InteliGen 200

Controller for parallel gen-set


applications

SW version 1.2.0
1 General information 2
2 Changes in the version 1.2.0 3
3 Changes in the version 1.1.2 5
4 Changes in the version 1.1.1 6
5 Changes in the version 1.1.0 7
6 Related information 9
7 Notes 10

Copyright © 2018 ComAp a.s.


Written by Michal Slavata
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: info@comap-control.com, www.comap-control.com New Features List
1 General information
1.1 Version information
Major version with several new features and bug repairs.

1.2 Clarification of notation


Note: This type of paragraph calls readers attention to a notice or related theme.

IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

Example: This type of paragraph contains information that is used to illustrate how a specific function
works.

InteliGen 200 1.2.0 New Features List 2


2 Changes in the version 1.2.0
2.1 New features
ECU Key Switch
New LBI ECU KEY SWITCH added

ECU Key Switch


Description
ECU Key Switch function is used to switch ECU power supply on, when engine start is not requested. It is
intended to enable engine values reading, when engine doesn't run. It works in this way:
LBO ECU POWER RELAY is active, if LBI ECU KEY SWITCH is active.
LBO ECU POWER RELAY functionality is not affected, if LBI ECU KEY SWITCH is inactive.

Adjustable idle RPM


New setpoint Idle RPM added

Idle RPM
Setpoint group Engine Settings Range [units] 100 .. 4000 [RPM]
Default value 900 Step 1 RPM
Config level Standard Related applications SPtM, MINT
Description
This setpoint adjusts idle speed.

Regulation loops improvement


Regulations should be more similar to IGS-NT regulations
PLC block number increase
Number of Force Prot block is increased to 4
Mains hysteresis for mains undervoltage and mains overvoltage protections
Level for activation is adjusted via setpoins (Mains Undervoltage, Mains Overvoltage)
Level for deactivation is counted in this way:
If Mains Undervoltage setpoint is <= 90% then hysteresis is between Mains Undervoltage setpoint
and Mains Undervoltage setpoint + 4%
If Mains Overvoltage setpoint is >= 110% then hysteresis is between Mains Overvoltage setpoint
and Mains Overvoltage - 4%
If Mains Undervoltage setpoint is >90% then hysteresis is betweenMains Undervoltage setpoint and
40% from (100 – Mains Undervoltage setpoint)
If Mains Overvoltage setpoint is <110% then hysteresis is between Mains Overvoltage setpoint and
40% from (100 – Mains Overvoltage setpoint)
Aftertreatment lamps
Red, Yellow and Wait to Start lamps are alarm indication only + history record is created

InteliGen 200 1.2.0 New Features List 3


Extended range of setpoint MCB Close Delay
Range is extended from 60s to 600s
Extended range of setpoint Transfer Wrn Delay
Range is extended from 60s to 600s

2.2 Repairs
Binary Output Regen Needed
This binary output is connected to DPF lamp
Tier IV screen hiding
Screen is visible only for ECUs with SPN 3695 or SPN 3696
Connection type Autodetect
Autodetect didn´t hold detected connection type after Engine stop
Now, connection type detected by Autodetect is used also after engine stop

InteliGen 200 1.2.0 New Features List 4


3 Changes in the version 1.1.2
3.1 Repairs
Activation of LBO READY TO LOAD
Sometimes this LBO was not activated when gen-set was ready to take the load
Breakers control improvement
Correction of length of OFF pulse and ON pulse
Synchronization of shared setpoints
Shared setpoints are correctly synchronized between all controllers on CAN2 line
Regulation loops improvement
Frequency and Angle regulation loops are more similar to IGS-NT regulation loops

InteliGen 200 1.2.0 New Features List 5


4 Changes in the version 1.1.1
4.1 Repairs
Power management fix
Power management may after some time work incorrectly. It is highly recommended to use this fix to
rule out the possibility.

InteliGen 200 1.2.0 New Features List 6


5 Changes in the version 1.1.0
5.1 New features
Distributed power management signals
Automatic sharing of selected power management signals is available
For detailed information see chapter Distributed power management signals in the InteliGen 200 1.1.0
Global Guide
Control groups support
It is possible to use Bus Tie Breakers (BTB's) to divide system into multiple groups of gensets .It
enables independent operation of groups of gensets, which can perform power management , load
sharing and VAr sharing independently.
New parameters Control Group, Group Link L and Group Link R are available
New LBI: Group link is available
For detailed information see chapter Control groups in the InteliGen 200 1.1.0 Global Guide
Efficient priorities switching with relative power management mode
It is possible to use efficient mode of engine priorities control (#Priority Auto Swap = Efficient) when
relative power management mode is used (#Power Management Mode = REL(%))
Protections blocking
It is possible to enable/disable selected protections using setpoints in the new group Protections or
control protections blocking with the new LBI: Force Protection Disable.
Synchronisation screen automatic switching
Synchronisation screen is automatically displayed when synchronisation is started. Main (the first)
screen is displayed when synchronisation is over. There is no transition to the mains screen, if user
decides to leave the synchronisation screen during the synchronisation.
Alarm list automatic switching
Transition from the main (first) screen to alarm list is done automatically when a new alarm is issued.
Automatic transition back to the main screen is done when all alarms are cleared.
Analog inputs used as a Tristate/Binary input
Tristate and Binary sensors can be used with controller analog inputs
PLC Delay modules
Number of available PLC modules Delay has been increased from 2 to 4
Alarm messages handling with CAT engines
Handling of J1939 alarm messages from CAT engines has been changed to avoid repeated
activation/deactivation of engine alarms

InteliGen 200 1.2.0 New Features List 7


5.2 Repairs
Synchronisation in WebSupervisor
WebSupervisor did not display information that controller performs synchronisation. It has been fixed.
Coils reading with Modbus
Reading of some Modbus coils (function code 1) did not work. It has been fixed.

InteliGen 200 1.2.0 New Features List 8


6 Related information
6.1 Available files
Firmware (*.exe)
For InteliGen 200
InteliConfig-Install-Suite-1.2.0.4.exe

Table 6.1 Available firmware

Archives (*.aig3)
For InteliGen 200
InteliGen200-GC-1.2.0.4

Table 6.2 Available archives

6.2 Overview of all available hardware


InteliGen 200
Binary Inputs 8
Binary Outputs 8
Analog Inputs 4
Analog Outputs 0
Communications USB, RS232-485, 4G, GPRS, Ethernet

Table 6.3 Available hardware

6.3 Available related documentation


Documents Description
InteliGen 200 1.1.0 Global The manual provides general information how to install and operate InteliGen
Guide 200 controllers.
InteliGen 200 Datasheet Basic information about InteliGen 200

Table 6.4 Available documentation

InteliGen 200 1.2.0 New Features List 9


7 Notes
7.1 Document history
Revision number Related sw. version Date Author

4 1.2.0 16.10.2018 Michal Slavata


3 1.1.2 3.9.2018 Michal Slavata
2 1.1.1 22.6.2018 Vladimír Zubák
1 1.1.0 25.4.2018 Vladimír Zubák