Documente Academic
Documente Profesional
Documente Cultură
Before starting the "Phasor Diagram" we should know how electrical model of a transformer looks. It is called Equivalent circuit of a
transformer.
Say the Primary winding has T1 turns & Secondary winding has T2 turns, then,
(E1/E2)=(T1/T2)
I2= Secondary Current or Load Current, Since the load is inductive current shall be lagging in nature.
V2=Secondary Terminal Load Voltage. (We shall consider this as our reference, hence its position has been selected as 0 degree)
E2=V2+I2(R2+jX2) (Vector addition), In case I2=0 i.e. trafo is on no load this E2 will appear at transformer terminal as no load
voltage
E1=(T1/T2) X E2
Φ m=Maximum value of linked flux (Flux responsible for induced voltage i.e. E2 & E1)
I0=No-Load current
I0=Ie+Im(Vector addition)
I1=Primary Current
I1=I0+I2'(Vector addition)
V1=E1'+I1(R1+jX1)(Vector addition)
Now Let us start Construction of the transformer phase diagram.It will be easier to understand the phasor diagram and transformer's
working principle it secondary terminal Load voltage i.e. V2 is taken as reference phasor. Lets See.
A transformer is rated with its secondary no load voltage. for example for supplying 415 V load voltage you will have to
select secondary no load voltage higher than 415 V. n practice this shall be 433 V. So a 11/0.433 kV transformer means it will
step down the voltage from 11 kV to 0.433 kV at no load. Depending upon the load secondary load voltage shall be
determined. This transformer shall never be specified as 11/0.415 kV. for getting 6.6 kV output transformer secondary rating
shall be 6.9 kV.
Fig 6: Transformer phasor diagram_Computation of Secondary induced voltage or no load terminal voltage/
https://electricaltechnologyrishi.blogspot.com
Determination of maximum flux. Since the voltage induced in transformer is due to the change of flux hence it shall lag the flux by 90
degree. Lets see how.
The in the core is sinusoidal.
Φ =Φ m Sin wt
this derivation indicates that induced voltage lags behind the flux by 90 degree. hence we can say the flux leads the induced voltage
by 90 degree.
https://electricaltechnologyrishi.blogspot.com
Induced voltage at primary winding shall also lag the flux by 90 degree. However its magnitude shall be E1=(T1/T2)*E2
Fig 8: Transformer phasor diagram_Primary induced voltage lags the flux by 90 degree/
https://electricaltechnologyrishi.blogspot.com
The flux is generated by magnetizing current. So both of them shall be in phase. Im is in phase with the flux.
Fig 9: Transformer phasor diagram_Magnetizing current shall be in phase with flux./
https://electricaltechnologyrishi.blogspot.com
https://electricaltechnologyrishi.blogspot.com
No load current.
Vector Sum of Im & Ie shall give I0 i.e. the no load current. From the equivalent circuit also you can see that this current will always
flow through the transformer even if the secondary is open circuited.
Fig 11: Transformer phasor diagram_No load current/
https://electricaltechnologyrishi.blogspot.com
https://electricaltechnologyrishi.blogspot.com
https://electricaltechnologyrishi.blogspot.com
’
Fig 13a.: Transformer phasor diagram_Primary induced voltage E1 reflected to primary/
https://electricaltechnologyrishi.blogspot.com
Voltage drop due to primary winding resistance shall be parallel with I1. As Primaty input voltage is applied first, and induced voltage
E1 is result of applied input voltage hence V1 shall be obtained after adding all voltage drops with primary induced voltage.
Fig 13b.: Transformer phasor diagram_I1R1 drop added with E1'/
https://electricaltechnologyrishi.blogspot.com
I1X1 drop shall be 90 degree ahead of I1R1.
Fig 13c.: Transformer phasor diagram_I1X1 drop added with I1R1/
https://electricaltechnologyrishi.blogspot.com
V1 shall be vector sum of E1', I1R1 & I1X1.
Fig 13c.: Transformer phasor diagram_V1/
https://electricaltechnologyrishi.blogspot.com
https://electricaltechnologyrishi.blogspot.com
COMPLETE TRANSFORMER PHASOR DIAGRAM
https://electricaltechnologyrishi.blogspot.com