KNEE POINT VOLTAGE CALCULATION FOR MIB 202

TRANSFORMER DETAILS:
TRANSFORMER 66KV / 11KV, 10 MVA, DYN11, Z = 8 %

CT RATIO: 100 / 1 AMP (66KV SIDE), RCT = 5 Ohm at 75 deg c

: 600 / 1 AMP (11 KV SIDE), RCT = 8.89 ohm at 75 deg C

66 KV SIDE

RATED CURRENT: 10000 / 66KV * 1.732 = 87.479 A


CT SEC CURRENT: 87.499 / 100 = 0.87479 A

Vk REQUIREMENT FOR MIB 202 RELAY ON 66 KV SIDE CTS

THROUGH FAULT CURRENT If = 87.479 / 0.08 = 1093.48 A

CT SECONDARY CURRENT = 1093.48 / 100 = 10.934 A

VK = 2 If (RCT + RL), RL = 2 x 60M x 8 ohm/1000 met = 1.0 Ohm


= 2 x 10.934 (RCT + 1)
= 21.868 (RCT + 1)
= 131.2 V for RCT = 5 Ohm

= 132 Volt Approx.

11 KV SIDE

RATED CURRENT: 10000 / 11KV * 1.732 = 524.879 A

CT SEC CURRENT: 524.879/ 600 = 0.8747 A

Vk REQUIREMENT FOR MIB 202 RELAY ON 11 KV SIDE CTS

THROUGH FAULT CURRENT If = 524.879/ 0.08 = 6560.98 A

CT SECONDARY CURRENT = 6560.98 / 600 = 10.9349 A

VK = 2 If (RCT (S) + RL), RL = 0.24


= 2 x 10.93 (RCT+ 0.24)
= 21.86 X 8.24
= 180.12 V for RCT = 8 Ohm say 180V