V
E a r th fa u lt C o m p e n s a tio n C o n tr o lle r E F C 5 0
M o to r : S tr o m k le in e r S tr o m k le in e r
E r d s c h lu s s K o m p e n s a tio n s r e g le r E F C 5 0
m o to r : c u r r e n t d e c r e a s in g D O X 4 /2 K 2 .1 X 1 /1 8 c u r r e n t d e c r e a s in g
-U H
-S V M o to rs c h ü tz e
c u r r e n t in c r e a s in g m o to r c o n ta c to rs
M o to r: S tro m g rö ß e r D O X 1 /1 7
S tro m g rö ß e r
m o to r : c u r r e n t in c r e a s in g X 4 /1 K 1 .1
-U H X 7 /1
K C O M .3 -S V ( W id e r s ta n d s s te u e ru n g )
X 4 /1 2 + U H / + S V
( W id e r s ta n d E IN )
D ( W id e r s ta n d e in ) ( R e s is to r C o n tr o l) D
( r e s is to r o n ) X 4 /9 K 6 .3 N O X 7 /2 ( R e s is to r O N )
S o ftw a r e o p tio n
R e s e rv e A u s g a n g X 4 /1 0
S p a re o u tp u t K 7 .3 N O
X 4 /1 1 K 7 .3 N C
X 4 /8 K C O M .2
E r d s c h lu s s / e a r th fa u lt D O X 4 /7 K 5 .2
A u to m a tik e in X 4 /6 K 4 .2
D O
a u to m a tic o n
K e in e S tö r u n g X 4 /4 K 3 .2 N O
n o m a lfu n c t. D O ( ...) O p tio n
K 3 .2 N C
C S tö r u n g / m a lfu n c tio n a n a lo g e r E in g a n g C
X 4 /5 A I a n a lo g in
- U H / -S V a n a lo g e r A u s g a n g
A O
X 9 /8 E C O M .2 a n a lo g o u t
A u to m a tik a u s
a u to m a tic o ff D I
X 9 /7 E 6 .2 d ig ita le r E in g a n g
A u to m a tik e in D I d ig ita l in
a u to m a tic o n D I
X 9 /6 E 5 .2 d ig ita le r A u s g a n g
D O
A u to m a tik b lo c k ie r t d ig ita l o u t
a u to m a tic b lo c k e d D I
X 9 /5 E 4 .2
+ /-U H H ilfs s p a n n u n g
W id e r s ta n d A u s lö s u n g D I + /-S V s ig n a l v o lta g e
R e s is to r fo r c e d tr ig g e r X 9 /4 E 3 .2
V e rs o rg u n g s s p a n n u n g
p o w e r s u p p y X 1 1 /1 P E
1 0 0 -2 4 0 V A C /D C X 1 1 /2 L (+ )
B (2 0 -7 0 V D C ) B
N (-)
X 1 1 /3
C A D e r s te llte Z e ic h n u n g . K e in e m a n u e lle n Ä n d e r u n g e n d u r c h fü h r e n . T o le r a n z e n n a c h
D ie W e it e r g a b e o d e r V e r v ie lfä ltig u n g d ie s e r U n te r la g e
IS O 2 7 6 8 -Ö N O R M M 1 3 6 5
O b e r flä c h e M a ß s ta b : M a te r ia l:
s o w ie d ie V e r w e r tu n g u n d M it t e ilu n g ih r e s In h a lte s is t T e il1 T e il2
o h n e a u s d r ü c k lic h e G e n e h m ig u n g n ic h t g e s ta t te t. f m c v H K L K u n d e :
Z u w id e r h a n d lu n g e n v e r p flic h te n z u S c h a d e n e r s a tz . A b m .: m m ; 0 -5 0 0 3 %
A lle R e c h te v o r b e h a lt e n . T R E N C H A U S T R IA G M B H 5 0 0 -2 0 0 0 2 % ; > 2 0 0 0 1 % A .N r.: F .N r.:
D a tu m N a m e
B e a rb . 2 4 .1 1 .2 0 0 9 M P K -S c h E r d s c h lu s s K o m p e n s a tio n s r e g le r E F C 5 0
G e p r. 9 .1 2 .2 0 0 9 T E -S i E a r th fa u lt C o m p e n s a tio n C o n tr o lle r E F C 5 0
B a s e V e r s io n
A A
B la tt
E N O A G 0 1 0 1 1
0 1 d iv . A n p a s s u n g e n 9 .7 .2 0 1 0 S c h Ä n d . Z u s t. B l.
Z u s t. Ä n d e ru n g D a tu m N a m e U rs p r.: E rs .f.: E rs .d .:
4 3 2 1
4 3 2 1
E r d s c h lu s s L ö s c h s p u le n a c h T A - S ta n d a r d
A r c s u p p r e s s io n c o il a c c o r d in g to T A - S ta n d a r d
F (n e u tr a l to e a rth v o lta g e 2 ) X 1 4 /1 u 3 F
(V e r la g e ru n g s s p a n n u n g 2 ) X 6 /3
A I A n d e r e S p u le
(n u r fü r K u p p lu n g s e rk e n n u n g ) X 1 4 /2 v 3
0 -1 1 0 V A C
V 0 2
( o n ly fo r c o u p lin g d e te c tio n ) X 6 /4 O th e r c o il
X 1 4 /3 k 1 l
X 1 /2 4
M e s s u n g E in s p e is e s tr o m
m e a s u r e m e n t in je c te d c u r r e n t
A I X 1 4 /4 l1
1 A
Ie c i1 k
X 1 /2 5
E C I: a d d itio n a l d ig ita l in /o u tp u ts te r m in a ls X 1 2 - X 1 4
E C I: z u s ä tz lic h e E in /A u s g ä n g e K le m m e n X 1 2 - X 1 4
X 1 4 /5 k 2
R e s e r v e S tr o m e in g a n g
S p a r e c u r r e n t in p u t A I X 1 4 /6 l2 1 A
X 1 4 /7 k 3
R e s e r v e S tr o m e in g a n g
S p a r e c u r r e n t in p u t A I X 1 4 /8 l3
1 A
E C I- S tr o m e in s p e is e g e r ä t M o d e ll3
E E C I- C u r r e n t In je c tio n D e v ic e M o d e l3 E
X 1 2 /1 2 K C O M 4 + U H -U H
+ S V -S V
( R e g le r is t M a s t e r ) X 1 2 /1 1 K 1 2 .4 N O
( C o n t r o lle r is M a s t e r ) D O ( S la v e in p u t o t h e r E F C 5 0 )
X 1 /1 6
E C I- 1 n e g a tiv e E in s p e is u n g X 1 2 /1 0 K 1 1 .4 N O X 1 /1 7
D O
E C I - 1 n e g a t iv e in je c t io n
X 1 /8
E C I - 1 p o s itiv e E in s p e is u n g X 1 2 /9 K 1 0 .4 N O X 1 /9
E C I - 1 p o s itiv e in je c t io n
D O
X 1 2 /8 K 9 .4 N O
(E C I u s e d ) D O ( U s e d in p u t o th e r E F C 5 0 )
(E C I re q u e s t) D O
X 1 2 /7 K 8 .4 N O
( R e q u e s t in p u t o th e r E F C 5 0 )
D D
X 1 2 /6 E C O M .3 -U H
-S V
X 1 2 /5 E 1 1 .3
( R e g le r is t S la v e ) D I (M a s te r o u tp u t o th e r E F C 5 0 )
( C o n t r o lle r is S la v e )
+ U H
+ S V X 1 /2 0
E C I- 1 n e g a tiv e E in s p e is u n g X 1 2 /4 E 1 0 .3
E C I - 1 n e g a t iv in je c t io n D I X 1 /2 1
+ U H
X 1 /1 2
E C I - 1 p o s itiv e E in s p e is u n g X 1 2 /3 E 9 .3 + S V
E C I - 1 p o s itiv in je c t io n D I X 1 /1 3
X 1 2 /2 E 8 .3
(E C I u s e d ) D I (U s e d o u tp u t o th e r E F C 5 0 )
X 1 2 /1 E 7 .3
(E C I re q u e s t) D I (R e q u e s t o u tp u t o th e r E F C 5 0 )
C C
X 1 3 /4 3 - ( ...) n u r fü r 2 S S - B e tr ie b
( 0 - 2 0 m A V e r la g e r u n g s s p a n n u n g 2 ) A O 3 o n ly fo r 2 B B - o p e r a tio n
( 0 - 2 0 m A n e u tr a l to e a r th v o lta g e 2 ) X 1 3 /3 3 +
a n a lo g e r E in g a n g
X 1 3 /2 2 - A I a n a lo g in
0 - 2 0 m A V e r la g e r u n g s s p a n n u n g
A O 2 X 1 3 /1 2 + a n a lo g e r A u s g a n g
0 - 2 0 m A n e u tr a l to e a r th v o lta g e A O
a n a lo g o u t
d ig ita le r E in g a n g
D I d ig ita l in
d ig ita le r A u s g a n g
D O
d ig ita l o u t
+ /-U H H ilfs s p a n n u n g
B + /-S V s ig n a l v o lta g e
T o le r a n z e n n a c h
C A D e r s t e llt e Z e ic h n u n g . K e in e m a n u e lle n Ä n d e r u n g e n d u r c h f ü h r e n
IS O 2 7 6 8 -Ö N O R M M 1 3 6 5
O b e r flä c h e M a ß s ta b : M a te r ia l:
D ie W e ite r g a b e o d e r V e r v ie lfä ltig u n g d ie s e r U n te r la g e T e il1 T e il2
s o w
o h n
ie d ie V e r w e r tu n g
e a u s d r ü c k lic h e G
u n d M itte ilu n g ih r e s In h
e n e h m ig u n g n ic h t g e s ta
a lte s is t
tte t. f m c v H K L K u n d e :
Z u w id e r h a n d lu n g e n v e r p flic h te n z u S c h a d e n e rs a tz . A b m .: m m ; 0 -5 0 0 3 %
A lle R e c h te v o r b e h a lte n . T R E N C H A U S T R IA G M B H 5 0 0 -2 0 0 0 2 % ; > 2 0 0 0 1 % A .N r.: F .N r.:
D a tu m N a m e E F C 5 0 m it E C I
B e a rb . 2 4 .1 1 .2 0 0 9 M P K -S c h
9 .1 2 .2 0 0 9
z u s ä tz lic h e E in /A u s g ä n g e
G e p r. T E -S i
E F C 5 0 w ith E C I
A a d d itio n a l in /o u tp u ts A
B la tt
E N O A G 0 1 0 1 2
0 1 d iv . A n p a s s u n g e n 9 .7 .2 0 1 0 S c h Z e ic h n u n g s n u m m e r Ä n d . Z u s t. 3 B l.
Z u s t. Ä n d e ru n g D a tu m N a m e U rs p r.: E rs .f.: E rs .d .:
4 3 2 1
4 3 2 1
X 5 /1 2 E C O M .5
-U H / -S V
F F
( e x te r n e r L e is tu n g s s c h a lte r ) X 5 /1 1 E 2 1 .5
( e x te r n a l p o w e r s w itc h ) D I
( K o m m a n d o W id e r s ta n d b lo c k ie r e n ) X 5 /1 0 E 2 0 .5
( C o m m a n d R e s is to r tr ig g e r ) D I
(R e s e rv e ) X 5 /9 E 1 9 .5
D I
(S p a re )
K o m m a n d o S tr o m tie fe r X 5 /8 E 1 8 .5
D I
C o m m a n d c u rre n t d o w n
K o m m a n d o S tro m h ö h e r X 5 /7 E 1 7 .5
D I
O p t io n : z u s ä tz lic h e d ig ita le E in /A u s g ä n g e K le m m e n X 5 - X 6
C o m m a n d c u rre n t u p
X 5 /6 E C O M .4
o p t io n : a d d itio n a l d ig ita l in /o u tp u ts te r m in a ls X 5 - X 6
E -U H / -S V E
M e ld u n g F ix s p u le e in X 5 /5 E 1 6 .4
M e s s a g e fix c o il o n D I
T e m p e r a tu r tr ip X 5 /4 E 1 5 .4
D I
te m p e r a tu r e tr ip
T e m p e ra tu r W a rn u n g X 5 /3 E 1 4 .4
D I
te m p e r a tu r e w a r n in g
B u c h h o lz T r ip X 5 /2 E 1 3 .4
D I
B u c h h o lz tr ip
B u c h h o lz W a r n u n g X 5 /1 E 1 2 .4
D I
B u c h h o lz w a r n in g
D D
X 6 /1 2 K C O M .7
+ U H / + S V
N e tz u n s y m m e tr ie > Z f X 6 /1 1 K 2 1 .7 N O
N e t-a s y m m e try > Z f D O
A b g e s tim m t, n ic h t k o m p e n s ie r t X 6 /1 0 K 2 0 .7 N O
D O
T u n e d , n o t c o m p e n s a te d
A b g e s tim m t, k o m p e n s ie r t D O X 6 /9 K 1 9 .7 N O
T u n e d , c o m p e n s a te d
X 6 /8 K C O M .6 + U H / + S V
T e m p e r a tu r tr ip X 6 /7 K 1 8 .6 N O
te m p e r a tu r e tr ip D O
C T e m p e ra tu r W a rn u n g X 6 /6 K 1 7 .6 N O C
D O
te m p e r a tu r e w a r n in g
( ...) S o ftw a r e - O p tio n
B u c h h o lz T r ip X 6 /5 K 1 6 .6 N O a n a lo g e r E in g a n g
B u c h h o lz tr ip D O A I a n a lo g in
B u c h h o lz W a r n u n g X 6 /4 K 1 5 .6 N O a n a lo g e r A u s g a n g
D O A O
a n a lo g o u t
B u c h h o lz w a r n in g
d ig ita le r E in g a n g
K C O M .5 D I d ig ita l in
X 6 /3 + U H / + S V d ig ita le r A u s g a n g
D O
( K o m m a n d o F ix s p u le e in ) D O K 1 4 .5 N O d ig ita l o u t
( C o m m a n d fix c o il o n ) X 6 /2
+ /-U H H ilfs s p a n n u n g
( K o m m a n d o F ix s p u le a u s ) D O K 1 3 .5 N O + /-S V s ig n a l v o lta g e
( C o m m a n d fix c o il o ff) X 6 /1
T o le r a n z e n n a c h
C A D e r s te llte Z e ic h n u n g . K e in e m a n u e lle n Ä n d e r u n g e n d u r c h fü h r e n
D ie W e it e r g a b e o d e r V e r v ie lfä ltig u n g d ie s e r U n te r la g e
IS O 2 7 6 8 -Ö N O R M M 1 3 6 5
O b e r flä c h e M a ß s ta b : M a te r ia l:
s o w ie d ie V e r w e r tu n g u n d M it t e ilu n g ih r e s In h a lte s is t T e il1 T e il2
o h n e a u s d r ü c k lic h e G e n e h m ig u n g n ic h t g e s ta t te t. f m c v H K L K u n d e :
Z u w id e r h a n d lu n g e n v e r p flic h te n z u S c h a d e n e r s a tz . A b m .: m m ; 0 -5 0 0 3 %
A lle R e c h te v o r b e h a lt e n . T R E N C H A U S T R IA G M B H 5 0 0 -2 0 0 0 2 % ; > 2 0 0 0 1 % A .N r.: F .N r.:
D a tu m N a m e E F C 5 0 m it O p tio n s p la tin e :
B e a rb . 2 4 .1 1 .2 0 0 9 M P K -S c h
G e p r. 9 .1 2 .2 0 0 9
z u s ä tz lic h e d ig ita le E in /A u s g ä n g e
T E -S i
E F C 5 0 o p tio n b o a r d :
A a d d itio n a l d ig ita l in /o u tp u ts A
B la tt
E N O A G 0 1 0 1 3
1 d iv . A n p a s s u n g e n 9 .7 .2 0 1 0 S c h Z e ic h n u n g s n u m m e r Ä n d . Z u s t. 3 B l.
Z u s t. Ä n d e ru n g D a tu m N a m e U rs p r.: E rs .f.: E rs .d .:
4 3 2 1
3 Operation
· Operation level
Access (standard password 1) to main parameter for correction of service performance are available (see also
chapter 5).
· Commissioning level
Access (standard password 2) to parameter necessary for start-up procedure are available (see chapter 4).
· Expert level
Access (standard password 3) to all parameters relevant for fine tuning of the device are available for the
advanced user. Also the standard passwords can be individually changed on this level. The structure of the
menu levels is fixed and can’t be changed.
Furthermore, due to the adaptive menu control parameters of not released options are not shown in the display.
For example parameter for resistor control are only shown if this option has been released by input of the correct
password. This operation concept ensures maximum clarity for different users.
EFC50-V1.00 Page 27
December 2010 3 Operation
3.3 Standard control panel
3.3.1 Display
- The next line informs about the actual state of the controller (on or off).
- The following line is reserved for messages during operation (see also chapter 6).
- The display of the following lines depends on the current selected function. For example resonance curve and
calculated network parameter are displayed in the controller is switched on (see also chapter 5).
- Selection of function is done in the command line below the shown separation line.
- A short help text is available in the last two lines
FT … Forced trigger
(R) ... manual trigger for resistor control
(only at released option, if enabled)
FT ... forced trigger for tuning operation
D ... change display
I ... show important information
S ... show statistics
x ... change into menu mode
Page 28 EFC50-V1.00
3 Operation December 2010
3.3.2 Scroll wheel
The scroll wheel allows for a simple and comfortable operation of the controller. Turning the wheel moves the
rectangular, black cursor shown in the display. Pressing the wheel activates the function corresponding to the
current cursor position.
Adjustment of contrast
The EFC50 has an automatic contrast adjustment. A manual adjustment by the user is not necessary therefore.
Enter menu
Turning the scroll wheel until the background of the letter x changes to black. After pushing, the controller changes
to the beginning of the menu (password is required, if menu is password protected).
Exit menu
Turning the scroll wheel until the background of the line „Exit menu“ changes to black. After pushing the scroll
wheel the query „Store parameter“ or „Exit without store“ appears. After confirmation the controller continues
operating, if it is switched on.
By means of this key all remote control commands are blocked in the manual mode (CONTROLLER OFF). This
status (local) is indicated by a green LED.
By pushing the CONTR – key the device changes between manual and automatic mode.
This key can be used for jumping back one step in the menu or to quit changes without storing.
EFC50-V1.00 Page 29
December 2010 3 Operation
3.5 programming PLC
At „programming PLC“ in the menu „in/outputs“ the window of the PLC – file editor opens.
SCR (Scroll)
The PLC- file can be scrolled up / down with scroll wheel.
ED (Edit)
A program line can be entered, after the line (or an empty line) is scrolled by the cursor keys and the “edit“ function
is selected.
By means of the „“edit“ command a “help editor“ or a “line editor“ will be called.
ID (Insert/Delete) CUT
Insert/delete line cut out a line
COPY PASTE
Copy a line paste in a line, which was copied or cut out
3.5.1 H - Editor
The help editor opens the window for comfortable input of a program line and supports the programmer by means
of program elements (help assistant).
A „Token“ is one single part of the whole command such as operands, operators, assignments, comments, etc.
SCROLL
Scrolling from one “Token“ to the next
Page 30 EFC50-V1.00
3 Operation December 2010
EDIT
The “Edit“ command opens the window, where the Token will be replaced by PLC-function, variable, operator or a
comment.
INS
A new “Token“ is inserted at the actual cursor position.
DEL
The “Token“ at the actual cursor position is deleted.
Example: A counter should be programmed, counting (step +1) the earthfault events in the network.
EFC50-V1.00 Page 31
December 2010 3 Operation
The output function OF[EARTHFAULT] is selected for trigger to increment the counter.
The counter is installed. The program line is stored at the main window of the help editor. By selection of ESC or
“previous menu“ you come back step per step (one menu level) to the main window .
The “Save & Exit“ command stores the actual program line, after the automatic syntax check is successfully passed.
A detected syntax error (e.g. “)“ is missing) can be corrected and the “Save & Exit“ command can be executed
again.
After the program line is stored, the help editor will be closed. The programming can be continued in the
PLC - editor.
Page 32 EFC50-V1.00
3 Operation December 2010
3.5.2 Line editor
The line editor fulfils the usual editor functions without any help assistance.
SCR The program line can be scrolled by scroll wheel or the <cursor left> and <cursor right> keys at the PC.
Store the actual line after the syntax check is passed successfully.
3.6 EFC50Term
The terminal program package EFC50Term (incl. EFD20Param, EFD20Analyse) may be used for the following
functions (detailed description chapter 8):
Software update
The software of EFD50 will be updated via the serial interface. This function requires software update files and
password provided by Trench Austria.
EFC50-V1.00 Page 33
December 2010 3 Operation
Page 34 EFC50-V1.00
3 Operation December 2010
4 Start-up
4.1 Necessary preparations
4.1.1 Safety
Warning
Beside the general safety hints (see chapter 1) the following hints have to be considered:
- Personnel working at the ASC must not be endangered by simultaneous coil adjustment via the EFC50
controller
- Measuring circuit of neutral-to-ground voltage may rise to 110 V AC in the case of an earthfault.
- If messages from the EFC50 are generated for test purposes, control room staff should be informed prior
(otherwise messages might be further transmitted, e.g. earthfault message).
- Company regulations (e.g. authorization for switching operations, safety) are to be followed.
Hint
- Re-check mechanical mounting of the device. Pay special attention in keeping required distances for cooling of
the device.
- Avoid any cutting operation near the device. Never put small parts on top of the device, they could enter
unnoticed.
- Replacement of fuses is done at the back of the device. Hence, swing frame installation resp. possibility for rear
access is recommended. If fixed installation in wall-cabinet is used, appropriate length of wiring (for necessary
pulling out of the device) has to be considered.
EFC50-V1.00 Page 35
December 2010 4 Start-up
4.2 Start-up instruction
First time users of this device are recommended to read chapter 3 to become familiar with this operation.
Advanced users may choose the faster procedure by means of EFCTerm (offline programming and up-loading a
prepared start-up file).
Switch on the device by means of main switch (power supply). Wait until the device finishes booting, then open the
menu.
Enter the standard password (“2“) for start-up level and move into the
submenu “System configuration”
4.2.1.2 Language
English or German is available
Page 36 EFC50-V1.00
44 Start-up December 2010
4.2.1.3 EFC50Term Parameter
COM1
Situated on the front of the device, recommended for connection of a PC
or modem. The COM1 is always active at 115 kBd.
COM2
Situated on the back of the device, recommended for connection of a
modem or Scada system.
Hint
The COM2 at the back and the COM1 at the front side cannot be used for EFC50Term at the same time. Switch off
an eventually connected modem at the back COM2, if you want to connect the PC at front COM1. Settings of
controller and of EFC50Term must match. If different addresses are used, multiple devices can be addressed by
means of one modem only combined with an interface distribution box (available on request).
Baud rate
By the use of a modem the baud rate of 9.600 bd is recommended, with direct connection higher baud rates are
possible.
Device and station name: these names are stored together with the
parameter and data files and allow an easy identification therefore. The
names are also displayed at the remote display at EFCterm connection
and allow to check that the connection is really established with the
correct device.
EFC50-V1.00 Page 37
December 2010 4 Start-up
The adjusted ratio for inputs, which are not used (e.g. Vo2, Vo3) , does not affect the control behavior. We however
recommend to use the same values, as adjusted for the used inputs,
corresponding to the voltage level of the network.
Hint
If your ASC is designed for a higher voltage level than actually used, the values have to be recalculated in order
to get a correct % - display of the voltages.
Example:
A coil is designed for 20 kV system voltage and equipped with a measurement winding from 11.55 kV to 100 V.
If the coil is used in a 10 kV system, the ratio of 5.77 kV to 50 V has to be programmed.
The current is injected into the network’s starpoint via the power auxiliary winding of the coil. The primary
injected current is calculated with the following data:
- ratio of the power auxiliary winding (PAW)
- ratio of the current transformer inside the ECI, (10/1A; I-Transf. sec. = 1A
Example
A coil designed for 20 kV system voltage and a transformer ratio of 11.55kV/500V for the PAW gives following
results:
I-primary = 10/(11550/500) = 0.43
Attention
Eventually it is necessary to turn the polarity of the injected current. This can be done by input of a (-) in front of
the secondary value. (e.g. -1).
If the (-) is entered in front of the primary value it is reset to 0. Therefore it is not allowed there.
Page 38 EFC50-V1.00
44 Start-up December 2010
Usual secondary values are 100V (in some countries 110V) for voltages and 1A (5A) for current inputs.
The assignment of the signals to measuring inputs is done in the menu “AI channel assignment”. Beside the
available physical inputs (X…) there is also the possibility to assign the measured value channels A01 … A08,
which can be defined inside the PLC file.
EFC50-V1.00 Page 39
December 2010 4 Start-up
4.2.2.2 Controller works with
The selection „ASC1/BB1/ECI1“ means, that the controller tunes with Petersen coil 1 and the network parameters
are calculated with Vo1 and IECI1 (factory settings). At presence of a second ( or third) ASC it is possible, for better
distinction between the voltages to use the voltages Vo2 (or Vo3) at a second (or third) EFC50.
At use of Vo2 for example the second current injection ECI2 and the relevant in- and output functions for ECI2 must
be used !
These parameters allow a voltage / current correction if the zero sequence impedance of the neutral transformer
cannot be neglected. Normally this impedance should be small compared with the impedance of the coil.
We recommend not to use these parameters without feedback of Trench, if there are any doubts concerning too
high impedance of the coil’s transformer.
4.2.2.4 coil
Hint
If your ASC is designed for a higher voltage level than actually used, the values have to be recalculated in order
to get a correct coil position in [A].
Example:
If a coil for 20kV nominal voltage and a nominal range of 15- 150A, a recalculated range of 7,5 – 75A must be
entered if the coil is used in a 10kV network.
Page 40 EFC50-V1.00
44 Start-up December 2010
Digital In- and outputs:
Digital in- and outputs are assigned to in- and output functions inside the PLC – file. The list of available functions
can be found at the end of chapter 7.
The necessary in- and outputs for the coil are prepared in the standard (factory) setting, in correspondence to the
standard connection diagram (see chapter 2). More factory settings can be found in the program EFC50Param.
Hint
If in- and outputs are used differently from the standard settings, the assignment inside the PLC file must be
changed. We recommend to change this offline with the help of the program EFC50Param.
(see chapter 8).
EFC50-V1.00 Page 41
December 2010 4 Start-up
List of digital outputs EFC50:
Leave the menu at „Exit Menü“ and store the parameters. Adjust the controller to „CONTROLLER OFF“ and adjust
the coil by means of the <> buttons a little bit into both directions..
You should hear the closing of the relevant relay . The value of Ipos should change a little bit.
The coil calibration requires that the motor commands work, the coil moves, the potentiometer works and the end
switches must operate.
Page 42 EFC50-V1.00
44 Start-up December 2010
coil calibration
Start the calibration. This procedure adjusts the coil over the whole range and lasts for some minutes. It is not
necessary that the coil is already connected to the medium voltage network during that procedure.
After successful calibration a few calculated data of potentiometer and coil are displayed.
In case that the controller generates an error signal after a certain time, the reasons with highest probability and
solutions are mentioned under chapter 6.
Push the scroll wheel after the calibration and confirm “Store” after “Exit menu”. Then you adjust the coil manually
over the whole range and compare the coil position in the display with the indication at the coil. If there are
deviations bigger than 2% of the entire range, you should enter the “coil characteristics” (linearization table).
Coil characteristics:
Method 1:
The values for coil position I [A] and the potentiometer values Pot [A, Ohm]
(e.g. for a 1 kOhm potentiometer from the routine test report of the coil) can be
entered directly.
If the test report is not available the potentiometer values can be measured by adjusting the ASC from graduation
mark to graduation mark and measuring the corresponding resistance.
EFC50-V1.00 Page 43
December 2010 4 Start-up
Method 2:
After calibration the following values are shown on ASC position indication (IASC) resp. on controller display
(ICONTROLLER):
At the menu coil characteristics the values of ASC position indication (IASC) can
be entered into the column „I“ and the values of controller display
(ICONTROLLER) into the column „Pot“. After storing and exit of the menu, the
display of controller matches with ASC position indication.
With linear characteristic Vo_min [%] to Vo_max [%] is linear represented by Vo_min
[mA] to Vo_max [mA]
With break characteristic the two ranges Vo_min [%] to Vo_break [%] resp. Vo_break
[%] to Vo_max [%] are represented by the corresponding [mA] ranges.
Hint
Necessary conditions:
Vo_min [%] < Vo_break [%] < Vo_max [%] and Vo_min [mA] < Vo_break [mA] < Vo_max [mA]
Page 44 EFC50-V1.00
44 Start-up December 2010
With logarithmic characteristic the range from log (Vo_min [%] ) to log (Vo_max
[%] ) is represented by the range Vo_min [mA] to Vo_max [mA].
Hint
Necessary conditions:
Vo_min [%] must be > 0 !
For the coil position usually a linear characteristic is chosen. If a fix coil is used and activated, the current-sum of fix
coil and Petersen coil is displayed. The %-value in the display (if %-display activated) is referred to the max. sum
of Imax + Ipos as well.
At the mA - output only the Petersen coil is considered, independently from the state of the fix coil.
EFC50-V1.00 Page 45
December 2010 4 Start-up
4.3 Current injection
This description is only relevant if you use the EFC50 with current injection. Therefore the control with ECI must be
activated, as well as the available current injection devices.
Hint
The adjustment „with ECI“ or „without ECI“ also influences the menu structure. In connection with these settings
some parameters become without sense and are therefore automatically removed from the menu.
For the current injection important are following functions, which should be tested before the first tuning operation:
It is required that the necessary circuits are wired and activated. The fuse of the power auxiliary wiring must be in
place and the current injection device (ECI) supplied and switched on.
a.) Activate the current injection device. The ECI now injects a current into the power auxiliary winding.
The injected current is recalculated and displayed at primary values. (e.g. Ieci = 0.30A / 150°). Depending on
system voltage and type of ECI thefollowing values are expected:
Page 46 EFC50-V1.00
44 Start-up December 2010
b.) If the message 1+ ECI appears on the display during this test also he feedback of the current injection works.
Hint
The feedback of the ECI can be cancelled, if the input function IF[MIF_ECI_POS_1]is directly assigned to the
command output function OF[ECI_POS_1].
If more devices have access to the same current injection device the feedback should be wired anyway.
c.) Put the current injection back to normal condition. Activate the Forced Trigger with the letters „FT“.
At the display appears ECI..1+ , which shows that the controller send a switch on
command to the current injection.
If the coil is already connected to the network, the network parameter are
calculated as well. The value for Ro must be positive.
(At negative Ro the polarty of either Vo or Ieci must be turned.)
According to the actual network condition the following scenarios are possible:
EFC50-V1.00 Page 47
December 2010 4 Start-up
4.5 Enable software options
The software options will be enabled by typing in the the correct passwords (please refer to delivered do-cuments
resp. back side of the controller).
If the software option is enabled, the parameters are available in the menu (Commissioning level;. Expert level).
If the password has been entered correctly, the code will be shown as “1“.
Hint
Please note, that the serial number of the controller must be entered correctly for offline parameter set-tings with
EFC20iParam. Otherwise the enabled options will be disabled by the controller.
Note date and time of commissioning, device and order data and anomalies which eventually occurred. You can
use the attached commissioning report for this purpose.
Page 48 EFC50-V1.00
44 Start-up December 2010
Title Page
Commissioning report TRENCH
EFC50 1/2 Austria GmbH
Customer : __________________________________________
Customer reference : __________________________________________
Station : __________________________________________
Order No : __________________________________________
Type : __________________________________________
Fabrication number : __________________________________________
1. Wiring checked:
2. Parameter settings:
4. Software Options:
Functional check performed
_________________________________________________________________
_________________________________________________________________
This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used
forany unauthorized purpose. Contravention will be prosecuted. All rights reserved. TRENCH AUSTRIA GMBH
5 Service
5.1 Main parameter
For the service level the following menu items can be reached by means of the standard password („1“).
Compensation (Detuning)
This parameter determines the degree of detuning at the tuning point (adjustable in % or A).
Under-compensation can be set by input of „-“ prior to the value. The „%“ value is related to coil position in the
resonance point. The presence of a eventual fix-coil is considered only if the relevant menu setting is
programmed (see chapter 7).
By means of this parameter it can be selected the control of detuning degree or of voltage level. At control of
detuning degree („compensation Iv“) the tuning point is determined by the resonance point Ires and the desired
compensation degree (Iv).
If the control operation is restricted by Vmax (or Vmax2), then at control of voltage („voltage V max“) the tuning
point is selected so that the adjusted neutral to ground voltage Vmax is reached. The compensation degree
(over -compensation Iv>0, under-compensation Iv<0) will be considered if possible. If the controller cannot reach
the right side of the resonance curve because of Vmax (or Vmax2), then a compensation warning will be
generated.
EFC50-V1.00 Page 51
December 2010 5 Service
Vo – trigger level
The neutral-to-ground voltage is stored as reference after each control procedure. A new control procedure is
started, if the actual neutral-to-ground voltage Vo exceeds the trigger threshold (in % of the reference value) for
longer time than the pre-set trigger delay time.
Vearth
In case of an earthfault the controller blocks the coil movement. Any simultaneous control process is stopped
immediately. If this happens during control procedure or if the earthfault lasts longer than the programmed time
for transient earth faults, a forced trigger is released after the earthfault vanishes. Hence, the controller performs
a control operation in any case.
Signal delay
Delay time of the output function OF[EARTHFAULT] for earthfault message.
Threshold Zu
After the end of an automatic tuning operation the controller calculates the asymmetry impedance of the network. If
the value falls below the adjusted threshold (e.g. during a high resistive fault) the output function OF[ASYMMETRY]
(“asymmetry trip“) will be set, which can be assigned to a digital output. A necessary requirement is, that the
controller operates in automatic mode and that automatic tuning is possible (Vo < Vearth).
Page 52 EFC50-V1.00
5 Service December 2010
5.2 Evaluations
5.2.1 Measurement buffer
The controller is equipped with a ring buffer for 1000 measurement points. The measurement points are recorded
according to a settable time interval (starting with 1 s) and at special events (e.g. start of earthfault). Following data
are recorded:
- Date
- Time
- Neutral-to-ground voltage Vo
- Coil position Ipos
- Network parameter (Ires, k, v, d)
- Status information (automatic on/off and so on)
- In- and output functions
The measurement buffer is loaded and evaluated by means of the program EFC50Term (see chapter 8) on a
PC/laptop.
Archive:
The data buffer is only stored in the RAM and will be overwritten, in case it becomes full. However before the
contents of the buffer is written to a permanent memory (archive 0 -9). The archives are written in a cyclic manner
as well, it means, if all archives are full, the oldest one will be overwritten.
Also the archive files can be loaded with the program EFC50Term (see chapter 8) onto the PC/Laptop and
evaluated there.
All, but the counter for the operating time total, can be reset to zero (within commissioning level at “basic
preselection“ or expert level at system configuration).
EFC50-V1.00 Page 53
December 2010 5 Service
5.3 Show important informations
By selection of „I“ in automatic or manual mode and turning the scroll wheel the following informations can be
displayed:
- Fault informations
- Event list
The list of available in- and output functions can be found in chapter 8.
Page 54 EFC50-V1.00
5 Service December 2010
Serial numbers:
This screen shows the IP – addresses of other devices, with which the EFC50
exchanges PLC data.
EFC50-V1.00 Page 55
December 2010 5 Service
Page 56 EFC50-V1.00
5 Service December 2010
6 Messages / Malfunctions
6.1 Messages
6.1.1 Signal bar of coil position
Lower end switch
(blocked)
The controller is blocked by the input function “controller block“ and will therefore not perform any tuning
operation. The message is also visible in manual mode. When the input function is reset, the controller will start
a new tuning operation, if it was in automatic mode before.
_LS
Indication at activated option „Control by external circuit breaker“
CONTROLLER OFF
The controller performs no automatic coil adjustments. A manual adjustment of the coil is possible by operation
e.g. at the controller.
Tuned
The controller successfully finished the control procedure.
Trigger + (123)
The neutral-to-ground voltage has exceeded the upper trigger threshold. The remaining time until start of the
control procedure is shown in brackets.
Trigger - (123)
The neutral-to-ground voltage has exceeded the lower trigger threshold. The remaining time until start of the
control procedure is shown in brackets.
EFC50-V1.00 Page 57
December 2010 6 Messages / Malfunctions
Search for estimation (Vo > Vlimit)
The search procedure was started towards direction of „coil middle position“. The message is shown during the
„minimum coil adjustment“. At the end of this „minimum coil adjustment“ the estimated values are accepted.
Positioning
- The controller adjusts the coil to the predefined middle position after Vo<Vmin.
- The controller adjusts the coil onto the previously determined resonance point at activated option „Readjustment
to exact compensation“.
- At activated option “external circuit breaker“ the controller adjusts the coil to the predefined position.
(Vmin)(15')
The coil is adjusted to the „pre-set coil middle position“. At the end of the set delay time (see chapter 7) the
„Vmin“ message is released (if a new control procedure is not started within the set time). The remaining time
(in minutes) until release of the relay message is shown in brackets.
(Vmax)
The neutral-to-ground voltage has exceeded the threshold Vmax.
Page 58 EFC50-V1.00
6 Messages / Malfunctions December 2010
(Vmax) Tuned
The neutral-to-ground voltage is within the range (Vmax - 25%) < Vo < (Vmax + 10%) and the controller has
successfully finished its control procedure.
Transient earthfault
The neutral-to-ground voltage has exceeded the threshold for recognition of earthfaults. However, the time for a
permanent earthfault was not exceeded yet.
(Earthfault)
The neutral-to-ground voltage has exceeded the voltage threshold for recognition of earthfaults. The earthfault
is present at least for the transient earthfault time.
R on, R off
The switch condition of the resistor is indicated. (Option „resistor control“, see chapter 9)
R blocked
The reconnection of the resistor is blocked due to an exceeded temperature threshold (controller uses an
internal temperature model) or an external block via digital input. (Option „resistor control“, see chapter 9)
ASC on/off
The controller adjusts the coil on the valid tuning point. While passing the resonance peak the ASC will be
disconnected from the network. (Option „Automatic switch for Vo>Vmax“, see chapter 9)
Pos. R
The controller adjusts the coil on the valid tuning point. While passing the resonance peak the additional resistor
is connected. (Option „Automatic switch for Vo>Vmax“, see chapter 9)
EFC50-V1.00 Page 59
December 2010 6 Messages / Malfunctions
6.1.2.1. Errors
An error has occurred. The reason is indicated in the following line. In addition a malfunction is signalized.
(Coil movement)
The controller has released an adjustment command to the coil. However, no movement (> 0,1 %) within the
pre-set time or a movement into the wrong direction was reported back.
(DSP Error)
There is a conflict at the internal data communication.
(Set time)
The controller has no valid time, due to an empty buffer capacitor for the integrated circuit of the internal
clock.
6.2 LEDs
The meaning of the LEDs 1 – 8 is internally predefined, but can be changed by the user inside the PLC - file. The
LEDs for POWER, CONTR and LOCAL are fixed.
The inscription of the LEDs can be actualized by exchange of the paper stripes, which are inserted in the front plate.
Each LED can be used red or green and assigned to a specific PLC function. The factory setting is as follows:
LED1GREEN=OF[TUNED]
LED2GREEN=OF[TUNED_NC]
LED3GREEN=OF[FIX_ON]
LED4GREEN=OF[RP_ON]|OF[R_ON_V_MAX]
LED5RED=OF[EARTHFAULT]
LED6RED=OF[V_MAX]
LED7GREEN=OF[V_MIN]
LED8GREEN=OF[END_I_MAX]|OF[END_I_MIN]
ERROR
The ERROR-LED lights only red. The factory setting is:
ERRORLED=OF[ERROR]|OF[HW_ALARM]|OF[PARA_ALARM]. If required this setting can be easily.
Page 60 EFC50-V1.00
6 Messages / Malfunctions December 2010
POWER
The POWER-LED lights only green. If you have problems please check the connected supply voltage.
LOCAL
The green LED indicates the „Local“ – state of the controller. In this state commands from outside (via digital
input or Scada) are blocked. Switching to Local-mode is only possible, if the controller is OFF (CONTROLLER
OFF).
CONTR
The green LED indicates that the controller is ON (CONTROLLER ON = Automatic mode)
6.3 Malfunctions
6.3.1 Problems during start-up
Reloading of the factory setting
The program “EFC50Param” contains factory settings (menu: “file / factory settings”), which can be used for the
EFC50. It must be observed that these files do not contain any released software options. Therefore eventual
options need to be activated again. We recommend to keep the required option codes somewhere near to the
device.
Example:
If this test is successful, check the assignment inside the PLC-file. There the analogue output channel must be
assigned to a float value in the range of 0 – 100. For example the factory setting for the coil position is:
AO[AO01]=AOFUNC_1(AI[IPOS_P]) coil position in the range between 0 and 100%
EFC50-V1.00 Page 61
December 2010 6 Messages / Malfunctions
Attention
If there are multiple assignments for the same channel inside the PLC-file, only the command, which is the last in
the text file will be executed.
a.) The input is ON, but should be OFF. Check the voltage that is applied between the input contact and the
corresponding common. Since the binary inputs are very high resistive, coupling (inductive or capacitive) of
voltages from neighbouring wires may happen.
If such coupling exists, a solution is sometimes to change to DC-control voltages or to install intermediate
(mechanical) relays, because their input resistance normally is a little bit lower.
b.) The input is OFF, but should be ON. Check if the required signal voltage is applied to the terminals (min. 48V
AC/DC). This voltage must be supplied externally (a make contact only is not sufficient!). If the input is not
operated at all, it is most likely defective. Since the binary inputs are not equipped with changeable fuses,
contact Trench Austria.
Page 62 EFC50-V1.00
6 Messages / Malfunctions December 2010
c.) The status of a binary input function does not fulfill the expectations. First check if the corresponding physical
input is correctly set. Check in the menu „Check IF“, if the input function really shows a different value than
expected.
If this is the case, check the assignment of the input function to the physical input. Correct eventual errors.
Observe, that the assignment becomes only active after the parameters are stored.
If the relay is functioning properly, check the assignment of the output function to the output relay. Correct
eventual errors. Note, the assignment is only active if the parameters are stored. The assignment of the output
functions can be tested by setting the corresponding output function in the menu „Check output functions“.
EFC50-V1.00 Page 63
December 2010 6 Messages / Malfunctions
Exchange of „-Pot“ and „+Pot“
The indicated position changes into the wrong direction.
A quick solution is to double the last value; means, if there is a problem with the standard setting of 15%, then
the next trial can be done with 30% and so on, until there are no more switching operations recognized. The
maximum value is 200%.
Important is that the resonance point, which is found at several repeated trials is more or less always the same,
of course after the presumption that the network size has not really changed.
In case of Vo>Vlimit the neutral to ground voltage is checked, after the tuning point is reached. The tolerated
voltage range is a multiple of the trigger threshold.
At „Sensitivity tuning check“ = 2 for example, the difference between expected Vo (which results from the
calculated network parameter k,v,d) and the actual Vo-voltage must be smaller than the double trigger threshold,
so that the tuning point will be accepted.
If the problem „Recognition of switching operations“ only appears after the final approach to the tuning point,
then the parameter „ Sensitivity tuning check“ should be increased in a similar way as described above. The
maximum value is 10.
Page 64 EFC50-V1.00
6 Messages / Malfunctions December 2010
Fluctuating Vo during tuning procedure
Fluctuations of the neutral-to-ground voltage during the tuning procedure may be recognized as switching
operations. Therefore a wrong resonance point could be determined, if the resonance curve shows „side
resonances“ due to such voltage fluctuations.
Hence, if such fluctuations of the neutral-to-ground voltage are present, the parameter „Vlimit“ should be set
higher than the actual neutral-to-ground voltage. This forces the controller to find voltage values before and
after the resonance peak, which are in an adjustable ratio smaller than the resonance voltage. (e.g. 80%, also
see chapter 1).
EFC50-V1.00 Page 65
December 2010 6 Messages / Malfunctions
Fluctuating Vo during the run of the day
In some networks the neutral-to-ground voltage fluctuates very slowly during the run of the day. These slow
fluctuations can not be suppressed by means of the trigger delay and of the measurement filter. However, the
situation is improved by „Follow-up of the neutral-to-ground voltage“ where the actual neutral-to-ground voltage is
taken as a reference value at regular time intervals (e.g. every 60 min). Lower values than 5 min are not settable.
Operation:
After the end of a tuning operation the controller stores the actual neutral to ground voltage. The adjusted trigger
threshold (in %) is related to that stored voltage.
If the stored voltage follows eventual slow changes of the neutral to ground voltage in your network, then
unnecessary tuning operations will be avoided.
Page 66 EFC50-V1.00
6 Messages / Malfunctions December 2010
7 Parameters
Parameter for device programming are within a structured menu. The structure of the menu levels is fixed and can
not be changed. The following three menu levels can be protected with password, if desired.
Parameter overview
The following structure includes the parameters of all user levels. The character in brackets shows the availability of
parameter at individual user level.
EFC50-V1.00 Page 67
December 2010 7 Parameters
stepped coil (2)
stepped coil interface (2)
coil characteristics (2)
time definitions (2)
pulse time [ms] (2)
delay time [ms] (2)
delay time [0.1s] (2)
min. changes of posit. [%] (2)
current injection devices (2)
ECI 1 installed (2)
ECI 2 installed (2)
ECI 3 installed (2)
controller configuration (1) (2) (3)
compensation [%,A] (1) (2) (3)
fixed coil (3)
activate fix coil (3)
fix coil [A] (3)
control behaviour (1) (3)
Vo-triggerlevel [%] (1) (3)
trigger delay time [s] (1) (3)
time constant t_filt_Vo[s] (3)
follow-up Vo [min] (3)
period. check tuning [min] (3)
Vmin [%] (3)
Signal delay [min] (3)
Vlimit [%] (3)
Vmax [%] (3)
signal delay [s] (3)
Vearth [%] (1) (3)
transient earthfault[0.1s] (1) (3)
signal delay [s] (1) (3)
threshold Zu[kOhm] (1) (3)
multiple busbar operating (3)
controller operating mode (3)
behaviour slave contr. (3)
behaviour slave controller (3)
predef. coil position [%] (3)
fine tuning controller (3)
coil middle pos.Imiddle[%] (3)
tolerated mismatch DeltaIv [A] (3)
max. tries of tuning op. (3)
Vo < Vmin (3)
Vmin-triggerlevel [%] (3)
block coil if V < Vmin (3)
Vo < Vlimit (3)
resonance volt. rate [%] (3)
sensit. search operat. [%] (3)
Vo > Vlimit (3)
sensitivity tuning - check (3)
sens.during search operat. (3)
Vo > Vmax (3)
check V > Vmax (3)
Vmax + hysteresis [%] (3)
Vmax - hysteresis [%] (3)
Page 68 EFC50-V1.00
7 Parameters December 2010
options (2) (3)
fix coil control (2) (3)
activated (2) (3)
fix coil [A] (2) (3)
activate fix coil (2) (3)
fix coil off Ipos [%] (2) (3)
fix coil on Ipos [%] (2) (3)
resistor control (2) (3)
activated (2) (3)
automatic activated (2) (3)
permissible duty [s] (2) (3)
cooling time [min] (2) (3)
delay times (2) (3)
turn on delay 1 [0.1s] (2) (3)
turn on time 1 [0.1s] (2) (3)
turn on delay time 2[0.1s] (2) (3)
turn on time 2 [0.1s] (2) (3)
external power switch (2) (3)
activated (2) (3)
coilposition [%] (2) (3)
control at earthfault (2) (3)
to resonance point (2) (3)
trigger delay [s] (2) (3)
current injection, ECI (1) (2) (3)
definition cycle operation (2) (3)
max. retries of ECI cycles (1) (3)
time definitions (1) (3)
measurem. time [ms] (1) (3)
response time [ms] (1) (3)
settling time [ms] (1) (3)
wait for end of Vo variat. (3)
min. voltage change DeltaV [V] (3)
min. inj. current DeltaIeci[A] (3)
max. voltage variation [%] (3)
max. voltage variation [V] (3)
use ECI device up to [%] (3)
inverse mode (3)
activate (3)
start threshold [V] (3)
multiple BB mode, use (1) (3)
coupling detection via Vo (1) (2) (3)
activate (1) (2) (3)
tolerance DeltaVo=Vo1-Vo2 [%] (3)
minimum tolerance DeltaVo [V] (3)
toler. DeltaDeltaVo=DeltaVo1-DeltaVo2[%] (3)
new check at dVo [%] (3)
delay time [0.1s] (3)
pass control (3)
EFC50-V1.00 Page 69
December 2010 7 Parameters
in/outputs (1) (2) (3)
programming PLC (2) (3)
text definitions (1) (2) (3)
text analog outputs AO (1) (2) (3)
text definition, flags M (1) (2) (3)
def. SCADA variables LT (1) (2) (3)
AO characteristics (1) (2) (3)
output characteristic 1 (1) (2) (3)
characteristic (1) (2) (3)
min. value %-scale [%] (1) (2) (3)
min. value mA-scal [mA] (1) (2) (3)
break value %-scale [%] (1) (2) (3)
break value mA-scale [mA] (1) (2) (3)
max. value %-scale [%] (1) (2) (3)
max. value mA-scale [mA] (1) (2) (3)
output characteristic 2 (1) (2) (3)
characteristic (1) (2) (3)
min. value %-scale [%] (1) (2) (3)
min. value mA-scale [mA] (1) (2) (3)
break value %-scale [%] (1) (2) (3)
break value mA-scale [mA] (1) (2) (3)
max. value %-scale [%] (1) (2) (3)
max. value mA-scale [mA] (1) (2) (3)
output characteristic 3 (1) (2) (3)
characteristic (1) (2) (3)
min. value %-scale [%] (1) (2) (3)
min. value mA-scale [mA] (1) (2) (3)
break value %-scale [%] (1) (2) (3)
break value mA-scale [mA] (1) (2) (3)
max. value %-scale [%] (1) (2) (3)
max. value mA-scale [mA] (1) (2) (3)
Page 70 EFC50-V1.00
7 Parameters December 2010
system configuration (1) (2) (3)
language (1) (2) (3)
data recorder (1) (2) (3)
recording interval [s] (1) (2) (3)
screensaver [min] (1) (2) (3)
password assignment (3)
use passwords (3)
operation level (3)
commissioning level (3)
expert level (3)
LAN settings (1) (2) (3)
IP address EFC50 (1) (2) (3)
Subnetmask (1) (2) (3)
IP addr. standard-gateway (1) (2) (3)
EFC50Term (1) (2) (3)
EFC50Term port: (1) (2) (3)
terminal address (1) (2) (3)
baudrate (1) (2) (3)
SCADA (e.g. IEC60870-5-103) (3)
activated (3)
device address (3)
interface parameter (3)
SCADA to port (3)
baudrate (3)
data bit (3)
parity (3)
stop bits (3)
event configuration (3)
command configuration (3)
motor pulse time [s] (3)
protocol fine tuning (3)
IEC mval 120% = (3)
measurands send via (3)
measurands I FUNC (3)
measurands I INFO (3)
value Ipos[A] (3)
ID message COL (3)
ID message FUNC (3)
EFC50-V1.00 Page 71
December 2010 7 Parameters
7.1 Enable options
The following options can be enabled by input of the correct option password (see attachment to manual or
backside of device). The relevant option parameters will only be displayed in the menu „options“ after the option
has been released.
- tuning method
with ECI / without ECI
- Vectorial trigger
Trigger procedure considers amount and phase of the neutral to ground voltage if activated. Reference voltage
obligatory.
- Resistor control
Home position R
The home position is the state of the resistor (ON/OFF) in the sound network.
Command for trigger
If activated (“YES“) the first cycle of resistor control can be started from the command line in the display (“R“).
- Fix coil control
Enables the controller to automatically switch a fix coil.
- External circuit breaker
Moves the coil into a predefined position
- Control at earthfault
Moves the coil exactly into the resonance point
- Scada
Scada protocol
The following Sacda protocols can be selected: SPABus, IEC 103, IEC60870-5-101 unbalanced/balanced,
IEC60870-5-103, IEC60870-5-104, IEC61850).
- Additional controller
- Automatic switch for V>Vmax
AI primary
Primary nominal voltages V12, Vo1, Vo2, Vo3 and nominal currents Ieci1, Ieci2, Ieci3
AI secondary
Secondary nominal voltages V12, Vo1, Vo2, Vo3 and nominal currents Ieci1, Ieci2, Ieci3
AI channel
Assignment of channels for voltages V12, Vo1, Vo2, Vo3 and nominal currents Ieci1, Ieci2, Ieci3.
It is possible to make assignments to analogue inputs (X10 respectively X14) but also to make no assignment (for
signals , not used) or to use virtual inputs AIE, which can be defined inside the PLC-file.
Page 72 EFC50-V1.00
7 Parameters December 2010
7.2.1 coil
Coil calibration
Procedure, which automatically calculates the operating characteristic after setting the above mentioned parameter.
Is available for the controller only after storing the configuration data.
Coil characteristics
Programming of interpolating points for the operating characteristic which was calculated by the automatic routine.
Coil calibration
the coil is always adjusted only by one step. After the adjusted delay time [ms] the new potentiometer value in [%] is
recorded in the coil characteristic. The maximum number of steps is 64.
Coil characteristics
The individual steps are recorded into the characteristics during the coil calibration. If required the measured coil
position / resistance of potentiometer / mA-value can be corrected here.
Time definitions
Delay time [0.1s] This delay is used only during coil calibration. After the adjustment of the next step the
controller waits fort he adjusted time until it records the potentiometer value into the coil
characteristics.
Minimum change
of posit. [%] A change of the coil position is only recognized if the coil position changes at least the
adjusted percentage.
EFC50-V1.00 Page 73
December 2010 7 Parameters
7.2.1.3 current injection devices (only with ECI)
ECI1 (ECI2, ECI3) installed
Activation of available current injection devices. If the control works with ASC1 and ECI1 (ASC2 and ECI2, ASC3
and ECI3) but ECI1 (ECI2, ECI3) is adjusted to “NO”, the control will work in redundancy mode.
Vectorial trigger
The vector trigger criterion is used, if the reference voltage U12 is available in order to measure the neutral to
ground voltage in amount and angle
(in case of a EFC50i hardware).
Follow-up Vo [min]
Owing to weather influence fluctuations of the neutral-to-ground voltage may occur at overhead lines without any
change of the switching condition of the network. The actual neutral-to-ground voltage (according to the set time
interval) is used as new reference for the calculation of the trigger threshold (if actually, the controller is not in
trigger state or does not perform a tuning procedure). Input of „0“ deactivates the follow-up of the neutral-to-ground
voltage. The minimum value is 5 min.
Page 74 EFC50-V1.00
7 Parameters December 2010
Vmin [%]
Maximum values of the neutral-to-ground voltage lower than the set threshold Vmin are not accepted as resonance
maximum by the controller. If no voltage higher than Vmin is measured over the entire tuning range of the coil, the
controller adjusts the coil to the defined middle position (or alternatively blocks the coil - controller fine tuning).
Vlimit [%]
Threshold for change of the used control procedure. If the neutral-to-ground voltage does not exceed the set
threshold during the search operation, the resonance maximum is accepted only after checking the criteria for the
resonance voltage.
Vmax [%]
The controller may adjust the coil until reaching the set maximum voltage value. When reaching the threshold the
controller stops the tuning procedure.
(Depending on the settings under “Vo>Vmax“, see controller fine tuning)
Vearth [%]
The controller treats neutral to ground voltages higher than the set threshold as earthfault and immediately blocks
the coil movement during the tuning process.
Threshold Zu [kOhm]
The controller calculates the asymmetry of the network after each automatic tuning operation.
If the value falls below the adjusted threshold, the output function (“ASYMMETRY“) is set. This output function can
be assigned to any free output contact. It is also possible to assigned the same contact, that is already used for the
general earthfault signal (at Vo > Vearth).
In order to see the calculated value on the EFC50, probably the displays must be changed.
EFC50-V1.00 Page 75
December 2010 7 Parameters
7.3.2.1.1 Vo < Vmin
7.3.2.1.2 Vo<Vlimit
7.3.2.1.3 Vo>Vlimit
7.3.2.1.4 Vo>Vmax
Vmax2 [%]
If Vmax2 (Vmax2>Vmax) is also exceeded when passing the resonance peak (check V>Vmax at „after tuning“), the
EFC50 stops the coil and tunes back to Vmax. Then the controller signalizes a compensation warning and
generates the message „tuned, not compensated“. If it is not possible to tune back to Vmax because of an end
switch, the coil will be stopped in the end switch (message „end switch“).
In this case some manual interference is necessary because Vo is bigger than Vmax.
after tuning: If it is necessary, the controller adjusts the coil over the resonance maximum and positions the coil to
the tuning point or stops tuning procedure, if the actual neutral to ground voltage reaches Vmax.
Vmax + Hysteresis
Upper limit for the tolerance on Vmax
Vmax - Hysteresis
Lower limit for the tolerance on Vmax
Page 76 EFC50-V1.00
7 Parameters December 2010
7.3.3 Options
The option parameters can be set here. They are only displayed, if the option has been activated before (Menu
“Enable options”)
activated
Activation or deactivation of the option
Type “Standard“:
activated
Activation or deactivation of the option
Automatic activated
Activation or deactivation of the automatic resistor control
EFC50-V1.00 Page 77
December 2010 7 Parameters
7.3.3.3 External power switch
activated
Activation or deactivation of the option
activated
Activation or deactivation of the option
To resonance point
The option is activated, if the parameter is set to „YES“.
Switching behaviour
Choice between connection of a resistor or disconnection of the ASC.
Page 78 EFC50-V1.00
7 Parameters December 2010
7.4 In/Outputs
Analog inputs
Measured values without consideration of transformer ratios
AO characteristics
Check analogue outputs
Digital inputs
Check state of digital inputs and input functions
Digital outputs
Check and set digital outputs
Check and set digital output functions (-> Create scada events if available)
Language
Available is German or English
Interval [s]
Within a set interval the measurements are stored in a ring buffer. Additionally, during a tuning procedure, data are
stored in the measurement buffer. The limits of the interval are 1 and 1800 s (steps of 1 s).
Numbers between 1 and 32767 can be used as pass-word. All other inputs will be reset to the standard password
of the individual service level.
EFC50-V1.00 Page 79
December 2010 7 Parameters
Use passwords
The menu is password protected with setting „YES“.
Operation level
Change of standard password „1“ for operation level.
Commissioning level
Change of standard password „2“ for commissioning level.
Expert level
Change of standard password „3“ for expert level.
For getting the correct settings (IP address, subnet mask, standard gateway, etc.) of the LAN interface please
contact your network administrator.
7.5.4 EFC50Term
Terminal address
For communication of the controller with a PC (and EFC50Term) the set address has to correspond with the used
address in the terminal program. By use of different terminal addresses it is possible to communicate with multiple
EFC50 controllers via only one modem. The controllers can be connected to the modem via an interface distribution
box. A whole number between 0 and 255 is used for the address.
Baudrate
Standard transmission rates between 1.200 and 115.200 baud are selectable for the used interface.
7.5.5 Scada
Only the parameters for the selected protocol version will be displayed (SPABus, IEC101, IEC 103, IEC61850).
General parameters:
Activated
Activation or deactivation of the option.
Device address
The device address set in the controller must correspond to the address used by SCADA.
The standard setting is 10.
Interface parameters:
Scada to port
For the communication with Scada the interface COM1 is used.
Baudrate
Standard transmission rates between 1.200 and 19.200 baud are selectable for the used interface.
Page 80 EFC50-V1.00
7 Parameters December 2010
Databit
The choice has do be done corresponding to the used protocol. Number of data bits / parity / stop bits.
Release of event
Each event must be enabled in the event filter:
c coming
g going
c/g coming / going
off not enabled
Configuration
The events signalizing to the Scada system must be enabled in the menu configuration. The events can be
configured by the following way:
c ... coming
g ... going
c/g ... coming / going
OFF ... disabled
The standard command configuration (INFO) is described in chapter 9. If desired, the information number may be
changed. 16 free Scada flags can be set by Scada and used inside the PLC file.
EFC50-V1.00 Page 81
December 2010 7 Parameters
7.5.5.2.2 Measurands configuration
Configuration
Complex measurands are transferred with amount and phase. The transmission of measurands can be individually
switched on / off. If desired, the information number may be changed. The measurands are transferred cyclically
every 60s.
TypeID, counter
The following adjustments are selectable for transmission of counters (statistics and amount of earthfault signals
per feeder):
- M_IT_NC_1 ... statistics without time tag
- M_IT_TC_1 ... statistics with time tag (CP24Time2a)
- M_IT_TF_1 ... statistics with time tag (CP56Time2a)
The transmission of counters can be individually switched on / off. If desired, the information number may be
changed.
Release of event
Each event can be enabled / disabled with the event filter
c coming only
g going only
c/g coming and going
off deactivated
The standard settings are described in chapter 9. The numbers may be changed if necessary.
16 free Scada flags can be set by Scada and used inside the PLC file.
Measurands
The function type (standard = 1) and the information number (standard 20) of the transferred values (data unit 3)
may be changed if necessary.
Page 82 EFC50-V1.00
7 Parameters December 2010
Value Ipos
The coil position (in %) is calculated out of following values:
That value will be transferred as percentage value (0-120%) into the Scada. In order to avoid a data overflow the
value must not exceed 120%.
ID message
The function type (standard = 5) and the compatibility state (standard = 0) for the device identification can be
adjusted. The Identification is transferred with data unit (5) and contains following information:
The EFC50 with protocol 61850 is equipped with an additional network card, which communicates with Scada via
Ethernet (RJ45 connector).
The parameters necessary for network communication (TCP/IP) are adjusted here, Since these parameters are
needed on the additional network card, they need to be transferred to this card (serial cable connection).
(Alternatively the adjustment is also possible via IEC61850 configurator (via Ethernet), however the settings then
are only stored inside the network card and not inside the parameter file.
Device sub-address (A or B)
If two EFC50 are used with a common 61850 network card.
SNTP server
For correct IP adjustment of time synchronization via SNTP (simple network time protocol) please contact your
network administrator.
EFC50-V1.00 Page 83
December 2010 7 Parameters
Page 84 EFC50-V1.00
7 Parameters December 2010
8 EFC50Term
8.1 Basics
EFC50Term is a program for Microsoft Windows for support of the earthfault compensation controller EFC50. The
program is able to communicate with the controller via the serial interface - direct or via modem. The program
consists of three different parts according to the following functions:
- EFC50Term Terminal program for remote control, data transfer and online parameter setting
- EFC50Analyse Analysis of the measured data stored by the controller.
- EFC50Param Offline parameter setting of the controller
EFC50-V1.00 Page 85
December 2010 8 EFC50Term
8.3 Installation
- Insert the EFC50Term – CD into the CD drive.
- Start EFC50Term -> setup.exe
- During the installation you are requested to enter installation path and program group. Confirm the end of the
installation with OK. The installation is finished and EFC50Term can be executed in the chosen program group.
8.4 EFC50Term
The terminal program starts with the following window.
Open
*.par. parameter file, the parameter program will be opened
*.mwp data buffer – or archive file, the analyze program will be opened
*.inf information file, the text editor will be opened
EFC50Analyse
This menu item opens the program part, where an evaluation of stored measured values (data buffer) can be done.
EFC50Param
This menu item opens the program part, where controller parameters can be prepared.
Exit
The terminal program is finished.
Remark: if the data buffer becomes full, it will be stored into an archive file.
Page 86 EFC50-V1.00
8 EFC50Term December 2010
Load archive
Enter name and directory for the archiv file of the EFC50. The program informs about the available archive files
(record period, number of data sets). The xxx.inf file contains a kind of event list of the corresponding data buffer.
If you use a slow modem connection it is better to first download the small xxx. Inf file in order to evaluate if the
xxx.mwb file is worth to be downloaded.
Load statistics
Enter name and directory for the statistics text file. After downloading of the statistics all counters (exception: total
counters) can be reset.
Monitoring controller
The terminal mode of EFC50Term (remote operation) starts. The controller display will be shown on the PC-monitor
and the controller software version is included to the headline of the window.
Softwareupdate
Enter the serial number of the controller and the corresponding password for the softwareupdate.
Please also enter name and directory of the new EFC50 - version (controller software) or eventually of the new
DSP-version (software for signal processor).
The password and the necessary files can be ordered at Trench Austria.
After confirmation (Parameters saved and then OK) a second window opens, where you state, if you want to
transfer EFC50 (and/or DSP) software or if you just want to verify.
Please save actual parameter file and data buffer before you start with the software update.
Attention: Do not disconnect the device from the power supply during the software – update !
After correct transmission, the new software is on the controller and can be
activated with „YES“. With NO you can still cancle the update.
EFC50-V1.00 Page 87
December 2010 8 EFC50Term
Before Running the new software the controller needs to be rebooted..
Softwareupdate EFX
The expansion box EFX could provide the EFC50 with additional digital in- and outputs.
If a software update is required for the expansion unit EFX, this will be possible via this menu item. The software
update works only via the serial interface and at 9600baud, data configuration 8N1.
At connection via LAN it is strongly recommended to have a direct connection from PC to EFC50 via a crossover
cable !
Communication
Page 88 EFC50-V1.00
8 EFC50Term December 2010
Several different modems can be added in the window “modem”. The file „kommpar.dat“ contains all adjustments
for controllers (station name, phone numbers, etc) which are available via modem. The directory of this file is
adjustable there.
The communication parameters of defined modems can be set here. You can find the relevant settings for your
modem in the relevant modem instruction manual.
Init string
In principle modems, which are initialized by factory settings (&F), can operate with EFCTerm. Additional
adjustments (e.g. X3) correspond to the individual phone plants.
For instance, if a Devolo Microlink is used, the init string &F%C0%G1%B9600 effects, that data compression is
deactivated and transmission speed is constant (9600 Bd).
LAN settings
The device can be operated alternatively to the RS232
interface by Ethernet (RJ45) as well.
If the controller is connected to an existing network a free IP
address must be given by your network administrator and
assigned to the device.
EFC50-V1.00 Page 89
December 2010 8 EFC50Term
Disconnect communication
Disconnects an existing connection
Connect communication
Tries to build up a connection. If „Use modem“ is selected, a window opens, where you have to select the desired
station.
Language
German or English
Color setting
Colors of letters and background can be adjusted here.
Status bar
displays or hides the bar
Page 90 EFC50-V1.00
8 EFC50Term December 2010
8.4.5 Menu About EFC50Term
8.5 EFC50Analyse
The analysis program starts with the following window.
Open
A stored file (*.mwp) can be selected and opened.
Save
A revised file can be stored under the same name.
Save as
A revised or new file can be stored. Name and directory can be stated.
The data can be stored in ASCII-format (*.asc) in order to support also other programs (e.g. Excel, Access,
etc. ).
Print...
Prints the evaluated curves.
Print preview
Displays the printer output on the monitor.
Print setup
The setup of the installed printer can be adjusted.
Last files
The 4 last opened files can be chosen.
EFC50Term
EFC50-V1.00 Page 91
December 2010 8 EFC50Term
This menu item opens the program part with the terminal function.
EFC50Param
This menu item opens the program part, where controller parameters can be prepared.
Exit
The analysis program is finished.
Select curves
When a file is opened or transferred no curves are selected first. This window shows the selectable curves. The
desired curves must be added into the right window.
Page 92 EFC50-V1.00
8 EFC50Term December 2010
Representation
calls the window „Display measured values“
- The program connects data points with lines. The curves look better in
this way.
- At complex values it is possible to show also the phase of the signal.
The curves however become a little bit less readable
- Same scale for same type of curves. Useful when different signals of
the same type (e.g. 3 voltages) are compared.
EFC50-V1.00 Page 93
December 2010 8 EFC50Term
Example 1
In order to get the complete resonance curve, the coil could be adjusted through the whole range. After-wards the
data buffer is transferred to the PC and the corresponding time range should be selected before the changing into
x-y diagram.
Example 2
In order to get the local curve of the neutral to ground voltage Vo by assigning the voltage to both axis at the
settings of the x-y diagram (it’s assumed, that EFC50i hardware and reference voltage is used).
Page 94 EFC50-V1.00
8 EFC50Term December 2010
Event list settings
This dialog fulfills the function of a signal filter. The individual event corresponds to the output function of the
controller and can be configured as entry to the event list.
Rectangular Zoom
The cursor in the main window changes into a magnifier lens. A rectangular cut out can be selected for zooming in.
The maximum expansion depends on the number of selected curves and the displayed time range. If the expansion
is not sufficient the number of curves must be decreased or the selected time range must be shortened.
Fit
The selected curves are fitted into the actual window size. This command is also available in the symbol bar.
Reset
The scaling of the curves is made according to the individual ranges of the displayed values. This command is also
available in the symbol bar.
Set...
Input of factors for zoom in x and y direction.
EFC50-V1.00 Page 95
December 2010 8 EFC50Term
8.5.4.Menu Settings
Language
German or English
Time interval
Entire : The range of values will again be extended onto all values of the data buffer.
Current : The range will be restricted onto the zoom – range
Symbol bar
displays or hides the bar
Double horizontal
Status bar
displays or hides the bar
Display values
opens the window with the measured values at the actual cursor position. A double click creates a cursor line at the
actual mouse pointer position.
Page 96 EFC50-V1.00
8 EFC50Term December 2010
Display event list
opens the window, which includes the entries of the event list during the selected time (Representation)
EFC50-V1.00 Page 97
December 2010 8 EFC50Term
8.5.6 Menu About EFC50Analyse
8.6 EFC50Param
The parameter program starts with the following window.
New
A new parameter file (*.par) can be opened.
Open
A stored file (*.par) can be selected and opened.
Save
A revised file can be stored under the same name.
Save as...
A revised or new file can be stored. Name and directory can be stated.
Factory settings
Factory settings according to standard connection (with or without option board) can be opened. (Connection
diagrams see chapter 2)
Print...
Prints the parameter list. Only the parameters of the selected service level will be listed. The headline of the print
includes the serial number (ID) and the installed software version of the controller.
Page 98 EFC50-V1.00
8 EFC50Term December 2010
Print preview
Displays the printer output on the monitor.
Print setup
The setup of the installed printer can be adjusted.
Last files
The 4 last opened files can be chosen.
EFCTerm
This menu item opens the program part with the terminal function.
EFCAnalyse
This menu item opens the program part, where an evaluation of stored measured values (data buffer) can be done.
Exit
The parameter program is finished.
The parameter structure of the PC-program corresponds to the structure of the controller menu.
Operation level
Only access to the most important parameters („Top Ten Parameter“) is available.
Commissioning level
All parameters are available, which are necessary for the first controller start up.
Expert level
All parameters for special settings are available.
All levels
All parameters are available.
Language
German or english.
Symbol bar
Displays or hides the bar
EFC50-V1.00 Page 99
December 2010 8 EFC50Term
The symbols correspond to the following commands:
Symbol Command
Neue Datei
Open
Save
Print preview
Print preview
About EFCParam
Status bar
Displays or hides the bar
The example shows assignments which have been defined in the factory settings for the standard configuration
„Master ECI bipolar“.
Boolic, arithmetic, comparison operators and PLC -functions (delays, impulses, etc.) are available in order to
achieve the required behavior of the device. Additionally any comment may be entered behind a <;> character. The
editor also checks for correct syntax and provides with proposals.
Edit:
Letzte Aktion rückgängig machen / Text suchen / Text weitersuchen
Undo (last action) / Find (text) / Find next
View:
Display index:
In the square brackets the index number of the used item (e.g. digital output, flag etc.) is shown. This display is
useful, when you have to input several similar functions, because you only have to change the index number but
not the text.
Display defines:
In the square brackets the defined name of the used item (e.g. digital output, flag etc.) is shown.
Update colours: Comments, brackets, functions, etc. will be shown indifferent colours. After input of some text, the
update of this colour setting can be performed.
Single commands:
Line assistant:
The line assistant guides through the program line and also provides operators between the individual items. This
function is better for users which are not yet very familiar with the use of operators.
The checksum is calculated as XOR - logical operation of the individual message bytes. The start bytes ”>”
and ”<” are included. The special SPABus bytes cr, lf and & as well as the checksum itself are not included. If the
controller EFC50 receives the byte ”XX” instead of the checksum, the controller will not check. The EFC50 always
adds the checksum when sending.
The EFC50 checks the received serial data for the start byte ”>”. If the following bytes contain the device address
(adjustable in the menu) of the EFC50 or if they contain the broadcast address 900, then the following commands
will be checked. If the calculated checksum does not fit, a NACK-Message ( Not acknowledge - Error Code 0 ) will
be answered. In the other case the received command will be decoded and processed.
The dialog between SPABus-Master (Request >...) and EFC50 (Answer <...) is described in the following examples
(Device address 18 and checksum XX) .
>10RC:XX or read Slave Status >900WT:ss.sss:XX or BROADCAST write time
>10R0C:XX >900W0T:ss.sss:XX in ss.sss in actual
<10D:1:XX no answer hh.mm the seconds are
>10WC:0:XX or clear Slave Status set
>10W0C:0:XX >10RD:XX or read date & time
<10A:XX >10R0D:XX jjjj-mm-tt hh:mm:ss.sss
>10RF:XX or get Ident <10D:01-11-13
>10R0F:XX 11,10;14.707:XX
<10D:EFC50V1.00:XX >10WD:yy-mm-dd Set actual date and actual
>10RT:XX or read time in ss.sss hh.mm;ss.sss:XX or time
>10R0T:XX >10W0D:yy-mm-dd (at impossible time or
<10D:59.042:XX hh.mm;ss.sss:XX date
>10WT:ss.sss:XX or write time in ss.sss <10A:XX e.g. 30. FEB the answer is
>10W0T:ss.sss:XX the seconds are set in <10N:8:XX)
<10A:XX actual hh.mm >900WD:yy-mm-dd BROADCAST write date
(at impossible time hh.mm;ss.sss:XX or actual date
e.g. > 59.999 the answer >900WD:yy-mm-dd yy-mm-dd and actual
is hh.mm;ss.sss:XX time hh.mm;ss.sss
<10N:8:XX) no answer are set
Read backup
When the EFC50 is switched ON, initially all states (events) are set to 0. The controller answers to the request
„read backup >10RB:XX“ with <10D:00.000 0E50:3F, as long as for the first time the request „read last
events“ (>10RL:XX) is received. Then the answer to „read backup“ will be the same as for „read last events“.
<10D:0/0/1/1/0/1/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0:XX
<10D:0/0/1/1/0/1/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0:XX
Vo > Vmax.
<10D:0/0/1/1/0/1/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0:XX
The controller is in automatic mode.
Following the request >10R0V3:XX the controller answers <10D:1:XX („There is an earthfault in the network“)
Following the request >10R0V1/3:XX the controller answers <10D:1/0/0:XX („ASC is adjusted towards higher
current“)
Following the request >10RO:XX the EFC50 sends all measured values [in %] in following sequence:
Following to the request >10RO(Index):XX the actual measured value with the specified index will be answered.
Example 1:
Example 2:
Commands by Scada are only accepted if the controller is not in the menu or in local - mode.
The command >10WI1:1:XX sets the output function „OF1_mot_up“ and the assigned output relay for „Motor up“.
The ASC moves in direction „Imax“ until the command >10WI1:0:XX sets back the output relay or until the end
position is reached.
OF[CONTR_BLOCK]
Automatic
7
OF[BUCH_WARN] Buchholz warning 31
blocked OF[BUCH_TRIP] Buchholz trip 32
remote control:
OF[LOCAL] 8 OF[TEMP_WARN] Temperature warning 33
local state
End switch
OF[TEMP_TRIP] Temperature trip 34
OF[END_I_MAX] 9 OF[IS_MASTER] Controller is Master 35
Imax
End switch OF[IS_SLAVE] Controller is Slave 36
OF[END_I_MIN] 10
Imin OF[COUPLED_BB1_BB2] coupling BB1-2 37
OF[HW_ALARM] Hardware problem 11 OF[COUPLED_BB1_BB3] coupling BB1-3 38
OF[PARA_ALARM]
12 OF[COUPLED_BB2_BB3] coupling BB2-3 39
Parameter problem OF[ECI_REQUEST] ECI Request 40
reference voltage too
OF[V12_TOO_LOW] 13 OF[ECI_USED] ECI in use 41
small
Tuned, OF[ECI_POS_1] ECI1 plus 42
OF[TUNED_NC] 14 OF[ECI_POS_2] ECI2 plus 43
not compensated
OF[TUNED] Tuned 15 OF[ECI_POS_3] ECI3 plus 44
OF[V_MIN] Uo < Umin 16 OF[ECI_NEG_1] ECI1 minus 45
Schaltautomatik 17 OF[ECI_NEG_2] ECI2 minus 46
OF[R_ON_V_MAX]
für U>Umax OF[ECI_NEG_3] ECI3 minus 47
OF[ASC_OFF] coil disconnected 18 OF[ECI_ERROR_1] Error ECI1 48
OF[RESERVED_18] reserve 19 OF[ECI_ERROR_2] Error ECI2 49
OF[RP_ON]
resistor on
20 OF[ECI_ERROR_3] Error ECI3 50
command OF[ECI_ERROR] Error ECI 51
expansion Controller in red-
OF[XBOX_1_OK] 21 OF[CONTR_RED] 52
box1 ok undancy mode
expansion ECI in use
OF[XBOX_2_OK] 22 OF[ECI_USED4CONTR] 53
box2 ok for control
resistor blocked 23 OF[RESERVED_53] reserve 54
OF[RP_BLOCK]
54....62 reserve 55-63
high resistive earth - 24
OF[ASYMMETRY] OF[RESERVED_63] reserve 64
fault
compensation- M000 flag 0 65
OF[COMP_WARN] 25
warning M001-M062 flag 1-62 66-127
OF[IEC101_TIMEOUT] Scada error 26 M063 flag 63 128
Measured value Description INFO Measured values are transferred after a general interrogation,
V12 amount (V) 1025 cyclic or at a relative change of 3% (only if the value is bigger
0,05% of it’s maximum). The following table shows the
phase (°) 1026
standard setting of the information numbers, which can be
V12 % 1027 changed if required.
Vo1 amount (V) 1028
phase (°) 1029
Vo2 amount (V) 1030
phase (°) 1031
Vo3 amount (V) 1032
phase (°) 1033
Vo1 % 1034
Vo2 % 1035
Vo3 % 1036
Ipos coil position (A) 1037
Ifix coil position (A) 1038
Ipos+Ifix coil position (A) 1039
Id coil position (A) 1040
Iv coil position (A) 1041
Ires coil position (A) 1042
Ieci1 amount (V) 1043
injection current phase (°) 1044
Ieci2 amount (V) 1045
injection current phase (°) 1046
Ieci3 amount (V) 1047
injection current phase (°) 1048
If you need further information (e.g. interoperability list), please contact the manufacturer of your Scada - system or
Trench Austria.
The common address of ASDU is the adjusted device address (refer to chapter 7.5.3).
Data Unit (1) Signalling with time stamp Data Unit (3) Measurement data 1
v: detuning
d: damping
IEC mval 120% correspond either to integer 2048 or 4096 (adjustable in the menu)
Type identification 6
marking of the variable structure 129
Cause of transmission COT 8
Common address of ASDU
Function type GLB 255
Information number 0
Seven octett
Binary-time
Type identification 8
marking of the variable structure 129
Cause of transmission COT 10
Common address of ASDU
Function type GLB 255
Information number 0
received from
„scan number“ trigger of
general
interrogation
Type identification 6
Marking of variable structure
Cause of transmission COT
Common addresse of ASDU
Function type GLB
Information number
Seven octett
Binary-time
Type identification 7
Marking of variable structure
Cause of transmission COT
Common address of ASDU
Function type GLB
Information number
„scan number“
9.4.4 Commands
Data Unit (20) General command
Type identification 20
Marking of variable structure
Cause of transmission COT
Common address
of ASDU
Function type FUNC (siehe
follow. list)
Information number INFO (siehe
follow. list)
„Double point“command
Feedback information
Commands from SCADA are only processed by the EFC50 if the controller is not in the menu mode and not in
„local“ - state.
The EFC50 gets commands from the SCADA control unit by means of „Double point“- commands. (Data Unit 20).
The receipt of a possible command is acknowledged with COT 20 (command acknowledge positive). All other
commands are acknowledged with COT 21 (command acknowledge negative).
The execution of a command is not indicated with COT 12 (remote operation) but with COT 1 (spontaneous).
That means that commands are executed without feedback.
The controller is in automatic mode. The command with INFO 6, FUNC 140, DPI = 2 sets the controller into manual
mode.
The command with INFO 1, FUNC 140, DPI = 2 adjust the coil in direction Imax until:
The command INFO 3, FUNC 140, DPI = 2 adjusts the coil in direction Imax, until the adjusted motor impulse time
expires or the upper end switch is reached.
The command with INFO 140, FUNC 5, DPI = 2 sets back the controller to Automatic.
Output function Description FUNC INFO Output function Description FUNC INFO
Event Event
OF[MOT_UP] Motor up 243 0 OF[RESERVED_26] reserve 243 26
OF[MOT_DOWN] Motor down 243 1
Fix coil on
OF[EARTHFAULT] Earth fault 243 2 OF[FIX_ON] 243 27
command
OF[V_MAX] Vmax 243 3
OF[RESERVED_28] reserve 243 28
OF[ERROR] malfunction 243 4
ECI in use
OF[CONTR_IS_ON] Automatic on 243 5
OF[ECI_USED4CD] for coupling- 243 29
Automatic
OF[CONTR_BLOCK] 243 6 detection
blocked
remote control: OF[BUCH_WARN] Buchholz warning 243 30
OF[LOCAL] 243 7 OF[BUCH_TRIP] Buchholz trip 243 31
local state
End switch 243 OF[TEMP_WARN] Temperature warning 243 32
OF[END_I_MAX] 8
Imax OF[TEMP_TRIP] Temperature trip 243 33
End switch OF[IS_MASTER] Controller is Master 243 34
OF[END_I_MIN] 243 9
Imin
OF[IS_SLAVE] Controller is Slave 243 35
OF[HW_ALARM] Hardware problem 243 10
OF[COUPLED_BB1_BB2] coupling BB1-2 243 36
243
OF[PARA_ALARM]
Parameter problem
11 OF[COUPLED_BB1_BB3] coupling BB1-3 243 37
reference voltage too 243 12 OF[COUPLED_BB2_BB3] coupling BB2-3 243 38
OF[V12_TOO_LOW]
small OF[ECI_REQUEST] ECI Request 243 39
OF[TUNED_NC]
Tuned,
243 13
OF[ECI_USED] ECI in use 243 40
not compensated OF[ECI_POS_1] ECI1 plus 243 41
243 OF[ECI_POS_2] ECI2 plus 243 42
OF[TUNED] 14
Tuned
OF[ECI_POS_3] ECI3 plus 243 43
OF[V_MIN] Uo < Umin 243 15
Schaltautomatik
OF[ECI_NEG_1] ECI1 minus 243 44
243
OF[R_ON_V_MAX] 16 OF[ECI_NEG_2] ECI2 minus 243 45
für U>Umax
coil disconnected 243 17 OF[ECI_NEG_3] ECI3 minus 243 46
OF[ASC_OFF] OF[ECI_ERROR_1] Error ECI1 243 47
OF[RESERVED_18] reserve 243 18 OF[ECI_ERROR_2] Error ECI2 243 48
resistor on OF[ECI_ERROR_3] Error ECI3 243 49
OF[RP_ON] 243 19
command OF[ECI_ERROR] Error ECI 243 50
expansion Controller in red-
OF[XBOX_1_OK] 243 20 OF[CONTR_RED] 243 51
box1 ok undancy mode
expansion ECI in use
OF[XBOX_2_OK] 243 21 OF[ECI_USED4CONTR] 243 52
box2 ok for control
resistor blocked 243
OF[RP_BLOCK] 22 OF[RESERVED_53] reserve 243 53
high resistive earth -fault 54....62 reserve 243 54-62
243 23
OF[ASYMMETRY] OF[RESERVED_63] reserve 243 63
compensation- 24 M000 flag 0 243 64
OF[COMP_WARN] 243
warning M001-M062 flag 1-62 243 65-126
OF[IEC101_TIMEOUT] Scada Error 243 25 M063 flag 63 243 127
On the CD, which is attached to the controller’s packing you can find following data:
IEC61850 configurator
The PC program allows direct communication between PC and 61850 board in order to set network data and to
transfer configuration files.
ICD-file
This file contains the preconfigured device- and communication description (EFC50) in xml-format. The standard
IED name is EPSY, the type EFC50. If you want to use other names they must be edited in the ICD-file as well as
in the Mapping – file.
The resistor temperature (T) is indicated as percent value. The maximum value (100%) is the temperature, which
the resistor reaches after continuous load at solid earthfault (Vo = 100%) during the set permissible duty time.
The minimum value (0%) is the ambient temperature.
When the maximum temperature is reached the controller will automatically set the command to switch off the
resistor. Then the resistor control stays blocked until a reconnection is possible without exceeding the maximum
temperature.
Warning
In any case check the adjustments for permissible duty time (at Vo = 100%) and cooling time of your
resistor according to the manufacturer’s data (rating plate, manual of coil or resistor, etc.)
Example
Parameter 1 2 3
Turn on delay 1 1 1 4
Turn on time 1 2 2 2
Turn on delay 2 3 0 0
Turn on time 2 4 4 0
Example 1
On
Off
0 1 2 3 4 5 6 7 8 9 10
Example 2
On
Off
0 1 2 3 4 5 6 7 8 9 10
Example 3
On
Off
0 1 2 3 4 5 6 7 8 9 10
Example1
Uearth
0 1 2 3 4 5 6 7 8 9 10
On
Off
0 1 2 3 4 5 6 7 8 9 10
Example 2
Uearth
0 1 2 3 4 5 6 7 8 9 10
On
Off
0 1 2 3 4 5 6 7 8 9 10
If after a certain time delay Vo still is above Vearth the controller adjusts the coil to the calculated resonance point.
The controller sets the “On“-command, if the available tuning range in direction to the estimated tuning point is
bigger than the parameter “minimum width [%]“
If this is not the case, the tuning point at the other side of the resonance curve will not be available and the
controller sets „Vmax“ and „Tuned, not compensated“.
The controller sets the “Off“-command for the ASC, if the available tuning range in direction to the estimated tuning
point is bigger than the parameter “maximum width [%]“
If this is not the case, the controller sets „Vmax“ and „Tuned, not compensated“.
After disconnection of the ASC the controller adjusts the coil by the value defined „maximum width“ across the
resonance point. The controller then connects the coil again and start a new tuning operation at the correct side of
the resonance curve.
If the neutral to ground voltage exceeds Vmax after reclosing of the ASC, the controller sets the “Off“-command
again. In this case the coil will be moved back across the resonant point to coil position, where the threshold Vmax
was exceeded. Then the ASC will be closed in and the controller starts a new tuning process.
If the Vo voltage again reaches Vmax the controller stops and sets „Vmax“ and „Tuned, not compensated“.
After a sufficient change (trigger threshold) of Vo each controller calculates it’s own trigger delay based on a
random number operation (of course within certain limits).
The controller with the shortest trigger delay starts the tuning operation first. All other controllers are still supervising
the neutral to ground voltage.
If other controllers recognise a Vo change bigger than „tolerance range of trigger“ times „trigger threshold“ within
the set time „% of coil running time“, they interpret this change as result of tuning activity caused by the first
controller. Then they calculate new random trigger delays.
If there is no voltage change within this time the other controllers start their tuning operations also.
Normally the first controller is already able to tune the network. The following controllers will only perform tuning
checks but adjust their coils on the same position afterwards.
If this is not the case the second (or following) controller(s) finally tune(s) the network.
Hint
If the desired compensation degree is adjusted in percentage, the network parameters resp. the resonance
point of the network - determinated by the second (or following) controller(s) - is decreased by the detuning
degree of the first controller.
In order to avoid a couple of tuning procedures of all controllers, an absolute detuning degree (compensation [A])
is recommended.
If the option is activated the controller adjusts the coil onto a predefined position if the transformer is disconnected.
If the transformer is reconnected the controller gets a forced trigger and starts a new tuning operation.
If the measured neutral to ground voltage Vo doesn’t exceed the Vmin - threshold over the tuning range of Petersen
coil, the controller switches off the fix coil (resp. switches on, if the fix coil is disconnected) and adjusts the Petersen
coil to predefined coil middle position, if the neutral to ground voltage doesn’t exceed the Vmin - threshold over the
entire tuning range.
If the option is activated the lightning LED “fixcoil on“ indicates that the controller has set the command to switch on
the fix coil.
The adjustment of lower and upper position limits should consider the size of fix coil in order to avoid unstable
behaviour of the tuning procedure.
Im
trigger threshold standard
local curve
0 Vo_res
Re
vectorial trigger
The phase measurement requires a reference voltage V12 (maximum 110 VAC) synchronous to the network. The
reference voltage can be taken from busbar measuring bay (phase 1 to phase 2 voltage secondary)
An easier arrangement can also be a single phase transformer (230/100 VAC) connected to station power supply.
Attention
AC-voltage supplied by frequency converter (UPC) is not suitable due to phase inaccuracy !