Documente Academic
Documente Profesional
Documente Cultură
Internship Report on
Submitted By
Name USN
SAHANA KULKARNI 2KE16EE027
SAHANA SANGAM 2KE16EE028
SANJAY HIREMATH 2KE16EE033
SHASHIKALA. S. K 2KE16EE039
SHWETA. D 2KE16EE043
SHWETHA. S. BALIGAR 2KE16EE044
SPOORTI JADAV 2KE16EE045
SRINIDHI JOSHI 2KE16EE046
SUSHMA. K 2KE16EE049
TRUPTI. M 2KE16EE050
Subject Code:15EE84
CERTIFICATE
This is certified that the work of Internship a bonafide work carried out at HESCOM by
SAHANA KULKARNI(2KE16EE027), SAHANA SANGAM(2KE16EE028), SANJAY
HIREMATH(2KE16EE033), SHASHIKALA S K(2KE16EE039), SHWETA D(2KE16EE043),
SHWETHA S BALIGAR((2KE16EE044), SPOORTI JADHAV(2KE16EE045), SRINIDHI
JOSHI(2KE16EE046), SUSHMA K(2KE16EE049), TRUPTI M(2KE16EE050)of Electrical and
Electronics Engineering KLEIT, Hubballi during the Academic year 2019-20. The report has
reached the standard, fulfilling the requirements.
We are also thankful to Dr. Sharad G Joshi, Dean Academics, for creating right kind
of milieu and giving moral support.
We are also thankful to Dr. Vinoda S., Head of Electrical and Electronics Engineering
Department, who has given valuable suggestions during the work and her moral support
and encouragement.
We are very much thankful to Hon’ble MD, HESCOM, for providing an opportunity to
carry out our internship in your esteemed organization.
We are thankful for Mr. Jagadeesh Belagali, GM (Technical) HESCOM, for your
guidance to allot an internship.
We are thankful for Mr. S. Rangaraju, Executive Engineer, DSM and R&D section,
HESCOM, for providing regular input, guidance and also monitoring the work flow.
We are also thankful for all the supporting staff of HESCOM who contributed directly
or indirectly for completion of the internship
We are also thankful to my guide Prof. Kumar Swamy V, Department of Electrical
and Electronics Engineering for his encouragement, effective guidance and valuable
suggestions right from the beginning of the seminar till its completion, without which
this internship work would not have been accomplished. We are greatly indebted to him.
We would like to express my heart full thanks to all the teaching faculty and staff
members of the department of Electrical and Electronics Engineering for constructive
suggestion and constant encouragement.
We also thank to my parents and all my friends wholeheartedly who have rendered their
help, motivation and support to accomplish this work.
ABSTRACT
This report describes the work carried in HESCOM, Hubballi. HESCOM is the Hubli
electricity supply company. The various activities of the HESCOM viz., different
substation , electrical stores, Billing section and other major work has been studied with
respect to energy. This report also covers the fundamental aspects of power requirement
towards the consumer. The main objective of this report is to present a systematic flow of
different machineries involved in substations , maintenance of transformer and overall
functioning the distributing company HESCOM, Hubli.
CONTENTS
Chapter No. Page No.
1. Introduction 1
1. INTRODUCTION
1.1 Background of HESCOM:
Hubli Electricity Supply Company Limited (HESCOM) is a power distribution company in
the state of Karnataka serving seven districts. It was formed in the year 2002 under the Companies Act
1956. HESCOM has the sole responsibility for power distribution in Dharwad, Gadag, Bijapur, Bagalkot,
Uttar Kannada, Haveri and Belgaum districts of Karnataka.
The Karnataka Power Transmission Corporation Limited, also known as KPTCL, is the
sole electricity transmission and distribution company in state of Karnataka. Its origin was in Karnataka
Electricity Board (KEB). Until 2002, the Karnataka Electricity Board handled electricity transmission and
distribution across the state. It was then broken up, with Karnataka Power Transmission Corporation Ltd
(KPTCL) established to manage the transmission business. This electricity transmission and distribution
entity was corporatized to provide efficient and reliable electric power supply to the people of Karnataka
state. HESCOM covers an area of 54513 Sq. Km. serving a population of over 14 millions.
1.2 Vision:
To provide 24 Hours Power Supply to all the consumers by the year 2020
1.3 As a part of the reforms, the distribution sector was further divided into 5
companies viz.
The Karnataka Power Transmission Corporation Limited, also known as KPTCL, is the sole
electricity transmission and distribution company in state of Karnataka. Its origin was in Karnataka
Electricity Board. Until 2002, the Karnataka Electricity Board (KEB) handled electricity transmission
and distribution across the state. It was then broken up, with Karnataka Power Transmission
Corporation Ltd (KPTCL) established to manage the transmission business. This electricity
transmission and distribution entity was corporatized to provide efficient and reliable electric power
supply to the people of Karnataka state. Company is governed under the purview of Ministry of
Energy. KPTCL buys power from power generating companies like Karnataka Power Corporation
Limited (KPCL) and other IPPs (Independent Power Producers) like GMR, Jindal, Lanco (UPCL) etc.,
and sell them to their respective ESCOMS.
HESCOM – Hubli Electricity Supply Company Limited is responsible for power distribution in
7 districts of Karnataka, namely, Dharwad, Gadag, Bijapur, Bagalkot, Uttar Kannada, Haveri and
Belgaum. HESCOM covers an area of 54513 Sq.Kms. with a population of over 1.66 Crores. The
company has 2 operating zones – Hubli and Belgaum, 7 Circles, 16 Divisions.Hubli Electricity Supply
Company Limited (HESCOM) has taken over the responsibility from KPTCL for the distribution of
electricity in 7 districts and commenced its operation from 1 st June 2002.
1.4 Day wise report of work carried out during internship at HESCOM:
1. 15/07/2019 to 18/07/2019
At the starting 4days of our internship we had been to 33kv/11kv Substation at Industrial Estate.
We learnt about the various components installed at the substation and their function.
2.19/07/2019 to 20/07/2019
Next we had been to 220/110/33/11kv Substation at Sharavati Receiving Station (SRS).There we
Witnessed method of monitoring the station and its control by SCADA technology. We were also
given knowledge about various Acts on Electricity, KERC rules and regulations, theft of electricity
Dept. of EEE, KLEIT, Hubballi Page 3
HESCOM: Hubballi Electricity Supply Company
etc. We came to know about material inspection, different types of conductors, insulators etc.
3.22/07/2019 to 24/07/2019
Later we had been to City sub-division-3 at Industrial Estate Hubballi. The AEE of subdivision office
Explained about various wings involved in the functioning of the company like Corporate Office,
Revenue section, Technical, Accounts etc. We also learnt about the billing of electricity, HT
installation process etc.
4.25/07/2019 to 31/07/2019
Later we had been to Rural and Urban Sub-division at Tabib land, Hubballi. With the permission of
AEE of this division we had been to Anchatageri village to attend awareness program on the usage of
electricity organized to the people of that village. Later we learnt about the effective means to install
transformers at different site locations like at layouts, apartments, commercial buildings etc. Also
understood the lying of underground and overhead cables.
5. 01/08/2019 to 03/08/2019
Later we had been to Meter and Relay Testing Division at SRS. We studied various sub-divisions
Functioning for testing division such as LT rating sub-division, HT rating sub-division, Breakdown
sub-division, Laboratory sub-division etc. Also learnt about Electro-mechanical meters and their
protection.
Lightning arrester diverts the abnormal high voltage to the ground without affecting the continuity
of supply. It is connected between the line and earth, i.e., in parallel with the equipment to be protected at
Dept. of EEE, KLEIT, Hubballi Page 5
HESCOM: Hubballi Electricity Supply Company
the substation.When a travelling wave reaches the arrestor, its sparks over at a certain prefixed voltage as
shown in Fig1. The arrestor provides a conducting path to the waves of relatively low impedance between
the line and the ground. The surge impedance of the line restricts the amplitude of current flowing to
ground. The lightning arrester provides a path of low impedance only when the travelling surge reaches the surge
diverter, neither before it nor after it.
2.2.2 Circuit Breaker: A circuit breaker is a switching device that interrupts the abnormal or fault current.
It is a mechanical device that disturbs the flow of high magnitude (fault) current and in additions performs
the function of a switch. The circuit breaker is mainly designed for closing or opening of an electrical
circuit, thus protects the electrical system from damage.
Circuit breaker essentially consists of fixed and moving contacts. These contacts are touching each other
and carrying the current under normal conditions when the circuit is closed. When the circuit breaker is
closed, the current carrying contacts, called the electrodes, engaged each other under the pressure of a
spring. The figure of circuit breaker is as shown in Fig 3.Whenever a fault occurs on any part of the system,
the trip coil of the breaker gets energized and the moving contacts are getting apart from each other by
some mechanism, thus opening the circuit.
2.2.3 Bus bar: In electric power distribution, a bus bar is a metallic strip or bar, typically housed
inside switchgear, panel boards, and bus way enclosures for local high current power distribution.
The above Fig4 shows the typical diagram of bus bars. They are also used to connect high voltage
equipment at electrical switchyards, and low voltage equipment in battery banks. They are generally non-
insulated, and have sufficient stiffness to be supported in air by insulated pillars. These features allow
sufficient cooling of the conductors, and the ability to tap in at various points without creating a new joint.
The material composition and cross-sectional size of the bus bar determine the maximum amount of
current that can be safely carried. Bus bars can have a cross-sectional area of as little as 10 square
millimeters (0.016 sq in), but electrical substations may use metal tubes 50 millimeters (2.0 in) in diameter
(20 square millimeters (0.031 sq in)) or more as bus bars. An aluminium smelter will have very large bus
bars used to carry tens of thousands of amperes to the electrochemical cells that produce aluminium from
molten salts.
Fig 5: CVT
In its most basic form, the device consists of three parts: two capacitors across which the
transmission line signal is split, an inductive element to tune the device to the line frequency as shown in
the Fig 5. A voltage transformer is used to isolate and further step down the voltage for metering devices
or protective relay.
The tuning of the divider to the line frequency makes the overall division ratio less sensitive to
changes in the burden of the connected metering or protection devices.[1] The device has at least four
terminals: a terminal for connection to the high voltage signal, a ground terminal, and two secondary
terminals which connect to the instrumentation or protective relay.
Capacitor C1 is often constructed as a stack of smaller capacitors connected in series. This provides a large
voltage drop across C1 and a relatively small voltage drop across C2. As the majority of the voltage drop
is on C1, this reduces the required insulation level of the voltage transformer.
2.2.5 Wave Trap: Wave trap is used to create high impedance to the carrier wave high
frequency communication entering in to unwanted destinations typically substation. Carrier
wave communication uses up to 150 kHz to 800 kHz frequency to send the all the communication. These
high frequency damages the power system components which are designed to operate 50 or 60 Hz.
Wave traps are also called as line traps. It consists of an inductor coil which is connected in
series with the high voltage power system as shown in Fig 6.
Main Coil is nothing but an outer part of the wave trap circuits and which is made from
stranded aluminum cable. If the application of more than one layer is necessary, separation between layers
is required to provide a cooling duct between them to avoid overheating. The cooling duct is created with
spacer bars made out of epoxy resin and fiberglass. The coil carries rated continuous power
frequency currents, therefore this is the power inductor in this system. It provides a low impedance path
for the electricity flow. The total current carrying capacity of the transmission system will be calculated,
and the trap coil are designed according to that. That’s why the coil become bigger size as you can see in
High voltage transmission.
2.2.6 Instrument Transformer: Instrument transformers are high accuracy class electrical devices used
to isolate or transform voltage or current levels. The most common usage of instrument transformers is to
operate instruments or metering from high voltage or high current circuits, safely isolating secondary
control circuitry from the high voltages or currents. The primary winding of the transformer is connected
to the high voltage or high current circuit, and the meter or relay is connected to the secondary circuit as
shown in Fig 7.
These are further classified into two types which are discussed below.
a. Current Transformers
b. Potential Transformers
A. Current Transformer: a typical Current Transformer is shown in Fig 8. A Current Transformer (CT)
is a type of transformer that is used to reduce or multiply an C (AC). It produces a current in its secondary
which is proportional to the current in its primary. Current transformers, along with voltage or potential
transformers are instrument transformers.
Instrument transformers scale the large values of voltage or current to small, standardized values
that are easy to handle for measuring instruments and protective relays. The instrument transformers
isolate measurement or protection circuits from the high voltage of the primary system.
A current transformer provides a secondary current that is accurately proportional to the current
flowing in its primary. The current transformer presents a negligible load to the primary circuit. Current
transformers are the current-sensing units of the power system and are used at generating stations,
electrical substations, and in industrial and commercial electric power distribution.
B. Potential Transformer: A typical Potential Transformer is shown in Fig 9. Potential transformer is a
voltage step-down transformer which reduces the voltage of a high voltage circuit to a lower level for the
purpose of measurement. These are connected across or parallel to the line which is to be monitored.
Compared to the conventional transformer, potential transformers or PTs use larger conductor sizes and
core. PTs designed for ensuring the greater accuracy and hence, at the time of designing economy of the
material are not considered as main aspect. PTs are made with special high quality core operating at lower
flux densities in order to have small magnetizing current so that no load losses are minimized. Both core
and shell type constructions are preferred for PTs. For high voltages, core type PTs are used while shell
type is preferred for low voltages
2.2.7 Transformer
The above Fig10 the depicts the power transformer. The transformer is transported on trailer to
substation site and as far as possible directly unloaded on the plinth. Transformer tanks up to 25 MVA
capacity are generally oil filled, and those of higher capacity are transported with N2 gas filled in them
positive pressure of N2 is maintained in transformer tank to avoid the ingress of moisture. This pressure
should be maintained during storage, if necessary by filling N2 Bushings - generally transported in wooden
cases in horizontal position and should be stored in that position. There being more of fragile material,
care should be taken while handling them. Radiators – These should be stored with ends duly blanked
with gaskets and end plates to avoid in gross of moisture, dust, and any foreign materials inside. The care
should be taken to protect the fins of radiators while unloading and storage to avoid further oil leakages.
The radiators should be stored on raised ground keeping the fins intact.
The Oil piping should also be blanked at the ends with gasket and blanking plates to avoid in gross
of moisture, dust, and foreign All other accessories like temperature meters, oil flow indicators, PRVs,
buchholz relay; oil surge relays; gasket ‘ O ‘ rings etc. should be properly packed and stored indoor in
store shed. Oil is received in sealed oil barrels. The oil barrels should be stored in horizontal position with
the lids on either side in horizontal position to maintain oil pressure on them from inside and subsequently
avoiding moisture and water ingress into oil. The transformers are received on site with loose accessories
hence the materials should be checked as per bills of materials.
2.2.8 Isolator: The isolator is one type of switching device, and the main function of this is to make sure
that a circuit is totally not triggered in order to perform the preservation. These are also recognizable like
isolation switches to isolate the circuits as shown in Fig 11. These switches are applicable in industrial,
distribution of electrical power, etc. High voltage type isolation switches are utilized in substations for
permitting isolation of equipment like transformers, circuit breakers. Usually, the disconnector switch is
not proposed for circuit control but it is for isolation. Isolators are activated either automatically or
manually.
The isolator can be defined as; it is one type of mechanical switch used to isolate a fraction of
the electrical circuit when it is required. Isolator switches are used for opening an electrical circuit in the
no-load condition. It is not proposed to be opened while current flows through the line. Generally, these
are employed on circuit breaker both the ends thus the circuit breaker repair can be done easily without
any risk.
2.2.9 Control and Relay Panel: The Fig 12 shows control and relay panel employed in substations.
Control and Relay panel is most important equipment of the substation as it works as shield guard for all
substation equipments and electrical network. Moreover, these panels are useful to control the flow of
electricity as per the Voltage class and detect the faults in transmission lines.
2.2.10 Protective Relays: Fig 13 shows the protective relays. In electrical engineering, a protective relay
is a relay device designed to trip a circuit breaker when a fault is detected. The first protective relays were
electromagnetic devices, relying on coils operating on moving parts to provide detection of abnormal
operating conditions such as over-current, over-voltage, reverse power flow, over-frequency, and under-
frequency.
Microprocessor-based digital protection relays now emulate the original devices, as well as
providing types of protection and supervision impractical with electromechanical relays.
Electromechanical relays provide only rudimentary indication of the location and origin of a fault. In many
cases a single microprocessor relay provides functions that would take two or more electromechanical
devices. By combining several functions in one case, numerical relays also save capital cost and
maintenance cost over electromechanical relays. However, due to their very long life span, tens of
thousands of these "silent sentinels" are still protecting transmission lines and electrical apparatus all over
the world. Important transmission lines and generators have cubicles dedicated to protection, with many
individual electromechanical devices, or one or two microprocessor relays.
Protective relays can also be classified by the type of measurement they make. A protective relay may
respond to the magnitude of a quantity such as voltage or current. Induction relays can respond to the
product of two quantities in two field coils, which could for example represent the power in a circuit.
It is not practical to make a relay that develops a torque equal to the quotient of two AC quantities.
This however is not important; the only significant condition for a relay is its setting and the setting can
be made to correspond to a ratio regardless of the component values over a wide range.
Several operating coils can be used to provide "bias" to the relay, allowing the sensitivity of response in
one circuit to be controlled by another. Various combinations of "operate torque" and "restraint torque"
can be produced in the relay.
By use of a permanent magnet in the magnetic circuit, a relay can be made to respond to current in
one direction differently from in another. Such polarized relays are used on direct-current circuits to detect,
for example, reverse current into a generator. These relays can be made bistable, maintaining a contact
closed with no coil current and requiring reverse current to reset. For AC circuits, the principle is extended
with a polarizing winding connected to a reference voltage source.
2.2.11 DC Battery and Charger: All but the smallest substations include auxiliary power supplies. AC
power is required for substation building small power, lighting, heating and ventilation, some
communications equipment, switchgear operating mechanisms, anti-condensation heaters and motors.
The above Fig 14 shows the DC battery set used to control substation. DC power is used to feed
essential services such as circuit breaker trip coils and associated relays, Supervisory Control and Data
Acquisition (SCADA) and communications equipment. This describes how these auxiliary supplies are
derived and explains how to specify such equipment. It has Single 100% battery and 100% charger, Low
capital cost, No standby DC System outage for maintenance. Need to isolate battery/charger combination
from load under boost charge conditions in order to prevent high boost voltages.
There are quite a few different aluminium conductor steel reinforced cables. There was a table
generated back in the 1970s that describes every aspect of their construction. They have given all of them
code words, such as popular ACSR coyote conductor, ACSR dog conductor and so on. They are still used
today, making it easier to place orders when you are making a purchase. When you are going to buy coyote
wire, you can ask if the supplier can provide ACSR coyote conductor free samples. That can help you to
know if they are meet your requirements. Each of the tables will discuss different aspects of the cable
including nominal copper and aluminium in the cables themselves. They will discuss the different types
of conductors, which would be aluminium or steel, as well as the diameter and approximate weight of
these cables per a certain lengthwise measurement. These conductors are also called size AWG. The
diameter of the aluminium and steel wires are identical. It uses in 18 to 1 stranding arrangement, and they
are extremely efficient when it comes to longevity and the delivery of electricity. They can have a
maximum length of the thousand feet. Once you have evaluated the different companies that sell ACSR
osprey conductors, you will likely find that huadong is the best. On the one hand, our products are in line
with the international standards. On the other hand, Huadong ASTM osprey conductor price is very
reasonable.
Fig 15(a): ASCR Coyote Conductor Fig 15(b): ACSR Rabbit Conductor
3.2 Insulators: Electrical Insulator must be used in electrical system to prevent unwanted flow of
current to the earth from its supporting points. The insulator plays a vital role in electrical system.
3.3.2 Suspension type Insulator: As the voltage level increases, pin type insulators become very
bulky and their cost also increases rapidly. Hence the most popular insulators used for very high
voltage transmission lines are suspension type insulators which are suspended as shown in Fig 18.
In the cemented cap type there is a metal cap at the top and a metal pin underneath as shown in Fig
19. To form a string, the cap is so recessed that it can take the pin of another unit. The upper surfaces
of all types of insulators are so shaped that water will drop down from the surface easily.
In the Hewlett type of design each disc has two curved tunnels lying in planes at right angles
to each other as shown in Fig 20. Steel U-shaped links covered with lead are threaded into these
tunnels. They are fastened to similar links to other discs in the string. The Hewlett type insulator is
more reliable than the cemented cap type, but the porcelain in this case is subjected to higher
electrostatic stress and hence liable to puncture more than the cemented cap type.
3.3.3 Strain type Insulator: A strain insulator is an electrical insulator that is designed to work in
mechanical tension (strain), to withstand the pull of a suspended electrical wire or cable. They are
used in overhead electrical wiring, to support radio antennas and overhead power lines. A strain
insulator may be inserted between two lengths of wire to isolate them electrically from each other
while maintaining a mechanical connection, or where a wire attaches to a pole or tower, to transmit
the pull of the wire to the support while insulating it electrically. Strain insulators were first used in
telegraph systems in the mid 19th century.
as spool insulators. Shackle Insulators are used at the end of distribution lines or at sharpturns where
there is excessive tensile load on the lines. These insulators can be mounted either in the vertical or
horizontal position as shown in Fig 22. The Shackle Insulator is mounted axially. The loading is on
circumferential grooves in the insulator. The conductor is secured in the groves by means of soft-
bending wires. The insulators are bolted to the cross-arm of the pole.
Underground cables are used for power applications where it is impractical, difficult, or dangerous to
use the overhead lines. They are widely used in densely populated urban areas, in factories, and even
to supply power from the overhead posts to the consumer premises.
Classification by Voltage:
LT cables: Low-tension cables with a maximum capacity of 1000 V
Extra super voltage cables: with maximum voltage ratings beyond 132 KV
Classification by Construction:
Belted cables: Maximum voltage of 11KVA
Classification by Insulation:
Various insulating materials used in cable construction are Rubber, Paper, PVC, XLPE (Cross linked
Polyethene) etc. Such classification is based upon operating temperature limitations. Following are
some insulating materials used and their maximum operating temperatures.
XLPE 90°C
RUBBER 90°C
RUBBER – EPR IE-2, EPR IE-3, EPR IE-4, SILICON IE-5 150°C
The gaps between the conductors and the paper insulation are filled with fibrous material such as the
jute. This makes the cable to have a circular cross-sectional shape.
A lead sheath is used to cover the belt hence protect it from moisture and provide mechanical strength.
The lead sheath is then covered with a single or multiple layers of an armoring material and finally
an outer cover.
The weakening of the insulation may lead to the formation of air spaces in the insulation. Under high
voltages the air may be ionized and cause deterioration and breakdown of insulation. For this reason,
the belted cables are only suitable for voltages up to 11KVa and not higher.
H Type Cables: In a typical 3-core cable, each of the three cores is insulated by impregnated paper
and covered by perforated aluminum foil or other metallic screen. The arrangement of the cores is
designed to allow each of the three metallic screens to make contact with each other. The three cores
are then wrapped around using a conduction belt made of copper woven fabric tape.
The H-type screened cable does not have an insulating belt; however, it has the lead sheath, followed
by bedding, armoring and a then a serving. The core screens in the cable are all electrically connected
to both the conducting belt and the lead sheath.
S.L Type Screened Cable: The S.L type cables construction is almost like that of the H-type,
however, each of the insulated cores is covered separately with its own lead sheath. Unlike the H-
type, the S.L screened cable does not have an overall sheath, however it has the armoring and serving.
Pressure Cables: These are high power cables used for voltages above 66KV. The cable construction
is different from the above two and majority uses a cooling gas or oil.
1. Suitable for congested urban areas where overhead lines may be difficult or impossible to install
2. Low maintenance
4. Fewer faults
5. Not susceptible to shaking and shorting due to vibrations, wind, accidents, etc.
1. More expensive.
2. Difficult in identifying and repairing broken cables Damage to cables or electrocution may occur
to people digging the ground and if they are unaware of the cable’s existence.
The Fig 24 shows the single line diagram of 33/11kv substation at Industrial Estate. Industrial Estate
has 33/11Kv Master Unit Substation (MUSS).The Substation has two incoming lines from Tarihal
and Sharavati Receiving Station (SRS), and has seven outgoing feeders which supply power to nearby
industrial estate areas. The substation has one 5MVA Transformer and 11Kv/440V Distribution
Transformer. The battery charging set has total 55 batteries of 2V capacity each.
Circuit Breaker 33KV and 11KV Protects from over currents or over load due to
5 SF6 33kv, short circuit
9 vacuum 11kv
Bus Bars 33KV and 11KV To distribute electric power from supply point to
2 33kv, 111kv output circuits
The Fig 25 shows the single line diagram of 220/110/33/11kv substation at SRS. Sharavati Receiving
Station consist of 220/110/33/11Kv Substation. It has 9 incoming lines that is 3 from Nagjari, 2 from
Narendra,2 from Bidnal and 2 from Sirsi and has 9 outgoing lines supplying power to Anand Nagar,
Industrial Estate, Saunshi and other areas. The battery charging set has total 110 batteries of 2V
capacity each.
6.1.1 Laminated Core: The laminated core is as shown in the Fig27. Eddy current losses within a
transformer core cannot be eliminated completely, but they can be greatly reduced and controlled by
reducing the thickness of the steel core. Instead of having one big solid iron core as the magnetic core
material of the transformer or coil, the magnetic path is split up into many thin pressed steel shapes
called “laminations”. The laminations used in a transformer construction are very thin strips of
insulated metal joined together to produce a solid but laminated core as we saw above. These
laminations are insulated from each other by a coat of varnish or paper to increase the effective
resistivity of the core thereby increasing the overall resistance to limit the flow of the eddy currents.
The result of all this insulation is that the unwanted induced eddy current power-loss in
the core is greatly reduced, and it is for this reason why the magnetic iron circuit of every transformer
and other electro-magnetic machines are all laminated. Using laminations in a transformer
construction reduces eddy current losses.
6.1.2 Windings: There are different types of windings used for different kinds of applications and
arrangements. Windings are the conductors wrapped in various forms like helical, disc, cylindrical,
crossover which generates mmf that is carried by the core to other windings for having the different
level of voltages. Windings are wounded as shown in Fig 28.
In core type, we wrap the primary, and the secondary winding on the outside limbs and in shell type
we place the primary and secondary windings on the inner limbs. Concentric type windings are used
in core type transformer. Low voltage winding is placed near to the core. However, to reduce leakage
reactance, windings can be interlaced. Winding for core type depends on many factors like current
rating, short circuit withstand capacity, limit of temperature rise, impedance, surge voltage, transport
facilities, etc.
There are different types of Windings:
Cylindrical windings are layered type and uses rectangular or round conductor. The
conductors are wound on flat sides and wound on the rib side. Cylindrical windings are low
voltage windings used up to 6.6 kV for kVA up to 600-750, and current rating between 10 to
600A.
We use helical windings low voltage, high capacity transformers, where current is higher, at
the same time windings turns are lesser. The output of transformer varies from 160 – 1000
kVA from 0.23-15 kV. To secure adequate mechanical strength the cross-sectional area of the
strip not made less than 75-100 mm square. The maximum number of strips used in parallel
to make up a conductor is 16.
Single Helical Windings consist of winding in an axial direction along a screw line with an
inclination. There is only one layer of turns in each winding. The advantage of Double Helical
Winding is that it reduces eddy current loss in conductors. This is on account of the reduced
number of parallel conductors situated in the radial direction.
In Disc-Helical Windings, the parallel connected strips are placed side by side in a radial
direction to occupy total radial depth of winding.
Multi layer helical winding is used for high voltage ratings for 110 kV and above. These types
of winding consist of several cylindrical layers concentrically wound and connected in series.
Cross over windings for high voltage windings of small transformers. The conductors are
paper covered round wires or strips. The windings are divided into a number of coils in order
to reduce voltage between adjacent layers.
heat insulating materials. Thermal preservation is to prevent heat from spreading or losing, whereas
heat insulation is to prevent external heat from entering. According to chemical composition, thermal
insulating materials are classified to inorganic, organic and composite. Inorganic thermal insulating
materials adopt minerals as raw materials, usually in fibrous form and porous form, and can be
produced into panels, sheets, coils or pipe shells. Organic insulating materials are made of organic
raw materials (kinds of resins, corks, wood-wools and wood chips etc.).
6.1.4 Conservator: This is a cylindrical tank mounted on supporting structure on the roof the
transformer main tank as shown in Fig 30. The main function of conservator tank of transformer is to
provide adequate space for expansion of oil inside the transformer.
6.1.5 Breather: The breather is shown in Fig 31. Silica gel Breather is cylindrical type container
which is fitted to the conservator tank through a pipe line which is totally filled with silica gel crystals
used for absorbing any moisture present in the air during breathing action of transformer due to
expansion and contraction of transformer oil in the transformer. The size of Breather depends on the
volume of transformer main tank as well as quantity of transformer oil in the transformer. A oil pot
is connected under the breather.
When the Silica gel breather is first installed, the crystals have a blue tint, and after a period of
operation, the color of the tinted crystals gradually changes to pink , this is an indication that the silica
gel is becoming saturated and losing its absorbent properties. When there is a preponderance of pink
crystals the silica gel should be changed or reactivated.
6.1.6 Tap Changer: The purpose of a tap changer is to regulate the output voltage of a transformer.
It does this by altering the number of turns in one winding and thereby changing the turn’s ratio of
the transformer. There are two types of transformer tap changers: an on-load tap changer (OLTC) and
a de-energized tap changer (DETC). Note that not all transformers have tap changers. Fig 32 shows
a tap changer.
An OLTC varies the transformer ratio while the transformer is energized and carrying
load. The switching principle uses the “make before break” contact concept. An adjacent tap is
bridged before breaking contact with the load carrying tap for the purpose of transferring load from
one tap to the other without interrupting or appreciably changing the load current. While in a bridging
position (i.e., contact is made with two taps), some form of impedance (resistive or reactive) is present
to limit circulating current. A high speed resistive type OLTC uses a resistor pair to absorb energy
and does not use the bridging position as a service position. A reactive type OLTC uses a reactor that
is designed for continuous loading, e.g., a preventative autotransformer, and therefore uses the
bridging position as a service position.
6.1.7 Cooling Tubes: Cooling tubes are used to cool the transformer oil. They are as shown in Fig
33. The transformer oil is circulated through the cooling tubes. The circulation of the oil may either
be natural or forced. In natural circulation, when the temperature of the oil rises the hot oil naturally
rises to the top and the cold oil sinks downward. Thus the oil naturally circulates through the tubes.
In forced circulation, an external pump is used to circulate the oil.
6.1.8 Buchholz Relay: Buchholz relay in transformer is an oil container housed the connecting pipe
from main tank to conservator tank. It has mainly two elements. The upper element consists of a float.
The float is attached to a hinge in such a way that it can move up and down depending upon the oil
level in the Buchholz relay Container. Buchholz relay is shown in Fig 34.
One mercury switch is fixed on the float. The alignment of the mercury switch hence depends upon
the position of the float. The lower element consists of a baffle plate and mercury switch. This plate
is fitted on a hinge just in front of the inlet (main tank side) of Buchholz relay in transformer in such
a way that when oil enters in the relay from that inlet in high pressure the alignment of the baffle plate
along with the mercury switch attached to it, will change.
6.1.9 Explosion Vent: An explosion vent or rupture panel is a safety device to protect equipment or
buildings against excessive internal, explosion-incurred pressures, by means of pressure relief. An
explosion vent will relieve pressure from the instant its opening (or activation) pressure has been
exceeded.
Several explosion vent panels can be installed on the same process vessel to be protected.
Explosion vents are available in the versions self-destructive, non-self-re-closing and re-usable, self-
re-closing.
Fig 35 shows the diagram of explosion vent. Explosion vent construction must balance the
contradictory requirements "low inertia" and "high strength". Inertia negatively affects an explosion
vent's efficiency. High strength is required to endure the considerable forces that move the vent's
venting element in order to open the venting orifice. Unintended disintegration must not cause
disintegrating parts turning into a missile.
6.2 Transformer ratings observed at SRS and industrial Estate
Substations .
Nagjari- 3
Narendra - 2
Bidnal - 2
Sirsi - 2
SRS has 9 outgoing lines :Ramanakoppa,Bidnal 1,Bidnal 2,P H compound (These are from 110 kV
lines).Kalaghatagi,Kadanakoppa,Anandnagar/Akshaya colony,Tarihal 1 and Tarihal 2 (These are
from 33 kV lines).
F1 - Anchatageri
F2 - Auxillary 1
F3 - Siddharudha
F4 - Kalaghatagi
F5 - ESI
F6 -Auxillary 2
F7 - M R T
F8 - Giriyal
F9 - Hubli city
F10 - Kundagol
5 MVA Transformer details from 33/11 kV substation, CSD – 3, Industrial area Hubballi.
Pour Point
Density
Kinematic Viscosity
The details of conducting these tests are available in standards released by IEC, ASTM, IS, BS, and
testing can be done by any of the methods. The Furan and DGA tests are specifically not for
determining the quality of transformer oil, but for determining any abnormalities in the internal
windings of the transformer or the paper insulation of the transformer, which cannot be otherwise
detected without a complete overhaul of the transformer. Suggested intervals for these test are:
General and physical tests - bi-yearly
Dissolved gas analysis - yearly
Furan testing - once every 2 years, subject to the transformer being in operation for min 5
years.
A substation contains a number of electrical devices and equipment. It is essentially made of power
transformers, switchgear, protective and measuring instruments. The Substation equipment must
receive a high standard of maintenance in terms of quality and not quantity. The current practices of
substation maintenance are basically following the principle of time-based preventive maintenance
(TBPM), which is doing routine checks and inspections at fixed intervals.To improve the reliability
of electric supply it is important to reduce the time needed for the restoration of the ability of
supplying power after failure of components or due to general maintenance work.Therefore,
substations must operate effectively while minimizing and reducing costly maintenance.With a well-
organized preventive Maintenance (PM) program, potential hazards that can cause failures of
equipment or interruptions of electrical services can be discovered and corrected.The goal of the
substation PM program is to ensure that the entire substation’s equipment will function properly when
called upon to operate.
Substation has many components, among which power transformer is chief. The maintenance of
power transformer is carried out by conducting various tests.
The following tests and inspections were considered for the power transformer.
Dept. of EEE, KLEIT, Hubballi Page 46
HESCOM: Hubballi Electricity Supply Company
The other maintenance systems used in the substation and their functions are given below:
2. Overhead earth wire shielding To protect the outdoor substation equipment from
or Lightning masts. lightning strokes.
9. Auxiliary standby power For supplying starting power, standby power for
system. auxiliaries.
10. Fire Fighting system - Sensors, To sense the occurrence of fire by sensors and to
detection system - water spray initiate water spray, to disconnect power supply to
system - fire port, panels, alarm affected region to pinpoint location of fire by
System. - water tank and spray indication in control room.
system.
The role of the meter Testing Division is very important to enhance revenue and also to reduce the
commercial losses of the distribution company. It is necessary that the testing, maintenance,
rectification of faults, periodical checking of the meters and metering equipments shall be carried out
and recorded in proper formats so as to know the history of their performance and hence the follow
up actions.
Metering is to be done very accurately so that there is no revenue loss. This applies to not only meters
but also to instrument current and potential transformers. Most of the meters used in high value
consumer installations are tri-vector meters measuring three vital parameters for assessing the cost of
energy.
Today Energy accountability is important than ever before hence the importance of the Energy meter.
Hence its time "not to ask what a meter cost", "ask what is the cost not to meter".
Energy Meter is a device that measures the amount of electrical energy consumed by residence or
commercial unit over a period of time.
Energy=Power *Time.
The most common unit of measurement on the electricity meter is the kilowatt hour, which is
equal to the amount of energy used by a load of one kilowatt over a period of one hour, or
36,00,000 Joules.
As per the tariff adopted by the KERC at present, the following types of meter are in use for
record/billing purpose
Single phase meters and three phase four wire meters are used for measuring energy in single
phase and three phase loads of LT(low tension), HT(high tension) and EHT consumers with balanced
and unbalanced loads, while three phase three wire meters are used in consumer installations with
balanced loads. The potential transformers used in HT consumers are rated for 110volts on secondary.
Railways are exceptional HT consumer with two phase HT supply for their electrification works.
Single phase supply is availed by the domestic, commercial and small power consumers while three
phase supply either LT or HT is availed by major consumers for industrial, agricultural and other
purposes.
Single phase and three phase whole current meters are connected directly to the supply voltage.
Three phase three wire & three phase four wire meters are generally connected with CTs or
combination of CTs &PTs. Current Transformers are used to limit the flow of load current directly
through the meter when the line currents are high and to reduce the terminal losses. PTs are used for
metering purpose, when the supply voltages are more than 400volts.
This is to ensure the safety because of the insulation problem. The single and poly phase meters
provide energy value in kWh maximum demand values in kVA or kW with integration period of 15
or 30 minutes. The energy meters installed at consumer terminal provide a basis for the billing of the
energy consumed. The Meter reading helps in the computation of energy loss in the distribution
system. Measurement of error means loss of revenue. The monetary loss by way of replacement of
defective meters and metering equipments, short billing of energy based on the consumption shown
by the defective metering is generally high.
The defects or faults in the energy meters and metering equipments arise due to improper design,
unscientific practices in manufacturing process, improper installation & commissioning, in adequacy
of proper testing, improper maintenance and operational exigencies etc. The tamper practices in the
metering system accounts to substantial loss of revenue.
Fig 39: Different types of Energy meters High and Low Tension
i. Electromechanical meter
It consists of an aluminium disc positioned between two electromagnets, one of whose coils is
connected to the load and is the current coil and the coil of another electromagnet is connected to
the supply voltage
The interaction of the fluxes between the two coils is responsible for providing a torque to the
disc, which starts rotating, with the revolutions proportional to the load current.
The counter records the number of revolutions and displays them, which indicates the energy
consumed.
It consists of current and voltage sensors which sense the amount of current and voltage consumed
and this analogue signal is sampled and digitized using ADCs.
The digital signals are then processed using a DSP or a Microcontroller, which then displays the
amount of energy consumed on an LCD or a LED display. Even though after replacement of
digital meters has not changed the system. A person from the electricity department goes to one
and every house and reads the wattage consumed and gives a printed slip of electricity bill. It is
not even get ended here, for the payment consumer has to stand in a line at the municipal offices
for hours.
Cost efficient and can reduce problems associated with billing like No bill production, No bill
distribution.
No LOAD(CREEP) TEST
Starting TEST
Repeatability ERROR TEST
Earth (Ground) Test
Dial Test
Routine Test
1. at 5% of marked current with unity power factor
2. at 100% or 200% of marked current unity power factor
3. at marked current and 0.5lagging power factor
Figure 39 shows the tests carried out on energy meters at HESCOM
A common method of tampering on older meters is to attach magnets to the outside of the meter.
These magnetically saturate the coils or current transformers, preventing the alternating current
from forming eddy currents in the rotor, or inducing voltages in the current transformer. But
modern electronic energy meter has sensor that can report magnetic anomalies.
Rectified DC loads because mechanical rotating coils of meters to under-register. But electronic
meter does not have a rotating part so it measures the accurate reading
Connecting the neutral terminal from source to load inside the meter, make the meter to stop for
taking the readings. However, modern tamper-resistant meters can detect it and bill it at standard
rate. Now electronics energy meter can also be tampered by placing a 35KV EHT inside the meter
thus reducing the speed of rotation of the disc. But model digital meter immediately records this
type of tampering by sensors placed inside the modern digital meter.
The below figure shows the current transformers testing device and potential transformer testing
device
The visit to Hubli Urban and Hubli Rural Division in Tabib land, Hubli during internship briefed us
about the low tension installations and tariffs sections proposed for different electric installations.
1. LT-1 Bhagyajyothi
The existing tariff and the tariff proposed are given below:
The GOK, as a policy, has extended free power to all BJ/KJ consumers, whose consumption is not
more than 18 units per month. The tariff payable by these consumers is revised to Rs.5.52 per
unit. Further, the ESCOMs have to claim subsidy for only those consumers who consume 18 units
or less per month per installation. If the consumption exceeds 18 units per month or any BJ/KJ
installation is found to have more than one out let, it shall be billed as per the Tariff Schedule LT
2(a).
Since GOK is meeting the full cost of supply to BJ / KJ, the Tariff payable by these Consumers
is shown as nil. However, if the GOK does not release the subsidy in advance, a Tariff of Rs.5.52
per unit subject to monthly minimum of Rs. 30/- per Installation per month shall be demanded
and collected from these Consumers.
Note: If the consumption exceeds 18 units per month or any BJ/KJ installation is found to have
more than one light point being used, it shall be billed as per Tariff Schedule LT 2(a)
Applicable to areas coming under City Municipal Corporations and all areas under Urban Local
Bodies
Energy Charges exceeding 30 Units 31 to 100 units: 370 paise / 31 to 100 units:490 paise
per month unit / unit
101 to 200 units:495 paise 101 to 200 units: 645
/unit paise /unit
Above 200 units: 575 paise Above 200 units: 730
/unit paise /unit
The Commission has decided to continue the two tier tariff in respect of the domestic consumers
as shown below:
(i) Areas coming under city Municipal Corporations and all Urban Local Bodies
Energy Charges up to 30 Units per Month (0- Upto 30 units: 360 paise/unit
30 Units)-
Lifeline Consumption
Energy Charges in case the Consumption 31 to 100 units: 490 paise/unit
exceeds 30 units per month
Energy Charges 101 to 200 units: 675 paise/unit
Above 200 units: 730 paise/unit
LT2 (b) Private Professional and other Private Educational Institutions, Private Hospitals
and Nursing Homes.
The details of the existing and the proposed tariff under this category are given in the Table below:
LT 2 (b) (i) Private Professional Educational Institutions& Private Hospitals and Nursing
Homes.
Applicable to all areas coming under Urban Local Bodies including Municipal Corporations
LT 2 (b) (ii) Private Professional Educational Institutions &Private Hospitals and Nursing
Homes.
Commission’s decision
As in the previous Tariff Order dated 12th May 2014, the Commission decides to continue the tariff
at two levels i.e.
(i) Municipal Corporation Areas and Areas coming under Urban Local bodies.
Approved Tariff for LT 2 (b) (i) Private Professional and other Private EducationalInstitutions,
Private Hospitals and Nursing Homes
Applicable to areas coming under City Municipal Corporations and all areas under urban
Local Bodies.
Details Tariff approved by the Commission
Fixed Charges per Month Rs.75per KW subject to a minimum of Rs.100 per Month.
Approved Tariff for LT 2 (b) (ii) Private Professional and other Private Educational
Institutions, Private Hospitals and Nursing Homes.
Applicable in areas under all Urban Local Bodies including City Municipal Corporations
Energy Charges For the first 50 units:675 paise per For the first 50 units:800 paise
unit per unit
For the balance units: 775 paise per For the balance units:900 paise
unit per unit
Demand based tariff (optional) where sanctioned load is above 5 KW but below 50 KW
Energy Charges For the first 50 units:625 paise per For the first 50 units:750 paise
unit per unit
For the balance units: 725 paise per For the balance units: 850
unit paise per unit
Demand based tariff (optional) where sanctioned load is above 5 KW but below 50 KW
Commission’s decision
As in the previous Tariff Order dated 12th May 2014, the Commission decides to continue tariffs
at two levels i.e.
(i) Municipal Corporation and areas coming under other urban local bodies
Applicable to areas under all Urban Local Bodies including Municipal Corporations
Demand based tariff (Optional) where sanctioned load is above 5 kW but below 50 kW.
LT-3 (ii) Commercial Lighting Heating& Motive Power Applicable to areas under Village
Panchayats
The Government of Karnataka has extended free supply of power to farmers as per Government
Order No. EN 55 PSR 2008 dated 04.09.2008. As per this policy of GoK, the entire cost of supply
to IP sets Upto and inclusive of 10 HP is being borne by the GoK through tariff subsidy. In view
of this all the categories under the existing LT-4a tariff are covered under free supply of power.
Considering the cross subsidy contribution from categories other than IP Sets & BJ/KJ Categories,
the Commission determines the tariff for IP Set under LT4(a) category as follows:
Particulars HESCOM
Approved ARR in Rs. Crores 5319.38
Revenue from other than IP & BJ/KJ in Rs. Crores 2573.65
Amount to be recovered from IP & BJ/KJ in Rs. Crores 2558.71
Regulatory Asset Rs. Crores 95.82
Approved Sales to BJ/KJs in MU 87.28
Revenue from BJ/KJ at Average Cost of supply in Rs. Crores 48.18
Accordingly, the Commission decides to approve tariff of Rs.5.08 per unit as CDT for FY16 for
IP Set category under LT4(a). In case the GOK does not release the subsidy in advance, a tariff
of Rs.5.08 per unit shall be demanded and collected from these consumers.
Applicable to Private Horticultural Nurseries, Coffee and Tea plantations up to & inclusive of 10
HP
Applicable to Private Horticultural Nurseries, Coffee and Tea plantations above 10 HP.
i) Fixed charges
TOD Tariff
Commission’s Decision:
Commission’s Decision:
As decided in the previous Tariff Order dated 12th May 2014, the tariff specified for
installations with sanctioned load / contract demand above 67 HP is covered under the HT
temporary tariff category under HT5.
Further, the Commission decides to bifurcate the existing LT7 tariff schedule applicable to
both for temporary and permanent connection basis into two levels of tariff category under LT7
(a) applicable to temporary power supply for all purposes and LT7 (b) power supply on permanent
connection basis.
The Commission decides to approve the tariff for LT-7 category as follows:
Applicable to Hoardings & Advertisement boards, Bus Shelters with Advertising Boards, Private
Advertising Posts / Sign boards in the interest of Public such as Police Canopy Direction boards,
and other sign boards sponsored by Private Advertising Agencies / firms on permanent .
Connection basis.
9. CONCLUSION
On the whole the internship was useful experience. We have gained knowledge, skill by achieving
several of our learning goals; we got insight into professional practices currently advocated in the
HESCOM. We learned the different facts of working within a well established company. Related to
our study we learned more about the distribution system of electricity. Being able to visit each of the
electrical supply components in HESCOM, I gained better understanding and further knowledge on
electrical systems and how they work. The internship programme was not one sided, but it was a way
of sharing knowledge, ideas and opinions. This helped us to define what skills and knowledge we
have to improve in the upcoming days. We can confidently assert that the knowledge we gained
through this internship is sufficient to contribute towards our future endeavors. At last this internship
has given us new insights and motivation to pursue a career in core electrical departments.
The educational objective of outcome of the internship carried out at “HESCOM” HUBBALLI-
DHARWAD was met by taking active participation. I was able to apply electrical engineering and
academic background to their practical and personal endeavors and could adopt evolving job
responsibilities. Through this I was able to apply knowledge of mathematics, science and engineering.
It helped me to analyze the connection between the GENERATION,TRANSMISSION and
DISTRIBUTION of POWER.
REFERENCES
[1] "Joint Consultation Paper: Western Metropolitan Melbourne Transmission Connection and
Subtransmission Capacity" (PDF). Jemena. Powercor Australia, Jemena, Australian Energy Market
Operator. Retrieved 4 February 2016.
[2] Steinberg, Neil. "Lights On but Nobody Home: Behind the Fake Buildings that Power Chicago".
Retrieved 14 December 2013.
[3] "Transformer Fire Video". metacafe. User Eagle Eye. Retrieved 4 February 2016.
[4] A B Donald G. Fink, H. Wayne Beatty Standard Handbook for Electrical Engineers Eleventh
Edition, McGraw Hill 1978 ISBN 0-07-020974-X Chapter 17 Substation Design.
[5] Baker, Joseph W,. "Eliminating Hurricane Induced Storm Surge Damage to Electric Utilities Via
In-place Elevation of Substation Structures and Equipment" (PDF). DISTRAN Packaged Substations.
Crest Industries. Retrieved 4 February 2016.
[6] John, Alvin. "EE35T - Substation Design and Layout". The University of The West Indies at St.
Augustine, Trinidad And Tobago. Retrieved 4 February 2016.
[7] Technical website www.ieeeexplorer.com