(Zone 07)
Chapter 1
1. Introduction 5
Chapter 2
2. Design Parameter 6
2.1. Design Code 6
2.2. Material Specifications: 7
Chapter 3
3. Loading 8
3.1. Dead Load 8
3.2 Live Load 8
3.3 Wind Load 8
3.4 Seismic Load 9
Chapter 4
4. Mathematical Model 10
4.1. Elevations and Plans 10
4.2. StaadPro Input Data 13
4.3 StaadPro Analysis Output30
4.4 Analysis Result 30
Chapter 5
5. Base Plate and connection Design 61
Appendix A
Loading of the Duct. 98
Chapter 1
1.Introduction
Different types of duct support hangers are used to secure heating and air conditioning ducts to
surrounding walls or ceilings. Installers fasten each duct support to the ceiling using a bolt,
screw, or other fastener, then secure the duct within the support hanger. Some ducts simply rest
inside of the support, while others include integral hangers for easy installation. Duct supports
must be installed at carefully chosen intervals to ensure adequate support and reduce the risk of
failure.
a. Suspended duct.
Page 5 of 6
.
Chapter 2
2.Design Parameter
1. The loads as described in design summary sheet have been applied on the structure in
accordance with-
OR
BSI: CP3: Chapter V: Part 2: September 1972
Basic Data for the design of buildings Chapter V. Loading –Part 2 Wind loads.
British Standards Institution
2 Park Street, London WIA 2BS
OR
Page 6 of 6
AISC “American Institute of Steel Construction”
3. Cold formed components (if any) have been designed in accordance with
Page 7 of 6
Chapter 3
3.Loading
3.1.Dead Load
This includes all types of permanent load such as all self weight of the ducts and it's supporting
arrangement.
It's include the weight of the material passing through the ducts.
Total weight of the duct is given in this report in the Appendix 01.
Wind load acting to the duct is calculated as per the ASCE 7 - 10. The design wind force for the
duct is determined by the following equation.
Page 8 of 6
3.4 Seismic Load
UBC97 is followed to calculate seismic force for the duct support as per the following equation.
Page 9 of 6
Chapter 4
4.Mathematical Model
Page 10 of 6
Fig. 4.2: Duct weight
Page 11 of 6
Fig. 4.3: Wind Load from +x direction
Page 12 of 6
4.2.StaadPro Input Data
Page 29 of 6
4.3 StaadPro Analysis Output
_
98 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.027 26
1.61 C 86.78 0.00 0.00
99 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.027 25
1.61 C 86.78 0.00 0.00
100 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.034 25
0.01 C 0.00 196.65 600.00
101 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.047 26
0.86 C 154.41 0.00 0.00
102 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.047 25
0.86 C 154.41 0.00 0.00
103 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.027 25
0.00 C 0.00 155.59 600.00
104 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.447 28
2.87 C 1524.53 -15.71 0.00
105 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.425 27
3.76 C 1510.44 7.71 0.00
106 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.304 27
0.07 C -8.56 1473.35 1673.90
Page 31 of 6
107 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.059 28
0.93 C 190.40 0.00 0.00
108 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.059 27
0.93 C 190.40 0.00 0.00
109 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.032 27
0.00 C 0.00 182.40 710.00
110 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.415 27
2.47 C -1473.35 -0.19 1770.00
111 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.133 26
0.67 C -1.95 676.71 0.00
112 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.113 25
1.35 C -398.54 -0.29 1125.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 295
_
113 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.183 43
1.29 C 933.12 -78.00 0.00
114 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.183 43
1.29 C 933.12 78.00 0.00
115 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.119 25
0.09 C 0.00 1367.49 1250.00
116 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.422 26
5.90 C 0.00 -5378.99 0.00
117 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.422 25
Page 32 of 6
5.90 C 0.00 5378.99 0.00
118 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.418 26
7.55 C 0.00 -5166.62 0.00
119 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.418 25
7.55 C 0.00 5166.62 0.00
120 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.589 25
0.11 C 0.00 3079.50 1300.00
121 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.586 25
0.08 C 0.00 3190.74 1000.00
122 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.417 28
3.39 C 1441.19 0.00 0.00
123 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.417 27
3.39 C 1441.19 0.00 0.00
124 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.252 27
0.03 C 0.00 1365.89 1050.00
125 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.163 26
1.63 C 568.37 0.00 0.00
126 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.163 25
1.63 C 568.37 0.00 0.00
127 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.098 25
0.01 C 0.00 536.64 950.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 296
_
128 ST UB152X89X16 (BRITISH SECTIONS)
Page 33 of 6
PASS LRFD-H1-1B-C 0.147 43
1.06 C 1053.69 -23.43 0.00
129 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.147 43
1.06 C 1053.69 23.43 0.00
130 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.153 43
1.08 C 1087.52 -39.52 0.00
131 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.153 43
1.08 C 1087.38 39.53 0.00
132 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.142 25
0.02 C 0.00 776.13 950.00
133 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.141 25
0.03 C 0.00 721.20 1434.32
134 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.332 42
1.55 C -1644.19 291.75 0.00
135 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.569 41
2.99 C 2989.32 -23.12 0.00
136 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.219 28
0.72 C 0.03 3244.42 0.00
137 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.147 28
1.82 C 0.00 1687.58 0.00
138 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.157 27
1.53 C -558.84 0.00 995.00
139 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.180 28
1.04 C 0.00 882.46 0.00
140 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.221 27
0.52 C -0.01 3201.01 3175.75
141 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.119 28
2.57 C -2.79 -2392.50 600.00
142 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.350 42
1.83 C -2467.18 -217.98 0.00
Page 34 of 6
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 297
_
146 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.142 28
1.32 C -506.26 0.00 1115.00
147 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.143 27
1.32 C -507.19 0.00 1115.00
148 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.143 28
1.32 C -507.20 0.00 1115.00
149 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.142 27
1.32 C -506.25 0.00 1115.00
150 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.083 28
0.85 C 0.00 -818.70 1063.11
151 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.083 27
0.85 C 0.00 -818.70 1063.11
152 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.015 28
1.41 C -2.63 212.73 0.00
153 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.023 41
0.57 C 105.14 -14.70 0.00
154 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.014 28
0.00 C -0.71 163.23 0.00
155 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.265 28
1.80 C -944.72 0.00 1385.00
156 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.265 27
Page 35 of 6
1.80 C -944.73 0.00 1385.00
157 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.091 27
0.16 C 0.00 944.73 2019.70
158 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.012 26
0.50 C 61.34 -0.92 1785.00
159 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.012 25
0.01 T 0.03 147.92 884.40
160 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.009 28
0.80 C -0.17 -163.23 415.01
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 298
_
161 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.015 25
0.08 C -0.05 176.83 884.40
162 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.020 44
0.51 C -103.96 -7.56 0.00
163 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.016 41
0.60 C -32.30 157.51 0.00
164 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.192 26
2.20 C 678.01 0.00 0.00
165 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.192 25
2.20 C 678.01 0.00 0.00
166 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.111 25
0.04 C 0.00 627.28 750.00
167 ST CH100X50X10 (BRITISH SECTIONS)
Page 36 of 6
PASS LRFD-H1-1B-C 0.287 28
2.41 C 1026.42 1.02 0.00
168 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.295 27
1.80 C -1054.23 -0.03 1450.00
169 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.107 28
0.20 C 6.28 1058.35 0.00
170 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.107 26
1.34 C 381.00 0.00 0.00
171 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.107 25
1.34 C 380.97 0.00 0.00
172 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.058 26
1.07 C 204.37 -1.52 0.00
173 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.295 28
1.80 C -1058.35 -0.04 850.00
174 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.060 25
0.08 C 0.00 338.30 698.00
175 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.060 25
0.62 C 1.49 325.18 698.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 299
_
176 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.136 43
1.77 C 982.37 -53.58 0.00
177 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.136 43
1.77 C 982.09 53.66 0.00
Page 37 of 6
178 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.164 43
1.54 C 859.51 -22.47 0.00
179 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.163 43
1.53 C 857.71 22.61 0.00
180 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.158 26
4.20 C 53.26 -2145.48 0.00
181 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.303 28
3.79 C -1575.41 -52.45 0.00
182 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.128 25
0.73 T 0.00 1253.74 2540.66
183 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.130 25
0.41 T 0.00 1443.63 1542.79
184 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.140 25
0.39 T 37.53 1433.90 1542.79
185 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.047 26
1.20 C 0.00 1069.68 725.01
186 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.047 25
1.20 C 0.00 -1069.64 725.01
187 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.061 26
1.52 C 0.00 919.66 725.01
188 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.061 25
1.52 C 0.00 -919.61 725.01
189 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.061 26
1.52 C -0.09 915.46 725.01
190 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.046 25
1.51 C -1.06 -915.19 725.01
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 300
Page 38 of 6
ALL UNITS ARE - KN MMS (UNLESS OTHERWISE Noted)
_
191 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.114 25
0.81 C 0.00 1069.64 2540.66
192 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.084 25
0.44 C 0.00 919.61 1542.79
193 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.084 26
0.44 C -0.54 915.46 0.00
194 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.374 28
0.32 C 169.52 1358.49 0.00
195 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.322 27
2.52 C 1028.69 -274.91 0.00
196 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.141 28
2.56 C 494.90 0.00 0.00
197 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.141 27
2.56 C 494.90 0.00 0.00
198 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.117 27
0.18 T 0.00 624.53 1100.00
199 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.104 28
1.02 C -369.82 0.00 590.00
200 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.104 27
1.02 C -369.82 0.00 590.00
201 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.070 27
0.25 C 0.00 369.82 1100.00
202 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.054 28
0.91 C 189.03 0.00 0.00
203 ST CH100X50X10 (BRITISH SECTIONS)
Page 39 of 6
PASS LRFD-H1-1B-C 0.054 27
0.91 C 189.03 0.00 0.00
204 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.031 27
0.07 C 0.00 176.06 650.00
205 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.031 28
0.67 C 95.70 0.00 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 301
_
206 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.031 27
0.67 C 95.70 0.00 0.00
207 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.031 28
0.67 C 95.70 0.00 0.00
208 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.031 27
0.67 C 95.70 0.00 0.00
209 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.059 28
0.88 C 191.59 0.00 0.00
210 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.059 27
0.88 C 191.59 0.00 0.00
211 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.044 28
0.69 C 143.85 -32.36 0.00
212 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.061 27
0.76 C 143.46 149.06 0.00
213 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.016 27
0.00 C 0.00 91.89 700.00
Page 40 of 6
214 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.016 27
0.00 C 0.00 91.89 700.00
215 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.033 27
0.00 C 0.00 183.17 796.17
216 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.055 28
0.04 C -46.12 138.05 0.00
217 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.043 28
0.36 C -137.47 37.92 2110.01
218 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.026 26
0.08 T -0.41 145.36 704.70
219 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.041 26
0.08 C -10.57 192.87 704.70
220 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.019 28
0.60 C 10.73 186.71 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 302
_
221 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.025 25
0.71 C 68.01 -30.64 0.00
222 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.124 41
1.32 C 605.49 145.47 0.00
223 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.124 41
1.32 C 605.49 -145.47 0.00
224 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.124 41
Page 41 of 6
1.32 C 605.49 145.47 0.00
225 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.124 41
1.32 C 605.49 -145.47 0.00
226 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.089 28
2.98 C -14.05 1707.12 0.00
227 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.122 41
1.33 C 598.71 -142.69 0.00
228 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.112 41
1.78 C 590.85 17.66 0.00
229 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.116 41
1.86 C 615.87 -10.49 0.00
230 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.119 27
0.21 C 0.00 1284.15 1750.00
231 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.119 27
0.21 C 0.00 1284.15 1750.00
232 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.119 27
0.21 C -0.05 1282.32 1729.20
233 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.110 27
0.30 C 0.00 1194.68 1700.00
235 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.087 41
1.19 C 414.20 157.81 0.00
236 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.090 41
1.24 C 431.76 -153.89 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 303
_
252 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.184 28
0.55 C 0.00 920.92 0.00
253 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.165 26
1.66 C 585.19 0.00 0.00
254 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.165 25
1.66 C 585.19 0.00 0.00
255 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.109 25
0.20 C 0.00 567.67 1250.00
256 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.046 41
0.57 C 240.73 0.58 0.00
257 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.046 41
0.57 C 240.73 -0.58 0.00
258 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.046 41
0.57 C 240.73 0.58 0.00
259 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.046 41
0.57 C 240.73 -0.58 0.00
260 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.025 27
0.01 T 0.00 144.51 650.00
261 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.025 27
Page 44 of 6
0.01 T 0.00 144.51 650.00
262 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.007 28
0.32 C 0.00 -95.79 600.01
263 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.007 27
0.32 C 0.00 95.79 600.01
264 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.007 28
0.32 C 0.00 -95.79 600.01
265 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.007 27
0.32 C 0.00 95.79 600.01
266 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.017 27
0.01 C 0.00 95.79 650.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 305
_
267 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.017 27
0.01 C 0.00 95.79 650.00
268 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.018 26
1.21 C 59.04 0.00 0.00
269 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.018 25
1.21 C 59.04 0.00 0.00
270 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.018 26
1.04 C 59.86 0.00 0.00
271 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.018 25
1.04 C 59.86 0.00 0.00
272 ST CH76X38 (BRITISH SECTIONS)
Page 45 of 6
PASS LRFD-H1-1B-C 0.019 25
0.00 C 0.00 108.67 400.00
273 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.019 25
0.00 C 0.00 108.55 500.00
274 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.020 26
0.57 C 68.50 0.00 0.00
275 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.020 25
0.57 C 68.50 0.00 0.00
276 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.020 26
0.51 C 68.57 0.00 0.00
277 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.020 25
0.51 C 68.57 0.00 0.00
278 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.012 25
0.00 C 0.00 69.90 400.00
279 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.012 25
0.00 C 0.00 70.55 500.00
280 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.026 28
0.56 C 80.88 -7.24 0.00
281 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.024 27
0.67 C 80.52 1.78 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 306
_
282 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.016 27
0.00 C -2.50 78.85 802.60
Page 46 of 6
283 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.014 27
0.55 C 46.26 -1.05 0.00
284 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.015 26
0.04 C -0.02 80.02 0.00
285 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.022 27
0.24 C -78.85 -0.04 650.00
286 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.014 26
0.04 C -0.80 75.92 0.00
287 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.012 25
0.60 C 39.00 1.48 0.00
288 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.012 25
0.17 C -42.86 -0.00 1150.00
289 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.019 26
1.40 C 60.32 0.00 0.00
290 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.019 25
1.40 C 60.32 0.00 0.00
291 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.021 25
0.00 C 0.00 122.35 400.00
292 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.025 26
0.69 C 83.42 0.00 0.00
293 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.025 25
0.69 C 83.42 0.00 0.00
294 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.015 25
0.00 C 0.00 84.21 400.00
295 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.287 28
2.29 C 1017.26 0.00 0.00
296 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.287 27
2.29 C 1017.26 0.00 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 307
Page 47 of 6
_
_
297 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.093 27
0.10 C 0.00 1014.35 1700.00
298 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.071 26
0.78 C 254.39 0.00 0.00
299 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.071 25
0.78 C 254.39 0.00 0.00
300 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.045 25
0.18 C 0.00 237.79 1130.10
301 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.164 28
2.88 C 575.98 0.00 0.00
302 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.164 27
2.88 C 575.98 0.00 0.00
303 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.131 27
0.19 T 0.00 704.61 1050.00
304 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.114 28
1.15 C -406.69 0.00 565.00
305 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.114 27
1.15 C -406.69 0.00 565.00
306 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.076 27
0.26 C 0.00 406.69 1050.00
307 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.181 28
1.60 C 642.59 0.00 0.00
308 ST CH100X50X10 (BRITISH SECTIONS)
Page 48 of 6
PASS LRFD-H1-1B-C 0.180 27
1.65 C 640.81 0.00 0.00
309 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.124 27
0.23 C 0.00 627.12 1449.99
310 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.059 28
0.86 C 208.70 0.00 0.00
311 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.059 27
0.86 C 208.70 0.00 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 308
_
312 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.034 27
0.12 C 0.00 191.37 750.00
313 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.165 26
2.40 C 581.26 0.00 0.00
314 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.165 25
2.40 C 581.26 0.00 0.00
315 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.093 25
0.03 C 0.00 535.31 550.00
316 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.003 44
0.06 C -10.76 0.00 750.00
317 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.003 43
0.06 C -10.76 0.00 750.00
318 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.003 15
0.02 C 0.00 -12.48 675.00
Page 49 of 6
319 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.165 28
2.40 C 581.26 0.00 0.00
320 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.165 27
2.40 C 581.26 0.00 0.00
321 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.165 28
2.40 C 581.26 0.00 0.00
322 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.165 27
2.40 C 581.26 0.00 0.00
323 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.093 27
0.03 C 0.00 535.31 550.00
324 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.093 27
0.03 C 0.00 535.31 550.00
325 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.145 41
1.53 C 1512.07 9.25 0.00
326 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.145 41
1.53 C 1512.07 -9.25 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 309
_
327 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.070 27
0.01 C 0.00 843.25 450.00
328 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.115 44
4.81 C -839.02 690.22 0.00
329 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.115 43
Page 50 of 6
4.81 C 839.02 -690.19 0.00
330 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.114 44
3.77 C -869.20 709.06 0.00
331 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.114 43
3.77 C 869.23 -709.66 0.00
332 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.082 43
0.00 C -0.00 990.55 600.03
333 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.086 43
0.01 C -0.00 1024.21 909.15
334 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.052 41
0.74 C 373.73 11.65 0.00
335 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.052 41
0.74 C 373.73 -11.65 0.00
336 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.052 41
0.74 C 373.73 11.65 0.00
337 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.052 41
0.74 C 373.73 -11.65 0.00
338 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.090 42
6.54 C -1740.89 -695.36 0.00
339 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.067 42
0.85 C -436.68 -155.31 0.00
340 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.028 27
0.01 C 0.00 332.51 950.00
341 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.028 27
0.01 C 0.00 332.51 950.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 310
Page 51 of 6
MEMBER TABLE RESULT/ CRITICAL COND/ RATIO/ LOADING/
FX MY MZ LOCATION
=======================================================================
_
342 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.075 28
0.23 T 1.21 749.88 0.00
343 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.064 27
5.69 C -7.07 -5892.23 0.00
344 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.052 41
4.37 C 3.07 957.65 0.00
345 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.071 41
1.25 T -0.06 789.71 1290.50
346 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.054 27
5.28 C -27.35 -4795.88 0.00
347 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.087 41
3.00 C 2.40 1497.03 0.00
348 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.171 42
1.58 T 0.47 1925.78 0.00
349 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.233 41
0.58 C 65.45 2379.08 1500.00
350 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.068 42
4.69 C 1196.64 1274.01 1225.00
351 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.094 41
5.61 C 2008.13 221.78 0.00
352 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.195 27
0.61 C 4.20 4504.06 5457.53
353 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.264 41
3.55 C 5603.25 817.13 0.00
354 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.048 27
2.90 C -0.01 4504.06 500.00
Page 52 of 6
355 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.215 27
0.46 C 2.31 4978.53 5457.53
356 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.325 42
3.72 C -6939.22 796.86 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 311
_
357 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.054 41
2.10 C 949.28 1107.28 0.00
358 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.403 41
5.72 C 8931.67 350.02 0.00
359 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.403 41
5.72 C 8934.02 -349.69 0.00
360 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.345 27
2.01 T 0.00 6596.16 6407.51
361 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.114 41
2.55 C 1967.71 1598.19 0.00
362 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.114 41
2.55 C 1968.27 -1598.08 0.00
363 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.266 27
2.36 C 0.00 5004.25 6407.51
364 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.418 41
5.31 C 9242.01 359.29 0.00
365 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.418 41
Page 53 of 6
5.31 C 9241.78 -359.33 0.00
366 ST UB152X89X16 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.360 27
2.96 T 0.00 3802.53 6284.21
367 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.111 28
3.35 C 0.00 -6598.23 1100.00
368 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.111 27
3.35 C 0.00 6598.25 1100.00
369 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.343 27
3.25 C 0.00 6598.25 6284.21
370 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.416 41
3.62 C 4483.06 41.90 0.00
371 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.416 41
3.62 C 4483.22 -41.86 0.00
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 312
_
372 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.113 27
0.13 C 0.00 1958.29 2195.91
373 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.346 41
2.33 C 3569.58 283.28 0.00
374 ST UB254X102X25 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.346 41
2.33 C 3569.70 -283.27 0.00
375 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.183 27
0.19 C 0.00 3168.80 2195.91
376 ST UB254X146X31 (BRITISH SECTIONS)
Page 54 of 6
PASS LRFD-H1-1B-C 0.072 27
5.39 C 55.96 -4092.33 0.00
377 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.097 44
4.17 C 984.66 3139.01 0.00
378 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-T 0.168 43
0.18 T 249.79 1147.57 0.00
379 ST UB127X76X13 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.129 26
0.70 C 0.85 2352.04 0.00
380 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.126 42
4.02 C 878.68 -5436.08 0.00
381 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.130 44
5.00 C -2405.21 -1217.15 0.00
382 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.130 43
5.00 C 2405.20 1217.07 0.00
383 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.130 44
5.00 C -2405.21 -1217.15 0.00
384 ST UB254X146X31 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.130 43
5.00 C 2405.20 1217.07 0.00
385 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.192 43
0.09 C -0.00 2117.73 1600.04
386 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.192 43
0.09 C -0.00 2117.73 1600.04
_ DXF IMPORT OF ZONE7 FRAME2004.DXF -- PAGE NO. 313
_
Page 55 of 6
387 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.417 26
3.39 C 1441.19 0.00 0.00
388 ST CH100X50X10 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.417 25
3.39 C 1441.19 0.00 0.00
389 ST CH76X38 (BRITISH SECTIONS)
PASS LRFD-H1-1B-C 0.252 25
0.03 C 0.00 1365.89 1050.00
Page 56 of 6
4.4 Analysis Result
Channel 76x38
Page 57 of 6
Channel 100x50x10
Page 58 of 6
UB 127x76x13 Kg/M
UB 152x89x16 Kg/M
Page 59 of 6
UB 203x133x25 Kg/M
UB 254x146x31 kg/m
Page 60 of 6
Chapter 5
5.Base Plate and connection Design
Page 61 of 6
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 200 + HIT-Z M12
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: DIN EN ISO 4042
Evaluation Service Report: ESR-3187
Issued I Valid: 4/1/2019 | 3/1/2020
Proof: Design method ACI 318-11 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Anchor plate: lx x ly x t = 150 mm x 150 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: U profile, U 100; (L x W x T x FT) = 100 mm x 50 mm x 6 mm x 9 mm
Base material: cracked concrete, C25/30, fc' = 3,626 psi; h = 250 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Anchor forces are calculated based on the assumption of a rigid anchor plate. Compression
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 8.793 35.620 25 OK
Pullout Strength* 8.793 28.470 31 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 17.586 38.836 46 OK
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [mm2] futa [N/mm2]
84 650.00
Calculations
Nsa [kN]
54.800
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
54.800 0.650 35.620 8.793
Variables
la Np [kN]
1.000 43.800
Calculations
-
-
Results
Npn [kN] f concrete f Npn [kN] Nua [kN]
43.800 0.650 28.470 8.793
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-11 Eq. (D-4)
f Ncbg ≥ Nua ACI 318-11 Table D.4.1.1
ANc see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-11 Eq. (D-5)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-11 Eq. (D-10)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-11 Eq. (D-12)
1.5
Nb = kc l a √fc hef
'
ACI 318-11 Eq. (D-6)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
120 0 0 ∞ 1.000
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
1,65,600 1,29,600 1.000 1.000 1.000 1.000 46.759
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
59.748 0.650 38.836 17.586
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 1.025 14.460 8 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Concrete Breakout 4.100 106.882 4 OK
Strength controls)**
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)
Variables
Ase,V [mm2] futa [N/mm2]
84 650.00
Calculations
Vsa [kN]
24.100
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
24.100 0.600 14.460 1.025
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-11 Eq. (D-10)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-11 Eq. (D-12)
1.5
Nb = kc l a √fc hef
'
ACI 318-11 Eq. (D-6)
Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 120 0 0 ∞
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
2,11,600 1,29,600 1.000 1.000 1.000 1.000 46.759
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
152.689 0.700 106.882 4.100
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-11,
Part D.9.1
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + HIT-Z M12
Profile: U profile, U 100; (L x W x T x FT) = 100 mm x 50 mm x 6 mm x Installation torque: 0.040 kNm
9 mm
Hole diameter in the fixture (pre-setting) : df = 14 mm Hole diameter in the base material: 14 mm
Hole diameter in the fixture (through fastening) : df = 16 mm Hole depth in the base material: 120 mm
Plate thickness (input): 12 mm Minimum thickness of the base material: 180 mm
Recommended plate thickness: not calculated
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to
instructions for use is required
75 75
25
3 4
75
100
x
75
1 2
25
25 100 25
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 -50 -50 - - - -
2 50 -50 - - - -
3 -50 50 - - - -
4 50 50 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 200 + HIT-Z M12
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: DIN EN ISO 4042
Evaluation Service Report: ESR-3187
Issued I Valid: 4/1/2019 | 3/1/2020
Proof: Design method ACI 318-11 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Anchor plate: lx x ly x t = 250 mm x 150 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: I profile, ; (L x W x T x FT) = 127 mm x 76 mm x 4 mm x 7 mm
Base material: cracked concrete, C25/30, fc' = 3,626 psi; h = 250 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 15.154 35.620 43 OK
Pullout Strength* 15.154 28.470 54 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 30.308 47.279 65 OK
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [mm2] futa [N/mm2]
84 650.00
Calculations
Nsa [kN]
54.800
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
54.800 0.650 35.620 15.154
Variables
la Np [kN]
1.000 43.800
Calculations
-
-
Results
Npn [kN] f concrete f Npn [kN] Nua [kN]
43.800 0.650 28.470 15.154
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-11 Eq. (D-4)
f Ncbg ≥ Nua ACI 318-11 Table D.4.1.1
ANc see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-11 Eq. (D-5)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-11 Eq. (D-10)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-11 Eq. (D-12)
1.5
Nb = kc l a √fc hef
'
ACI 318-11 Eq. (D-6)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
120 0 0 ∞ 1.000
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
2,01,600 1,29,600 1.000 1.000 1.000 1.000 46.759
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
72.736 0.650 47.279 30.308
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 0.673 14.460 5 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Concrete Breakout 2.693 130.117 3 OK
Strength controls)**
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)
Variables
Ase,V [mm2] futa [N/mm2]
84 650.00
Calculations
Vsa [kN]
24.100
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
24.100 0.600 14.460 0.673
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-11 Eq. (D-10)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-11 Eq. (D-12)
1.5
Nb = kc l a √fc hef
'
ACI 318-11 Eq. (D-6)
Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 120 0 0 ∞
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
2,57,600 1,29,600 1.000 1.000 1.000 1.000 46.759
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
185.882 0.700 130.117 2.693
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-11,
Part D.9.1
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + HIT-Z M12
Profile: I profile, ; (L x W x T x FT) = 127 mm x 76 mm x 4 mm x 7 mm Installation torque: 0.040 kNm
Hole diameter in the fixture (pre-setting) : df = 14 mm Hole diameter in the base material: 14 mm
Hole diameter in the fixture (through fastening) : df = 16 mm Hole depth in the base material: 120 mm
Plate thickness (input): 12 mm Minimum thickness of the base material: 180 mm
Recommended plate thickness: not calculated
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to
instructions for use is required
125 125
25
3 4
75
100
x
75
1 2
25
25 200 25
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 -100 -50 - - - -
2 100 -50 - - - -
3 -100 50 - - - -
4 100 50 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 200 + Rebar 12mm
Effective embedment depth: hef,act = 180 mm (hef,limit = - mm)
Material: B500B
Evaluation Service Report: ESR-3187
Issued I Valid: 4/1/2019 | 3/1/2020
Proof: Design method ACI 318-11 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 16 mm
Anchor plate: lx x ly x t = 325 mm x 150 mm x 16 mm; (Recommended plate thickness: not calculated
Profile: I profile, ; (L x W x T x FT) = 152 mm x 89 mm x 4 mm x 8 mm
Base material: cracked concrete, C25/30, fc' = 3,626 psi; h = 250 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 15.450 40.300 39 OK
Bond Strength** 28.432 56.517 51 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 28.432 77.741 37 OK
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [mm2] futa [N/mm2]
113 550.00
Calculations
Nsa [kN]
62.000
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
62.000 0.650 40.300 15.450
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Nag = (AA ) y
Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-11 Eq. (D-19)
f Nag ≥ Nua ACI 318-11 Table D.4.1.1
ANa = see ACI 318-11, Part D.5.5.1, Fig. RD.5.5.1(b)
ANa0 = (2 cNa)2 ACI 318-11 Eq. (D-20)
cNa = 10 da √ t uncr
1100
ACI 318-11 Eq. (D-21)
( )
1
y ec,Na = e' ≤ 1.0 ACI 318-11 Eq. (D-23)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( ) ca,min
cNa
≤ 1.0 ACI 318-11 Eq. (D-25)
y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-11 Eq. (D-27)
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables
2 2
t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] aoverhead t k,c [N/mm ]
11.21 12 180 ∞ 1.000 7.78
ec1,N [mm] ec2,N [mm] cac [mm] la
13 27 438 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
145 1,78,760 84,363 1.000
y ec1,Na y ec2,Na y cp,Na Nba [kN]
0.919 0.845 1.000 52.822
Results
Nag [kN] f bond f Nag [kN] Nua [kN]
86.950 0.650 56.517 28.432
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-11 Eq. (D-4)
f Ncbg ≥ Nua ACI 318-11 Table D.4.1.1
ANc see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-11 Eq. (D-5)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-11 Eq. (D-10)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-11 Eq. (D-12)
1.5
Nb = kc l a √fc hef
'
ACI 318-11 Eq. (D-6)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
180 13 27 ∞ 1.000
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
4,67,100 2,91,600 0.955 0.910 1.000 1.000 85.902
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
119.601 0.650 77.741 28.432
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 1.051 22.500 5 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength 4.206 176.420 3 OK
controls)**
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)
Variables
Ase,V [mm2] futa [N/mm2]
113 550.00
Calculations
Vsa [kN]
37.500
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
37.500 0.600 22.500 1.051
( )
1
y ec,Na = e' ≤ 1.0 ACI 318-11 Eq. (D-23)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( )ca,min
cna
≤ 1.0 ACI 318-11 Eq. (D-25)
y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-11 Eq. (D-27)
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables
2 2
kcp aoverhead t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] t k,c [N/mm ]
2 1.000 11.21 12 180 ∞ 7.78
ec1,N [mm] ec2,N [mm] cac [mm] la
0 0 438 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
145 2,01,260 84,363 1.000
y ec1,Na y ec2,Na y cp,Na Nba [kN]
1.000 1.000 1.000 52.822
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
252.028 0.700 176.420 4.206
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-11,
Part D.9.1
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + Rebar 12mm
Profile: I profile, ; (L x W x T x FT) = 152 mm x 89 mm x 4 mm x 8 mm Installation torque: -
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 16 mm Hole depth in the base material: 180 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 212 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to
instructions for use is required
163 163
25
3 4
75
100
x
75
1 2
25
50 225 50
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 -113 -50 - - - -
2 113 -50 - - - -
3 -113 50 - - - -
4 113 50 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 8
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 200 + Rebar 12mm
Effective embedment depth: hef,act = 180 mm (hef,limit = - mm)
Material: B500B
Evaluation Service Report: ESR-3187
Issued I Valid: 4/1/2019 | 3/1/2020
Proof: Design method ACI 318-11 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 16 mm
Anchor plate: lx x ly x t = 400 mm x 175 mm x 16 mm; (Recommended plate thickness: not calculated
Profile: I profile, ; (L x W x T x FT) = 203 mm x 133 mm x 6 mm x 8 mm
Base material: cracked concrete, C25/30, fc' = 3,626 psi; h = 250 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 14.887 40.300 37 OK
Bond Strength** 29.314 64.020 46 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 29.314 84.444 35 OK
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [mm2] futa [N/mm2]
113 550.00
Calculations
Nsa [kN]
62.000
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
62.000 0.650 40.300 14.887
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Nag = (AA ) y
Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-11 Eq. (D-19)
f Nag ≥ Nua ACI 318-11 Table D.4.1.1
ANa = see ACI 318-11, Part D.5.5.1, Fig. RD.5.5.1(b)
ANa0 = (2 cNa)2 ACI 318-11 Eq. (D-20)
cNa = 10 da √ t uncr
1100
ACI 318-11 Eq. (D-21)
( )
1
y ec,Na = e' ≤ 1.0 ACI 318-11 Eq. (D-23)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( ) ca,min
cNa
≤ 1.0 ACI 318-11 Eq. (D-25)
y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-11 Eq. (D-27)
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables
2 2
t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] aoverhead t k,c [N/mm ]
11.21 12 180 ∞ 1.000 7.78
ec1,N [mm] ec2,N [mm] cac [mm] la
10 21 438 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
145 1,93,283 84,363 1.000
y ec1,Na y ec2,Na y cp,Na Nba [kN]
0.933 0.872 1.000 52.822
Results
Nag [kN] f bond f Nag [kN] Nua [kN]
98.492 0.650 64.020 29.314
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-11 Eq. (D-4)
f Ncbg ≥ Nua ACI 318-11 Table D.4.1.1
ANc see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-11 Eq. (D-5)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-11 Eq. (D-10)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-11 Eq. (D-12)
1.5
Nb = kc l a √fc hef
'
ACI 318-11 Eq. (D-6)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
180 10 21 ∞ 1.000
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
4,94,100 2,91,600 0.963 0.927 1.000 1.000 85.902
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
129.914 0.650 84.444 29.314
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 1.250 22.500 6 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength 5.000 193.533 3 OK
controls)**
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)
Variables
Ase,V [mm2] futa [N/mm2]
113 550.00
Calculations
Vsa [kN]
37.500
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
37.500 0.600 22.500 1.250
( )
1
y ec,Na = e' ≤ 1.0 ACI 318-11 Eq. (D-23)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( )ca,min
cna
≤ 1.0 ACI 318-11 Eq. (D-25)
y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-11 Eq. (D-27)
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables
2 2
kcp aoverhead t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] t k,c [N/mm ]
2 1.000 11.21 12 180 ∞ 7.78
ec1,N [mm] ec2,N [mm] cac [mm] la
0 0 438 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
145 2,20,783 84,363 1.000
y ec1,Na y ec2,Na y cp,Na Nba [kN]
1.000 1.000 1.000 52.822
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
276.475 0.700 193.533 5.000
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-11,
Part D.9.1
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + Rebar 12mm
Profile: I profile, ; (L x W x T x FT) = 203 mm x 133 mm x 6 mm x 8 Installation torque: -
mm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 16 mm Hole depth in the base material: 180 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 212 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to
instructions for use is required
200 200
38
3 4
88
100
x
88
1 2
38
63 275 63
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 -138 -50 - - - -
2 138 -50 - - - -
3 -138 50 - - - -
4 138 50 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 8
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 200 + Rebar 12mm
Effective embedment depth: hef,act = 180 mm (hef,limit = - mm)
Material: B500B
Evaluation Service Report: ESR-3187
Issued I Valid: 4/1/2019 | 3/1/2020
Proof: Design method ACI 318-11 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 16 mm
Anchor plate: lx x ly x t = 475 mm x 250 mm x 16 mm; (Recommended plate thickness: not calculated
Profile: I profile, ; (L x W x T x FT) = 260 mm x 148 mm x 7 mm x 13 mm
Base material: cracked concrete, C25/30, fc' = 3,626 psi; h = 250 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 12.463 40.300 31 OK
Bond Strength** 41.134 81.970 51 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 41.134 96.895 43 OK
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [mm2] futa [N/mm2]
113 550.00
Calculations
Nsa [kN]
62.000
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
62.000 0.650 40.300 12.463
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Nag = (AA ) y
Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-11 Eq. (D-19)
f Nag ≥ Nua ACI 318-11 Table D.4.1.1
ANa = see ACI 318-11, Part D.5.5.1, Fig. RD.5.5.1(b)
ANa0 = (2 cNa)2 ACI 318-11 Eq. (D-20)
cNa = 10 da √ t uncr
1100
ACI 318-11 Eq. (D-21)
( )
1
y ec,Na = e' ≤ 1.0 ACI 318-11 Eq. (D-23)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( ) ca,min
cNa
≤ 1.0 ACI 318-11 Eq. (D-25)
y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-11 Eq. (D-27)
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables
2 2
t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] aoverhead t k,c [N/mm ]
11.21 12 180 ∞ 1.000 7.78
ec1,N [mm] ec2,N [mm] cac [mm] la
0 61 438 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
145 2,86,494 84,363 1.000
y ec1,Na y ec2,Na y cp,Na Nba [kN]
1.000 0.703 1.000 52.822
Results
Nag [kN] f bond f Nag [kN] Nua [kN]
126.108 0.650 81.970 41.134
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-11 Eq. (D-4)
f Ncbg ≥ Nua ACI 318-11 Table D.4.1.1
ANc see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-11 Eq. (D-5)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-11 Eq. (D-10)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-11 Eq. (D-12)
1.5
Nb = kc l a √fc hef
'
ACI 318-11 Eq. (D-6)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
180 0 61 ∞ 1.000
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
6,21,000 2,91,600 1.000 0.815 1.000 1.000 85.902
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
149.068 0.650 96.895 41.134
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 1.760 22.500 8 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength 10.559 251.133 5 OK
controls)**
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)
Variables
Ase,V [mm2] futa [N/mm2]
113 550.00
Calculations
Vsa [kN]
37.500
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
37.500 0.600 22.500 1.760
( )
1
y ec,Na = e' ≤ 1.0 ACI 318-11 Eq. (D-23)
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( )ca,min
cna
≤ 1.0 ACI 318-11 Eq. (D-25)
y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-11 Eq. (D-27)
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables
2 2
kcp aoverhead t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] t k,c [N/mm ]
2 1.000 11.21 12 180 ∞ 7.78
ec1,N [mm] ec2,N [mm] cac [mm] la
0 0 438 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
145 2,86,494 84,363 1.000
y ec1,Na y ec2,Na y cp,Na Nba [kN]
1.000 1.000 1.000 52.822
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
358.762 0.700 251.133 10.559
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-11,
Part D.9.1
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + Rebar 12mm
Profile: I profile, ; (L x W x T x FT) = 260 mm x 148 mm x 7 mm x 13 Installation torque: -
mm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 16 mm Hole depth in the base material: 180 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 212 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to
instructions for use is required
238 238
50
4 5 6
125
150
x
125
1 2 3
50
58 180 180 58
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -180 -75 - - - - 4 -180 75 - - - -
2 0 -75 - - - - 5 0 75 - - - -
3 180 -75 - - - - 6 180 75 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.8
Company: Page: 8
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 20-04-20
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Appendix A
Loading of the Duct.
Dimensions (mm) Selected Approximate
Sr # Unit Reference Reference Unit Reference Qty
Width Height Length Attenuator Weight (kg)
BASEMENT-2
1 AHU-B2-01 Supply H.T & L.T ROOM 800 350 1500 RS5EP 1 65.00
2 AHU-B2-01 Retrurn H.T & L.T ROOM 800 350 1500 RS5EP 1 65.00
3 AHU-B2-02 Supply TRENSFORMER ROOM 1750 800 1800 RS6EP 1 215.00
4 AHU-B2-02 Retrurn TRENSFORMER ROOM 1750 800 1800 RS6EP 1 215.00
BASEMENT-1
5 AHU-B1-01 Supply DENTISTRY 1750 900 2400 RS8EP/M 1 385.00
6 AHU-B1-01 Retrurn DENTISTRY 1600 900 2100 RS7DP/M 1 307.00
7 AHU-B1-02 Supply LAUNDRY 1000 550 1500 RS5EP 1 115.00
8 AHU-B1-02 Retrurn LAUNDRY 1000 500 900 RS3EP 1 60.00
9 AHU-B1-03 Supply MECHANICAL ROOM 800 350 900 RS3EP 1 45.00
10 AHU-B1-03 Retrurn MECHANICAL ROOM 800 350 900 RS3EP 1 45.00
11 AHU-B1-04 Supply MECHANICAL ROOM 700 400 900 RS3EP 1 46.00
12 AHU-B1-04 Retrurn MECHANICAL ROOM 700 400 900 RS3EP 1 46.00
13 AHU-B1-05 Supply L.T ROOM 800 300 900 RS3ESP 1 45.00
14 AHU-B1-05 Retrurn L.T ROOM 800 300 900 RS3ESP 1 45.00
15 AHU-B1-06 Supply TRANSFORMER ROOM 1600 900 1800 RS6GP 1 230.00
16 AHU-B1-06 Retrurn TRANSFORMER ROOM 1600 900 1800 RS6GP 1 230.00
17 AHU-B1-07 Supply H.T ROOM 650 350 900 RS3DP 1 40.00
18 AHU-B1-07 Retrurn H.T ROOM 650 350 900 RS3DP 1 40.00
19 AHU-B1-09 Supply MAT. MANAGEMENT 1400 500 1500 RS5EP 1 105.00
20 AHU-B1-09 Retrurn MAT. MANAGEMENT 1200 500 1200 RS4ESP 1 95.00
21 AHU-B1-10 Supply BLOOD BANK 1300 600 2100 RS7DP/M 1 205.00
22 AHU-B1-10 Retrurn BLOOD BANK 1300 500 1800 RS6DP/M 1 162.00
23 AHU-B1-11 Supply1 STAFF FACILITIES 1350 450 500 RS5EP 1 50.00
23 AHU-B1-11 Supply2 STAFF FACILITIES 1350 450 1000 RS5EP 1 70.00
24 AHU-B1-11 Retrurn STAFF FACILITIES 1350 450 1200 RS4EP 1 80.00
25 AHU-B1-12 Supply PRODUCTION PHARMACY 1600 750 2100 RS7DP/M 1 286.00
26 AHU-B1-12 Retrurn PRODUCTION PHARMACY 1250 550 1500 RS5DP/M 1 145.00
27 AHU-B1-13 Supply SERVICE AREA 1100 500 1500 RS5FP 1 110.00
28 AHU-B1-13 Retrurn SERVICE AREA 1100 500 1200 RS4FP 1 75.00
29 AHU-B1-14 Supply SERVICE AREA 650 450 900 RS3DP 1 46.00
30 AHU-B1-14 Retrurn SERVICE AREA 650 450 900 RS3DP 1 46.00
31 AHU-B1-15 Supply-1 SERVICE AREA 1050 500 750 RS5EP 1 60.00
31 AHU-B1-15 Supply-2 SERVICE AREA 1050 500 750 RS5EP 1 60.00
32 AHU-B1-15 Retrurn SERVICE AREA 1050 400 1200 RS4EP 1 55.00
33 AHU-B1-16 Supply-1 I.T DEPARTMENT 900 400 750 RS5EP 1 45.00
33 AHU-B1-16 Supply-2 I.T DEPARTMENT 900 400 750 RS5EP 1 45.00
34 AHU-B1-16 Retrurn I.T DEPARTMENT 900 400 1200 RS4EP 1 50.00
35 AHU-B1-17 Supply CYCLOTRON 1600 650 2100 RS7DP/M 1 266.00
36 AHU-B1-17 Retrurn CYCLOTRON 1600 500 1800 RS6DP/M 1 215.00
37 AHU-B1-18 Supply PRISON SERVICE 1500 550 1800 RS6FP 1 165.00
38 AHU-B1-18 Retrurn PRISON SERVICE 1500 550 1500 RS5FP 1 165.00
39 AHU-B1-19 Supply-1 RECRUITMENT 1400 600 900 RS6EP 1 82.00
Page 32 of 6
39 AHU-B1-19 Supply-2 RECRUITMENT 1400 600 900 RS6EP 1 82.00
40 AHU-B1-19 Retrurn RECRUITMENT 1250 600 1500 RS5DP 1 146.00
Dimensions (mm) Selected Approximate
Sr # Unit Reference Reference Unit Reference Qty
Width Height Length Attenuator Weight (kg)
41 AHU-B1-20 Supply CANCER CENTER 1600 800 2100 RS7DP/M 1 307.00
42 AHU-B1-20 Retrurn CANCER CENTER 1250 800 1800 RS6DP/M 1 195.00
43 AHU-B1-22 Supply COMPRESSED 700 400 900 RS3EP 1 44.00
44 AHU-B1-22 Retrurn COMPRESSED 700 400 900 RS3EP 1 44.00
45 AHU-B1-23 Supply MECHANICAL ROOM 700 350 900 RS3EP 1 40.00
46 AHU-B1-23 Retrurn MECHANICAL ROOM 700 350 900 RS3EP 1 40.00
47 AHU-B1-24 Supply MECHANICAL ROOM 700 350 900 RS3EP 1 40.00
48 AHU-B1-24 Retrurn MECHANICAL ROOM 700 350 900 RS3EP 1 40.00
49 AHU-B1-25 Supply MECHANICAL ROOM 650 500 900 RS3DP 1 48.00
50 AHU-B1-25 Retrurn MECHANICAL ROOM 650 500 900 RS3DP 1 48.00
51 AHU-B1-26 Supply MECHANICAL ROOM 900 450 900 RS3DP 1 60.00
52 AHU-B1-26 Retrurn MECHANICAL ROOM 900 450 900 RS3DP 1 60.00
53 AHU-B1-27 Supply KITCHEN-WARE WASH 700 400 1500 RS5EP/M 1 60.00
54 AHU-B1-27 Retrurn KITCHEN-WARE WASH 700 400 900 RS3EP/M 1 46.00
55 FAU-B1-01 Supply KITCHEN-1 1000 350 1500 RS5EP/M 1 70.00
56 FAU-B1-02 Supply KITCHEN-2 1000 350 1500 RS5EP/M 1 70.00
57 FAU-B1-03 Supply KITCHEN-3 700 400 1500 RS5EP/M 1 60.00
58 FAU-B1-04 Supply KITCHEN-4 700 400 1500 RS5EP/M 1 60.00
59 FAU-B1-05 Supply KITCHEN-5 1000 450 1500 RS5EP/M 1 65.00
60 FAU-B1-06 Supply BLOOD BANK-2 1150 450 1500 RS5EP/M 1 70.00
61 FAU-B1-07 Supply BLOOD BANK-3 1000 500 1500 RS5EP/M 1 70.00
62 FAU-B1-08 Supply LAUNDRY 1100 950 1800 RS6FP 1 160.00
GROUND
63 AHU-GF-01 Supply MAIN ENTRANCE 800 750 1800 RS6GP 1 110.00
64 AHU-GF-01 Retrurn MAIN ENTRANCE 800 750 1500 RS5GP 1 90.00
65 AHU-GF-01A Supply MAIN ENTRANCE-SHOPS 800 750 1800 RS6GP 1 110.00
66 AHU-GF-01A Retrurn MAIN ENTRANCE-SHOPS 850 600 1500 RS5GP 1 92.00
67 AHU-GF-02 Supply ATRUIM 1350 400 1500 RS5EP 1 90.00
68 AHU-GF-02 Retrurn ATRUIM 1350 400 1200 RS3EP 1 65.00
69 AHU-GF-02A Supply SERVIES/ CALL CENTER 1050 450 1500 RS5EP 1 65.00
70 AHU-GF-02A Retrurn SERVIES/ CALL CENTER 1050 450 1200 RS3EP 1 55.00
71 AHU-GF-03 Supply MRI-2 950 700 1800 RS6DP/M 1 135.00
72 AHU-GF-03 Retrurn MRI-2 950 650 1800 RS6DP/M 1 127.00
73 AHU-GF-04 Supply MRI-1 650 750 1800 RS6DP/M 1 95.00
74 AHU-GF-04 Retrurn MRI-1 650 700 1800 RS6DP/M 1 92.00
75 AHU-GF-06 Supply EMERGENCY 1600 950 2100 RS7DP/M 1 310.00
76 AHU-GF-06 Retrurn EMERGENCY 1600 700 1800 RS6DP/M 1 250.00
77 AHU-GF-07 Supply GENERAL RAD CLUSTER 1950 850 2100 RS7DP/M 1 385.00
78 AHU-GF-07 Retrurn GENERAL RAD CLUSTER 1950 750 1800 RS6DP/M 1 312.00
79 AHU-GF-08 Supply EDUCATION CENTER 1050 850 1800 RS6EP 1 155.00
80 AHU-GF-08 Retrurn EDUCATION CENTER 1050 600 1500 RS5EP 1 120.00
81 AHU-GF-09 Supply TRUMA 1950 850 2100 RS7DP/M 1 385.00
82 AHU-GF-09 Retrurn TRUMA 1950 750 1800 RS6DP/M 1 312.00
83 AHU-GF-10 Supply AUDITORIUM 950 550 1800 RS6DP 1 123.00
84 AHU-GF-10 Retrurn AUDITORIUM 950 550 1500 RS5DP 1 105.00
85 AHU-GF-11 Supply PHARMACY 650 600 1500 RS5DP/M 1 71.00
Page 33 of 6
Dimensions (mm) Selected Approximate
Sr # Unit Reference Reference Unit Reference Qty
Width Height Length Attenuator Weight (kg)
86 AHU-GF-11 Retrurn PHARMACY 650 600 1500 RS5DP/M 1 71.00
87 AHU-GF-12 Supply DAY CARE 1600 600 1800 RS6DP/M 1 230.00
88 AHU-GF-12 Retrurn DAY CARE 1600 500 1800 RS6DP/M 1 215.00
89 AHU-GF-13 Supply PUBLIC STAFF CAFETERIA 1250 450 1500 RS5DP/M 1 135.00
90 AHU-GF-13 Retrurn PUBLIC STAFF CAFETERIA 1250 450 1500 RS5DP/M 1 135.00
91 AHU-GF-14 Supply STAFF RESTURANT 950 700 1500 RS5DP/M 1 115.00
92 AHU-GF-14 Retrurn STAFF RESTURANT 950 600 1500 RS5DP/M 1 105.00
93 AHU-GF-15 Supply PT/OT 1600 1200 2100 RS7DP/M 1 345.00
94 AHU-GF-15 Retrurn PT/OT 1600 850 1800 RS6DP/M 1 265.00
95 AHU-GF-16 Supply NUC MEDICINE CLUSTER 1300 500 1800 RS6DP/M 1 162.00
96 AHU-GF-16 Retrurn NUC MEDICINE CLUSTER 1300 400 1500 RS5DP/M 1 135.00
97 AHU-GF-17 Supply ULTRASOUND CLUSTER 1600 600 1800 RS6DP/M 1 230.00
98 AHU-GF-17 Retrurn ULTRASOUND CLUSTER 1600 500 1500 RS5DP/M 1 180.00
First Floor
99 AHU-1F.01 Supply NURSING STATION 1300 650 1800 RS6DP/M 1 180.00
100 AHU-1F.01 Retrurn NURSING STATION 1300 500 1500 RS5DP/M 1 162.00
101 AHU-1F.02 Supply NURSING STATION 1300 650 1800 RS6DP/M 1 180.00
102 AHU-1F.02 Retrurn NURSING STATION 1300 500 1500 RS5DP/M 1 162.00
103 AHU-1F.03 Supply OFFICES 1400 900 1800 RS6EP 1 212.00
104 AHU-1F.03 Retrurn OFFICES 1400 800 1800 RS6EP 1 200.00
105 AHU-1F.04 Supply CCU 1300 650 1800 RS6DP/M 1 180.00
106 AHU-1F.04 Retrurn CCU 1300 500 1500 RS5DP/M 1 162.00
107 AHU-1F.05 Supply NON INVASIVE CARDIOLOGY 650 750 1500 RS5DP/M 1 80.00
108 AHU-1F.05 Retrurn NON INVASIVE CARDIOLOGY 600 600 1500 RS5DP/M 1 71.00
109 AHU-1F.06 Supply ENDOSCOPY 1300 650 1800 RS6DP/M 1 180.00
110 AHU-1F.06 Retrurn ENDOSCOPY 1300 500 1500 RS5DP/M 1 162.00
111 AHU-1F.07 Supply Cardiology 1300 800 1800 RS6DP/M 1 195.00
112 AHU-1F.07 Retrurn Cardiology 1300 650 1800 RS6DP/M 1 180.00
113 AHU-1F.08 Supply Neurology 950 400 1500 RS5DP/M 1 95.00
114 AHU-1F.08 Retrurn Neurology 950 400 1500 RS5DP/M 1 95.00
115 AHU-1F.09-A Supply OP 600 900 1500 RS5DP/M 1 90.00
116 AHU-1F.09-A Retrurn OP 600 700 1500 RS5DP/M 1 80.00
117 AHU-1F.09-B Supply OP 600 900 1500 RS5DP/M 1 90.00
118 AHU-1F.09-B Retrurn OP 600 700 1500 RS5DP/M 1 80.00
Second Floor
119 AHU-2F.01 Supply NURSING STATION 1300 650 1800 RS6DP/M 1 180.00
120 AHU-2F.01 Retrurn NURSING STATION 1300 500 1500 RS5DP/M 1 162.00
121 AHU-2F.02 Supply NURSING STATION 1300 650 1800 RS6DP/M 1 180.00
122 AHU-2F.02 Retrurn NURSING STATION 1300 500 1500 RS5DP/M 1 162.00
123 AHU-2F.03 Supply PEDIATRIC 1300 650 1800 RS6DP/M 1 180.00
124 AHU-2F.03 Retrurn PEDIATRIC 1300 500 1500 RS5DP/M 1 162.00
125 AHU-2F.04 Supply PICU 1600 900 2100 RS7DP/M 1 307.00
126 AHU-2F.04 Retrurn PICU 1300 800 1800 RS6DP/M 1 195.00
127 AHU-2F.05 Supply ADULT DAY CARE 600 450 1500 RS5DP/M 1 62.00
128 AHU-2F.05 Retrurn ADULT DAY CARE 600 400 1500 RS5DP/M 1 60.00
129 AHU-2F.06 Supply RENAL 950 450 1500 RS5DP/M 1 95.00
Page 34 of 6
Dimensions (mm) Selected Approximate
Sr # Unit Reference Reference Unit Reference Qty
Width Height Length Attenuator Weight (kg)
130 AHU-2F.06 Retrurn RENAL 950 400 1500 RS5DP/M 1 95.00
131 AHU-2F.07 Supply Ophtalmology 950 450 1500 RS5DP/M 1 95.00
132 AHU-2F.07 Retrurn Ophtalmology 950 450 1500 RS5DP/M 1 95.00
133 AHU-2F.08 Supply PEDS DIAGNOSIS 650 750 1500 RS5DP/M 1 80.00
134 AHU-2F.08 Retrurn PEDS DIAGNOSIS 650 600 1500 RS5DP/M 1 71.00
135 AHU-2F.09 Supply PEDS Surgery 650 550 1500 RS5DP/M 1 65.00
136 AHU-2F.09 Retrurn PEDS Surgery 650 500 1500 RS5DP/M 1 65.00
137 AHU-2F.10-A Supply OP 950 650 1500 RS5DP/M 1 110.00
138 AHU-2F.10-A Retrurn OP 650 700 1500 RS5DP/M 1 80.00
139 AHU-2F.10-B Supply OP 650 900 1500 RS5DP/M 1 90.00
140 AHU-2F.10-B Retrurn OP 650 700 1500 RS5DP/M 1 80.00
Third Floor
141 AHU-3F.01 Supply OBSTERICAL 1950 900 2100 RS7DP/M 1 395.00
142 AHU-3F.01 Retrurn OBSTERICAL 1600 750 1800 RS6DP/M 1 255.00
143 AHU-3F.02 Supply OBSTERICAL 1950 900 2100 RS7DP/M 1 395.00
144 AHU-3F.02 Retrurn OBSTERICAL 1600 750 1800 RS6DP/M 1 255.00
145 AHU-3F.03 Supply GYNOCOLOGICAL 1950 900 2100 RS7DP/M 1 395.00
146 AHU-3F.03 Retrurn GYNOCOLOGICAL 1600 750 1800 RS6DP/M 1 255.00
147 AHU-3F.04 Supply NICU 1300 600 1800 RS6DP/M 1 175.00
148 AHU-3F.04 Retrurn NICU 1300 500 1500 RS5DP/M 1 162.00
149 AHU-3F.05 Supply Labour & Delivery 1300 600 1800 RS6DP/M 1 175.00
150 AHU-3F.05 Retrurn Labour & Delivery 1300 500 1500 RS5DP/M 1 162.00
151 AHU-3F.06-A Supply WOMEN DIAGNOSIS A 950 500 1500 RS5DP/M 1 100.00
152 AHU-3F.06-A Retrurn WOMEN DIAGNOSIS A 950 500 1500 RS5DP/M 1 100.00
153 AHU-3F.06-B Supply WOMEN DIAGNOSIS B 950 400 1500 RS5DP/M 1 95.00
154 AHU-3F.06-B Retrurn WOMEN DIAGNOSIS B 950 400 1500 RS5DP/M 1 95.00
155 AHU-3F.07 Supply Operation department 1300 350 1500 RS5DP/M 1 125.00
156 AHU-3F.07 Retrurn Operation department 1300 350 1500 RS5DP/M 1 125.00
157 AHU-3F.08-A Supply OP 650 900 1500 RS5DP/M 1 90.00
158 AHU-3F.08-A Retrurn OP 650 700 1500 RS5DP/M 1 80.00
159 AHU-3F.08-B Supply OP 650 900 1500 RS5DP/M 1 90.00
160 AHU-3F.08-B Retrurn OP 650 700 1500 RS5DP/M 1 80.00
Forth Floor
161 AHU-4F.01 Supply SURGICAL NURSING 1950 900 2100 RS7DP/M 1 395.00
162 AHU-4F.01 Retrurn SURGICAL NURSING 1600 750 1800 RS6DP/M 1 255.00
163 AHU-4F.02 Supply SURGICAL NURSING 1950 900 2100 RS7DP/M 1 395.00
164 AHU-4F.02 Retrurn SURGICAL NURSING 1600 750 1800 RS6DP/M 1 255.00
AHU-4F.03
165 1950 900 ELBOW RS7DP/M 1 525.00
(ELBOW) Supply SURGICAL NURSING
166 AHU-4F.03 Retrurn SURGICAL NURSING 1600 750 1800 RS6DP/M 1 255.00
167 AHU-4F.04 Supply ICU 1300 600 1800 RS6DP/M 1 175.00
168 AHU-4F.04 Retrurn ICU 1050 500 1500 RS5DP/M 1 70.00
169 AHU-4F.05 Supply SECOND STAGE RECOVERY 950 600 1500 RS5DP/M 1 105.00
170 AHU-4F.05 Retrurn SECOND STAGE RECOVERY 950 450 1500 RS5DP/M 1 95.00
171 AHU-4F.06-A Supply STAFF AREA 650 350 1200 RS4DP 1 45.00
172 AHU-4F.06-A Retrurn STAFF AREA 500 450 900 RS3DP 1 40.00
173 AHU-4F.06-B Supply STAFF AREA 750 800 1500 RS5FP 1 88.00
Page 35 of 6
Dimensions (mm) Selected Approximate
Sr # Unit Reference Reference Unit Reference Qty
Width Height Length Attenuator Weight (kg)
174 AHU-4F.06-B Retrurn STAFF AREA 750 650 1200 RS4FP 1 65.00
175 AHU-4F.08-A Supply OP 650 700 1500 RS5DP/M 1 80.00
176 AHU-4F.08-A Retrurn OP 650 700 1500 RS5DP/M 1 80.00
177 AHU-4F.08-B Supply OP 650 700 1500 RS5DP/M 1 80.00
178 AHU-4F.08-B Retrurn OP 650 700 1500 RS5DP/M 1 80.00
Fifth Floor
179 AHU-5F.01 Supply VIP NURSING 1300 700 1800 RS6DP/M 1 185.00
180 AHU-5F.01 Retrurn VIP NURSING 1300 600 1500 RS5DP/M 1 160.00
181 AHU-5F.02 Supply VIP NURSING 1050 600 1800 RS6DP/M 1 125.00
182 AHU-5F.02 Retrurn VIP NURSING 1050 600 1500 RS5DP/M 1 95.00
183 AHU-5F.03 Supply OFFICES 1750 1000 1800 RS6EP 1 295.00
184 AHU-5F.03 Retrurn OFFICES 1750 900 1800 RS6EP 1 285.00
185 AHU-5F.04 Supply 01 Offices 1450 750 1500 RS5EP 1 135.00
186 AHU-5F.04 Supply 02 Offices 1450 750 1500 RS5EP 1 135.00
187 AHU-5F.04 Retrurn 01 Offices 1450 650 1500 RS5EP 1 130.00
188 AHU-5F.04 Retrurn 02 Offices 1450 650 1500 RS5EP 1 130.00
189 AHU-5F.05 Supply DOCTORS OFFICES 750 1100 1800 RS6EP 1 125.00
190 AHU-5F.05 Retrurn DOCTORS OFFICES 750 900 1800 RS6EP 1 115.00
191 AHU-5F.06 Supply SURGERY PREPARATION 1300 900 2100 RS7DP/M 1 240.00
192 AHU-5F.06 Retrurn SURGERY PREPARATION 1300 650 1800 RS6DP/M 1 180.00
193 AHU-5F.07 Supply SVVIP NURSING STATION 1300 800 1800 RS6DP/M 1 195.00
194 AHU-5F.07 Retrurn SVVIP NURSING STATION 1300 800 1800 RS6DP/M 1 195.00
195 AHU-5F.08 Supply SVVIP SUIT 950 300 1500 RS5DP/M 1 85.00
196 AHU-5F.08 Retrurn SVVIP SUIT 950 300 1500 RS5DP/M 1 85.00
197 AHU-5F.09 Supply SVVIP SUIT 650 350 1500 RS5DP/M 1 55.00
198 AHU-5F.09 Retrurn SVVIP SUIT 650 300 1500 RS5DP/M 1 55.00
199 AHU-5F.10 Supply SVVIP SUIT 650 300 1500 RS5DP/M 1 55.00
200 AHU-5F.10 Retrurn SVVIP SUIT 650 300 1500 RS5DP/M 1 55.00
201 AHU-5F.11 Supply SVVIP SUIT 950 300 1500 RS5DP/M 1 85.00
202 AHU-5F.11 Retrurn SVVIP SUIT 950 300 1500 RS5DP/M 1 85.00
Serving Multiple Floors
203 AHU-R1.01 Supply STAFF SUPPORT 1850 1000 1800 RS6FP 1 305.00
204 AHU-R1.01 Retrurn STAFF SUPPORT 1850 900 1800 RS6FP 1 290.00
205 AHU-R1.02 Supply STAFF SUPPORT 1850 900 1800 RS6FP 1 290.00
206 AHU-R1.02 Retrurn STAFF SUPPORT 1850 900 1800 RS6FP 1 290.00
207 AHU-PU.01 Supply PUBLIC CORRIDORS 1875 1400 2100 RS7FP 1
208 AHU-PU.01 Retrurn PUBLIC CORRIDORS 1875 1250 1800 RS6FP 1 321.00
209 AHU-PU.02 Supply PUBLIC CORRIDORS 1875 1100 1800 RS6FP 1 310.00
210 AHU-PU.02 Retrurn PUBLIC CORRIDORS 1500 1100 1800 RS6FP 1 235.00
211 AHU-PU.03 Supply PUBLIC CORRIDORS 1875 1400 2100 RS6FP 1 355.00
212 AHU-PU.03 Retrurn PUBLIC CORRIDORS 1875 1150 1800 RS6FP 1 315.00
213 AHU-PU.04 Supply PUBLIC CORRIDORS 1500 1400 1800 RS6FP 1 280.00
214 AHU-PU.04 Retrurn PUBLIC CORRIDORS 1500 1350 1800 RS6FP 1 270.00
215 AHU-PU.05 Supply Atrium 1500 1200 1800 RS6FP 1 255.00
216 AHU-PU.05 Retrurn Atrium 1500 1000 1800 RS6FP 1 230.00
HRU
Page 36 of 6
Dimensions (mm) Selected Approximate
Sr # Unit Reference Reference Unit Reference Qty
Width Height Length Attenuator Weight (kg)
217 HRU-B1-05 Supply Waste Management 1200 600 1200 RS4CP 1 115.00
218 HRU-B1-05 Extract Waste Management 1200 600 900 RS3CP 1 90.00
219 HRU-B1-04 Supply CSSD 950 850 1500 RS5DP 1 125.00
220 HRU-B1-04 Extract CSSD 950 800 1200 RS4DP 1 120.00
221 HRU-RF-04 Supply Critical and Instensive care 1950 1400 2400 RS8DP/M 1 537.00
222 HRU-RF-04 Extract Critical and Instensive care 1600 1500 2400 RS8DP/M 1 437.00
223 HRU-GF-01 Supply Trauma 650 600 2400 RS8DP/M 1 113.00
224 HRU-GF-01 Extract Trauma 650 600 2100 RS7DP/M 1 100.00
225 HRU-3F-01 Supply Operating Rooms 650 600 2100 RS7DP/M 1 100.00
226 HRU-3F-01 Extract Operating Rooms 650 600 1800 RS6DP/M 1 85.00
227 HRU-3F-02 Supply Operating Rooms 600 650 1800 RS6CP/M 1 91.00
228 HRU-3F-02 Extract Operating Rooms 600 650 1500 RS5CP/M 1 75.00
229 HRU-4F-02 Supply Operration Rooms 650 600 1800 RS6DP/M 1 85.00
230 HRU-4F-02 Extract Operration Rooms 650 600 1800 RS6DP/M 1 85.00
231 HRU-4F-03 Supply Operration Rooms 650 600 1800 RS6DP/M 1 85.00
232 HRU-4F-03 Extract Operration Rooms 650 600 1800 RS6DP/M 1 85.00
233 HRU-4F-04 Supply Operration Rooms 1300 650 1800 RS6DP/M 1 180.00
234 HRU-4F-04 Extract Operration Rooms 1300 650 1800 RS6DP/M 1 180.00
235 HRU-4F-05 Supply Operration Rooms 650 600 1800 RS6DP/M 1 85.00
236 HRU-4F-05 Extract Operration Rooms 650 600 1800 RS6DP/M 1 85.00
237 HRU-5F-01 Supply VIP Procedure Room 600 600 1500 RS5CP/M 1 71.00
238 HRU-5F-01 Extract VIP Procedure Room 600 600 1500 RS5CP/M 1 71.00
FORENSIC MEDICINE
239 PU-01 Supply FORENSIC MEDICINE 1300 550 1500 RS5DP/M 1 165.00
240 PU-01 Retrurn FORENSIC MEDICINE 1300 500 1500 RS5DP/M 1 162.00
241 PU-02 Supply FORENSIC MEDICINE 950 600 1500 RS5DP/M 1 105.00
242 PU-02 Retrurn FORENSIC MEDICINE 950 550 1500 RS5DP/M 1 105.00
243 PU-03 Supply FORENSIC MEDICINE 950 500 1500 RS5DP/M 1 100.00
244 PU-03 Retrurn FORENSIC MEDICINE 750 500 1500 RS5EP/M 1 65.00
245 PU-04 Supply FORENSIC MEDICINE 750 350 1500 RS5EP/M 1 65.00
246 PU-04 Retrurn FORENSIC MEDICINE 750 350 1500 RS5EP/M 1 65.00
CENTR AL PLANT
247 AHU CP-02 Supply Central Plant Computre A.c. 1000 350 1500 RS5EP 1 70.00
248 AHU CP-02 Retrurn Central Plant Computre A.c. 1000 350 1200 RS4EP 1 65.00
249 AHU CP-03 Supply Central Plant Computre A.c. 650 400 1200 RS4DP 1 50.00
250 AHU CP-03 Retrurn Central Plant Computre A.c. 650 400 900 RS3DP 1 40.00
251 AHU CP-04 Supply Central Plant Computre A.c. 650 350 1200 RS4DP 1 48.00
252 AHU CP-04 Retrurn Central Plant Computre A.c. 650 350 900 RS3DP 1 40.00
256
37
38