Documente Academic
Documente Profesional
Documente Cultură
Technical Manual
Contents
1. Extinguishing control panel essertronic 8010 19”
10. Release solenoid
798955.GB0
pending GB Technical changes reserved!
05.2006
Extinguishing Control Computer 8010 – 19-Inch
Intended purpose
This software must only be used for the applications outlined in the catalogue and the technical description
and in combination with external components and systems which have been approved and /or
recommended.
Warning
In order to ensure correct and safe operation of the product, all guidelines concerning its transport, storage,
installation, and mounting must be observed. This includes the necessary care in operating the product.
Safety warnings
The following information is given in the interest of your personal safety and to prevent damage to the
product described in this manual and all equipment connected to it.
Safety information and warnings for the prevention of dangers putting at risk the life and health of user and
maintenance personnel as well as causing damage to the equipment itself are marked by the following
pictograms. Within the context of this manual, these pictograms have the following meanings:
Warning sign
Designates risks for man and/or machine. Non-compliance will create risks to man and/or
machine. The level of risk is indicated by the word of warning.
Dismantling
In accordance with Directive 2002/96/EG (WEEE), after being dismantled, electrical and
electronic equipment is taken back by the manufacturer for proper disposal.
2 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Table of contets
1 General ....................................................................................................................................................................... 4
FB 798955.GB0 / 05.06 3
Extinguishing Control Computer 8010 – 19-Inch
1 General
The Extinguishing Control Computer 8010 – 19-inch a fire alarm control panel with an integrated controller for
use in extinguishing systems and provides the connection of automatic fire detectors and Manual call points.
With a total of eight automatic detector zones and 30 connectable automatic fire detectors for each zone, it is
possible to monitor a single extinguishing area as defined by the VdS Guideline 2496.
In addition, five permanently assigned inputs are available for connecting technical zones of units, for example
the manual detector zone or the Emergency Stop zone. The required control functions can be realized with the
total of 13 programmable relay outputs.
A maximum of 100 additional outputs could be realised by using the optional esserbus® transponders.
The Extinguishing Control Computer 8010 can be directly connected to the analog loop of the fire alarm system
8000 / IQ8Control via the esserbus® communication transponder (Part No 808615). Up to eight Extinguishing
Control Computers can be operated on one loop with other loop devices, e.g. fire detectors or esserbus®
transponders. This enables up to eight individual extinguishing areas to be monitored via one analog loop.
The Extinguishing Control Computer 8010-19-inch design is programmed with the Microsoft Windows based
programming software LKDE from version V02.00 or higher.
Any operation on the installed fire alarm system must only be carried out by authorised personal in
accordance with relevant safety procedures and in coordination with the emergency services.
VdS compliant fire alarm systems must be designed in accordance with VdS guidelines.
LED lights up
LED flashes LED flashes yellow / ret
continuously
788014 Extinguishing Control Computer 8010 series 3 – 19-inch design with operating panel (3HE)
788015 Extinguishing Control Computer 8010 series 3 – 19-inch design without operating panel (3HE)
788024 Extinguishing Control Computer 8010 series 2 – 19-inch design with operating panel (3HE)
788025 Extinguishing Control Computer 8010 series 2 – 19-inch design without operating panel (3HE)
788653 Terminal card for C-mounting rail incl. 50-pole D-SUB cable, length 1m
788654 Terminal card for C-mounting rail incl. 50-pole D-SUB cable, length 2m
4 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
2 General View
All operations of the Extinguishing Control Computer can be carried out with the clearly arranged function keys.
The keys can be locked with the built-in key switch.
1 2 3 4 5 6 7
Detector zone
1 2 3 4 5 6 7 8
In operation Common trouble Relay (AE) 1 8
Extinguishing system Emergency
9 10 11 12 13
activated
Extinguishing system
operation Unlocked
enabled Fire/Switch off/Trouble
Power trouble 2 9
Emergency release Battery trouble
Switching off 3
Switchover Buzzer off
Ground fault 10
Test operation Trouble 1
Extra releasing 1 Blocking
4 11
Outputs Fan trouble
Alarm
5 12
Lamp test Panel reset
1 2 3 6 13
0005
Zone On
4 5 6
7
Output Off
7 8 9
Disconnection Test operation
0
11 10 9 8
5 Fault indicators
6 Control indicator
10 Ten-button keypad
FB 798955.GB0 / 05.06 5
Extinguishing Control Computer 8010 – 19-Inch
Switchover
With the key >Switchover<, it is possible to switch between indicating the zones or outputs
(Toggle operation).
Detector zone
1 2 3 4 5 6 7 8
9 10 11 12 13
Fire/Switch off/Trouble
6 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Switchover
With the key >Switchover<, it is possible to switch between indicating the zones or outputs
(Toggle operation).
In operation
Extinguishing system
activated
Extinguishing system Detector zone
enabled 1 2 3 4 5 6 7 8
Emergency release
Switching off 9 10 11 12 13
Test operation
Fire/Switch off/Trouble
Extra releasing 1
Status display of the outputs is Outputs
switched on Alarm
FB 798955.GB0 / 05.06 7
Extinguishing Control Computer 8010 – 19-Inch
In operation
Extinguishing system
activated
Extinguishing system
enabled
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Flashes System ready for operation, keypad enabled for operation with the key switch.
8 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Revision mode always has priority over the test mode in the display!
Outputs
On Indicates that an output has been triggered.
Additional information is given by the yellow LED in the status display of the outputs.
FB 798955.GB0 / 05.06 9
Extinguishing Control Computer 8010 – 19-Inch
Common trouble
Emergency
operation
Power trouble
Battery trouble
Ground fault
Trouble 1
Blocking
Fan trouble
10 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Call maintenance-service immediately in the case of failure messages and in the CPU-failure
mode of the Extinguishing Control Computer.
When a fault is present or in the CPU-failure mode, the Extinguishing Control Computer is
operational only with restrictions. Comprehensive functioning is no longer provided. Call
maintenance-service immediately.
FB 798955.GB0 / 05.06 11
Extinguishing Control Computer 8010 – 19-Inch
The keys can be locked with the built-in key-switch to prevent unauthorized operation.
12 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Unlocked In operation For operation, it is necessary to enable the keypad via the key-switch.
In operation In operation
Extinguishing system Extinguishing system
activated activated
Extinguishing system Extinguishing system Detector zone
Zone enabled Off enabled 1 2 3 4 5 6 7 8
Emergency release Emergency release
3
Switching off Switching off 9 10 11 12 13
Test operation Test operation
Fire/Switch off/Trouble
Extra releasing 1 Extra releasing 1
Outputs Outputs
Alarm Alarm
The deactivated zone is shown in the zone display with the continuously illuminated yellow LED.
The zone display can be switched between the display of the 13 zones and the 13 outputs with the function key
>Switchover<. When the keypad is locked, the status of the zones is always automatically shown, even if
outputs have been deactivated.
The following key combination must be pressed in order to switch on and reset the detector zones:
In operation In operation
Extinguishing system Extinguishing system
activated activated
Extinguishing system Extinguishing system Detector zone
Zone enabled On enabled 1 2 3 4 5 6 7 8
Emergency release Emergency release
3
Switching off Switching off 9 10 11 12 13
Test operation Test operation
Fire/Switch off/Trouble
Extra releasing 1 Extra releasing 1
Outputs Outputs
Alarm Alarm
The continuously illuminated yellow LED in the zone display is deactivated. The detector zone is in the normal
operation mode.
FB 798955.GB0 / 05.06 13
Extinguishing Control Computer 8010 – 19-Inch
Unlocked In operation For operation, it is necessary to enable the keypad via the key-switch.
In operation In operation
Extinguishing system Extinguishing system
activated activated
Extinguishing system Extinguishing system Detector zone
Output enabled Off enabled 1 2 3 4 5 6 7 8
Emergency release
7 Emergency release
Switching off Switching off 9 10 11 12 13
Test operation Test operation
Fire/Switch off/Trouble
Extra releasing 1 Extra releasing 1
Outputs Outputs
Alarm Alarm
The deactivated relay output is shown in the zone display with the continuously yellow LED. The green LED
>Outputs< also lights up to indicate that the zone display is showing the status of the outputs.
The zone display can be switched between the display of the 13 zones and of the 13 control outputs with the
function key >Switchover<. If the keypad is locked, the status of the zones is always automatically shown, even
if outputs have been deactivated.
In operation In operation
Extinguishing system Extinguishing system
activated activated
Extinguishing system Extinguishing system Detector zone
Output enabled On enabled 1 2 3 4 5 6 7 8
Emergency release
7 Emergency release
Switching off Switching off 9 10 11 12 13
Test operation Test operation
Fire/Switch off/Trouble
Extra releasing 1 Extra releasing 1
Outputs Outputs
Alarm Alarm
Fig. 10: Indication and Operation – Switching on the relay output No. 7
The continuously illuminated LED in the status display of the output turns out. The relay output is switched on
and will be activated in the case of an event.
14 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Unlocked In operation For operation, it is necessary to enable the keypad via the key-switch.
In operation In operation
Extinguishing system Extinguishing system
activated activated
Extinguishing system Extinguishing system Detector zone
Zone enabled Test operation enabled 1 2 3 4 5 6 7 8
Emergency release
6 Emergency release
Switching off Switching off 9 10 11 12 13
Test operation Test operation
Fire/Switch off/Trouble
Extra releasing 1 Extra releasing 1
Outputs Outputs
Alarm Alarm
Fig. 11: Indication and Operation – Switching on Test mode for detector zone No.6
The zone input in Test mode is indicated in the zone display with a yellow/red flashing LED. The yellow LED
>Test Mode< also lights up to indicate that the zone display is showing the status of the detector zone.
In operation In operation
Extinguishing system Extinguishing system
activated activated
Extinguishing system Extinguishing system Detector zone
Zone enabled On enabled 1 2 3 4 5 6 7 8
Emergency release
6 Emergency release
Switching off Switching off 9 10 11 12 13
Test operation Test operation
Fire/Switch off/Trouble
Extra releasing 1 Extra releasing 1
Outputs Outputs
Alarm Alarm
Fig. 12: Indication and Operation – Switching off Test mode for detector zone No.6
FB 798955.GB0 / 05.06 15
Extinguishing Control Computer 8010 – 19-Inch
Unlocked In operation For operation, it is necessary to enable the keypad via the key-switch.
The revision mode display has priority over the test mode. If an alarm zone is for example in test
mode and the revision mode is switched on in addition, the state of the >Test mode< LED changes
from ON to flashing.
In the deactivated revision mode the >Test mode< LED lits continuously.
In operation In operation
Extinguishing system Extinguishing system
activated activated
Extinguishing system Extinguishing system
Test operation enabled On enabled
Emergency release Emergency release
Switching off Switching off
Test operation Test operation
Extra releasing 1 Extra releasing 1
Outputs Outputs
Alarm Alarm
Selecting the revision mode activates all outputs programmed with the status function >Revision<. All outputs of
the Extinguishing Control Computer remain activated until the revision mode is deactivated.
Zones and outputs which are disconnected or out of order will not send an alarm in the event of a fire!
16 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Unlocked In operation For operation, it is necessary to enable the keypad via the key-switch.
A restart of the system does not take affect on disconnected detector zones or detector zones in
the test mode. This zone will not be switched on or resetted by a restart.
In operation
Extinguishing system
activated
Extinguishing system
enabled
Emergency release Panel reset
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Unlocked In operation For operation, it is necessary to enable the keypad via the key-switch.
In operation
Common trouble
Extinguishing system
activated Emergency
Extinguishing system operation
Detector zone
enabled 1 2 3 4 5 6 7 8 Power trouble
Emergency release
Lamp test Battery trouble
Switching off 9 10 11 12 13
Ground fault
Test operation
Trouble 1
Extra releasing 1 Fire/Switch off/Trouble
Blocking
Outputs
Fan trouble
Alarm
FB 798955.GB0 / 05.06 17
Extinguishing Control Computer 8010 – 19-Inch
The LED indicators no. 1 to 13 lit when the corresponding detector zone or output (relating to the customer data
programming) is activated. The description of each output can be edited in the lettering area.
5 12
6 13
0005
7
The mechanical alarm counter displays the total quantity of all recognized fire alarms and is incremented with
each new fire alarm.
18 FB 798955.GB0 / 05.06
Installation Instruction
798955.GB0
pending GB Technical changes reserved!
05.2006
Extinguishing Control Computer 8010 – 19-Inch
Table of contents
1 Operation Instruction...............................................................................................................................................1
4 Installation................................................................................................................................................................. 21
4.1.1 Installers responsibility................................................................................................................. 21
4.2 Standards and guidelines ................................................................................................................................. 22
4.3 Installation information....................................................................................................................................... 24
5 Mechanical configuration......................................................................................................................................... 26
10 Sequence diagram................................................................................................................................................... 65
12 Connections ............................................................................................................................................................. 71
20 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
4 Installation
The terminal assignment and wiring illustrated in these installation instructions refer exclusively to the facilities of the
operating system software for the Federal Republic of Germany [D].
The display illustration given in this manual may be differ from the real display indication due to a customized
and object related configuration of the system.
Operation of the Extinguishing Control Computer 8010 - 19-Zoll is governed by the national version of the operating
system software used and the country version programmed in the customer data.
Chapter Design by two installers with collective system recognition, connection without SST.
4.2.4
The 19-inch cabinet with safety glass and safety lock can be purchased without installations for self-assembly or
as a complete, ready-to-connect solution.
The increased mechanical protection of the 19-inch cabinet also makes it suitable for use in industrial
production facilities.
If the 19-inch installation/cabinet is assembled by the installation company, the installation company
automatically becomes the manufacturer of the systems with all rights and obligations according to
DIN ISO 900x and all the relevant standards and guidelines.
Fire alarm systems and other system components such as ELA technology must not be installed
together in one cabinet.
FB 798955.GB0 / 05.06 21
Extinguishing Control Computer 8010 – 19-Inch
In Germany, systems are considered to be in compliance with the general technical rules or the standards of the
EU for security systems if they meet the technical guidelines of the VDE (Verband Deutscher Elektrotechniker,
Association of German Electrical Engineers). They may also be considered to be in compliance with the
standards of the EU for security systems if they meet the technical guidelines of another comparable institution
within the European Community which have been accepted in accordance with directive 73/23 EEC of the
Council dd. 19 February 1973 – directive on low-voltage systems- (ABL. EG No. L 77 page 29). The same must
be applied for all applications of additional, product relating guidelines, e.g. EMI-Guideline 89/336/EEC and the
Construction Products Directive (CPD) 89/106/CE.
These technical guidelines must be observed within the European Community. The VDE guidelines must be
observed within Germany. In other countries (e.g. U.S.A.: NFPA and UL requirements), the relevant national
standards, guidelines and legislation must be observed.
22 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
In addition to the above, the guidelines of the German VdS Schadenverhütung GmbH (VdS) may apply for
systems installed in Germany.
FB 798955.GB0 / 05.06 23
Extinguishing Control Computer 8010 – 19-Inch
Assembly material
The panel must be installed with suitable fixing material (screws, threaded bolts) with no mechanical stress on
the assembly surface of the 19-inch cabinet. The panel may be operated only when it has been properly
installed on the surface with sufficient bearing power.
Energy supply
The fire alarm system is not suitable for connection to an IT voltage supply system.
Disturbance variables
Avoid electrical and mechanical disturbance variables. This applies especially to the installation of panels,
components and installation cables in the direct vicinity of fluorescent lamps or energy cables and mounting on
vibrating, unstable surfaces such as thin partition walls.
Cabinet ventilation
The ambient conditions for the assembly/operation of the fire alarm system must comply with Class 3k5
according to IEC 721-3-3:1994. If these climatic conditions cannot be fulfilled, appropriate countermeasures
must be taken.
If you believe that the ambient temperature is unsuitable for the installed devices, you must take appropriate
measures to air-condition the 19-inch cabinet.
In principle you must prevent heat accumulation between the installed devices and between the devices and the
walls of the 19-inch cabinet. Especially ensure that there is an adequate heat buffer between the highest
installed panel and the top of the 19-inch cabinet.
Door contact
The 19-inch cabinet is fitted with an electrical door contact that monitors when the door is opened. This door
contact may be used in fire alarm control panels to switch off the master box (MB) of one or more panels.
24 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Accessibility
The 19-inch cabinet must be accessible at all times for operation and maintenance work.
Ground
Even when switchgear is installed carefully and properly planned in advance this cannot completely prevent
undesired short circuits during operation of the fire alarm system. The corresponding safety measures must be
taken to reliably prevent damage to life and property in such cases.
If two or more panels are installed in the 19-inch cabinet, the following instructions must be
complied with:
Each panel must be connected to the terminal strip with a separate PE cable (required cable
cross-section 〈 1.5 mm²). Place the reference to leak current next to the terminal strip.
You will find further information about the required type-relevant grounding in the section on PE
connection and power supply.
EMC protection
As default the fire alarm control panels are fitted with an EMC secondary protection system. Use only protection
modules approved by Esser by Honeywell for any additional medium or coarse protection for power supply and
signal lines.
ESD protection
While handling electronic assemblies, the necessary precautions against electrostatic discharge
must be taken.
FB 798955.GB0 / 05.06 25
Extinguishing Control Computer 8010 – 19-Inch
5 Mechanical configuration
The Extinguishing Control Computer 8010 is suited for a direct mounting to a 19-inch rack. The arrangement of
the appropriate operating elements and connectors does not require to open the housing.
The housing must be opened only for the required jumper settings and to insert the batteries. All
internal cable wiring is done by factory.
8 7 6 5
4
Netz Relais 12 Relais 13
1 2 3
Fig. 19: Housing (Back view)
f Terminal card with 50-pole D-SUB connectors to the external terminal for zones and relays
i Toroid transformator
j Ventilation holes
26 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
3 2
2
1 2 3
4 5 6
7 8 9
0
4
1 1
7
2
8
3
9
0 00 5
Extinguishing area 1
0
5
2 1
4
2
5
3
6
0 00 5 Extinguishing area 2 1 1
7
2
0
3
9
0 00 5
7 8 9
1 2 3
0 00 5
Extinguishing area 3
4 5 6
3
7 8 9
1 2 3
0 00 5
4 5 6
7 8 9
4 6
8 1
4
7
2
5
0
3
6
9
0 00 5 Extinguishing area 8
9 8
Fig. 20: Front view of the 19-inch rack mounting (Example with Fire Alarm Control Panel)
f Remote indicating and operating panel of the FACP mounted in the cabinets door
g Ribbon cable wiring between FACP and the indicating and operating panel
h 19-inch swivel frame to mount the remote indicating and operating panels
k Cable duct
The batteries must be mounted in the appropriate place inside the housing of the Extinguishing
Control Computer. Observe the required orientation of the battery placement (refer to battery
label).
The connection of external batteries, e.g. placed on the cabinets floor is not permitted.
FB 798955.GB0 / 05.06 27
Extinguishing Control Computer 8010 – 19-Inch
The housing of the Extinguishing Control Computer must be inserted in an appropriate 19-inch mounting slot of
the cabinet and fastened by the 4 screws (see front side) from the front. To connect the zones and relay a
separate 50-pole terminal card is required. This terminal cards are mounted on a C-rail in the back of the
cabinet and connected via a D-SUB cable to the appropriate connectors on the back side of the Extinguishing
and Control Computers housing.
1 2
max. 2 m
150
100 mm > 500 mm X mm
X = cabling space
800 mm recommended
Cabinet requirements
It is highly recommended to use a cabinet (19-inch rack) with a mounting depth of 800mm. The to handle bars
on the housings front side require a mounting space from min. 100 mm measured to the cabinets door.
Ensure a sufficient space for the C-rail terminal connection behind the housing. Connect cable with a suited
bending to avoid a damage of the cable.
All required terminals are located on the external terminal card. The connection of cables to the
separate circuit boards inside the housing of the Extinguishing Control Computer 8010 is not
necessary.
28 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
The D-SUB plugs on the housings rear side are connected via a 50-pole cable (length 1m or 2m) with the
external terminal card on the C-rail.
1 2 2 1
Observe the different connectors for zones c (D-SUB jack) and relays d (D-SUB plug) at the
housings rear side when connecting the external terminal card.
All required terminals are located on the external terminal card. The connection of cables to the
separate circuit boards inside the housing of the Extinguishing Control Computer 8010 is not
necessary.
FB 798955.GB0 / 05.06 29
Extinguishing Control Computer 8010 – 19-Inch
• The FE (functional earth) and PE (protective earth) terminals of the panel’s housing must be connected with
the PE rail of the power distributor panel from which the fire alarm system will be powered (required cable
diameter ≥ 2,5 mm²).
• Electroconductive housing parts must be interconnected with a PE cable
(required cable diameter 1,5 mm², flexible).
2
A
5
4 3
Cable cross section at least
FE
≥ 2,5 mm² to PE rail
Fig. 22: Location of the terminals and PE connectors in the 19-inch rack (example)
30 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
The power supply of the Extinguishing Control Computer 8010 is provided via the built-in 24 V DC / 2.5 A
power supply unit. If necessary, an increased power requirement for external devices, e.g. caused by longer
cable lengths, must be compensated for with an external voltage supply via a separate power supply unit. In
case of an AC main power loss, the continuous voltage supply is ensured by the batteries. If the mains voltage
is not present after a delay time of 15 minutes (900s) a fault message is indicated. If the failure cause is
eliminated within this time no fault message will be generated. At a total loss of the mains and battery voltage, a
system start will be automatically carried out by the CPU if the main voltage supply (not the battery voltage) is
present again.
Netz
Anschlussklemmleiste
19-Zoll Schrank
Netz 230V~
L1
L1
N
N
PE
PE
3 x 1,5 mm²
Fig. 23: Connection of the 230 V AC main voltage and PE (schematic wiring)
The PE-connector of the mains terminal X2 is connected to the housings rear side with a prefabricated cable
This connection must not be disconnected!
• The 230 V AC mains supply must be installed in accordance with local regulations by a qualified technician.
• The Extinguishing Control Computer must be supplied from the 230 V mains through a separate isolator or
an appropriately labelled safety switch. In buildings fitted with earth fault devices (FI protection), a separate
device must be installed for the fire alarm system.
• Use an appropriate mains cable, e.g. NYM 3 x 1.5 mm2 or a cable type with similar specifications.
• The installation must comply with local regulations on electrical safety
All connected power and signal lines must be secured using appropriate fasteners, e.g. plastic
cable binders. Make sure the mains cable will not move and touch the signal lines. Make sure to
lead all cables complete with their outer sheaths intact into the cabinet. Only remove the insulation
from those sections which are inside the cabinet.
Power supply fuse
The fuses cannot prevent an unexpected fault in electrical modules; rather, these fuses are
intended to protect users and their surroundings from damage.
Therefore, never repair or bridge the fuse that is installed or replace it with anything other than the
stated type!
FB 798955.GB0 / 05.06 31
Extinguishing Control Computer 8010 – 19-Inch
For an emergency back-up time of 72 hours with the max. battery capacity a current of max. 230 mA is available
to power external loads.
Battery 1 F15
+ -
Battery 2
+ -
F14
Battery1 Battery2
Fig. 24: Position and polarity of the battery terminals on the Power supply and relay board
The batteries must be mounted in the appropriate place inside the housing of the Extinguishing
Control Computer. Observe the required orientation of the battery placement (refer to battery label).
The connection of external batteries, e.g. placed on the cabinets floor is not permitted.
In case of the final discharging voltage of the batteries a max. voltage of 21,2 V DC is available to
supply and activate the valves. The valves must match this application requirements.
32 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
8 9 10 1
4
Fig. 25: Position of the devices (Top view with open housing)
g Batteries max. 2 x 12 V DC / 24 Ah
h Fan
j Board with D-SUB connectors to connect the external terminal card (via a 50-pole cable)
FB 798955.GB0 / 05.06 33
Extinguishing Control Computer 8010 – 19-Inch
Internal connection
to zone terminals
Door contact
X27 X28
S1
X3
RESET
X29
Processor board
U17
X4
X12 Connector for the ribbon cable to the display and control panel
X13 64-pol. pole terminal strip for connecting to the zone board (19-Zoll)
X28 4- pole programming interface for Service PC.
This connector is also available on the operating panel.
X29 Terminals for the door contact of the cabinet (option)
U17 Operating system and customer data EEPROM
S1 Reset button (cold start)
By pressing the button a restart of the system will be initialized.
S2 Service key
To interrupt a running extinguishing procedure for test purposes hold down the S2 button (service)
and briefly push the S1 (RESET) button as well.
34 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
The alarm zone operating mode (standard or EDD) is set via the associated jumpers (J1 to J8). Mixed operation
on one alarm zone of series 9000 and 9100 automatic fire detectors is not permissible.
N J9
X16
PE
Zone board Groung fault
L1 identification
TRAFO PRIMARY
F2
X1 T1A X5
Trafo secund.
F1
T4A
To power supply- and relay card
X3
X4
Internal connection
to zone terminals
Fig. 27: Zone board series 2 (Part No. 771793) / position of the subassemblies
Terminals
The zone board is fully internal connected with the terminals of the mains supply voltage and the D-SUB board
of the external terminal card connection.
Unused detector zone inputs must be programmed as >unused< in the customer data or
alternatively terminated with an End-of-line resistor.
Do not connect Fire detectors series 9200 / IQ8Quad.
Mixed operation of automatic fire detectors, and/or technical alarm modules or esserbus®
transponders in a common detector zone is not permitted.
When connecting the mains voltage and the protective earth, refer to the instructions in the chapter
“Mains connection and earthing“.
FB 798955.GB0 / 05.06 35
Extinguishing Control Computer 8010 – 19-Inch
36 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Programming of the alarm zone operating mode (standard or EDD) is via the associated jumper.
Every alarm zone must be terminated with a 10 kΩ End-of-line resistor in the last detector base.
Unused alarm zones must also be connected with a 10 kΩ End-of-line resistor.
For installation, use the recommended cable with the specification I-Y (St)Y n x 2 x 0.8 mm ∅ (comp. telephone
cable, double-shielded). The maximum cable length per alarm zone must not exceed 1000 meters.
Terminals
The zone board is fully internal connected with the terminals of the mains supply voltage and the D-SUB board
of the external terminal card connection.
Detector zone 1
End of line
10K
EDD
Std.
detector
+ -
EDD
Std.
last detector
Detector zone 2
+ -
- End of line
EDD
Std.
10K
detector
EDD
+
Std.
last detector
Detector zone 3
J6
+ -
-
+
EDD
10K
EDD
Std.
Std.
Detector zone No. 1 to 8 Connection system for automatic fire alarm detectors (standard/EDD)
For detector zone No. 8 the operation mode >flow sensor< may be configured.
This zone input is suited to connect flow control contacts for a pipe system
monitoring (10kΩ normal/ 1kΩ activation)
FB 798955.GB0 / 05.06 37
Extinguishing Control Computer 8010 – 19-Inch
Five technical zones are available for non-automatic detectors (manual call points, push-button controls) and
inputs for connecting external dry contacts.
The detector zones are configured for connection of automatic fire detectors, and/or technical alarm modules, or
esserbus® transponders via the programming software LKDE from Version V02.00.
N J9
X16
PE
Zone board Groung fault
L1 identification
TRAFO PRIMARY
F2
X1 T1A X5
Trafo secund.
F1
T4A
To power supply- and relay card
X3
X4
Internal connection
to zone terminals
Fig. 29: Zone board series 3 (Part No. 771789) / position of the subassemblies
Terminals
The zone board is fully internal connected with the terminals of the mains supply voltage and the D-SUB board
of the external terminal card connection.
Unused alarm zones should be programmed as >unused< in the customer data or fitted with a
terminating resistor 4,7 K Ohm.
Do not connect fire detectors or technical alarm modules series 9000 / 9100.
Mixed operation of automatic fire detectors, and/or technical alarm modules or esserbus®
transponders in a common detector zone is not permitted.
38 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
X3 Plug for the ribbon cable to the power supply unit and relay board
X4 Plug-in contact for protective connection to the metal housing rear wall
Failure
Terminal, e.g. for a release system or manual contact to monitor End-of-line resistor
extinguishing
system
the extinguishing system 10kΩ normal /
1kΩ alarm
Blocking Terminal for a manual contact (e.g. shut-off cock in the pipe
network)
For mains voltage and protective earth connection, refer to the instructions in the chapter “Mains
connection and earthing“.
FB 798955.GB0 / 05.06 39
Extinguishing Control Computer 8010 – 19-Inch
Automatic Fire alarm detectors series 9200 / IQ8Quad (only 8010 - series 3)
Connection of max. 30. automatic Fire alarm detectors series 9200 (with integrated isolator in the detector base)
or 30 Fire alarm detectors IQ8Quad without alarm device (isolator integrated by factory default) per detector
zone.
Detector zone X
+
-
Only fire alarm detectors series 9000 could be connected to the detector zone inputs no. 1-8 of
the Extinguishing Control Computer 8010 - series 2.
Detector zone X
+
-
Connectable esserbus®-transponders:
40 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Detector zone X
+
-
Detector zone X
+ 4K7
FB 798955.GB0 / 05.06 41
Extinguishing Control Computer 8010 – 19-Inch
The external terminal card for he zone inputs of the Extinguishing Control Computer must be mounted on the
C-rail of the 19-inch rack.
The external terminal cards of the manufactures type „Phoenix“ or „Weidmüller“ should be used fort his purpose.
The following section describe the different terminal assignment for both types of the terminal card.
2m
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 G
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
or 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 P
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Fig. 30: External C-rail terminal for zone inputs Fig. 31: External C-rail terminal for zone inputs
(manufacturer Phoenix, type FLKM- (manufacturer Weidmüller, type RSSD 50 S
D50 SUB/S/MKKDS) UNC LPK2)
Ensure that only PIN compatible terminal cards are connected. Other types as the recommended
terminal cards in this manual must be applied only with a confirmation of the technical sales
department or customer service.
42 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Fig. 32: External C-rail terminal card for zone inputs (manufacturer Phoenix )
FB 798955.GB0 / 05.06 43
Extinguishing Control Computer 8010 – 19-Inch
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 G
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 P
Fig. 33: External C-rail terminal card for zone inputs (manufacturer Weidmüller)
44 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Only fire alarm detector series 9000/9100 may be connected to the detector zone inputs no. 1 to
8 of the Extinguishing Control Computer 8010- 19-inch series 3 (refer to the appropriate section
“zone board series 2 or series 3).
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
Special application fort he detector zones no. 7+8 (operation mode = conventional zone)
Programming
The detector zones no. 1-8 are configured with the programming software LKDE from version
V02.00.
FB 798955.GB0 / 05.06 45
Extinguishing Control Computer 8010 – 19-Inch
Direct alarming
When an alarm in this zone is triggered, the output is triggered directly without a delay. In the case of manual
call points, direct alarming is absolutely essential.
Triggering of an detector zone with an alarm verification time does not directly result in an alarm on the panel.
The triggered zone is automatically reset. If this is not successful because, for example, the cause of the
triggering of an alarm in this zone has not been dealt with, the triggering of the zone results in an alarm after the
verification delay expires. However, if the triggered zone can be reset inside the delay time, no alarm occurs.
The alarm verification delay is used to prevent incorrect alarms.
In accordance to the VDE 0833-2 guideline an alarm verification delay must not
exceed 10 seconds!
With automatic detector zones, activation of an extinguishing system may always only occur with a
2DD- coincidence or a 2ZD- coincidence.
Two-zone-coincidence (2ZD)
The triggering of an automatic detector zone with a 2ZD function does not directly result in the alarm. An
external alarm only occurs when an associated second automatic detector zone is triggered.
If no associated zone is triggered inside approximately 30 seconds after the first detector zone is triggered, the
result is “an internal alarm“. This involves all alarm devices being activated, apart from the Fire department
notifying system. The 2ZD-function is used for monitoring critical areas.
The two-zone- coincidence (2ZD) can be programmed with 4 2ZD areas (A, B, C, D) and 4 different levels:
In the case of automatic detector zones, activation of an extinguishing system may only take place
with a 2ZD coincidence or a two-detector- coincidence (2DD).
46 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Each technical zone must be terminated in the last device with a 10 kΩ End-of-line resistor.
Unused zone inputs must also be connected with a 10 kΩ End-of-line resistor.
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
- +-+ -+ -+-+
MANUAL FAILURE
10K ALARM EXTINGUISHING 10K
SYSTEM
1K
EMERGENCY
10K STOP BLOCKING 10K
1K
Fig. 35: Connecting the technical zones at the external zone terminal card (type Phoenix)
It is not possible to connect addressable automatic detectors (EDD) and conventional automatic
detectors with switch-on-control operation (SOC) to this system.
FB 798955.GB0 / 05.06 47
Extinguishing Control Computer 8010 – 19-Inch
A fire alarm is signalled if the zone is triggered before the evacuation alarm.
If the zone is triggered after the start of the evacuation alarm period, this triggering is regarded as a post-
flooding command provided that the post-flooding function is enabled. Otherwise, the triggering is evaluated as
a fire alarm.
When an extinguishing alarm is triggered, activation of the valves can be prevented during the evacuation alarm
period by continuously pressing the Stop button. The activated evacuation alarm period is not influenced.
When the Stop button is released, flooding is triggered after the evacuation alarm period. Activation of this zone
is indicated constantly on the control panel by the illuminated LED “Emergency Stop“.
In the event of a failure or if the zone is deactivated, the extinguishing outputs are not triggered.
The fault or deactivation is shown on the control panel. The trouble of the zone is latching.
Post-flooding can be initiated via this input. The valves are then activated for the duration of the programmed
post-flooding time. A condition for triggering of the extra-release-zone is that the fire alarm is still present, the
initial flooding has already been completed and the visual/audible alarming has not yet been reset.
Trouble zone
Inputs for connecting trouble alarm contacts of the extinguishing system, e.g. weighing contacts.
Triggering of the zone results in a system failure message. Zone-related relays can also be activated
Blocking zone
Input for connecting mechanical switch contacts (e.g. cutoff cocks / valves) for monitoring deluge / release flow.
Triggering of the zone results in a system fault message. Zone-related relays can also be activated
48 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
-+-+
BUZZER
10K OFF
1K
10K RESET
1K
Fig. 36: Control input MG14 and MG15 at the external zone terminal card (type Phoenix)
Reset (MG15)
Input to reset the panel with an external switch. The activation of this input performs a panel reset if the panel is
in an appropriate operation status. This input is identical to the button >panel reset< on the operation panel. To
reset the system during the activated extinguishing time is not possible.
A common fault message is displayed at the control panel if a failure occurs for this input. The fault message will
be displayed until it has been acknowledged.
It is not permitted to connect addressable automatic detectors to this input.
FB 798955.GB0 / 05.06 49
Extinguishing Control Computer 8010 – 19-Inch
The power supply of the Extinguishing Control Computer 8010 is monitored continuously of:
• Mains failure
• Battery charge
• Battery charge, current limited
• Earth fault identification (insulation)
Interal connection
to relay terminals
F2
Battery 1
F15
F3 + -
Power supply and Relay board F14 + -
Battery 2
Emergency operation
F4
F10
F1 F7
Poti
Internal connection
to relay terminals
Fig. 37: Power supply unit and relay board
Terminals
The power supply and relay board is internally wired with the 50-pole D-SUB plug to connect the external
terminal card with the relay terminals no. 1 to 11 and both terminals of the mains voltage relays no. 12+13 at the
housings rear side.
Relay outputs
The power supply unit and relay board of the Extinguishing Control Computer provides 13 relay outputs for
switching and control functions. Status functions such as faults, deactivations, common fire or others of the
possible switching conditions can be assigned to the relays, whereby an OR logic operation of the individual
functions can also be programmed. All relay outputs are protected with separate melting fuses. The activation
time and the duration of each relay is programmable with the programming software.
50 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Low-voltage Relay
Relay 1 Î FuseF16
Relay 2 Î FuseF13
Relay 3 Î FuseF12
Relay 4 Î FuseF11 monitoring
T2 A /250 V or
Relay 5 Î FuseF9 dry contact
Contact rating
Relay 6 Î FuseF8
30 V DC / 2 A
Relay 7 Î FuseF6
Relay 8 Î FuseF5
Relay 9 Î FuseF2
Relais 10 Î FuseF3 T2 A /250 V dry contact
Relay 11 Î FuseF4
F10 Fuses of the supply voltage for external units, UBext, T 3,15 A / 250 V
Fuses of the emergency power supply (battery 1 + 2)
F14, F15 Battery 1: F14, T 3,15 A / 250 V
Battery 2: F15, T 3,15 A / 250 V
Jumpers to program the operating mode for relay no. 1 to 8, selectable to
J1 to J4, J6,
monitoring or dry contact.
J8 to J13, J18
Factory setting = dry contact
Jumper to set the CPU-failure-mode function for relay 11 >Emergency operation fault<
J5 (Relay 11) Inactive = CPU-failure-mode function deactivated (factory setting)
Active = CPU-failure-mode function activated
Jumper to set the CPU-failure-mode function for relay 10 >Emergency operation fire<
J7 (Relay 10) Inactive = CPU-failure-mode function deactivated (factory setting)
Active = CPU-failure-mode function activated
Poti Potentiometer for adjusting the battery charging voltage 27.5 V DC (@ 25°C)
X47 Terminal for the ribbon cable to the zone board
X57 Plug for PE connection to the housings rear side
X11 / UBEXT Terminals for the Supply voltage for external units +24 V DC / GND
FB 798955.GB0 / 05.06 51
Extinguishing Control Computer 8010 – 19-Inch
The external terminal cards of the manufactures type „Phoenix“ or „Weidmüller“ should be used fort his purpose.
The following section describe the different terminal assignment for both types of the terminal card.
2m
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 G
26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
or 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 P
50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27
Fig. 38: External C-rail terminal for relays Fig. 39: External C-rail terminal for relays
(manufacturer Phoenix, type FLKM-D50 (manufacturer Weidmüller, type RSSD 50 B UNC
SUB/B/MKKDS) LPK2)
The relays no. 1 to 11 must not be connected to high voltages even in the dry contact mode.
Switching an alternating voltage with this relay is not permissible!
Ensure that only PIN compatible terminal cards are connected. Other types as the recommended
terminal cards in this manual must be applied only with a confirmation of the technical sales
department or customer service.
52 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
GND
GND
GND
GND
GND
GND
NO
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
NC
C
C
Relay 2
Relay 6
Relay 5
Relay 3
Relay 1
Relay 4
50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27
GND
GND
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
C
C
Relay 10
Relay 11
Relay 9
Relay 8
Relay 7
The terminals of the both mains voltage relay no. 12+13 are mounted at the rear side of the
housing
FB 798955.GB0 / 05.06 53
Extinguishing Control Computer 8010 – 19-Inch
1 Relay 1 NC 27 Relay 7 NC
2 Relay 1 NO 28 Relay 7 NO
5 Relay 2 NC 31 Relay 8 NC
6 Relay 2 NO 32 Relay 8 NO
9 Relay 3 NC 35 Relay 9 NC
10 Relay 3 NO 36 Relay 9 NO
12 Relay 3 GND 38 PE
13 PE 39 PE
14 Relay 4 NC 40 Relay 10 NC
15 Relay 4 NO 41 Relay 10 NO
18 Relay 5 NC 44 Relay 11 NO
19 Relay 5 NO 45 Relay 11 C
22 Relay 6 NC 48 UBext
23 Relay 6 NO 49 UBext
26 PE - Shielding
54 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 G
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 P
14 Relay 4 NC 39 PE
15 Relay 4 NO 40 Relay 10 NC
16 Relay 4 C/24V 41 Relay 10 NO
17 Relay 4 GND 42 Relay 10 C
18 Relay 5 NC 43 Relay 11 NC
19 Relay 5 NO 44 Relay 11 NO
20 Relay 5 C/24V 45 Relay 11 C
21 Relay 5 GND 46 GND
22 Relay 6 NC 47 GND
23 Relais 6 NO 48 UBext
24 Relay 6 C/24V 49 UBext
25 Relay 6 GND 50 12V
The terminals of the both mains voltage relay no. 12+13 are mounted at the rear side of the
housing
FB 798955.GB0 / 05.06 55
Extinguishing Control Computer 8010 – 19-Inch
Example with Relay 7 Î dry contact (Relay terminal card type Phoenix)
REL 7
T2A
dry
contact
moni-
toring
30 29 28 27
F6
NO
GND
C
NC
Fig. 40: Schematic wiring of the dry contact mode – position of jumpers
Example with Relay 7 Î positive switching/monitoring (Relay terminal card Type Phoenix)
The cable to the external connected device is monitored in this operation mode.
dry
T2A
contact
moni-
toring
F6
30 29 28 27
NO
GND
C
NC
R*
Fig. 41: Schematic wiring of the t "positive switching/monitoring“ mode – position of jumpers
56 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
In case of an associated event, the relay is activated and the voltage (24 V DC) is switched to the external unit.
In the resting state, a voltage of approximately 1 V DC to 2 V DC must be present at the relay terminals during
the monitored mode.
D1
+
RL = low-resistance load R < 300 Ohm
relay RL D1 = series diode e.g. SB 340 (notice relays current max. 2 A)
-
D1
+ L = inductive load
relay D2 L D1 = series diode e.g. SB 340 (notice relays current max. 2 A)
D2 = recovery diode e.g. 1N4007 o.ä.
-
+
RL = high-resistance load > 2 kOhm
relay R RL
R = parallel resistor 2 kOhm
-
Fig. 42: Schematic wiring positive-switching / monitoring mode
FB 798955.GB0 / 05.06 57
Extinguishing Control Computer 8010 – 19-Inch
The two relays no. 10 and 11 can be configured for the emergency operation via the appropriate jumpers.
During emergency operation, the corresponding relay mode is permanently assigned to the two relays. In a
CPU-failure-mode of the system these relays are activated.
T2A
T2A
F2
REL9
45 44 43 42 41 40 39 38 37 36 35 F3
REL10
Emergency
NO
NO
NO
NC
NC
NC
C
operation
F4
REL11
Relay 11 Relay 10 Relay 9
Fig. 43: Schematic wiring of the three dry contact relays No. 9, 10 and 11
58 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
The relay terminals are placed at the housings rear side. For each relay terminal a separate PE-connector
and a cord grip is available.
Relay 12 Relay 13
2 1 2 1
C PE
Relay 12 NO NO Relay 13
PE C
Power supply relay
230V AC
Fig. 44: Schematic wiring of the relays no. 12 and 13
For each connected power cable to the relay 12+13 a separate PE-cable must be connected to the
c relating PE-terminal on the housings rear side.
d Cord grip
Switching an external AC mains voltage with relay 12+13 requires a separate PE-connection for
each cable.
FB 798955.GB0 / 05.06 59
Extinguishing Control Computer 8010 – 19-Inch
Die Relais (AE) schalten entsprechend der fest zugeordneten Betriebsart bzw. bei den
Relais Nr.1 bis Nr.8 gemäß der programmierten Betriebsart überwacht oder potentialfrei.
Pre-alarm (VA)
The assigned relay (AE) is activated for the duration of the pre-alarm time.
Evacuation alarm (RA)
The assigned relay (AE) is activated for the duration of the evacuation alarm time.
Area valve (BV)
The assigned relay (AE) is activated at the start of the evacuation alarm until all alarms are reset.
In case of pre-controlled dry systems the alarm valve of the associated alarm valve control is activated.
Tank valve (TV)
The assigned relay (AE) of the tank valve is activated for the duration of the release and extra releasing time.
Emergency Stop valve (NSV)
The assigned relay (AE) for activating the emergency stop valve (NSV) can be activated at the start of release
for the duration of the actual release time.
Pre-control valve (VV)
The assigned relay (AE) for activating the pre-control valve (VV) is activated at the start of the release or extra
releasing time and remains active until the end of the respective extra releasing time.
Control valve (SV)
The assigned relay (AE) for activating the control valve (SV) is activated at the start of the evacuation time.
Pilot valve (PV)
This output is used in extinguishing systems with separate activation for the main and spare tanks.
The assigned relay (AE) for activating the pilot valve (PV) is activated if the spare detector zone (MG7) is not
active at the start of extinguishing. Its time behaviour is the same as the tank valve (TV). If the spare detector
zone is active, this output remains inactive.
Spare valve (RV)
This output is used in extinguishing systems with separate activation for the main and spare tanks.
The assigned relay (AE) for activating the spare valve (RV) is activated if the spare detector zone (MG7) is not
active at the start of extinguishing. Its time behaviour is the same as the tank valve (TV). Under normal
conditions, with an active spare zone, this output remains inactive.
Spraying nozzle (only for AquaSafe)
The relay activation (AE) relates to the programmed data of the AquaSafe functionality.
Switch-on/off times (spray intervals) to activate spray release systems can be implemented with this relay
output.
Switchover valve
The assigned relay (AE) is used to activate the switchover valve (UV) of an alarm valve station in
pre-controlled dry extinguishing systems. The relay is activated inversely to the area valve (BV).*
In addition to time-controlled behaviour, the relay is also activated with the following events, which could
possibly prevent extinguishing:
• A fire alarm zone in this area is defective and/or switched off.
• The area valve is defective and/or switched off
• Fault in the energy supply (grid/battery)
60 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Common trouble
The programmed relay (AE) is activated if a common trouble is recognized.
Common disconnection
The programmed relay (AE) is activated if a common deactivation is recognized.
Technical alarm
The programmed relay (AE) is activated if a technical alarm is recognized.
Revision
The programmed output is activated if the revision mode is recognized.
Preparation for service of the connected participants or the detector zones of the Extinguishing
Control Computer 8010 - series 3 with the programming software tools 8000.
Earth failure
The programmed relay (AE) is triggered when an failure, e.g. faulty insulation is recognized.
FB 798955.GB0 / 05.06 61
Extinguishing Control Computer 8010 – 19-Inch
Transponder trouble
The programmed relay (AE) is triggered when a transponder trouble is recognized between the esserbus®
communications transponder (Part No. 781335) and the fire alarm system 8000 / IQ8Control.
Hardware trouble
The program relay (AE) is triggered when a hardware trouble is recognized.
The relays activation (AE) relates to the assigned operating mode or, respectively for relays 1 to 8
relating to the selected mode >monitoring< or >dry contact<.
Zone / detectors
Select the detector zone here, as well as the associated detector, which will activate the programmed output in
the case of an event. An activation can also be triggered by up to 4 detectors combined through an OR-function.
62 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
For this purpose, the function >Emergency operation fire< (relay 10) and >Emergency operation trouble< (relay
11) must be configured with the corresponding jumpers.
In CPU-failure mode, all relays are de-energized and change the switching state except the relay >Emergency
Operation Trouble< (relay No. 11). The red display and control panel LED >Emergency operation< is
permanently activated.
Installed and operational detector zones continue to be monitored for the status >Fire<. If a fire is detected, the
relay >Emergency Operation Fire< (relay No. 10) changes the switching state.
F2
T2A
T2A
F3
REL10
Emergency
operation
F4
REL11
45 44 43 42 41 40 39
NO
NO
NC
NC
C
FB 798955.GB0 / 05.06 63
Extinguishing Control Computer 8010 – 19-Inch
The analog loop terminals are located on the external terminal card of the zones.
Up to eight Extinguish Control Computer 8010 (= 8 Extinguishing areas) could be connected to a single analog
loop of the Fire alarm system.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
- +- +
PE
UL- in
UL+ in
esserbus ®
UL- out
UL+ out
Fig. 46: Terminals to connect the analog loop wiring (type Phoenix)
To ensure a proper operation the cable shielding of the analog loop must be connected.
Use one of the PE-terminals of the detector zone terminal card to connect the cable shielding.
64 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
10 Sequence diagram
10.1 Time sequence on alarm (for Extinguishing System)
Time 1 2 2a 3 4 4a 5 6 7 8 8a 9 10
1st Alarm
2nd Alarm
HA/NF
NSG
RZ
FZ
RFZ
NFZ
VA
RA
UV*
BV
VV
TV
PV
RV
SV
NSV
DE
Time 1 2 2a 3 4 4a 5 6 7 8 8a 9 10
FB 798955.GB0 / 05.06 65
Extinguishing Control Computer 8010 – 19-Inch
VA : Pre-alarm
RA : Evacuation alarm
The evacuation time begins when a fire alarm occurs. The alarm systems for the evacuation
alarm are activated, the area valve (BV) is activated and activation of the switchover valve is
reversed (inverse activation).
The control valve (SV) is activated in systems with pneumatic extinguishing delay.
The delay times for activating the pressure relief flaps are started.
66 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Time 5 End of the release time (FZ), start of the residual releasing time (RFZ)
When the release time ends, the residual releasing time is started. All outputs/valves for the
release (tank valve, pilot or spare valve, emergency stop valve) are closed again.
Time 8 End of the extra releasing time (NFZ), start of the residual releasing time (RFZ)
When the extra releasing time ends, the residual releasing time is started. All valve
activations required for the release, e.g. for the tank, pilot, spare and emergency stop valves,
are reversed.
FB 798955.GB0 / 05.06 67
Extinguishing Control Computer 8010 – 19-Inch
Zone 1
Zone 2
2ZD
Fire
SZ
PZV
PZA
SPR
Time 1 2 3 4 5 6 7 8 9 10 11 12 13
68 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Time 2 2nd Alarm condition Ö Fire (Zone 2) / 2-zone coincidence (2ZD) is fulfilled
• The conditions for a fire alarm (2ZD = Zone 1 + Zone 2) are fulfilled.
• The first spray cycle starts when the spray time (SZ) begins.
Time 3 End of the spray time and start of the break for the first locked cycle
Time 5 End of the spray time and start of the break for a subsequent locked cycle
Time 7 A requested cycle is started because 2-zone coincidence (2ZD) is fulfilled again at this
point in time.
Start of a new spray time
Time 8 End of the spray time and start of the break for a requested cycle
Time 10 2-zone coincidence (2ZD) is fulfilled once more and thus requests a new spray cycle.
Start of spray time.
Time 11 End of the spray time and start of the break for a requested cycle
FB 798955.GB0 / 05.06 69
Extinguishing Control Computer 8010 – 19-Inch
11 Technische Daten
Main voltage : 230 V AC
Rated frequency : 50 Hz
Rated current : 0,25 A
Emergency power supply : 2 x 12 V DC / 24 Ah
Ambient conditions : class 3k5 in accordance to IEC 721-3-3:1994
Ambient temperature : -5 °C to +50 °C
Storage temperature : -10 °C to +55 °C
Protection type : I - in accordance to DIN EN 60950
Protection rating : IP 30
Housing : Sheet steel
Colour : Light grey, similar RAL 7035 / blue, similar RAL 5003
Weight : approx. 10,1 kg (without rechargeable battery)
Dimensions (W x H x D): : 482,6 x 131,6 x 403 (mm), without handle bars
VdS approval : pending
CE certificate : pending
Standard zone:
To connect external dry contacts
End-of-line resistor (4,7kΩ normal / 1kΩ alarm)
Technical zones : Monitored detector zone to connect series 9000 manual call points and/or
dry contacts
End-of-line resistor (10kΩ normal / 1kΩ alarm)
Relay contacts
Relays No. 1 to 8 : Changeover contacts, max. 30 V DC / 2 A
Operating mode dry contact or positive-switching / monitoring can be
selected via jumpers
Relays No. 9 to 11 : Changeover contacts, max. 30 V DC / 2 A
Programmable, relays 10 and 11 with selectable function
>Emergency Operation Trouble< and >Emergency Operation Fire<
Relays No. 12 and 13 : Dry contact (NO), max. 230 V AC / 2 A
suitable to switch AC Mains voltage
70 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
12 Connections
Fig. 47: Operation of the Extinguishing Control Computer in the Fire Alarm System 8000 / IQ8Control
FACP
8000 / IQ8Control
esserbus® / esserbus®-PLus
esserbus®
transponder esserbus®
transponder
Fig. 48: Extinguishing Control Computer 8010 connected to the analog loop
The Extinguishing Control Computer 8010 is only triggered through fire detectors that are directly
connected. It is not possible to trigger the LMST8010 through fire detectors connected elsewhere
within the system.
For additional information to the esserbus® communication transponder please refer to manual
(Part No. 798157).
FB 798955.GB0 / 05.06 71
Extinguishing Control Computer 8010 – 19-Inch
12.1 Multisector-Control
Installation information
• Observe the given and required specification of the diodes (power rating).
• To achieve a low voltage drop on the power cable it is recommended to install decoupling Schottky diodes
(V1) e.g. type SB340, SB540 from Vishay.
• Due to the schottky diodes an additional voltage drop of the double value of the forward voltage must be
considered. The forward voltage relates to the required current load of the triggered valve and is given in
the appropriate data sheet of the diodes.
• To protect the system against voltage peaks due to disconnected valves it is highly recommended to
connect a suited recovery diode (V2).
• The cable between valve and diode network (V1) is monitored for wire breakage. The diode-network must
be installed in a close range (max. 2m distance) to the corresponding valve.
• The cable of the valve must not be damaged by environmental effects. The diodes-network must be
installed relating to the ambient conditions in a suited enclosure with a minimum protection rating of IP54.
• Up to 8 Extinguishing Control Computer for triggering a multisector-valve may be interconnected.
• In case of the final discharging voltage of the batteries a max. voltage of 21,2 V DC is available to supply
and activate the valves (refer to section “Emergency power supply”). The valve must match this application
requirements. Furthermore a voltage drop at the decoupling diodes and on the power cable (caused by the
valve current) must be considered.
Example:
Final discharging voltage of the 8010 : 21,2 V DC
Valve current load : 750mA
Forward voltage V1 (SB340) at 750mA : 0,5V
Total resistance of the cable
(Length approx. 50m, diameter 0,8 mm) : 4Ohm
(21,2V DC– 2 x 0,5V DC) – (4 Ohm x 750 mA) = 21,2V DC– 1,0V DC – 3V = 17,2V DC
The installed valve must be suited for this voltage range (e.g. 17,2 V DC) and must ensure a the activation of
the valve.
72 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
1 2 3 8
V1 V1 V1 V1
+
Control
V2
valve
-
V1 V1 V1 V1
Diodes
1 = Schottky-diode (type SD340, SD540 or type with appropriate specification)
FB 798955.GB0 / 05.06 73
Extinguishing Control Computer 8010 – 19-Inch
Notes
74 FB 798955.GB0 / 05.06
Extinguishing Control Computer 8010 – 19-Inch
Notes
FB 798955.GB0 / 05.06 75
Novar GmbH a Honeywell Company
Dieselstraße 2, D-41469 Neuss
Internet: www.novar.de
E-Mail: info@novar.de
G
G&S BRANDSCHUTZ GMBH Westerwaldstraße 56424 Mogendorf &
S
2. Manual release
D GB Deutsch Englisch
Allgemeines General
Der Nichtautomatische Brandmelder (NAM) wird zur manuellen The Manual Call Point (MCP) is used for a manual release of a fire
Auslösung eines Brandalarmes bzw. einer Gefahrenmeldung in alarm or to release a hazard alarm in dry, non danger of explosion
trockenen, nicht explosions-gefährdeten Betriebsstätten eingesetzt. areas.
Installationsanleitung Elektronikmodule
Druck- u. Springknopfmelder (Standard) Beschaltung Druckknopf-/ Sprinknopfmelder Wiring Manual Call Point / Automatic Release MCP
Die Meldergruppe mit einem 10 kΩ Abschlußwiderstand im letzten A 10 kΩ end of line resistor has to be placed in the last Manual Call
Installation instructions Electronic Module Melder abschließen! Point in the zone!
Manual Call Point and Automatic Release MCP
Fernmeldekabel IY(St)Y n x 2 x 0,8 mm mit besonderer Kenn- Use cable IY(St)Y n x 2 x 0,8 mm with special specification or fire
(Standard)
zeichnung oder Brandmeldekabel verwenden! Mit Anschluß der detection cable! The shielding has to be conneced to terminal 9!
Kabelabschirmung werden die Signalleitungen gegen Störeinflüsse
geschützt. Kabelschirmung auf Klemme 9 verdrahten!
Wenn der Schalter -S2 mit der Schaltspannung 230 V AC Switch -S1 has to be unused if 230V AC are connected to
! beschaltet wird, darf der Schalter -S1 nicht beschaltet
werden.
! switch -S2.
Rückstellung Reset
Die Rückstellung erfolgt automatisch durch manuelle Betätigung des The reset of the call point is done by manual operation of the locking
Caradon Esser GmbH Arretierhebels. mechanism.
Dieselstraße 2 • D-41469 Neuss, Germany
Telefon +49 (0) 2137 17-1 • Telefax +49 (0) 2137 17-286 Springknopfmelder (Abb. 2) Automatic Release MCP (Abb. 2)
www.Caradon-Esser.de Gemäß den Richtlinien des Verbandes der Schaden- According to the standards of the association of German
FB 704390/02.99 VdS versicherer (VdS) ist der Einsatz von Springknopfmeldern VdS property insurance companies (VdS), it is not allowed to use
nicht zulässig. automatic release manuel call points.
Auslösung Release
Zur Auslösung ist die Schutzglasscheibe so zu zerstören, daß der To release the call point it is necessary to destroy the protection
Springknopf durch die eingebaute Feder herausgedrückt wird. Die glass so that the automatic release button can push out, powered by
Auslösung wird durch die Kontroll-LED des Melders angezeigt. an internal spring.
Rückstellung Release
Die Rückstellung des Melders erfolgt durch Schließen der Tür mit The reset of the automatic release call point is done by closing the
eingesetzter neuer Glasscheibe. door with a new glass.
Die Kombination aus einem Nichtautomatischen Druckknopf- VdS approved is the combination of these housings with one of the
Elektronikmodul und einem hier aufgeführten Gehäuse ist VdS above described Manual Call Point electronic module.
zugelassen.
Gehäusetyp: VdS-Zulassungsnummer: Type of housing: VdS approval:
ABS-Kunststoff (Sach-Nr. 704701) G 28523 ABS plastic (Part No. 704701) G 28523
Alu-Druckguß (Sach-Nr. 704801) G 27806 Die cast aluminium (Part No. 704801) G 27806
BMZ / FACP BMZ / FACP
MG - MG -
MG + MG +
Nächster Melder oder Abschlußwiderstand Nächster Melder oder Abschlußwiderstand
Next detector or end of line resistor Next detector or end of line resistor
+ +
R=10KΩ R=10KΩ
- -
PE
PE
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
X1 X1
4K7 1K 4K7 1K
LED LED
S1 S1
S2 S2
Option ! Option !
NC
Abb. 1 : Beschaltung Druckknopfmelder / Wiring Manual Call Point Abb. 2 : Beschaltung Springknopfmelder / Wiring Automatic Release Manual Call Point
DESCRIPTION ............................................................................................1
Outputs .................................................................................................1
LED .......................................................................................................2
Optical Integrity (Oi) ..............................................................................2
Communication .....................................................................................3
Data Logging / Event Monitoring...........................................................3
Integral Wiring Compartment ................................................................3
INSTALLATION............................................................................................6
Detector Positioning..............................................................................6
Detector Orientation..............................................................................6
Protection Against Moisture Damage ...................................................7
Wiring Procedure ..................................................................................7
EOL Resistors.......................................................................................8
Setting Device Network Addresses (EQP Model Only) ......................13
TROUBLESHOOTING...............................................................................14
Periodic Checkout Procedure .............................................................14
MAINTENANCE.........................................................................................15
Cleaning Procedure ............................................................................15
Oi Plate Removal ................................................................................15
Clock Battery.......................................................................................15
FEATURES................................................................................................16
SPECIFICATIONS .....................................................................................16
APPENDIX.................................................................................................20
DET-TRONICS
®
INSTRUCTIONS
IR Flame Detector
X9800
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating the
flame detection system.
ATTENTION
The X9800 includes the Automatic Optical Integrity
(oi) feature — a calibrated performance test that is
automatically performed once per minute to verify
complete detector operation capabilities. No
testing with an external test lamp is required.
DESCRIPTION
A multi-color LED on the detector faceplate indicates
The evolution continues with the new X9800 IR Flame detector status condition.
Detector. The X9800 meets the most stringent
requirements worldwide with advanced detection Microprocessor controlled heated optics increase
capabilities and immunity to extraneous sources, resistance to moisture and ice.
combined with a superior mechanical design. The
detector is equipped with both automatic and manual oi The X9800 housing is available in copper-free aluminum
test capability. The detector has Division and Zone or stainless steel, both with NEMA 4X and IP66 rating.
explosion-proof ratings and is suitable for use in indoor
and outdoor applications. OUTPUTS
2.1 2 95-8554
CAUTION stored in non-volatile memory when the event becomes
These tests require disabling of all extinguishing active, and again when the status changes. Data is
devices to avoid release resulting from a accessible using the RS-485 port or the EQP controller.
successful test.
INTEGRAL WIRING COMPARTMENT
The magnetic oi test is performed by placing a magnet
by the marked location (mag oi) on the outside of the All external wiring to the device is connected within the
detector. The manual o i test is accomplished by integral junction box. The screw terminals accept wiring
connecting the oi lead (terminal 22) to power supply from 12 to 22 AWG. The detector is furnished with four
minus via an external switch. The magnet or switch must conduit entries, with either 3/4 inch NPT or 25 mm
be held in place for a minimum of 6 seconds to threads.
complete the test. Either of these test methods activates
the calibrated IR emitter. If the resulting signal meets
the test criteria, indicating that greater than half of the SIGNAL PROCESSING OPTIONS
detection range remains, the Alarm relay changes state,
the indicating LED changes to red, and the 4-20 mA The X9800 features signal processing options. These
current output goes to 20 mA. This condition remains options determine the type of logic that the detector will
until the magnet is removed or the switch is released. If use for processing fire signals to customize the X9800 to
the alarm relay is configured for non-latching operation, the application. Two signal processing options are
it will change states and the red LED will turn to green. available for the X9800:
If the unit has latching relays, they can be reset by
removing input power (0.1 second minimum) or by – TDSA enabled
momentarily applying the magnet or manual oi switch. – Both TDSA and Quick Fire enabled (either initiates
fire alarm).
If less than half of the detection range remains, no alarm
is produced and a fault is generated. The fault
Time Domain Signal Analysis (TDSA)
indication can be reset by momentarily applying the
magnet or manual oi switch. The TDSA signal processing technique analyzes the
input signal in real time, requiring the IR signal to flicker
NOTE randomly in order to recognize it as a fire condition.
Magnetic oi is not available on the EQP model.
Using TDSA signal processing, the X9800 ignores
NOTE regularly chopped blackbody sources (occurring in
Refer to the Appendix for FM verification of Det- areas where moving conveyors and hot objects in
Tronics’ patented Optical Integrity oi™ function. proximity to one another result in a regularly chopped IR
signal), because it looks for a less uniform signal.
However, in the presence of a regularly chopped signal,
COMMUNICATION
the unit is more susceptible to false alarms due to
The X9800 is furnished with an RS-485 interface for sporadic IR that functions as a trigger when occurring in
communicating detector status and other information conjunction with the regularly chopped signal.
with external devices. The RS-485 uses MODBUS
protocol, with devices configured as slaves.
Quick Fire (High Speed)
NOTE The Quick Fire (High Speed) feature can be used in
The EQP model uses LON/SLC communication. conjunction with the TDSA signal processing method.
RS-485 communication is not available on the This method overrides TDSA requirements in the event
EQP model. of an intense signal. When Quick Fire is activated, the
detector is capable of responding to an intense fire
signal in less than 30 milliseconds (0.030 seconds).
DATA LOGGING / EVENT MONITORING
Using the Quick Fire feature in conjunction with TDSA
Data logging for event monitoring capability is also signal processing allows the detector to provide a high
provided. The detector can log up to 1500 events (up speed response to a large, non-flickering fire (such as
to 1000 general and 500 alarm events). Status in high pressure gas applications) while maintaining an
conditions such as normal, power down, general and oi ability to respond to smaller fires.
faults, pre-alarm, fire alarm, time and temperature are
recorded. Each event is time and date stamped, along
with the temperature and input voltage. Event data is
2.1 3 95-8554
GENERAL APPLICATION FALSE ALARM SOURCES
INFORMATION
The detector has been designed to ignore steady state
infrared sources that do not have a flicker frequency
RESPONSE CHARACTERISTICS
characteristic of a fire, however, it should be noted that
Response is dependent on distance, type of fuel, if these steady state infrared sources are hot enough to
temperature of the fuel, and time required for the fire to emit adequate amounts of infrared radiation in the
come to equilibrium. As with all fire tests, results must response range of the IR sensor and if this radiation
be interpreted according to an individual application. becomes interrupted from the view of the detector in a
pattern characteristic of a flickering flame, the IR sensor
See Appendix A for fire test results. can respond.
ARTIFICIAL LIGHTING
The X9800 should not be located within 3 feet of
artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
EMI/RFI INTERFERENCE
The X9800 is resistant to interference by EMI and RFI,
and is EMC Directive compliant and CE marked. It will
not respond to a 5 watt walkie-talkie at distances
greater than 1 foot.
NON-CARBON FIRES
The response of the X9800 is limited to carbonaceous
fuels. It should not be used to detect fires from fuels
that do not contain carbon, such as hydrogen, sulfur
and burning metals.
2.1 4 95-8554
FACTORS INHIBITING DETECTOR RESPONSE IMPORTANT SAFETY NOTES
Windows WARNING
Do not open the detector assembly in a hazardous
Glass and Plexiglas windows significantly attenuate area when power is applied. The detector contains
radiation and must not be located between the detector limited serviceable components and should never
and a potential flame source. If the window cannot be be opened. Doing so could disturb critical optical
eliminated or the detector location changed, contact alignment and calibration parameters, possibly
Detector Electronics for recommendations regarding causing serious damage. This type of damage
could be undetected and could result in failure to
window materials that will not attenuate radiation.
see a fire and/or false alarm.
Obstructions CAUTION
The wiring procedures in this manual are intended
Radiation must be able to reach the detector in order for to ensure proper functioning of the device under
it to respond. Care must be taken to keep physical normal conditions. However, because of the many
obstructions out of the line of view of the detector. variations in wiring codes and regulations, total
compliance to these ordinances cannot be
Smoke guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
Smoke will absorb radiation. If accumulations of dense doubt, consult the authority having jurisdiction
smoke can be expected to precede the presence of a before wiring the system. Installation must be
flame, then detectors that are used in enclosed areas done by a properly trained person.
should be mounted on the wall approximately 3 feet (1
meter) from the ceiling where the accumulation of CAUTION
smoke is reduced. To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
Detector Viewing Windows performing detection system tests or maintenance.
ATTENTION
It is important to keep the detector viewing windows as
Remove the protective cap from the front of the
free of contaminants as possible in order to maintain
detector before activating the system.
maximum sensitivity. Commonly encountered
substances that can significantly attenuate IR radiation ATTENTION
include, but are certainly not limited to, the following: Observe precautions for handling electrostatic
Dust and dirt buildup sensitive devices.
Paint overspray
Water and ice.
2.1 5 95-8554
INSTALLATION
NOTE
CENTER AXIS
The recommended lubricant for threads and O- OF DETECTOR
FIELD OF VIEW
rings is a silicone free grease (part number
005003-001) available from Detector Electronics.
Under no circumstances should a lubricant
containing silicone be used.
INCORRECT
DETECTOR POSITIONING
Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should also be taken into consideration:
CENTER AXIS
• Identify all high risk fire ignition sources. OF DETECTOR
FIELD OF VIEW
IR VIEWING WINDOW
DETECTOR STATUS
A2174 INDICATOR
2.1 6 95-8554
PROTECTION AGAINST MOISTURE DAMAGE WIRING PROCEDURE
It is important to take proper precautions during
Wire Size and Type
installation to ensure that moisture will not come in
contact with the electrical connections of the system. The system should be wired using a 12 to 22 gauge (2.5
The integrity of the system regarding moisture to 0.3 mm2) cable. The wire size selected should be
protection must be maintained for proper operation and based on the number of detectors connected, the
is the responsibility of the installer. supply voltage and the cable length. A minimum input
voltage of 18 vdc must be present at the X9800.
If conduit is used, drains must be installed at water
collection points to automatically drain accumulated NOTE
moisture. Conduit breathers should be installed at Refer to “Power Consumption” in the
upper locations to provide ventilation and allow water “Specifications” section of this manual.
vapor to escape. At least one breather should be used
with each drain. The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using
Conduit raceways should be inclined so that water will cables with shields, terminate the shields as shown in
flow to low points for drainage and will not collect inside Figures 7 through 12, and Figure 14. Consult the
enclosures or on conduit seals. If this is not possible, factory if not using shielded cable.
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the In applications where the wiring cable is installed in
detector with a conduit drain at the lowest point of the conduit, the conduit must not be used for wiring to other
loop. electrical equipment.
3.0
(7.6)
4.0
(10.2)
10.3
(26.2)
A2069
2.1 7 95-8554
Relay and 4-20 mA Output Models EOL RESISTORS (Not Used with EQP Model)
Follow the instructions below to install the X9800. To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
1. Make field connections following local ordinances by EOL resistors, observe the following guidelines when
and guidelines in this manual. Refer to Figures 4 installing the resistors.
through 12.
1. Required EOL resistor power rating must be 5 watts
2. Check all field wiring to be sure that the proper minimum.
connections have been made.
NOTE
IMPORTANT EOL resistors must be ceramic, wirewound type,
Do not test any wiring connected to the detector rated 5 watts minimum, with actual power
with a meg-ohmmeter. Disconnect wiring at the dissipation not to exceed 2.5 watts.
detector before checking system wiring for
continuity. 2. Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
3. Make the final sighting adjustments and ensure that
the mounting bracket hardware is tight. 3. Bend the leads and install the EOL resistor as
shown in Figure 6.
NOTE
All cable entry devices and blanking elements shall
be certified to “E-generation” or “ATEX” standards,
in type of explosion protection increased safety “e”
or flameproof enclosure “d” (as applicable),
suitable for the conditions of use and correctly
installed. They shall maintain the degree of
ingress protection IP66 for the apparatus. Unused
aperatures shall be closed with suitable blanking
elements.
2.1 8 95-8554
X9800 DETECTOR
FIRE ALARM PANEL
9 4-20 mA + 19 4-20 mA – SPARE 29
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
X9800 DETECTOR
FIRE ALARM PANEL
9 4-20 mA + 19 4-20 mA – SPARE 29
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
2.1 9 95-8554
X9800 DETECTOR X9800 DETECTOR
PLC PLC
– 7 17 27 – 7 17 27
4 TO 20 MA 6 16 26 4 TO 20 MA 6 16 26
5 15 25 + 5 15 25
+
24 VDC 24 VDC
4 14 24 4 14 24
– –
3 13 23 3 13 23
1 24 VDC – 11 21 1 24 VDC – 11 21
Oi TEST1 Oi TEST1
Figure 9—X9800 Detector Wired for Non-Isolated 4 to 20 ma Figure 10—X9800 Detector Wired for Non-Isolated 4 to 20 ma
Current Output (Sourcing) Current Output (Sinking)
24 VDC 24 VDC
X9800 DETECTOR
– + + – X9800 DETECTOR
PLC PLC
– 7 17 27 – 7 17 27
4 TO 20 MA 6 16 26 4 TO 20 MA 6 16 26
+ 5 15 25 5 15 25
+
24 VDC 24 VDC
4 14 24 4 14 24
– –
3 13 23 3 13 23
1 24 VDC – 11 21 1 24 VDC – 11 21
Oi TEST1 Oi TEST1
Figure 11—X9800 Detector Wired for Isolated 4 to 20 ma Figure 12—X9800 Detector Wired for Isolated 4 to 20 ma
Current Output (Sourcing) Current Output (Sinking)
2.1 10 95-8554
EQP Model 5. Check all field wiring to be sure that the proper
connections have been made.
1. Connect external wires to the appropriate
terminals inside the device junction box. (See
6. Replace the device cover.
Figure 13 for terminal identification.)
7. Make the final sighting adjustments and ensure that
2. Connect the shield of the power cable to “earth
the mounting bracket hardware is tight.
ground” at the power source.
NOTE
3. Connect shields for the LON cable as indicated.
Refer to the Eagle Quantum Premier system
See Figure 14.
manual (number 95-8533) for information
regarding power and network communication
NOTE
cable requirements.
DO NOT ground any shields at the detector
housing.
COM 1 A 5 15 COM 2 A
COM 1 B 4 14 COM 2 B
24 VDC + 2 12 24 VDC +
24 VDC – 1 11 24 VDC –
A2089
2.1 11 95-8554
2.1
+ +
– –
– POWER –
+ DISTRIBUTION +
+
–
+ – + –
CONTROLLER EQP3700DCIO EQP2100PSM EQPX9800 EQPX9800 EQPX9800 EQPX9800
P1 P1
6 SHIELD 3 4 SHIELD 9 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3
52 B 49 5 B 2 11 B 3 14 B 4 14 B 4 14 B 4 14 B 4
53 A 50 4 A 1 10 A 2 15 A 5 15 A 5 15 A 5 15 A 5
P6
BUS BAR P3
C 45 A2210
C 1 N
FAULT NO 46 P4 P3
B 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3
B IN–/OUT+ B + –
CH 1
CH 5
GND 5 57 GND GND 54 24 VDC 4 H
C COMMON C SUPPLY
RXD 2 58 RxD B 55
TXD 3 59 TxD A 56
12
A + SUPPLY A
DB-9 H N
P2 P3
CONNECTION B IN–/OUT+ B AC LINE
CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1– 5– 14 C COMMON C
+ –
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2– 6– 16 BATTERY
B IN–/OUT+ B
CH 3
CH 7
9 3+ 7+ 17
10 3– 7– 18 C COMMON C
11 4+ 8+ 19
DIGITAL INPUTS
A + SUPPLY A
12 4– 8– 20
B IN–/OUT+ B
CH 4
CH 8
P4 P5
21 C C 33 C COMMON C
22 NO NO 34
RELAY 5
RELAY 1
23 NC NC 35
24 C C 36
25 NO NO 37
RELAY 6
RELAY 2
26 NC NC 38
27 C C 39
28 NO NO 40
RELAY 7
RELAY 3
29 NC NC 41
30 C C 42
31 NO NO 43
RELAY 4
RELAY 8
32 NC NC 44
95-8554
ADDRESS SWITCHES SENSOR MODULE
REMOVED FROM HOUSING
A2191
WARNING 1 2 3 4 5 6 7 8
BINARY
The network address switches are located within VALUE 1 2 4 8 16 32 64 128
the detector housing. Disassembly of the
detector head that contains powered electrical NODE ADDRESS EQUALS THE ADDED VALUE OPEN = OFF
circuits is required to gain access to the network OF ALL CLOSED ROCKER SWITCHES CLOSED = ON
A2190
2.1 13 95-8554
STARTUP PROCEDURE TROUBLESHOOTING
When installation of the equipment is complete, perform WARNING
the “Fire Alarm Test” below. The sensor module (“front” half of the detector)
contains no user serviceable components and
Allow 20 to 30 minutes for the detector’s heated optics should never be opened. The terminal
to reach equilibrium. compartment is the only part of the enclosure
that should be opened by the user in the field.
FIRE ALARM TEST
1. Disable any extinguishing equipment that is
connected to the unit.
1. Disable any extinguishing equipment that is
connected to the system. 2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
2. Apply input power to the system. section for complete information regarding cleaning
of the detector viewing windows.)
3. Initiate an oi test. (See “Magnetic oi / Manual oi”
under Optical Integrity in the Description section of 3. Check input power to the unit.
this manual.
4. If the fire system has a logging function, check the
4. Repeat this test for all detectors in the system. If a fire panel log for output status information. See
unit fails the test, refer to the “Troubleshooting” Table 3 for information regarding 4 to 20 mA output.
section.
5. Turn off the input power to the detector and check
5. Verify that all detectors in the system are properly all wiring for continuity. Important: Disconnect
aimed at the area to be protected. (The Det-Tronics wiring at the detector before checking system
Q1201C Laser Aimer is recommended for this wiring for continuity.
purpose.)
6. If all wiring checks out and cleaning of the o i
6. Enable extinguishing equipment when the test is plate/window did not correct the fault condition,
complete. check for high levels of background IR radiation by
covering the detector with the factory supplied
cover or aluminum foil. If the fault condition clears,
extreme background IR radiation is present. Re-
adjust the view of the detector away from the IR
source or relocate the detector.
2.1 14 95-8554
MAINTENANCE oi PLATE REMOVAL
1. Loosen the two captive screws, then grasp the oi
plate by the visor and remove it from the detector.
IMPORTANT
See Figure 17.
Periodic flamepath inspections are not
recommended, since the product is not intended
2. Thoroughly clean the oi plate reflective surfaces,
to be serviced and provides proper ingress
holding it by its edges to avoid leaving fingerprints
protection to eliminate potential deterioration of
on the inside reflective surface.
the flamepaths.
3. Re-install the oi plate. Ensure that the plate is flat
WARNING
on the detector surface. Tighten the o i plate
The sensor module (“front” half of the detector)
screws securely (40 oz/inches).
contains no user serviceable components and
should never be opened. The terminal
NOTE
compartment is the only part of the enclosure
If the oi plate is removed, be sure to install the
that should be opened by the user in the field.
original oi plate. oi plates are not interchangeable
and should not be mixed with oi plates from other
To maintain maximum sensitivity and false alarm
detectors. If corrosive contaminants in the
resistance, the viewing windows of the X9800 must be
atmosphere cause the o i plate surface to
kept relatively clean. Refer to the procedure below for
deteriorate to the extent that it is no longer possible
cleaning instructions.
to restore it to its original condition, it must be
replaced. Consult factory for oi plate replacement
CLEANING PROCEDURE procedure.
NOTE
Remove input power when cleaning the detector
windows. The rubbing motion on the surface of the
windows during cleaning can create static
electricity that could result in unwanted output
activation. GRASP VISOR AND
REMOVE Oi PLATE
4. Re-install the o i plate following the procedure Figure 17—Oi Plate Removal
described below.
2.1 15 95-8554
FEATURES SPECIFICATIONS
• Responds to a fire in the presence of modulated OPERATING VOLTAGE—
blackbody radiation (i.e. heaters, ovens, turbines) 24 volts dc nominal (18 vdc minimum, 30 vdc
without false alarm. maximum).
• High speed capability — 30 milliseconds.
POWER CONSUMPTION—
• Built-in data logging / event monitoring, up to 1500 Without heater: 2.1 watts at 24 vdc nominal;
events (up to 1000 general, 500 alarms). 3.5 watts at 24 vdc in alarm.
2.2 watts at 30 vdc nominal;
• Microprocessor controlled heated optics for increased
4.0 watts at 30 vdc in alarm.
resistance to moisture and ice.
Heater only: 8 watts maximum.
• Automatic, manual or magnetic optical integrity (oi) Total power: 16.5 watts at 30 vdc with EOL resistor
testing. installed and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated 5
• Easily replaceable oi plate.
watts minimum, with actual power dissipation not to
• Fire, fault and auxiliary relays standard. exceed 2.5 watts.
• 4 to 20 mA isolated output (optional).
POWER UP TIME—
• Eagle Quantum Premier LON/SLC output (optional). Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
• Tricolor LED indicates normal operation, fire and fault
conditions.
OUTPUT RELAYS—
• Operates under adverse weather conditions. Fire Alarm relay, Form C, 5 amperes at 30 vdc:
The Fire Alarm relay has redundant terminals and
• Mounting swivel allows easy sighting.
normally open / normally closed contacts, normally
• Integral wiring compartment for ease of installation. de-energized operation, and latching or non-
latching operation.
• Explosion-proof/flame-proof detector housing. Meets
FM, CSA, CENELEC (ATEX Directive Compliant) and
Fault relay, Form A, 5 amperes at 30 vdc:
CE certification requirements.
The Fault relay has redundant terminals and
• Class A wiring per NFPA-72. normally open contacts, normally energized
operation, and latching or non-latching operation.
• Meets NFPA-33 response requirement for under 0.5
second (available when model selected).
Auxiliary relay, Form C, 5 amperes at 30 vdc:
• 3 year warranty. The auxiliary relay has normally open / normally
closed contacts, normally energized or de-
• Advanced signal processing (ARC).
energized operation, and latching or non-latching
• RFI and EMC Directive Compliant. operation.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
2.1 16 95-8554
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
RESPONSE TIME—
INCIDENCE DECREASES.
32 inch methane plume: < 10 seconds.
VIEWING ANGLE 1 foot x 1 foot n-Heptane: < 15 seconds.
15°
0°
15°
(See Appendix for details.)
100
60
VIBRATION—
DETECTION 50 Conformance per FM 3260: 2000, MIL-STD 810C (Curve
DISTANCE
(PERCENT) 40
AW), DNV Note 2.4 (Class B).
30
DIMENSIONS—
20
See Figure 19.
10
WIRING—
A1288 12 AWG (2.5 mm 2 ) to 22 AWG (0.3 mm 2 ) shielded
cable is recommended.
Figure 18—Detector Cone of Vision
Important: 18 vdc minimum must be available at the
detector. For ambient temperatures below
–10°C and above +60°C use field wiring
suitable for both minimum and maximum
ambient temperature.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
THREAD SIZE—
Storage: –67°F to +185°F (–55°C to +85°C).
Conduit connection: 3/4 inch NPT or M25.
Hazardous location ratings from -55°C to +75°C
Conduit seal not required.
available on flameproof model.
SHIPPING WEIGHT (Approximate)—
HUMIDITY RANGE—
Aluminum: 6 pounds (2.7 kilograms).
0 to 95% relative humidity, can withstand 100%
Stainless Steel: 10 pounds (4.5 kilograms).
condensing humidity for short periods of time.
Swivel Mount: 14 pounds (6.4 kilograms).
CONE OF VISION—
WARRANTY PERIOD—
The detector has a 90° cone of vision (horizontal) with
3 years.
the highest sensitivity lying along the central axis. See
Figure 18.
4.7
(11.9)
9.7 4.8
(24.6) (12.2)
A2142
2.1 17 95-8554
CERTIFICATION— REPLACEMENT PARTS
Class I, Div. 1, Groups B, C and D;
Class II, Div. 1, Groups E, F, and G; The detector is not designed to be repaired in the field.
Class I, Div. 2, Groups A, B, C and D (T3); If a problem should develop, refer to the
FM ®
APPROVED
Class II, Div. 2, Groups F and G (T3); Troubleshooting section. If it is determined that the
Class III. problem is caused by an electronic defect, the device
Enclosure NEMA/Type 4X. must be returned to the factory for repair.
Increased Safety Model
0539 II 2 GD
EEx de IIC T5–T6 T86°C DEVICE REPAIR AND RETURN
DEMKO 02 ATEX 132195
T6 (Tamb = –55°C to +60°C). Prior to returning devices, contact the nearest local
T5 (Tamb = –55°C to +75°C). Detector Electronics office so that a Service Order
IP66. number can be assigned. A written statement
describing the malfunction must accompany the
Flameproof Model
returned device or component to expedite finding the
0539 II 2 GD
cause of the failure.
EEx d IIC T5–T6 T86°C
DEMKO 02 ATEX 132195
Pack the unit properly. Use sufficient packing material
T6 (Tamb = –55°C to +60°C).
in addition to an antistatic bag as protection from
T5 (Tamb = –55°C to +75°C).
electrostatic discharge.
IP66.
Return all equipment transportation prepaid to the
Conforms with: Low Voltage Directive (73/23/EEC).
factory in Minneapolis.
Electromagnetic Compatibility Directive
(89/336/EEC).
NOTE
Explosive Atmosphere Directive
It is highly recommended that a complete spare be
(94/9/EC).
kept on hand for field replacement to ensure
Construction Product Directive.
continuous protection.
NOTE
Operational performance verified from -40°C to
+75°C.
NOTE
Refer to “EOL Resistors” section for installation
details. All cable entry devices and blanking
elements shall be certified to “E-generation” or
“ATEX” standards, in type of explosion protection
increased safety “e” or flameproof enclosure “d”
(as applicable), suitable for the conditions of use
and correctly installed. They shall maintain the
degree of ingress protection IP66 for the
apparatus. Unused aperatures shall be closed
with suitable blanking elements.
2.1 18 95-8554
ORDERING INFORMATION For assistance in ordering a system to fit your
application, please contact:
When ordering, please specify:
Detector Electronics Corporation
X9800 IR Flame Detector 6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Refer to the X9800 OS Matrix below for details. Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
ACCESSORIES
E-mail: detronics@detronics.com
Q9033B Swivel Mount Assembly is required for
mounting the detector.
Q1116A Air Shield for use in dirty environments. or contact your local sales office, which can be found
on the Det-Tronics web site:
Q1201C Laser Aimer is recommended for verifying
detector aiming. www.detronics.com
Weather Shield is recommended for outdoor
environments.
REPLACEMENT PARTS
X9800 OS Matrix
MODEL DESCRIPTION
X9800 Single Frequency IR Flame Detector
TYPE MATERIAL
A Aluminum
S Stainless Steel (316)
TYPE THREAD TYPE
4M 4 PORT, METRIC M25
4N 4 PORT, 3/4" NPT
TYPE OUTPUTS
11 Relay
13 Relay and 4-20 mA
14 Eagle Quantum Premier
15 Relay and Pulse
16 Addressable Module Only (Third Party Type)
TYPE APPROVAL AGENCY
W FM/CSA/CENELEC/CE
TYPE CLASSIFICATION**
1 Division/Zone EEx de
2 Division/Zone EEx d
2.1 19 95-8554
APPENDIX
FM Approvals Description and Performance Report
• Explosion-proof for Class I, Div. 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G Hazardous (Classified) Locations per FM 3615.
• Explosion-proof for Class I, Div. 2, Groups A, B, C and D (T3) Hazardous (Classified) Locations per FM 3611.
• Explosion-proof for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a loss of half of its detection range, an alarm signal is not generated.
2.1 20 95-8554
FM Approvals Description and Performance Report – Continued
RESPONSE CHARACTERISTICS:
High Sensitivity
Distance Typical Response Time
Fuel Size (feet) (seconds)* TDSA Quick Fire
n-Heptane 1 x 1 foot 50 8 On Off
Methane 32 inch plume 35 3 On Off
Pyrodex 40 grams 10 0.1 On On
Black Powder 40 grams 10 0.04 On On
n-Heptane 1 x 1 foot 50 6 On On
Low Sensitivity
Distance Typical Response Time
Fuel Size (feet) (seconds)* TDSA Quick Fire
n-Heptane 1 x 1 foot 15 8 On Off
False Alarm Source Distance Fire Source Distance Typical Response Time
(feet) (feet) (seconds)*
2.1 21 95-8554
FM Approvals Description and Performance Report – Continued
FIELD OF VIEW:
Fuel Size Distance Horizontal Typical Horiz. Response Time Vertical Typical Vert. Response Time
(feet) (degrees) (seconds)* (degrees) (seconds)*
Fuel Size Distance Horizontal Typical Horiz. Response Time Vertical Typical Vert. Response Time
(feet) (degrees) (seconds)* (degrees) (seconds)*
2.1 22 95-8554
Printed in USA
21 PIN 11 21 PIN 11
CEAG Apparatebau Hundsbach Maßbild/Dimensions drawing/
GmbH & Co KG
Bußmatten 10 - 12 70,4 9,7
77815 Bühl/Baden
Phone (+49) 07223 9909-117
Fax (+49) 07223 9909-140 EEx
Internet http//www.apparatebau-hundsbach.de
e-mail Info@apparatebau-hundsbach.de
68,2
23 PA 13 23 PA 13
Applikationen Sicherheitsbarrieren/ Application for safety barriers
DC-Barriere negativ/DC-barrier negative DC-Doppel mit Auswertezweig/ DC-double with return AC-Doppel/ AC double
ULast=12 V
ULast=12 V
I = 4 ... 20 mA I = 4 ... 20 mA
2 R = 250 W 2 R = 250 W
3 stabilisierte 24 V 3 stabilized 24 V
Neben der Funktionsbetrachtung ist die In addition to the function check safety
Sicherheitsbetrachtung für den Nach- consideration have to prove that the
weis der Eigensicherheit durchzuführen hole loop is intrinsically safe (see EN
(siehe EN 50039). 50039).
FB 798139/11.2001
Contents Page 2 Reset module
1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Reset module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1 Function of jumper X3 . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Function of jumper X4 . . . . . . . . . . . . . . . . . . . . . . 5
X1 X2
1
+UL
NC/FAULT
3 Installation and wiring examples . . . . . . . . . . . . . . . . . . . 6
ALARM
2
2
-UL
3.1 Linear smoke detection system RAS 51 B (761340) . . . . . . 6 X4 X3
3
3
+12V
3.2 Fireray 1401 . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 + C* +24V K1
4
RESET
5
RESET
5
3.3 Line-type smoke detector Beam Master 3 (761325) . . . . . 10 X8 X7 X6 X5
0V
0V
6
6
3.4 UV/IR flame detector (761353) . . . . . . . . . . . . . . . . 11
3.5 IR flame detector (761354) . . . . . . . . . . . . . . . . . . 12
3.6 UV flame detector (761355) . . . . . . . . . . . . . . . . . . 13
3.7 Line-type heat detector ADW 53 (761240) . . . . . . . . . . 14
Terminal 1+2 Connection to detector zone (G+/G-) of the FACP
3.8 Alarmline temperature sensor . . . . . . . . . . . . . . . . . 15
X1 +10.5 V to +28 V from ext. power supply unit or
4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Terminal 3+4
DC/DC converter
4.1 Summary of jumpers . . . . . . . . . . . . . . . . . . . . . 17 Terminal 5+6 0 Vext. from ext. voltage supply
Terminal 1+3 NC or fault contact of detector
1 General X2
Terminal 2+3 Alarm contact of detector
Terminal 4+5 Reset detector (see Section 2.1/2.2)
The reset module permits the connection and resetting of other makes of fire
detectors in conjunction with the essertronic® 3008. The reset module trans- Terminal 6 0Vext.
fers the detector zone ON/OFF status to the supply line of the fire detector that X3 Jumper for non-Esser detector reset (see Section 2.1)
is connected. Jumpers can be used for adapting the reset time from 0.15 to X4 Jumper for non-Esser detector reset (see Section 2.2)
11.7 seconds - for resetting the fire detector - to the particular detector type.
This way, it is possible in an alarm to reset fire detectors using the wiring of a X5, X6,
Jumpers for adjusting the reset times
detector zone independently of the essertronic® 3008 (100 ms) control panel X7, X8
reset, e.g., from a fire department operating panel. 4700 µF/35V capacitor, should be fitted in conjunction with
C* high-resistance ext. voltage supply (DC/DC converter and/or
Part no. 781333 Reset module kit inc. installation material for fitting non-Esser detectors with high starting current)
in (non-Esser) detectors.
Part no. 781332 Reset module in modular housing for installation on
C mounting bar.
1
+UL
NC/FAULT
3 Installation and wiring examples . . . . . . . . . . . . . . . . . . . 6
ALARM
2
2
-UL
3.1 Linear smoke detection system RAS 51 B (761340) . . . . . . 6 X4 X3
3
3
+12V
3.2 Fireray 1401 . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 + C* +24V K1
4
RESET
5
RESET
5
3.3 Line-type smoke detector Beam Master 3 (761325) . . . . . 10 X8 X7 X6 X5
0V
0V
6
6
3.4 UV/IR flame detector (761353) . . . . . . . . . . . . . . . . 11
3.5 IR flame detector (761354) . . . . . . . . . . . . . . . . . . 12
3.6 UV flame detector (761355) . . . . . . . . . . . . . . . . . . 13
3.7 Line-type heat detector ADW 53 (761240) . . . . . . . . . . 14
Terminal 1+2 Connection to detector zone (G+/G-) of the FACP
3.8 Alarmline temperature sensor . . . . . . . . . . . . . . . . . 15
X1 +10.5 V to +28 V from ext. power supply unit or
4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Terminal 3+4
DC/DC converter
4.1 Summary of jumpers . . . . . . . . . . . . . . . . . . . . . 17 Terminal 5+6 0 Vext. from ext. voltage supply
Terminal 1+3 NC or fault contact of detector
1 General X2
Terminal 2+3 Alarm contact of detector
Terminal 4+5 Reset detector (see Section 2.1/2.2)
The reset module permits the connection and resetting of other makes of fire
detectors in conjunction with the essertronic® 3008. The reset module trans- Terminal 6 0Vext.
fers the detector zone ON/OFF status to the supply line of the fire detector that X3 Jumper for non-Esser detector reset (see Section 2.1)
is connected. Jumpers can be used for adapting the reset time from 0.15 to X4 Jumper for non-Esser detector reset (see Section 2.2)
11.7 seconds - for resetting the fire detector - to the particular detector type.
This way, it is possible in an alarm to reset fire detectors using the wiring of a X5, X6,
Jumpers for adjusting the reset times
detector zone independently of the essertronic® 3008 (100 ms) control panel X7, X8
reset, e.g., from a fire department operating panel. 4700 µF/35V capacitor, should be fitted in conjunction with
C* high-resistance ext. voltage supply (DC/DC converter and/or
Part no. 781333 Reset module kit inc. installation material for fitting non-Esser detectors with high starting current)
in (non-Esser) detectors.
Part no. 781332 Reset module in modular housing for installation on
C mounting bar.
Jumper for non-Esser detector capable of being reset by briefly interrupting Jumper for non-Esser detector capable of being reset by a 0 V reset
the supply voltage (e.g., RAS 51 B) pulse (e.g., Fireray 1400/1401)
fitted fitted
X2 X2
1
1
NC/FAULT
FACP
NC/FAULT
FACP
ALARM
ALARM
2
2
3008 3008 X3
3
X3
3
X4 X4
normal operation normal operation potential-free
4
+24 V
4
potential-free
+24 V
5
5
K1 K1
6
6
0Vext. 0Vext.
X6 X5 X6 X5
fitted fitted
X2 X2
1
1
NC/FAULT
FACP
NC/FAULT
FACP
ALARM
ALARM
2
2
3008 3008 X3
X3
3
3
X4 X4
reset +24 V
reset 0Vext.
4
4
for the duration
potential-free potential-free
5
5
K1 K1 of reset time
for the duration
6
0Vext.
6
0Vext.
of reset time
X6 X5 X6 X5
Jumper for non-Esser detector capable of being reset by briefly interrupting Jumper for non-Esser detector capable of being reset by a 0 V reset
the supply voltage (e.g., RAS 51 B) pulse (e.g., Fireray 1400/1401)
fitted fitted
X2 X2
1
1
NC/FAULT
FACP
NC/FAULT
FACP
ALARM
ALARM
2
2
3008 3008 X3
3
X3
3
X4 X4
normal operation normal operation potential-free
4
+24 V
4
potential-free
+24 V
5
5
K1 K1
6
6
0Vext. 0Vext.
X6 X5 X6 X5
fitted fitted
X2 X2
1
1
NC/FAULT
FACP
NC/FAULT
FACP
ALARM
ALARM
2
2
3008 3008 X3
X3
3
3
X4 X4
reset +24 V
reset 0Vext.
4
4
for the duration
potential-free potential-free
5
5
K1 K1 of reset time
for the duration
6
0Vext.
6
0Vext.
of reset time
X6 X5 X6 X5
0V Gx+
6 5 4 3 2 1
X1
X8
X7
KL 2 KL 1
10
X6
X5
fit jumper X3
X4
fit spacers! X3
K1
X2
X1 X2
6 5 4 3 2 1
• Secure reset module to the fixing bracket using the nuts, bolts and spacers
provided.
10 9 8 7 6 5 4 3 2 1
• Bend the jumper removal tabs to the side in order to facilitate installation. terminal strip 2 terminal
strip 1
• Fasten fixing bracket on the circuit board of the RAS 51 B. Linear smoke detection system
RAS 51 B
0V Gx+
6 5 4 3 2 1
X1
X8
X7
KL 2 KL 1
10
X6
X5
fit jumper X3
X4
fit spacers! X3
K1
X2
X1 X2
6 5 4 3 2 1
• Secure reset module to the fixing bracket using the nuts, bolts and spacers
provided.
10 9 8 7 6 5 4 3 2 1
• Bend the jumper removal tabs to the side in order to facilitate installation. terminal strip 2 terminal
strip 1
• Fasten fixing bracket on the circuit board of the RAS 51 B. Linear smoke detection system
RAS 51 B
The reset module (781333) is fitted in the housing of the Fireray detector using Fire alarm control panel
3008
the spacers provided (M3/40mm long). External power
supply unit or
DC/DC converter
Gx-
Fireray 1401 +24V
6 5 4 3 2 1
0V Gx+
X1
reset module
X8 fit jumper X4
X7
6 5 4 3 2 1 fit spacers!
X6
X5
X1
X4
X3
X8
X7 K1
X2
X6
X5
X4 6 5 4 3 2 1
X3
K1
X2
reset switch OFF
6 5 4 3 2 1
13
RESET
Reset I/P
ON OFF
LED 2 RESET
RESET
ON OFF
RESET terminal card
Fireray 1401
terminal card
Fireray 1401
1 8
+ - NO COM NC COM NC NO
21V-31V ALARM FAULT
1 8
+ - NO COM NC COM NC NO
21V-31V ALARM FAULT
The reset module (781333) is fitted in the housing of the Fireray detector using Fire alarm control panel
3008
the spacers provided (M3/40mm long). External power
supply unit or
DC/DC converter
Gx-
Fireray 1401 +24V
6 5 4 3 2 1
0V Gx+
X1
reset module
X8 fit jumper X4
X7
6 5 4 3 2 1 fit spacers!
X6
X5
X1
X4
X3
X8
X7 K1
X2
X6
X5
X4 6 5 4 3 2 1
X3
K1
X2
reset switch OFF
6 5 4 3 2 1
13
RESET
Reset I/P
ON OFF
LED 2 RESET
RESET
ON OFF
RESET terminal card
Fireray 1401
terminal card
Fireray 1401
1 8
+ - NO COM NC COM NC NO
21V-31V ALARM FAULT
1 8
+ - NO COM NC COM NC NO
21V-31V ALARM FAULT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
1K
10K
H - H + HA
* jumper
RX filter
is installed
in receiver! UV/IR flame detector
1 2 3 4 5 6 7 761353
+
+ 1 1
- -
2 2
external voltage supplyor power
R ALARM Oi Oi
FACP 3008
supply unit FACP 3008 3 3
fit jumper X3 1K
NO 4 4 NO
0V
G-
X2 X1 +12V
FIRE C 5 5 C FIRE
5 6
5 6
(DC) G+
R END NC 6 6 NC
4
4
X3 FAULT
G-
C C
2
+24V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
1K
10K
H - H + HA
* jumper
RX filter
is installed
in receiver! UV/IR flame detector
1 2 3 4 5 6 7 761353
+
+ 1 1
- -
2 2
external voltage supplyor power
R ALARM Oi Oi
FACP 3008
supply unit FACP 3008 3 3
fit jumper X3 1K
NO 4 4 NO
0V
G-
X2 X1 +12V
FIRE C 5 5 C FIRE
5 6
5 6
(DC) G+
R END NC 6 6 NC
4
4
X3 FAULT
G-
C C
2
+24V
+ Vi Oi
UV flame detector
- Vi SPARE 761355
R END
SPARE R ALARM
FACP 3008 FIRE
NO CURRENT
FAULT
NO
CONTACTS SIGNALS CONTACTS
10K NO F F NO 1K 1 2 3 4 5
A
I
COM U COM G- TB3
R
L
NC T E NC G+ R ALARM
1K FACP 3008
R END
10K
ext. voltage supply(at least G-
1A switch current)
G+
0V
IR flame detector TB1 +(H) -(N) CKT
761354 +24V
TEST PWR PWR GND
+24V
fit jumper X3
fit jumper X3 6 6
5 X5 X6 X7 X8 5
6 6 4 K1 4
5 X5 X6 X7 X8 5 3 3
X3 X4
4 K1 4 2 2
3 3 1 X2 reset module X1 1
X3 X4
2 2
1 X2 reset module X1 1
+ Vi Oi
UV flame detector
- Vi SPARE 761355
R END
SPARE R ALARM
FACP 3008 FIRE
NO CURRENT
FAULT
NO
CONTACTS SIGNALS CONTACTS
10K NO F F NO 1K 1 2 3 4 5
A
I
COM U COM G- TB3
R
L
NC T E NC G+ R ALARM
1K FACP 3008
R END
10K
ext. voltage supply(at least G-
1A switch current)
G+
0V
IR flame detector TB1 +(H) -(N) CKT
761354 +24V
TEST PWR PWR GND
+24V
fit jumper X3
fit jumper X3 6 6
5 X5 X6 X7 X8 5
6 6 4 K1 4
5 X5 X6 X7 X8 5 3 3
X3 X4
4 K1 4 2 2
3 3 1 X2 reset module X1 1
X3 X4
2 2
1 X2 reset module X1 1
11
evaluation unit
12
13 TB2 + -
P P P
1 2 3
14
1 2 3 4 5 6 7 8 9 10 11 12
15 1K
6 5 4 3 2 1
16
1 2 3 4
1K
X1
external indicator X8
sensor cable
X7
reset module
X6
X3 6 6
5 X5 X6 X7 X8 5
K1 X2
4 K1 4
3 3
X3 X4
2 2
6 5 4 3 2 1
1 X2 reset module X1 1
11
evaluation unit
12
13 TB2 + -
P P P
1 2 3
14
1 2 3 4 5 6 7 8 9 10 11 12
15 1K
6 5 4 3 2 1
16
1 2 3 4
1K
X1
external indicator X8
sensor cable
X7
reset module
X6
X3 6 6
5 X5 X6 X7 X8 5
K1 X2
4 K1 4
3 3
X3 X4
2 2
6 5 4 3 2 1
1 X2 reset module X1 1
FB 798139/11.2001
G
G&S BRANDSCHUTZ GMBH Westerwaldstraße 56424 Mogendorf &
S
7. Sounder DB3 range
SOUNDERS
EExd(e), Weatherpr
Weatherpr oof, UL Listed, GOST Cer
eatherproof, tified
Certified
DB3 Range
New
Vo Integ
lum r
e C al
o nt
ro l
Sounder/Beacon
Combination Unit
ro EX ted
pp T is
A &A LL
U
d
ve
ow
N
ew
N
Introduction
This range of light weight all GRP, flameproof ★ Zone 1, Zone 2 and non-Ex use.
★ Class 1, Div. 2.
sounders intended for use in potentially explosive ★ EExde IIC T4/T5.
atmospheres has been designed with high ingress ★ ATEX approved,EXII 2G.
protection to cope with the harsh environmental ★ Optional Exe terminal chamber.
conditions found offshore and onshore in the oil, gas ★ CENELEC approved.
★ BASEEFA certified.
and petrochemical industries. ★ UL Listed.
The flamepaths, flare and the body, are manufactured ★ GOST certified.
★ IP66 and IP67.
completely from a UV stable glass reinforced
★ *Certified temperature –55°C to +55°C.
polyester. Stainless steel screws and sinter are ★ All GRP corrosion free flamepaths.
incorporated thus ensuring a corrosion free product. ★ Up to 115dBA output.
A tapered flamepath is used to overcome the ★ Integral volume control.
★ 27 tones, user selectable.
problems of assembly of parallel spigot flamepaths. ★ Tones comply with UK00A/PFEER guidelines.
An optional Exe terminal chamber is available. ★ Any two tones may be switched via the external
voltage supply.
An uncertified version is available for use in non- ★ Tones may be programmed to customer
explosive atmospheres. specification.
★ d.c. version accepts any voltage between
12V d.c. and 48V d.c.
★ End of line resistor option.
★ Sounder/Beacon Combination Unit available.
*Depending on version.
MEDC Ltd, Colliery Road, Pinxton, Nottingham NG16 6JF, UK.
Tel: +44 (0)1773 864100 Fax +44 (0)1773 582800
Sales Enq. Fax: +44 (0)1773 582830 Sales Orders Fax: +44 (0)1773 582832
E-Mail: sales@medc.com Web: www.medc.com
6DS094/G
Specification
Certification: CENELEC EN50014, 18, 19.
BASEEFA Cert. No. BAS00ATEX2097X, EExd IICT4/T5.
BASEEFA Cert. No. BAS00ATEX2098X, EExde IICT4/T5.
Zones 1 and 2.
UL Listed: Class 1 Div 2, Class 1 Zones 1 & 2.
Listing No: E203310.
Refer to UL data sheet at rear of catalogue for complete information.
GOST Certification: Contact MEDC for specifications.
Material: Body & horn in anti-static, UV stable, glass reinforced
polyester.
Swivel bracket in stainless steel.
Captive cover screws in stainless steel.
Finish: Body and horn, natural black or epoxy paint coated
to client’s colour requirements.
Sound Output: DB3 115dB(A) Typical.
Volume Control: Integral volume control
*Nominal Output Input Current
(dBa) (mA)
93 50
105 100
108 150
111 200
112 250
114 300
115 350
*Output measured with 24V input voltage. Tone set to
970Hz continuous.
Mounting: Stainless steel bracket with ratchet facility. Weight: 4.0kg approx. dependent on model.
Labels: Duty and tag labels optional. (Add 0.5kg for Exe version).
Certified Temperature: DP3(P) –20°C to +50°C (Exe version +45°C).
Cable Entries: 1 x 20mm EExd.
DB3L(P) & DB3(P)UL –55°C to +55°C.
2 x 20mm EExd/EExe.
1 x ½" NPT UL Ingress Protection: IP66 and IP67.
2 x ½" NPT UL
Voltage: Up to 48V d.c. Up to 254V a.c.
Tone Selection: DB3 – 27 user selectable tones available in a.c
Current Consumption: V I
versions.
Sounder/Beacon Unit: The DB3 may be combined with an MEDC beacon 12V d.c. 760mA
to create a combined audio/visual alarm. 24V d.c. 380mA
Contact MEDC for price and specification 48V d.c. 190mA
110V a.c 135mA
Two Tone Unit: DB3P – switchable between any two of the 27
120V a.c. 124mA
tones by either:
220V a.c. 68mA
(i) Reversing the polarity of the supply, or
240V a.c. 62mA
(ii) by a 3 wire common +ve system, switching
254V a.c. 59mA
between the two –ve lines.
Note: Two tone switchable unit available in d.c. Terminals: 4 x 2.5mm2 (a.c.), 6 x 2.5mm2 (d.c.).
versions (DB3P) only.
Earth Continuity: Included on EExde version.
Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code
for each component into the appropriate box.
Unit
Type Certification Voltage Labels Entries Features Colour
DB3
DB3P
*DB3L
*DB3LP Voltage Code Label Code Features Code
*DB3L & DB3LP 12V - 48V d.c. 048 Duty D* None N
available
*110V a.c. 110 Tag T* End of line
unpainted only.
*120V a.c. 120 None N resistor E*
Type Code *220V a.c. 220 *Please specify *State value.
*240V a.c. 240 wording
Uncertified U *254V a.c. 254 Entries Code Colour Code
EExd D
*DB3P not available in 1 x 20mm (EExd) 1B Natural Black N
EExde E
a.c. version. Red R
UL Listed UL 2 x 20mm (EExd/EExde) 2B
1 x ½" NPT (UL only) 1C Special S*
2 x ½" NPT (UL only) 2C *Please specify
All the above specifications, dimensions, weights and tolerances are nominal (typical) and MEDC reserve
the right to vary all data without prior notice. No liability is accepted for any consequence of use.
6/00
G
G&S BRANDSCHUTZ GMBH Westerwaldstraße 56424 Mogendorf &
S
8. Flash Light XB11 Range
5 JOULE XENON BEACONS ATEX
EExd, Weatherproof
XB11 Range
N
ow
Ce C
rt hin
ifi e
ed se
Beacon/Sounder
Combination Unit
Introduction
These certified beacons have been designed for use Zone 1 and Zone 2 use.
EExd IIB T4, T5 & T6.
in potentially explosive gas and dust atmospheres
ATEX approved, Ex II 2GD.
and harsh environmental conditions. The BASEEFA certified.
glass reinforced polyester enclosures are UL Listed for USA and Canada
suitable for use offshore or onshore, where light – Hazardous locations:
weight combined with corrosion resistance is Class I, Div 2, Groups C & D.
required. Class I, Zones 1 & 2, AExd IIB T4/T5.
– Ordinary locations: Visual-Signal Device.
The beacon housing is manufactured completely from Australian (SAA) certified.
a U.V. stable, glass reinforced polyester. Stainless Chinese (CQST) certified.
steel screws and mounting bracket are incorporated IP66 and IP67.
ensuring a totally corrosion free product. Certified temperature –55°C to +70°C.
Corrosion resistant GRP.
Units can be painted to customer specification and
Optional stainless steel backstrap.
supplied with identification labels. Various lens colours.
Optional lens guard.
Optional telephone initiation.
2 x M20 cable entries or 2 x 1/2" NPT*.
Earth continuity option (model dependent).
Filament version (20W) available†.
Fluorescent version (10W) available†.
Beacon/Sounder Combination Unit available.
*Model dependent.
†See FL11, FB11, FL12, FB12 data sheet.
D-40239 Düsseldorf
Grunerstr. 133
Telefon +49 (0) 211 / 63 10 65 info@berntgmbh.de
Telefax +49 (0) 211 / 62 61 10 www.berntgmbh.de
ALL DIMENSIONS IN MILLIMETRES
Specification
Certification: CENELEC EN50014 and EN50018. FOR COLOURED LENSES
Cert. No. BAS99 ATEX 2195X.
EExd IIB 135°C (-55 t.amb +70°C) T4. Colour Red Blue Amber Green Yellow
100°C (-55 t.amb +55°C) T5. Multiplying
85°C (-55 t.amb +40°C) T6.
Factor 0.15 0.12 0.51 0.49 0.86
UL Listed for USA and Canada to:
– Hazardous locations: The photometric data has been verified by BSI.
Class I, Div 2 Groups C & D.
Class I, Zones 1 & 2 AExd IIB T4/T5. A report is available if required.
UL Listing No: E187894. Weight: 2.5Kg.
– Ordinary locations: Visual-Signal Device.
UL listing No. S8128. Certified Temperature: EExd –55°C to +70°C (T4).
Refer to UL Datasheet at rear of catalogue for complete information. –55°C to +55°C (T5).
Chinese (CSQT) Certification: Exd IIB T5/T6. –55°C to +40°C (T6).
Material: Body: – Glass reinforced polyester (GRP). UL –55°C to +70°C.
Lens: – Glass.
Ingress Protection: IP66 & IP67.
Cover Screws + Backstrap: – Stainless steel 316.
Finish: Natural black or painted to customer specification. Fire Retardancy: GRP is fire retardant to ISO 1210.
DC AC50/60 Hz Earth Continuity: Optional for metal glands provided via a brass
plate. (Not available for UL version).
Voltage 24 110 240
XB11 Terminals: 6 x 2.5mm2.
Tube Energy Telephone initiation: Initiation by telephone ringing tone.
(Joules) 5 5 5
Peak Current Labels: Duty/Tag Label optional.
Consumption (mA) 320 100 60 Entries: 2 x 20mm ISO EExd.
Effective 2 x 1/2" NPT UL.
Intensity (Cd) 29 29 29 Beacon/Sounder Unit: The beacon may be combined with an MEDC
Peak Intensity (Cd) 22213 22213 22213 sounder to create a visual/audible alarm.
Power Consumption Contact MEDC for price and specification.
(Watts) 8 11 18
NOTE: The Cd figures are for a clear lens @ 1Hz flash rate.
Ordering Requirements
The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box. For standard products, available ex-stock, contact sales office for details.
Flash Lens Lens Unit Earth Tag/Duty Unit
Certification Voltage Rate Colour Guard Fixing Continuity Label Options Finish
XB11
Certification Code Colour Code Guard Code Label Code Option Code
Uncertified W Red R None N None N *Telephone initiate T
BASEEFA B Blue B Yes Y Yes Y Blanking Plug P
UL UL (Please specify) None N
UL (Ordinary UW Green G
Amber A Unit Fixing Code *Telephone option not
location)
Chinese (CQST) Q Yellow Y Direct Mounting D available in UL version.
Clear C Backstrap B
Finish Code
Voltage Code
Continuity* Code Natural Black N
24V d.c. 024 Flash Rate Code Red R
110V a.c. 110 60/min 06 None N Blue B
240V a.c. 240 Yes Y Yellow Y
Other flash rates Grey G
Other voltages available, available, please specify. *Earth continuity not White W
please specify. available in UL version. Special Finish S
All the above specifications, dimensions, weights and tolerances are nominal (typical) and MEDC reserve
the right to vary all data without prior notice. No liability is accepted for any consequence of use.
06/04
G
G&S BRANDSCHUTZ GMBH Westerwaldstraße 56424 Mogendorf &
S
9. Pressure switch
G
G&S BRANDSCHUTZ GMBH Westerwaldstraße 56424 Mogendorf &
S
10. Release solenoid